KORDINASI SETELAN OCR/GFR TRAFO TENAGA

Setelan Arus : u/ggn di bus 20 kV


150 kV OCR : Iset = 1,2 x InTRF(150 kV)
tset = 1,2 dt (Standard Inverse)
Iset mom = Blok
CT1 OCR
5P….. GFR
GFR : Iset = (0,5-0,7) x InTRF(150kV)
tset =1,2 dt (Standard Inverse) .
Iset mom = Blok

GFR

CTN1
5P10

TRF
Setelan Arus : u/ggn di bus 20 kV
CTN2 OCR : Iset = 1,2 x InTRF(20 kV)
5P10
tset = 0,7 dt (Standard Inverse)
Iset mom = 4,0 x In TRF
GFR tset = 0,3 dt

GFR : Iset = 0,4 x InTRF(20kV)


tset = 0,7 dt (Standard Inverse)
Iset mom = maks 4,0 x In TRF
CT2 OCR
tset = 0,3 dt
5P….. GFR

20 kV

Setelan Arus : u/ggn dibus 20 kV


CT3 OCR OCR : Iset = 1,2 x InCT3/CCCpeny. (peralatan terkecil
5P…. GFR
di penyulang).
tset = 0,3 dt (Standard Inverse)
Iset mom = 0,8 x 0,5 x (In Trf x (1/Zt (pu))
CCCpeny. = 0.8 x (10 atau 20) x In primer CT

tset = Inst

GFR : Iset = (0,2-0,5) x InCT3/CCCpeny.(peralatan


PENY. terkecil penyulang).
tset = 0,3 dt (Standard Inverse)
Iset highset = maks 2 x In TRF
tset = Inst