NETWORK THERMOSTAT

BACSTAT II™ DNT-T103


3-value; 96-segment with LCD Display
Description SPECIFICATIONS

The DNT-T103 BACStat II™ is an intelligent room sensor with a custom 3-value, 96 segment, LCD
LCDdisplay that is used with Delta’s™ BACnet™ Application Controllers which are capable of
3-value & various icons (96 total
communicating on Delta’s™ proprietary LINKnet™ network or directly on a BACnet™ MS/TP segments) w/optional backlighting
network.
Push Buttons
It is capable of displaying a wide range of digital or analog values, including setpoints,
4 stylized momentary push
temperature, air flow, heating and cooling status, fan speed, valve and damper position and buttons
more.
Temperature Sensor
When connected to an Application Controller
Thermistor Input - 10K Ω at 77°F
on a LINKnet™network it provides programmable (25° C)
remote sensor and expanded I/O capabilities to Accuracy +/-0.36° F from 32-158° F
the controller. When connected on the MS/TP (+/- 0.2° C from 0-70° C)
network, it functions as an independent BACnet™ Display resolution of 0.1°
sensor device.
Stability 0.24° F over 5 years
(0.13° C)
Application
Inputs - External
With 1 external universal input,
and 3 binary outputs and built-in 1 Universal Input - 10 bit
(supporting 0-5v, 0-10v, 10K)
control applications, the DNT-T103 is
capable of simple stand alone control Outputs - External
when directly connected on an MS/TP DNT-T103 Network Thermostat 3 Binary Triac outputs
network. (supporting Binary, PWM or Tri-State)
Features
Diverse applications include VAV, VVT Technology
> Native BACnet™ thermostat
Fan Coil Units, Unit Heaters, Radiation 8-bit processor c/w internal A/D,
or Reheat Control, Furnace, and other > Supports communicating on Flash and RAM >>
room applications. LINKnet™ or directly on an RS-485
MS/TP network
The DNT-T103 may also be connected
to a LINKnet™ network to provide > Programmable 3-value, 96 segment,
remote sensor and I/O mixing LCD display (via GCL over LINKnet™)
capabilities. with optional backlighting
> 4 Programmable buttons (via GCL
over LINKnet™)
> Derived Network Addressing (DNA)
for logical integration into a standard
network architecture
> Field selectable applications

Integrated Facilities Management Solutions. Simplified!


Delta Controls Inc. Technical specifications are subject to
17850 56th Avenue Tel: (604) 574-9444 revision without notice.
Surrey Fax: (604) 574-7793
British Columbia www.deltacontrols.com
Canada V3S 1C7 Rev. 09_01
NETWORK THERMOSTAT
BACSTAT II™ DNT-T103
SPECIFICATIONS (cont.)
Triacs
Connector Posts
for IP2 Device Type
Connector Posts Connector Posts
for Outputs for 24 VAC Configurable as a LINKnet™ or
OP3 COM OP2 COM OP1 [-] [+] IP2 GND ~24
Subnet device

INTERNAL
Connector Posts

EXTERNAL
1 2 1 2 3 1 2 1 2 3
Output Power for Network
Source Selector
Blocks (OP3) EXTERNAL
INTERNAL
Input Type Selector Device Addressing

10K 10V 5V
Blocks (IP2)
+
+ Set via Keypad Configuration Setup
Output Power
Source Selector
Blocks (OP1 & 2)
Standard Device Address Range
(via Keypad): 0-8 on LINKnet™ or
0-99 per MS/TP network segment
RESET
High Voltage
CPU
WARNING Warning - when Communications Ports
HIGH VOLTAGE devices with
AREA
backlighting are BACnet™MS/TP @ 9,600 or 19,200
powered on.
or 38,400 or 76,000 bps
(maximum of 99 nodes per MS/TP
segment)
698128 Rev 2.0
RJ II Service Port
Connectors
[-]

Thermistor
(Other Side of PCB)
Removable screwtype terminal
~24
[+]

Service
Port connectors
Wiring
2 for RS-485 LAN
Board Layout DNT-T103
2 for Power
Additional wiring for external inputs
and outputs
Wiring Class
Class II
Power
24 VAC , 2VA net including
output loading >>

Integrated Facilities Management Solutions. Simplified!


NETWORK THERMOSTAT
BACSTAT II™ DNT-T103
SPECIFICATIONS (cont.)
Ordering
Ambient
Order the Delta BACstat™II with the desired options according to the following
product numbers. 32° to 131° F (0° to 55°C)
10 - 90% RH (non-condensing)
Features DNS-24 DNT-T103 DNT-T221 Dimensions
Internal Thermistor Input ● ● 4.5 x 2.75 x 1.25 ins
(11.4 x 7 x 2.5cm)
Additional I/O (1 IP & 3 OP) ●
0.1 lb (50 g)
4-Button Model ● ●
Approvals/Standards
Backlighting Option B Option B Option B
UL916; CE; FCC Class A
Button Icons G1, G2, G3 G1, G2, G3 As Specified

Note: For the 4-Button Models, an appended button icon code must be included to
specify the desired icons embossed on the buttons as follows:
Default Bottom 2 buttons are ▼ & ▲ (Setpoint Adjust), top 2 are OFF and ON
INT Bottom 2 buttons are ▼ & ▲ (Setpoint Adjust), top 2 are O and I -
International
FAN Bottom 2 buttons are ▼ & ▲ (Setpoint Adjust), top 2 are INCREASE
and DECREASE Fan Speed

Accessories
RPT-768 Delta Network Repeater for MS/TP
TRM-768 Delta Network Terminator for MS/TP
CON-768 Delta Network Converter