Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Design Example 13
APPENDIX A
EXAMPLE 13 - VEHICLE COLLISION ON A PIER
GENERAL INFORMATION
Example 13 illustrates pier design to provide structural resistance to withstand the vehicular collision of
an oversized vehicle using LEAP Bridge Substructure software. The only load case investigated in this
example is Extreme Event II. Other load cases are not discussed for this example but should be
investigated in the complete pier design.
The following were also assumed in modeling the pier in the LEAP Bridge Substructure program:
→ The end of the column is fixed at the top of the drilled shaft
→ The drilled shaft point of fixity is located at 3x drilled shaft diameter = 13.5 ft.
→ Total drilled shaft length is 5x drilled shaft diameter = 23 ft.
The Designer should use the project geotechnical information and a suitable design tool to determine the
drilled shaft point of fixity and required drilled shaft total length and enter it in the LEAP Bridge
Substructure program.
y
x
Applied Loads:
In this example, the only loads included in the analysis are collision loads and dead loads, due to the
improbable coincidence of other loads (BDM Section 3.5.2). Designer may choose to include live loads,
but in most cases shear from vehicle impact will control the design.
If the LEAP Bridge Superstructure model is available, DC and DW loads may be imported to pier model.
Otherwise, they can be autogenerated as shown below.
DC: 1. Slab and girder dead loads - autogenerated from superstructure input, γ = 150 pcf
2. Barrier dead loads - total load per foot = 486 plf (see Structural Worksheets B-606-7B)
DW: 1. Wearing surface total load per foot = 36.67 psf *(57 ft clear roadway width) = 2090.19 plf
(refer to BDM Section 3.4.2)
CT: Equivalent static load = 600 kip, applied in a direction of 0 to 15 degrees, 5 ft. above the
ground (AASHTO 3.6.5.1)
In the case of a multi-column pier, the Designer must investigate the collision force CT acting
on each column separately and select the one with the maximum shear force. The Designer
should then check the shear capacity of the column. The Designer is responsible for
determining the most conservative load cases taking into account both directions of travel
under the bridge and the geometry of the bridge.
Note: The critical design section for a column is at the point of impact. The Designer should
add additional check points near the impact from the 'Structure Model' menu to get information
needed for design.
Column length in LEAP Bridge Substructure model (includes drilled shaft length to fixity)
L = 1/2 x 4 ft. cap depth + 20 ft. + 13.5 ft. = 35.50 ft.
Point of application of CT from drilled shaft point of fixity
y1 = 5 ft. + 2 ft. drilled shaft cover + 13.5 ft. = 20.50 ft.
FX =579.56 kip
FZ = 155.29 kip
Analysis of the columns is performed using the P-delta method. See below for the following outputs from
LEAP Bridge Substructure:
→ Summary of load combinations used in the design
→ Controlling column design results
→ Detailed shear design calculation for controlling column
Summary of Design:
Column reinforcement - main rebar 22 #10 bars, equally spaced
shear reinforcement #4 ties @ 6"
Design of a drilled shaft in the Extreme Event collision case is similar to the design of a drilled shaft in
the Strength cases and will not be shown for this example. The Designer must account for the collision
load in the drilled shaft design by applying Extreme Event loads from the bottom of the column to the top
of the caisson. It is recommended that the Designer use a suitable design tool to analyze shaft-soil
interaction to determine stability and strength requirements.
Sheet # 1
Job #
COLUMN DESIGN
DESIGN PARAMETERS
f'c = 4500.0 psi fy = 60000.0 psi
phi tens = 0.90 phi comp = 0.75
Tens above = 0.005 Comp below = 0.002
phi shear = 0.90 fy shear = 60000.00 psi
Ec = 4435.3 ksi Es = 29000 ksi
Concrete Type : Normal Weight.
Reinforcement
Rebar Pattern: Circular
Rebar Orientation: Face Parallel
Sheet # 2
Job #
Note:
Bar Dist refers to the distance between center of reinforcement and concrete surface.
COLUMN DESIGN
Bot/Top Elev. Pu Mux Muz pMn Incl
Comb pPn/Pu pMn/Mu
ft kips kips-ft kips-ft kips-ft deg
0.00 15 384.1 413.4 781.1 2737.7 62.11 1.00 3.09774
6.00 13 432.5 73.5 2247.3 2787.1 88.13 1.00 1.23953
7.00 13 430.8 73.2 2634.6 2786.8 88.41 1.00 1.05734 Controlling moment case
8.00 13 429.1 72.9 2475.8 2784.7 88.31 1.00 1.12426
22.00 16 284.2 202.4 1425.7 2622.3 81.92 1.00 1.82108
Sheet # 3
Job #
COLUMN DESIGN
Bot/Top Elev. As_min As_max As_prov
ft in^2 in^2 in^2
0.00 18.32 144.76 27.94
6.00 18.32 144.76 27.94
7.00 18.32 144.76 27.94
8.00 18.32 144.76 27.94
22.00 18.32 144.76 27.94
SHEAR DESIGN:
Loc Vu phi*Vn Av/s Aprv/s Vc Vs Theta b dv Smax Sprv
Pos Comb Beta Eps_s
ft kips kips in^2/ft in^2/ft kips kips deg in in in in
0.00 L 396.2 14 503.9 0.64 0.80 340.05 219.82 3.14 31.47 48.00 33.63 0.0007 24.00 6.00
6.00 R 396.2 14 433.1 0.64 0.80 275.23 206.00 2.54 33.15 48.00 33.63 0.0012 24.00 6.00
L 396.2 14 433.1 0.64 0.80 275.23 206.00 2.54 33.15 48.00 33.63 0.0012 24.00 6.00
7.00 R 396.2 14 413.1 0.73 0.80 257.61 201.34 2.38 33.75 48.00 33.63 0.0014 24.00 6.00
L 396.2 14 413.1 0.73 0.80 257.61 201.34 2.38 33.75 48.00 33.63 0.0014 24.00 6.00
8.00 R 214.2 1 462.7 0.64 0.80 301.85 212.23 2.79 32.37 48.00 33.63 0.0010 24.00 6.00
L 214.2 1 462.7 0.64 0.80 301.85 212.23 2.79 32.37 48.00 33.63 0.0010 24.00 6.00
22.00 R 214.2 1 632.7 0.64 0.80 465.64 237.36 4.30 29.54 48.00 33.63 0.0002 24.00 6.00
CDOT
Units: USBridge
(English)Design Manual Design Code: AASHTO LRFD 7 2016 Interims January 2018
EXAMPLE 13 - VEHICLE COLLISION ON A PIER 9
Column 1
Shear/Torsion
POI at location 7ft
Shear/torsion design details for Left
Controlling load combination 14
Description Values Units References
Materials
'
Specified compressive strength of concrete, fc 4500 psi