LARSEN & TOUBRO LIMITED

ECC Division - EDRC


DOCUMENT NO DATE
PROJECT STANDARDIZATION OF DESIGN CALCULATION
O12020-E-TP-GE-DC-3058 29/8/2012

DESIGNED CHECKED APPROVED SHEET


TITLE DG SET SIZING CALCULATION
MAG MVMR SKW Page2 of 17

DESIGN CALCULATION

DIESEL GENERATOR SET SIZING CALCULATION


LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION OF DESIGN CALCULATION
O12020-E-TP-GE-DC-3058 29/8/2012

DESIGNED CHECKED APPROVED SHEET


TITLE DG SET SIZING CALCULATION
MAG MVMR SKW Page3 of 17

INDEX

0.0.0 PURPOSE AND SCOPE 3

1.0.0 SYMBOLS AND UNITS 3

2.0.0 REFERENCE STANDARDS 4

3.0.0 ASSUMPTIONS 4

4.0.0 DESIGN INPUTS 4

5.0.0 ENVIRONMENTAL DETAILS 4

6.0.0 STEADY STATE CAPACITY CALCULATION 5

7.0.0 CHECKING OF CAPACITY FOR TRANSIENT CONDITION 5

8.0.0 6
CHECKING OF VOLTAGE DROP DURING TRANSIENT CONDITION
9.0.0 6
CHECKING OF VOLTAGE DROP DURING TRANSIENT CONDITION
10.0.0 RESULT 7
LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION OF DESIGN CALCULATION
O12020-E-TP-GE-DC-3058 29/8/2012

DESIGNED CHECKED APPROVED SHEET


TITLE DG SET SIZING CALCULATION
MAG MVMR SKW Page4 of 17

0.0.0 PURPOSE AND SCOPE


The purpose of the document is to select proper sizing of Diesel Generator (DG) set.

1.0.0 SYMBOLS AND UNITS


BL Base Load kVA

Cm Motor cable detail

CosØ Full load power Factor of largest rating motor

Cosqs Starting power Factor of largest rating motor

Cosθ System power factor

DM Design Margin

f Supply Frequency Hz

IFL Full load current of highest rating motor A

Im1 Base load current A

Im2 Increased Base load current due to motor starting A

IS Starting current of motor in terms of voltage A

Ist Starting current of largest rating motor A

K Ratio of starting current to full load current

Lm Length of motor cable kM

MD Total Maximum demand kVA

P Rating of largest rating motor kW

Rm Motor cable resistance Ω

Sinqs Reactive power factor of motor during starting

STLM Starting kVA of largest rating motor kVA

Design ambient temperature o


T C

TCL Total connected load kVA

V System Voltage Volts

Vb Bus voltage during motor starting Volts

Vm Motor terminal voltage during starting Volts

Vph Phase voltage at low voltage side Volts

Xm Motor cable reactance Ω

XS DG reactance Ω

η1 Full load Efficiency of largest rated motor

2.0.0 REFERENCE STANDARDS

IS 325 (1996) (Specifications for three phase Induction Motors)

3.0.0 ASSUMPTIONS

The DG set is having Automatic Voltage regulator which compensates the voltage drop due to source during steady state condition.
LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION OF DESIGN CALCULATION
O12020-E-TP-GE-DC-3058 29/8/2012

DESIGNED CHECKED APPROVED SHEET


TITLE DG SET SIZING CALCULATION
MAG MVMR SKW Page5 of 17

4.0.0 DESIGN INPUTS

4.1.1 System Voltage V : 415 V

4.1.2 Frequency f : 50 Hz

4.1.3 Total maximum demand for emergency load MD : 1477 kVA 2

4.1.4 Total maximum demand for emergency load TCL : 2183 kVA 2

4.1.5 Design margin DM : 15%

4.1.6 System power factor Cosθ : 0.85

4.1.7 Phase Voltage at low voltage side Vph : 239.61 V

4.1.8 Largest rating motor data

4.1.8.1 Rating of largest rating motor P : 55 kW (Refer MD calculation)

4.1.8.2 Type of motor and starter : Sq cage / DOL

4.1.8.3 Full load power factor CosØ : 0.8 (Refer Motor data sheet)

4.1.8.4 Full load Efficiency η1 : 93% (Refer Motor data sheet)

4.1.8.5 Starting power factor Cosqs : 0.2 1 (Refer Motor data sheet)

Sinqs : 0.98

4.1.8.6 Multiplication factor for starting current K : 6

4.1.8.7 Motor Cable detail Cm : 1# 3Cx240 Sqmm, XLPE, Al.


1
Length of the Cable Lm : 0.18 kM

Resistance of the Cable @ 90ºC / kM : 0.16 Ω / kM

Resistance of the Cable @ 90ºC Rm : 0.0288 Ω

Reactance of the Cable / kM : 0.07 Ω / kM

Reactance of the Cable Xm : 0.01278 Ω

4.2.0. Tie feeder rating PTie : 350.00 kVA 1

5.0.0 ENVIRONMENTAL DETAILS

5.1.1 Design Ambient Temperature o


T : 50 C

6.0.0 STEADY STATE CAPACITY CALCULATION

6.1.1 DG capacity required : ((MD-PTie) x 1+DM) + PTie


1

: ((1477.27103099304-350) x 1.15) + 350

: 1646.361686 kVA -----(1)


LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION OF DESIGN CALCULATION
O12020-E-TP-GE-DC-3058 29/8/2012

DESIGNED CHECKED APPROVED SHEET


TITLE DG SET SIZING CALCULATION
MAG MVMR SKW Page6 of 17

7.0.0 CHECKING OF CAPACITY FOR TRANSIENT CONDITION

7.1.1 Base load BL : MD - P / (CosØ x η1)


1

: 1477.27103099304 - 55 / ( 0.8 x 0.93)

: 1404 kVA

7.1.2 Base load current Im1 : BL*1000


√3 * V

: 1404 * 1000
√3 * 415

: 1953.31 A

7.1.3 Full load current of motor IFL : P * 1000


√3*V*CosØ * η1

: 55 * 1000
√3*415*0.8 * 0.93

: 102.85 A

7.1.4 Starting Current of motor Ist : 1.2 * K*IFL


20% tolerance on starting
current as per IS 325
: 1.2 *6*102.85 Table-1

: 740.52 A

7.1.5 Starting kVA of motor STLM : √3*V*Ist


1000

: √3*415*740.52
1000

: 532.28 kVA

7.1.6 Total starting kVA required : (STLM + BL)

: 532.28 + 1404

: 1936 kVA

7.1.7 The DG set is capable of withstanding 150% overloading

DG set required for this starting requirement : 1291 kVA ---- (2)

From Equation (1) and (2) above, the DG rating required : Maximum of (1) and (2)

: 1646

: 1750 kVA or 1.75 MVA


LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION OF DESIGN CALCULATION
O12020-E-TP-GE-DC-3058 29/8/2012

DESIGNED CHECKED APPROVED SHEET


TITLE DG SET SIZING CALCULATION
MAG MVMR SKW Page7 of 17

8.0.0 CHECKING OF STEADY STATE VOLTAGE DROP 1

Vph

IX
IR CosQ IX Sin (90-Q) Neglecting phase angle difference between Vm and Vph
Q Vm
IR IX Cos (90-Q)
I

from the above phasor diagram,


Vph : Vm + IR CosQ + IX Cos (90-Q)

: Vm + IR CosQ + IX SinQ

Therefore, Steady state voltage drop Vd : I (R CosQ + X SinQ)

Steady state voltage drop Vd : 102.85( 0.0288*0.8+0.01278*0.6)

: 3.1583

Percentage Voltage drop for this length %Vd : Vd * 100 * √3


V
: 3.1583* 100 *√3
415

: 1.32 %

Percentage Voltage Drop at MCC feeding this load : - %

Total Voltage Drop upto this level : 1.32+0 %


: 1.32 %

9.0.0 CHECKING OF VOLTAGE DROP DURING LARGEST MOTOR STARTING

9.1.1 Base parameters

Base impedance at 1 MVA and 0.415kV : 0.172225 Ω

9.1.3 DG set parameters

Transient reactance (PU value) Xd' : 15.00%


1
Transient reactance (Actual value) XS : Xd' * Base impedance / DG Rating

: 0.01500 Ohm

9.1.4 Phasor diagram


Vph

(Im2-Im1) Xs 2.53 V

Is Xs 9.65 V

Vb

Is Xm 8.22 V

Vm IS Rm

203.97 V
Vm Sinqs

Vm Cosqs IS
41.62589 204
LARSEN & TOUBRO LIMITED
ECC Division - EDRC
DOCUMENT NO DATE
PROJECT STANDARDIZATION OF DESIGN CALCULATION
O12020-E-TP-GE-DC-3058 29/8/2012

DESIGNED CHECKED APPROVED SHEET


TITLE DG SET SIZING CALCULATION
MAG MVMR SKW Page8 of 17
9.1.5 Calculation

From the above phasor diagram


Vph2 = (Vm Cosqs + IS Rm)2 + (Vm Sinqs +IS Xm +IS XS + XS (Im2-Im1))2 ---------- (I)

Motor Starting Current IS : Ist Vm/ Vph ----------(a)

For constant kVA modeling Im2 : Im1 Vph/ Vb ----------(b)

Also, bus voltage Vb 2 : (Vm cos qs+ IS Rm)2 + (Vm sin qs +IS Xm)2 ----------(c)
1
Putting the Equations (a), (b) & (c) in Equation (I) we get)
2 2
Vph2 = Vm Cosqs + Ist Rm Vm + Vm Sinqs + Ist Vm (Xm+ XS) + XS Im1 (Vph-Vb 2)
Vph Vph Vb

Please press Ctrl+K to run the Macro

Voltage available at Motor Terminal during starting of largest Motor

Vm : 208.13 V

: 86.87 %

Similarly, Voltage available at Bus during starting of largest Motor

Vb : 220.55 V

: 92.05 %

Increased Base load current due to motor starting

Im2 : 1953.31*239.61
220.55

: 2122.12 A

Starting current of motor in terms of voltage : 740.52 * 208.13


239.61

IS : 643.23 A

10.0.0 RESULT

Description Selected Value Required

Rating of DG (kVA) 1750 1646.36169

Thermal loading on the DG during motor starting 110.64% 150.00%

Steady state voltage drop 1.32% 3.00%

Voltage available at motor terminal during motor starting 86.87% 85%

Voltage available at Bus during motor starting 92.05% 90%

As all the conditions are satisfied, the selected DG set size of 1.75 MVA is Safe
415V ESSENTIAL SWITCHGEAR UNIT - 1

Load Rating Load Character


R Rated
Power Normal Start-up Shutdown Intermittent
Item UNI/ Module
D
e No. KKS No. Service Description Volt NAT Type Power Unit Current Factor Efficiency BI Ope Load Capacity Ope Load Capacity Ope Load Capacity Ope Load Capacity Length Location Control Remarks Type
(Load
v side) (V) (A) Factor (kVA) Factor (kVA) Factor (kVA) Factor (kVA) (Mtrs.) of load

415V ESSENTIAL SWGR-1A

STANDARD BREAKER RATING SHALL BE


INCOMER FROM UNIT-1 SWGR-1 415 ACTRIN P 2000 kVA 2782.5 1.00 1.00 Incomer
SELECTED.

STANDARD BREAKER RATING SHALL BE


INCOMER FROM EDG-1 415 ACTRIN P 1500 kVA 2086.9 1.00 1.00 Incomer
SELECTED.
STANDARD BREAKER RATING SHALL BE
BUS COUPLER 415 ACTRIN kVA 0.0 1.00 1.00
SELECTED.
1 220 V DC UNIT-1 BATTERY CHARGER-1 415 ACTRIN P 325.00 kVA 452.2 0.80 1.00 C X 0.50 162.50 0.40 0.00 ASSUMED & UNVERIFIED

2 220 V DC STATION BATTERY CHARGER-1 415 ACTRIN P 90.00 kVA 125.2 0.80 1.00 C X 0.50 45.00 0.40 0.00 ASSUMED & UNVERIFIED

F 3 UNIT-1 UPS CHARGER A 415 ACTRIN P 160.00 kVA 222.6 0.80 1.00 C X 0.50 80.00 0.40 0.00 BASED ON DEC LATEST INPUT

F 4 PLANT COMMUNICATION EPABX CHARGER 415 ACTRIN P 3.00 kVA 4.2 0.80 1.00 C X 0.50 1.50 0.40 0.00 BASED ON C&I LOADLIST

F 5 TO ESSENTIAL HVAC DB 415 ACTRIN P 50.00 kVA 69.6 0.80 1.00 C X 0.80 40.00 0.40 0.00 INPUT FROM MECHANICAL

6 BOILER AND AUXILIARIES - UNIT # 1

FROM DEC Electrical Load list Dtd


AUXILIARY ACTUATING MOTOR-1 415 ACTRI M 15.00 kW 30.7 0.80 0.85 C X 0.80 17.65 0.40 0.00
25/06/11

FROM DEC Electrical Load list Dtd


F Hydraulic coupling starting luboil pump motor 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/11, REV.F

STEAM-DRIVEN FEEDWATER PUMP LUBE-OIL


FROM DEC Electrical Load list Dtd
F STANDBY OIL PUMP MOTOR-1 415 ACTRI M 30.00 kW 56.1 0.80 0.93 C X 0.80 32.26 0.40 0.00
BFP TURBINE LUBE OIL STANDBY PUMP MOTOR-1
24/02/11, REV.F

OIL PUMP MOTOR OF PAF HYDRAULIC LUBE OIL FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 C X 0.80 3.38 0.40 0.00
STATION (PAF-1)-1 25/06/11

OIL PUMP MOTOR OF PAF HYDRAULIC LUBE OIL FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 S 0.80 0.00 0.40 0.00
STATION (PAF-2)-1 25/06/11

FROM DEC Electrical Load list Dtd


PAF MOTOR LUBE OIL PUMP (PAF-1)-1 415 ACTRI M 0.00 kW 0.0 0.80 0.65 S 0.80 0.00 0.40 0.00
25/06/11

FROM DEC Electrical Load list Dtd


PAF MOTOR LUBE OIL PUMP (PAF-2)-1 415 ACTRI M 0.00 kW 0.0 0.80 0.65 C X 0.80 0.00 0.40 0.00
25/06/11

POWER FOR HYDRAULIC OIL STATION MOTOR OF FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 C X 0.80 3.38 0.40 0.00
FDF (FDF-1)-1 25/06/11

POWER FOR HYDRAULIC OIL STATION MOTOR OF FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 C X 0.80 3.38 0.40 0.00
FDF (FDF-2)-1 25/06/11

POWER FOR LUBE OIL STATION MOTOR OF IDF (IDF- FROM DEC Electrical Load list Dtd
415 ACTRI M 1.10 kW 2.9 0.80 0.65 S 0.80 0.00 0.40 0.00
1)-1 25/06/11

POWER FOR LUBE OIL STATION MOTOR OF IDF (IDF- FROM DEC Electrical Load list Dtd
415 ACTRI M 1.10 kW 2.9 0.80 0.65 C X 0.80 1.69 0.40 0.00
2)-1 25/06/11
LOCALE CONTROL CABINET FOR LUBRICATION OIL-
FROM DEC Electrical Load list Dtd
F 1 POWER FOR LUBE OIL STATION MOTOR OF MILL- 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
1
24/02/11, REV.F

LOCALE CONTROL CABINET FOR LUBRICATION OIL- FROM DEC Electrical Load list Dtd
F 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
2 POWER FOR LUBE OIL STATION MOTOR OF MILL-2 24/02/11, REV.F

LOCALE CONTROL CABINET FOR LUBRICATION OIL- FROM DEC Electrical Load list Dtd
F 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
3 POWER FOR LUBE OIL STATION MOTOR OF MILL-3 24/02/11, REV.F

LOCALE CONTROL CABINET FOR LUBRICATION OIL- FROM DEC Electrical Load list Dtd
F 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
4 POWER FOR LUBE OIL STATION MOTOR OF MILL-4 24/02/11, REV.F
LOCALE CONTROL CABINET FOR LUBRICATION
FROM DEC Electrical Load list Dtd
F OIL-5 POWER FOR LUBE OIL STATION MOTOR 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
24/02/11, REV.F
OF MILL-5
LOCALE CONTROL CABINET FOR LUBRICATION
FROM DEC Electrical Load list Dtd
F OIL-6 POWER FOR LUBE OIL STATION MOTOR 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/11, REV.F
OF MILL-6
LOCALE CONTROL CABINET FOR LUBRICATION
FROM DEC Electrical Load list Dtd
F OIL-7 POWER FOR LUBE OIL STATION MOTOR 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
24/02/11, REV.F
OF MILL-7
415V ESSENTIAL SWITCHGEAR UNIT - 1

Load Rating Load Character


R Rated
Power Normal Start-up Shutdown Intermittent
Item UNI/ Module
D
e No. KKS No. Service Description Volt NAT Type Power Unit Current Factor Efficiency BI Ope Load Capacity Ope Load Capacity Ope Load Capacity Ope Load Capacity Length Location Control Remarks Type
(Load
v side) (V) (A) Factor (kVA) Factor (kVA) Factor (kVA) Factor (kVA) (Mtrs.) of load

LOCALE CONTROL CABINET FOR LUBRICATION


FROM DEC Electrical Load list Dtd
F OIL-8 POWER FOR LUBE OIL STATION MOTOR 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/11, REV.F
OF MILL-8

FROM DEC Electrical Load list Dtd


BOILER SOOT BLOWER POWER CABINET 415 ACTRIN P 4.80 kW 8.3 0.80 1.00 I 0.80 0.00 X 0.40 2.40
25/06/11

FROM DEC Electrical Load list Dtd


FLAME SCANNER AMPLIFIER CABINET 240 ACMONO P 0.00 kW 0.0 0.80 1.00 C X 0.80 0.00 0.40 0.00 2
25/06/11

AIR PREHEATER GAP ADJUST CONTROL CABINET


415 ACTRI P 8 kW 16.3676 0.8 0.85 I 0.8 0 X 0.4 4.705882 FROM DEC Electrical Load list Dtd 25/06/11 2
FOR A & B SIDE-1

FROM DEC Electrical Load list Dtd


5 TURBINE GENERATOR AND AUXILIARIES - UNIT # 1
25/06/11

STEAM TURBINE JACKING OIL PUMP AC FROM DEC Electrical Load list Dtd
415 ACTRI M 55.00 kW 102.8 0.80 0.93 C X 0.80 59.14 0.40 0.00
MOTOR(NORMAL) 25/06/11

FROM DEC Electrical Load list Dtd


EH OIL MAIN OIL PUMP MOTOR-1 415 ACTRI M 45.00 kW 84.1 0.80 0.93 C X 0.80 48.39 0.40 0.00
25/06/11

FROM DEC Electrical Load list Dtd


EH OIL CIRCULATIONL PUMP MOTOR 415 ACTRI M 1.50 kW 4.0 0.80 0.65 C X 0.80 2.31 0.40 0.00
25/06/11
From
FROM DEC Electrical Load list Dtd
F BFP-TURBINE TURNING GEAR MOTOR-1 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.80 0.00 0.80 0.00 0.40 0.00 ANSAL
DO,
25/06/11
BYPASS SYSTEM OIL STATION (WITH LOCAL From FROM DEC Electrical Load list Dtd
415 ACTRI P 15.00 kW 26.1 0.80 1.00 C X 0.80 15.00 0.80 0.00 0.80 0.00 0.40 0.00
CONTROL BOX)-1 ANSAL25/06/11
From FROM DEC Electrical Load list Dtd
6 SEALNG OIL AC MOTOR-1 415 ACTRI M 7.50 kW 15.3 0.80 0.85 S 0.80 0.00 0.80 0.00 0.80 0.00 0.40 0.00
ANSAL25/06/11
From FROM DEC Electrical Load list Dtd
7 SEALNG OIL RECIRCULATING AC MOTOR-1 415 ACTRI M 5.50 kW 11.3 0.80 0.85 C X 0.80 6.47 0.80 0.00 0.80 0.00 0.40 0.00
ANSAL25/06/11
From
FURNACE GAS TEMP. PROBE RIGHT SIDE FROM DEC Electrical Load list Dtd
8 415 ACTRI P 5.00 kW 10.2 0.80 0.85 C X 0.80 5.88 0.80 0.00 0.80 0.00 0.40 0.00 ANSA
LOCAL CONTROLCABINET 25/06/11
LDO,
From
FROM DEC Electrical Load list Dtd
F 8 415V SPARE AC POWER-1 415 ACTRIN P 1.00 kW 1.7 0.80 1.00 C X 0.80 1.00 0.80 0.00 0.80 0.00 0.40 0.00 ANSA
24/02/11, REV.F
LDO,
From
FROM DEC Electrical Load list Dtd
F 8 240V SPARE AC POWER-1 240 ACMONO P 1.00 kW 5.2 0.80 1.00 S 0.80 0.00 0.80 0.00 0.80 0.00 0.40 0.00 ANSA
24/02/11, REV.F
LDO,
9 ESSENTIAL LIGHTING DB-1 415 ACTRI P 150.00 kVA 208.7 1.00 1.00 C X 0.80 120.00 0.40 0.00 ASSUMED & UNVERIFIED

10 SPARE 415 ACTRI M kW 0.0 0.80 0.65 S 0.80 0.00 0.40 0.00

11 SPARE 415 ACTRIN P kW 0.0 0.80 0.65 S 0.80 0.00 0.40 0.00

12 RESERVED 415 ACTRIN P 5.00 kW 10.2 0.80 0.85 c X 0.80 5.88 0.40 0.00

SUB TOTAL 719.5 7.1


TOTAL LOAD ON BUS A
727 kVA
(NORMAL + INTERMITTENT)

415V ESSENTIAL SWGR-1B


STANDARD BREAKER RATING SHALL BE
INCOMER FROM UNIT-1 SWGR-2 415 ACTRIN P 2000 kVA 2782.5 1.00 1.00 Incomer
SELECTED.
STANDARD BREAKER RATING SHALL BE
TIE TO ESSENTIAL SWGR-2 415 ACTRIN P 350 kVA 486.9 0.80 1.00 c X 0.80 280.00 Incomer
SELECTED.

1 220 V DC UNIT-1 BATTERY CHARGER-2 415 ACTRIN P 325.00 kVA 452.2 1.00 1.00 c X 0.50 162.50 0.40 0.00 ASSUMED & UNVERIFIED

F 2 UNIT-1 UPS BYPASS TRANSFOMER 415 ACTRIN P 160.00 kVA 222.6 1.00 1.00 S 0.50 0.00 0.40 0.00 BASED ON DEC LATEST INPUT

3 BOILER AND AUXILIARIES - UNIT # 1


Added as per ACPL/EIPL Comments
4 FURNACE FLAME TV FOR A & B SIDE 240 ACMONO P 2 kW 16.0 0.80 0.65 C X 0.80 3.08 0.40 0.0
dated 17.7.2012
FROM DEC Electrical Load list Dtd
AUXILIARY ACTUATING MOTOR-1 415 ACTRI M 15.00 kW 30.7 0.80 0.85 C X 0.80 17.65 0.40 0.00
25/06/11
415V ESSENTIAL SWITCHGEAR UNIT - 1

Load Rating Load Character


R Rated
Power Normal Start-up Shutdown Intermittent
Item UNI/ Module
D
e No. KKS No. Service Description Volt NAT Type Power Unit Current Factor Efficiency BI Ope Load Capacity Ope Load Capacity Ope Load Capacity Ope Load Capacity Length Location Control Remarks Type
(Load
v side) (V) (A) Factor (kVA) Factor (kVA) Factor (kVA) Factor (kVA) (Mtrs.) of load
STEAM-DRIVEN FEEDWATER PUMP LUBE-OIL
STANDBY OIL PUMP MOTOR-2 FROM DEC Electrical Load list Dtd
F 415 ACTRI M 30.00 kW 56.1 0.80 0.93 C X 0.80 32.26 0.40 0.00
BFP TURBINE LUBE OIL STANDBY PUMP 24/02/11, REV.F
MOTOR-1
OIL PUMP MOTOR OF PAF HYDRAULIC LUBE OIL FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 C X 0.80 3.38 0.40 0.00
STATION (PAF-1)-2 25/06/11
OIL PUMP MOTOR OF PAF HYDRAULIC LUBE OIL FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 S 0.80 0.00 0.40 0.00
STATION (PAF-2)-2 25/06/11
FROM DEC Electrical Load list Dtd
PAF MOTOR LUBE OIL PUMP (PAF-1)-2 415 ACTRI M 0.00 kW 0.0 0.80 0.65 S 0.80 0.00 0.40 0.00
25/06/11
FROM DEC Electrical Load list Dtd
PAF MOTOR LUBE OIL PUMP (PAF-2)-2 415 ACTRI M 0.00 kW 0.0 0.80 0.65 C X 0.80 0.00 0.40 0.00
25/06/11
POWER FOR HYDRAULIC OIL STATION MOTOR FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 C X 0.80 3.38 0.40 0.00
OF FDF (FDF-1)-2 25/06/11
POWER FOR HYDRAULIC OIL STATION MOTOR FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 S 0.80 0.00 0.40 0.00
OF FDF (FDF-2)-2 25/06/11
POWER FOR LUBE OIL STATION MOTOR OF IDF FROM DEC Electrical Load list Dtd
415 ACTRI M 1.10 kW 2.9 0.80 0.65 C X 0.80 1.69 0.40 0.00
(IDF-1)-2 25/06/11
POWER FOR LUBE OIL STATION MOTOR OF IDF FROM DEC Electrical Load list Dtd
415 ACTRI M 1.10 kW 2.9 0.80 0.65 S 0.80 0.00 0.40 0.00
(IDF-2)-2 25/06/11

LOCALE CONTROL CABINET FOR LUBRICATION OIL-


FROM DEC Electrical Load list Dtd
F 1 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
POWER FOR LUBE OIL STATION MOTOR OF MILL-1
24/02/11, REV.F

LOCALE CONTROL CABINET FOR LUBRICATION OIL- FROM DEC Electrical Load list Dtd
F 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
2 POWER FOR LUBE OIL STATION MOTOR OF MILL-2 24/02/11, REV.F

LOCALE CONTROL CABINET FOR LUBRICATION OIL- FROM DEC Electrical Load list Dtd
F 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
3 POWER FOR LUBE OIL STATION MOTOR OF MILL-3 24/02/11, REV.F

LOCALE CONTROL CABINET FOR LUBRICATION OIL- FROM DEC Electrical Load list Dtd
F 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
4 POWER FOR LUBE OIL STATION MOTOR OF MILL-4 24/02/11, REV.F

LOCALE CONTROL CABINET FOR LUBRICATION


FROM DEC Electrical Load list Dtd
F OIL-5 POWER FOR LUBE OIL STATION MOTOR 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/11, REV.F
OF MILL-5

LOCALE CONTROL CABINET FOR LUBRICATION


FROM DEC Electrical Load list Dtd
F OIL-6 POWER FOR LUBE OIL STATION MOTOR 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
24/02/11, REV.F
OF MILL-6

LOCALE CONTROL CABINET FOR LUBRICATION


FROM DEC Electrical Load list Dtd
F OIL-7 POWER FOR LUBE OIL STATION MOTOR 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/11, REV.F
OF MILL-7

LOCALE CONTROL CABINET FOR LUBRICATION


FROM DEC Electrical Load list Dtd
F OIL-8 POWER FOR LUBE OIL STATION MOTOR 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
24/02/11, REV.F
OF MILL-8

FROM DEC Electrical Load list Dtd


BOILER SOOT BLOWER POWER CABINET 415 ACTRIN P 4.80 kW 8.3 0.80 1.00 S 0.80 0.00 0.40 0.00 2
25/06/11
FROM DEC Electrical Load list Dtd
FLAME SCANNER AMPLIFIER CABINET 415 ACTRIN P 0.00 kW 0.0 0.80 1.00 C X 0.80 0.00 0.40 0.00 2
25/06/11
TURBINE GENERATOR AND AUXILIARIES - UNIT FROM DEC Electrical Load list Dtd
4
#1 25/06/11
FROM DEC Electrical Load list Dtd
STEAM TURBINE TURNING GEAR MOTOR 415 ACTRI M 15.00 kW 30.7 0.80 0.85 C X 0.80 17.65 0.40 0.00
25/06/11
STEAM TURBINE LUBE OIL AUXILIARY PUMP FROM DEC Electrical Load list Dtd
415 ACTRI M 55.00 kW 102.8 0.80 0.93 C X 0.80 59.14 0.40 0.00
MOTOR 25/06/11
FROM DEC Electrical Load list Dtd
EH OIL MAIN OIL PUMP MOTOR-2 415 ACTRI M 45.00 kW 84.1 0.80 0.93 S 0.80 0.00 0.40 0.00
25/06/11
From
FROM DEC Electrical Load list Dtd
EH OIL TRANSFER PUMP MOTOR 415 ACTRI M 1.50 kW 4.0 0.80 0.65 C X 0.80 2.31 0.80 0.00 0.80 0.00 0.40 0.00 ANSA
25/06/11
LDO,
415V ESSENTIAL SWITCHGEAR UNIT - 1

Load Rating Load Character


R Rated
Power Normal Start-up Shutdown Intermittent
Item UNI/ Module
D
e No. KKS No. Service Description Volt NAT Type Power Unit Current Factor Efficiency BI Ope Load Capacity Ope Load Capacity Ope Load Capacity Ope Load Capacity Length Location Control Remarks Type
(Load
v side) (V) (A) Factor (kVA) Factor (kVA) Factor (kVA) Factor (kVA) (Mtrs.) of load
From
FROM DEC Electrical Load list Dtd
F BFP-TURBINE TURNING GEAR MOTOR-2 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.80 0.00 0.80 0.00 0.40 0.00 ANSA
24/02/11, REV.F
LDO,
From
BYPASS SYSTEM OIL STATION (WITH LOCAL FROM DEC Electrical Load list Dtd
415 ACTRI P 15.00 kW 30.7 0.80 0.85 C X 0.80 17.65 0.80 0.00 0.80 0.00 0.40 0.00 ANSA
CONTROL BOX)-2 25/06/11
LDO,
From
FROM DEC Electrical Load list Dtd
5 SEALNG OIL AC MOTOR-2 415 ACTRI M 7.50 kW 15.3 0.80 0.85 C X 0.80 8.82 0.80 0.00 0.80 0.00 0.40 0.00 ANSA
25/06/11
LDO,
From
FROM DEC Electrical Load list Dtd
6 BOILER LOCAL IGNITION CABINET 415 ACTRI P 0.00 kW 0.0 0.80 0.65 S 0.80 0.00 0.80 0.00 0.80 0.00 0.40 0.00 ANSA 2
25/06/11
LDO,
From
FURNACE GAS TEMP. PROBE LEFT SIDE LOCAL FROM DEC Electrical Load list Dtd
7 415 ACTRI P 5.00 kW 10.2 0.80 0.85 C X 0.80 5.88 0.80 0.00 0.80 0.00 0.40 0.00 ANSA
CONTROLCABINET 25/06/11
AIR PREHEATER FIRE DETECTION CABINET LDO,
From
FROM DEC Electrical Load list Dtd
F 8 FOR A & B SIDE 415 ACTRI P 1.00 kW 1.7 0.80 1.00 C X 0.80 1.00 0.80 0.00 0.80 0.00 0.40 0.00 ANSA
24/02/11, REV.F
415V SPARE AC POWER -2 LDO,
From
ANSA FROM DEC Electrical Load list Dtd
F 8 240V SPARE AC POWER-2 240 ACMONO P 1.00 kW 5.2 0.80 1.00 S 0.80 0.00 0.80 0.00 0.80 0.00 0.40 0.00
LDO, 24/02/11, REV.F
Rev.0
From
AIR PREHEATER GAP ADJUST CONTROL FROM DEC Electrical Load list Dtd
F 9 415 ACTRI P 8.00 kW 16.4 0.80 0.85 0.80 0.00 0.80 0.00 0.80 0.00 0.40 0.00 ANSA
CABINET FOR A & B SIDE-2 25/06/11
LDO,
From
FLAME SCANNING COOLING FAN AC MOTOR FROM DEC Electrical Load list Dtd
10 415 ACTRI P 15.00 kW 26.1 0.80 1.00 C X 0.80 15.00 0.80 0.00 0.80 0.00 0.40 0.00 ANSA
LOCAL CONTROL CABINET 25/06/11
LDO,
11 COMMUNICATION PANEL 415 ACTRI P 6.00 kW 10.4 0.80 1.00 C X 0.80 6.00 0.80 0.00 0.80 0.00 0.40 0.00 Assumed & unverified

12 AVIATION OBSTRUCTION LIGHTING FEEDER 415 ACTRI P 10.00 kW 17.4 0.80 1.00 0.80 0.00 0.40 0.00 Assumed & unverified

13 ESSENTIAL LIGHTING DB-2 415 ACTRI P 100.00 kVA 139.1 1.00 1.00 0.80 0.00 0.40 0.00 Assumed & unverified
Added as per ACPL/EIPL Comments
14 Chimney emergency load 415 ACTRI P 50.00 kVA 69.6 1.00 1.00 C X 0.80 40.00 0.40 0.00
dated 17.7.2012
Added as per ACPL/EIPL Comments
15 switchyard emergency load 415 ACTRI P 15.00 kVA 20.9 1.00 1.00 C X 0.80 12.00 0.40 0.00
dated 17.7.2012
16 SPARE 415 ACTRI M kW 0.0 0.80 0.65 S 0.80 0.00 0.40 0.00

17 SPARE 415 ACTRIN P kW 0.0 0.80 0.65 S 0.80 0.00 0.40 0.00

18 RESERVED 415 ACTRIN P 5.00 kW 10.2 0.80 0.85 c X 0.80 5.88 0.40 0.00

SUB TOTAL 747.0 0.0


TOTAL LOAD ON BUS B
747 kVA
(NORMAL + INTERMITTENT)
Total Load on Bus-A 727 kVA
Total Load on Bus-B 747 kVA
Total load on Bus-A & B 1474 kVA
Total load on Bus-A & B with 10% margin 1621 kVA
415V ESSENTIAL SWITCHGEAR UNIT - 2

Load Rating Load Character


R Rated
Power Normal Intermittent
Item UNI/ Module
D
e No. KKS No. Service Description Volt NAT Type Power Unit Current Factor Efficiency BI Ope Load Capacity Ope Load Capacity Length Location Remarks Type
(Load
v side) (V) (A) Factor (kVA) Factor (kVA) (Mtrs.) of load

415V ESSENTIAL SWGR-2A

STANDARD BREAKER RATING


INCOMER FROM UNIT-2 SWGR-1 415 ACTRIN P 2000 kVA 2782.5 1.00 1.00 Incomer
SHALL BE SELECTED.
STANDARD BREAKER RATING
INCOMER FROM EDG-2 415 ACTRIN P 1500 kVA 2086.9 1.00 1.00 Incomer
SHALL BE SELECTED.

STANDARD BREAKER RATING


BUS COUPLER 415 ACTRIN kVA 0.0 1.00 1.00
SHALL BE SELECTED.

1 220 V DC UNIT-2 BATTERY CHARGER-1 415 ACTRIN P 325.00 kVA 452.2 0.80 1.00 C X 0.50 162.50 0.40 0.00 ASSUMED & UNVERIFIED

2 220 V DC STATION BATTERY CHARGER-2 415 ACTRIN P 105.00 kVA 146.1 0.80 1.00 C X 0.50 52.50 0.40 0.00 ASSUMED & UNVERIFIED

F 3 UNIT-2 UPS CHARGER A 415 ACTRIN P 160.00 kVA 222.6 0.80 1.00 C X 0.50 80.00 0.40 0.00 BASED ON DEC LATEST INPUT

4 BOILER AND AUXILIARIES - UNIT # 2


FROM DEC Electrical Load list Dtd
AUXILIARY ACTUATING MOTOR-1 415 ACTRI M 15.00 kW 30.7 0.80 0.85 C X 0.80 17.65 0.40 0.00
25/06/11
FROM DEC Electrical Load list Dtd
F Hydraulic coupling starting luboil pump motor 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/12, REV.F
STEAM-DRIVEN FEEDWATER PUMP LUBE-OIL
STANDBY OIL PUMP MOTOR-1 FROM DEC Electrical Load list Dtd
F 415 ACTRI M 30.00 kW 56.1 0.80 0.93 C X 0.80 32.26 0.40 0.00
BFP TURBINE LUBE OIL STANDBY PUMP 24/02/12, REV.F
MOTOR-1
OIL PUMP MOTOR OF PAF HYDRAULIC LUBE FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 C X 0.80 3.38 0.40 0.00
OIL STATION (PAF-1)-1 25/06/11
OIL PUMP MOTOR OF PAF HYDRAULIC LUBE FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 S 0.80 0.00 0.40 0.00
OIL STATION (PAF-2)-1 25/06/11
FROM DEC Electrical Load list Dtd
PAF MOTOR LUBE OIL PUMP (PAF-1)-1 415 ACTRI M 0.00 kW 0.0 0.80 0.65 S 0.80 0.00 0.40 0.00
25/06/11
FROM DEC Electrical Load list Dtd
PAF MOTOR LUBE OIL PUMP (PAF-2)-1 415 ACTRI M 0.00 kW 0.0 0.80 0.65 C X 0.80 0.00 0.40 0.00
25/06/11
POWER FOR HYDRAULIC OIL STATION MOTOR FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 C X 0.80 3.38 0.40 0.00
OF FDF (FDF-1)-1 25/06/11
POWER FOR HYDRAULIC OIL STATION MOTOR FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 C X 0.80 3.38 0.40 0.00
OF FDF (FDF-2)-1 25/06/11
POWER FOR LUBE OIL STATION MOTOR OF FROM DEC Electrical Load list Dtd
415 ACTRI M 1.10 kW 2.9 0.80 0.65 S 0.80 0.00 0.40 0.00
IDF (IDF-1)-1 25/06/11
POWER FOR LUBE OIL STATION MOTOR OF FROM DEC Electrical Load list Dtd
415 ACTRI M 1.10 kW 2.9 0.80 0.65 C X 0.80 1.69 0.40 0.00
IDF (IDF-2)-1 25/06/11

LOCALE CONTROL CABINET FOR


FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-1 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-1
LOCALE CONTROL CABINET FOR
FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-2 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-2
415V ESSENTIAL SWITCHGEAR UNIT - 2

Load Rating Load Character


R Rated
Power Normal Intermittent
Item UNI/ Module
D
e No. KKS No. Service Description Volt NAT Type Power Unit Current Factor Efficiency BI Ope Load Capacity Ope Load Capacity Length Location Remarks Type
(Load
v side) (V) (A) Factor (kVA) Factor (kVA) (Mtrs.) of load

LOCALE CONTROL CABINET FOR


FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-3 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-3

LOCALE CONTROL CABINET FOR


FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-4 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-4

LOCALE CONTROL CABINET FOR


FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-5 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-5

LOCALE CONTROL CABINET FOR


FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-6 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-6
LOCALE CONTROL CABINET FOR
FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-7 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-7
LOCALE CONTROL CABINET FOR
FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-8 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-8
FROM DEC Electrical Load list Dtd
BOILER SOOT BLOWER POWER CABINET 415 ACTRIN P 4.80 kW 8.3 0.80 1.00 I 0.80 0.00 X 0.40 2.40 2
25/06/11
FROM DEC Electrical Load list Dtd
FLAME SCANNER AMPLIFIER CABINET 240 ACMONO P 0.00 kW 0.0 0.80 1.00 C X 0.80 0.00 0.40 0.00 2
25/06/11
AIR PREHEATER GAP ADJUST CONTROL CABINET FROM DEC Electrical Load list Dtd
415 ACTRI P 8 kW 16.36760328 0.8 0.85 I 0.8 0 X 0.4 4.705882 2
FOR A & B SIDE-1 25/06/11
TURBINE GENERATOR AND AUXILIARIES - FROM DEC Electrical Load list Dtd
5
UNIT # 2 25/06/11
STEAM TURBINE JACKING OIL PUMP AC FROM DEC Electrical Load list Dtd
415 ACTRI M 55.00 kW 102.8 0.80 0.93 C X 0.80 59.14 0.40 0.00
MOTOR(NORMAL) 25/06/11
FROM DEC Electrical Load list Dtd
EH OIL MAIN OIL PUMP MOTOR-1 415 ACTRI M 45.00 kW 84.1 0.80 0.93 C X 0.80 48.39 0.40 0.00
25/06/11
FROM DEC Electrical Load list Dtd
EH OIL CIRCULATIONL PUMP MOTOR 415 ACTRI M 1.50 kW 4.0 0.80 0.65 C X 0.80 2.31 0.40 0.00
25/06/11
FROM DEC Electrical Load list Dtd
F BFP-TURBINE TURNING GEAR MOTOR-1 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
25/06/11
BYPASS SYSTEM OIL STATION (WITH LOCAL FROM DEC Electrical Load list Dtd
415 ACTRI P 15.00 kW 26.1 0.80 1.00 C X 0.80 15.00 0.40 0.00
CONTROL BOX)-1 25/06/11
FROM DEC Electrical Load list Dtd
6 SEALNG OIL AC MOTOR-1 415 ACTRI M 7.50 kW 15.3 0.80 0.85 S 0.80 0.00 0.40 0.00
25/06/11
FROM DEC Electrical Load list Dtd
7 SEALNG OIL RECIRCULATING AC MOTOR-1 415 ACTRI M 5.50 kW 11.3 0.80 0.85 C X 0.80 6.47 0.40 0.00
25/06/11
FURNACE GAS TEMP. PROBE RIGHT SIDE FROM DEC Electrical Load list Dtd
8 415 ACTRI P 5.00 kW 10.2 0.80 0.85 C X 0.80 5.88 0.40 0.00
LOCAL CONTROLCABINET 25/06/11
FROM DEC Electrical Load list Dtd
F 8 415V SPARE AC POWER-1 415 ACTRIN P 1.00 kW 1.7 0.80 1.00 C X 0.80 1.00 0.40 0.00
24/02/12, REV.F
FROM DEC Electrical Load list Dtd
F 8 240V SPARE AC POWER-1 240 ACMONO P 1.00 kW 5.2 0.80 1.00 S 0.80 0.00 0.40 0.00
24/02/12, REV.F
9 ESSENTIAL LIGHTING DB-1 415 ACTRI P 100.00 kVA 139.1 1.00 1.00 C X 0.80 80.00 0.40 0.00 ASSUMED & UNVERIFIED

10 SPARE 415 ACTRI M kW 0.0 0.80 0.65 S 0.80 0.00 0.40 0.00
415V ESSENTIAL SWITCHGEAR UNIT - 2

Load Rating Load Character


R Rated
Power Normal Intermittent
Item UNI/ Module
D
e No. KKS No. Service Description Volt NAT Type Power Unit Current Factor Efficiency BI Ope Load Capacity Ope Load Capacity Length Location Remarks Type
(Load
v side) (V) (A) Factor (kVA) Factor (kVA) (Mtrs.) of load

11 SPARE 415 ACTRIN P kW 0.0 0.80 0.65 S 0.80 0.00 0.40 0.00

12 RESERVED 415 ACTRIN P 5.00 kW 10.2 0.80 0.85 c X 0.80 5.88 0.40 0.00

SUB TOTAL 645.5 7.1

TOTAL LOAD ON BUS A


653 kVA
(NORMAL + INTERMITTENT)

415V ESSENTIAL SWGR-2B


STANDARD BREAKER RATING
INCOMER FROM UNIT-2 SWGR-2 415 ACTRIN P 2000 kVA 2782.5 1.00 1.00 Incomer
SHALL BE SELECTED.
STANDARD BREAKER RATING
TIE TO ESSENTIAL SWGR-1 415 ACTRIN P 250 kVA 347.8 1.00 1.00 C X 1.00 250.00 0.40 0.00 Incomer
SHALL BE SELECTED.

1 220 V DC UNIT-2 BATTERY CHARGER-2 415 ACTRIN P 325.00 kVA 452.2 1.00 1.00 c X 0.50 162.50 0.40 0.00 ASSUMED & UNVERIFIED

F 2 UNIT-2 UPS BYPASS TRANSFOMER 415 ACTRIN P 160.00 kVA 222.6 1.00 1.00 S 0.50 0.00 0.40 0.00 BASED ON DEC LATEST INPUT

3 BOILER AND AUXILIARIES - UNIT # 2


Added as per ACPL/EIPL Comments
4 FURNACE FLAME TV FOR A & B SIDE 240 ACMONO P 2 kW 16.0 0.80 0.65 C X 0.80 3.08 0.40 0.0
dated 17.7.2012
FROM DEC Electrical Load list Dtd
AUXILIARY ACTUATING MOTOR-1 415 ACTRI M 15.00 kW 30.7 0.80 0.85 C X 0.80 17.65 0.40 0.00
25/06/11
STEAM-DRIVEN FEEDWATER PUMP LUBE-OIL
STANDBY OIL PUMP MOTOR-2 FROM DEC Electrical Load list Dtd
F 415 ACTRI M 30.00 kW 56.1 0.80 0.93 C X 0.80 32.26 0.40 0.00
BFP TURBINE LUBE OIL STANDBY PUMP 24/02/12, REV.F
MOTOR-1
OIL PUMP MOTOR OF PAF HYDRAULIC LUBE FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 C X 0.80 3.38 0.40 0.00
OIL STATION (PAF-1)-2 25/06/11
OIL PUMP MOTOR OF PAF HYDRAULIC LUBE FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 S 0.80 0.00 0.40 0.00
OIL STATION (PAF-2)-2 25/06/11
FROM DEC Electrical Load list Dtd
PAF MOTOR LUBE OIL PUMP (PAF-1)-2 415 ACTRI M 0.00 kW 0.0 0.80 0.65 S 0.80 0.00 0.40 0.00
25/06/11
FROM DEC Electrical Load list Dtd
PAF MOTOR LUBE OIL PUMP (PAF-2)-2 415 ACTRI M 0.00 kW 0.0 0.80 0.65 C X 0.80 0.00 0.40 0.00
25/06/11
POWER FOR HYDRAULIC OIL STATION MOTOR FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 C X 0.80 3.38 0.40 0.00
OF FDF (FDF-1)-2 25/06/11
POWER FOR HYDRAULIC OIL STATION MOTOR FROM DEC Electrical Load list Dtd
415 ACTRI M 2.20 kW 5.9 0.80 0.65 S 0.80 0.00 0.40 0.00
OF FDF (FDF-2)-2 25/06/11
POWER FOR LUBE OIL STATION MOTOR OF FROM DEC Electrical Load list Dtd
415 ACTRI M 1.10 kW 2.9 0.80 0.65 C X 0.80 1.69 0.40 0.00
IDF (IDF-1)-2 25/06/11
POWER FOR LUBE OIL STATION MOTOR OF FROM DEC Electrical Load list Dtd
415 ACTRI M 1.10 kW 2.9 0.80 0.65 S 0.80 0.00 0.40 0.00
IDF (IDF-2)-2 25/06/11
LOCALE CONTROL CABINET FOR LUBRICATION OIL-
FROM DEC Electrical Load list Dtd
F 1 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
POWER FOR LUBE OIL STATION MOTOR OF MILL-1
24/02/12, REV.F
415V ESSENTIAL SWITCHGEAR UNIT - 2

Load Rating Load Character


R Rated
Power Normal Intermittent
Item UNI/ Module
D
e No. KKS No. Service Description Volt NAT Type Power Unit Current Factor Efficiency BI Ope Load Capacity Ope Load Capacity Length Location Remarks Type
(Load
v side) (V) (A) Factor (kVA) Factor (kVA) (Mtrs.) of load

LOCALE CONTROL CABINET FOR LUBRICATION OIL-


FROM DEC Electrical Load list Dtd
F 2 POWER FOR LUBE OIL STATION MOTOR OF MILL- 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
2
24/02/12, REV.F

LOCALE CONTROL CABINET FOR LUBRICATION OIL-


FROM DEC Electrical Load list Dtd
F 3 POWER FOR LUBE OIL STATION MOTOR OF MILL- 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
3
24/02/12, REV.F

LOCALE CONTROL CABINET FOR LUBRICATION OIL-


FROM DEC Electrical Load list Dtd
F 4 POWER FOR LUBE OIL STATION MOTOR OF MILL- 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
4
24/02/12, REV.F

LOCALE CONTROL CABINET FOR


FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-5 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-5
LOCALE CONTROL CABINET FOR
FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-6 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-6
LOCALE CONTROL CABINET FOR
FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-7 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-7
LOCALE CONTROL CABINET FOR
FROM DEC Electrical Load list Dtd
F LUBRICATION OIL-8 POWER FOR LUBE OIL 415 ACTRI M 11.00 kW 22.5 0.80 0.85 C X 0.80 12.94 0.40 0.00
24/02/12, REV.F
STATION MOTOR OF MILL-8

FROM DEC Electrical Load list Dtd


BOILER SOOT BLOWER POWER CABINET 415 ACTRIN P 4.80 kW 8.3 0.80 1.00 S 0.80 0.00 0.40 0.00 2
25/06/11
FROM DEC Electrical Load list Dtd
FLAME SCANNER AMPLIFIER CABINET 415 ACTRIN P 0.00 kW 0.0 0.80 1.00 C X 0.80 0.00 0.40 0.00
25/06/11 2
TURBINE GENERATOR AND AUXILIARIES - FROM DEC Electrical Load list Dtd
4
UNIT # 2 25/06/11
FROM DEC Electrical Load list Dtd
STEAM TURBINE TURNING GEAR MOTOR 415 ACTRI M 15.00 kW 30.7 0.80 0.85 C X 0.80 17.65 0.40 0.00
25/06/11
STEAM TURBINE LUBE OIL AUXILIARY PUMP FROM DEC Electrical Load list Dtd
415 ACTRI M 55.00 kW 102.85 0.80 0.93 C X 0.80 59.14 0.40 0.00
MOTOR 25/06/11
FROM DEC Electrical Load list Dtd
EH OIL MAIN OIL PUMP MOTOR-2 415 ACTRI M 45.00 kW 84.15 0.80 0.93 S 0.80 0.00 0.40 0.00
25/06/11
FROM DEC Electrical Load list Dtd
EH OIL TRANSFER PUMP MOTOR 415 ACTRI M 1.50 kW 4.01 0.80 0.65 C X 0.80 2.31 0.40 0.00
25/06/11
FROM DEC Electrical Load list Dtd
F BFP-TURBINE TURNING GEAR MOTOR-2 415 ACTRI M 11.00 kW 22.51 0.80 0.85 S 0.80 0.00 0.40 0.00
24/02/12, REV.F
BYPASS SYSTEM OIL STATION (WITH LOCAL FROM DEC Electrical Load list Dtd
415 ACTRI P 15.00 kW 30.69 0.80 0.85 C X 0.80 17.65 0.40 0.00
CONTROL BOX)-2 25/06/11
FROM DEC Electrical Load list Dtd
5 SEALNG OIL AC MOTOR-2 415 ACTRI M 7.50 kW 15.34 0.80 0.85 C X 0.80 8.82 0.40 0.00
25/06/11
FROM DEC Electrical Load list Dtd
6 BOILER LOCAL IGNITION CABINET 415 ACTRI P 0.00 kW 0.0 0.80 0.65 S 0.80 0.00 0.40 0.00 2
25/06/11
FURNACE GAS TEMP. PROBE LEFT SIDE FROM DEC Electrical Load list Dtd
7 415 ACTRI P 5.00 kW 10.23 0.80 0.85 C X 0.80 5.88 0.40 0.00
LOCAL CONTROLCABINET 25/06/11
AIR PREHEATER FIRE DETECTION CABINET
FROM DEC Electrical Load list Dtd
F 8 FOR A & B SIDE 415 ACTRI P 1.00 kW 1.74 0.80 1.00 C X 0.80 1.00 0.40 0.00
24/02/12, REV.F
415V SPARE AC POWER -2
415V ESSENTIAL SWITCHGEAR UNIT - 2

Load Rating Load Character


R Rated
Power Normal Intermittent
Item UNI/ Module
D
e No. KKS No. Service Description Volt NAT Type Power Unit Current Factor Efficiency BI Ope Load Capacity Ope Load Capacity Length Location Remarks Type
(Load
v side) (V) (A) Factor (kVA) Factor (kVA) (Mtrs.) of load
FROM DEC Electrical Load list Dtd
F 8 240V SPARE AC POWER-2 240 ACMONO P 1.00 kW 5.21 0.80 1.00 S 0.80 0.00 0.40 0.00
24/02/12, REV.F
AIR PREHEATER GAP ADJUST CONTROL FROM DEC Electrical Load list Dtd
F 9 415 ACTRI P 8.00 kW 16.37 0.80 0.85 0.80 0.00 0.40 0.00
CABINET FOR A & B SIDE-2 24/02/12, REV.F

FLAME SCANNING COOLING FAN AC MOTOR FROM DEC Electrical Load list Dtd
10 415 ACTRI P 15.00 kW 26.09 0.80 1.00 C X 0.80 15.00 0.40 0.00
LOCAL CONTROL CABINET 25/06/11
11 COMMUNICATION PANEL 415 ACTRI P 6.00 kW 10.43 0.80 1.00 C X 0.80 6.00 0.40 0.00 Assumed & unverified

12 AVIATION OBSTRUCTION LIGHTING FEEDER 415 ACTRI P 10.00 kW 17.39 0.80 1.00 C X 0.80 10.00 0.40 0.00 Assumed & unverified

13 ESSENTIAL LIGHTING DB-2 415 ACTRI P 100.00 kVA 139.12 1.00 1.00 C X 0.80 80.00 0.40 0.00 Assumed & unverified
Added as per ACPL/EIPL Comments
14 Chimney emergency load 415 ACTRI P 50.00 kVA 69.6 1.00 1.00 C X 0.80 40.00 0.40 0.00
dated 17.7.2012
Added as per ACPL/EIPL Comments
15 switchyard emergency load 415 ACTRI P 15.00 kVA 20.9 1.00 1.00 C X 0.80 12.00 0.40 0.00
dated 17.7.2012
16 SPARE 415 ACTRI M kW 0.00 0.80 0.65 S 0.80 0.00 0.40 0.00

17 SPARE 415 ACTRIN P kW 0.00 0.80 0.65 S 0.80 0.00 0.40 0.00

18 RESERVED 415 ACTRIN P 5.00 kW 10.23 0.80 0.85 c X 0.80 5.88 0.40 0.00

SUB TOTAL 824.6 0.0

TOTAL LOAD ON BUS B


825 kVA
(NORMAL + INTERMITTENT)
Total Load on Bus-A 653 kVA

Total Load on Bus-B 825 kVA

Total load on Bus-A & B 1477 kVA

Total load on Bus-A & B with 10% margin 1625 kVA