Application Note 51331 Replacing the EGS-01 with EGS Full Authority
Contents
Woodward i
Replacing the EGS-01 with EGS Full Authority Application Note 51331
ii Woodward
Application Note 51331 Replacing the EGS-01 with EGS Full Authority
Woodward iii
Replacing the EGS-01 with EGS Full Authority Application Note 51331
iv Woodward
Application Note 51331 Replacing the EGS-01 with EGS Full Authority
Chapter 1.
General Information
Assumptions
1. Customer has read the entire EGS Control System Application Manual
26321.
2. Customer has understood and complied with all of the warnings highlighted
in the Manual 26321.
3. Customer understands that they are strongly encouraged and expected to
thoroughly develop and test specific EGS control schemes for their gas
engine application under normal and extreme operating conditions.
Introduction
Woodward’s EGS Full Authority can be used as a functional replacement for the
EGS-01 control. The EGS Full Authority was designed with many new features
and functions that are not built into the EGS-01. However, there are a few items
that may need special attention to make the EGS-02 function in an EGS-01
system.
Differences Summary
Due to internal control design differences, the customer wiring to the control
terminals is different. This application note illustrates the differences in wiring,
sensors, communication interfaces, and Service Tool.
Woodward 1
Replacing the EGS-01 with EGS Full Authority Application Note 51331
Inputs Differences
Inputs EGS-01 EGS Full Authority
Power supply Nominal: 10–32 Vdc, minimum Nominal: 8–32 Vdc, minimum
7 Vdc 6 Vdc; 15 W nominal (not
including driven loads)
Speed Sensor VR or Active Sensor VR or Active Sensor
2 Woodward
Application Note 51331 Replacing the EGS-01 with EGS Full Authority
Outputs Differences
Outputs EGS-01 EGS Full Authority
Throttle PWM - Push-Pull, 0–24 Vdc, PWM - Push-Pull, 0–24 Vdc,
Command 1000 Hz Frequency variable
Wastegate PWM - Push-Pull, 0–24 Vdc, PWM - Push-Pull, 0–24 Vdc,
Output 1000 Hz Frequency variable
TecJet Power 6 A steady state, 10 A peak for 1 None
sec
TecJet Keyswitch 10 mA max, activates the TecJet Use one of the speed switch
when the engine is rolling outputs and an interposing
relay
Fault Outputs Form C, dry contacts Low side relay drivers
Major Alarm De-energizes on Engine De-energizes on Engine
Shutdown Condition Shutdown Condition
Minor Alarm De-energizes on Control Warning De-energizes on Control
Condition Warning Condition
CPU OK De-energizes on Control De-energizes on Control
Watchdog Condition Watchdog Condition
Speed Switches None Individually configurable for
speed limit activation
AUX Power 5 Vdc, 70 mA for sensor power 5 Vdc, 300 mA for sensor
power
LED Indications Power, Fuel On, Alarm, Shutdown None
Communications Differences
Communications EGS-01 EGS Full Authority
Engine Control Custom CAN to TecJet(s) and J1939 CAN to TecJet(s),
Network FireFly only FireFly, IC-920, easYgen™
3200,
Plant Modbus® * Slave, RS-232 DB-9M J1939 CAN, CANopen on rev
Communications B
Service Serial RS-232 DB-9M, EGS DOS Tool RS-485 on main connectors,
Port custom protocol ServLink for Toolkit
*—Modbus is a trademark of Schneider Automation Inc.
Functionality Differences
Functionality EGS-01 EGS Full Authority
Speed Control Option Included
Mono AFR Option Included
System
Stereo AFR Option Not currently scheduled to
System include
Single TecJet Option Included
AFR System
Dual TecJet AFR Option Included
System
Dual Fuel AFR Not included Option
System – Fuel
Blending
Woodward 3
Replacing the EGS-01 with EGS Full Authority Application Note 51331
Detailed Comparison
Analog Inputs
The EGS-01 has software configurable two-wire grounded or ungrounded analog
inputs. The EGS Full Authority has fixed one-wire analog inputs with J1-B24
(XDRG_B) as common return. See Figure 1-14.
Speed Sensor
Both the EGS-01 and the EGS Full Authority are capable of using Magnetic
Pick-up (Variable Reluctance sensor) or Active Pick-Up (ferrous or magnetic
target Hall-effect pickup).
MAP Sensor
The standard Manifold Absolute Pressure sensor used for the EGS-01 is
compatible with the EGS Full Authority. However, the EGS Full Authority is
capable of using a sensor that provides 0–5 Vdc; a 5 Vdc Auxiliary supply is
available to power the sensor.
MAT Sensor
The standard Manifold Air Temperature sensor used for the EGS-01 is not
compatible with the EGS Full Authority. The EGS-01 uses a Pt100 RTD type
sensor. The EGS Full Authority MAT input consists of an internal 2.21 k pull-up
resistor to 5.0 Vdc and is best suited for a Negative Temperature Coefficient
(NTC) Thermistor probe. The input voltage can be calculated from the resistance
curve of the sensor and defined in an 8-point calibration curve in the EGS Full
Authority. The EGS Full Authority firmware revision B and later will also support a
PWM MAT Sensor.
kW, CH4%, Load Reference, Speed Bias, Throttle Position Sensor Inputs
The EGS-01 can accept these sensors via 0–20 mAdc/0–10 Vdc or 0–5 Vdc
software selectable inputs. The EGS Full Authority can accept these inputs as
0–5 Vdc.
UEGO Sensor
The standard NGK UEGO sensor with converter used for the EGS-01 is
compatible with the EGS Full Authority. The EGS Full Authority is also capable of
using the Bosch LSU 4.2 UEGO sensor directly without using a converter box.
Discrete Inputs
All EGS-01 Discrete Inputs are common to 24 Vdc return and close to 24 Vdc
positive to activate. All EGS Full Authority Discrete Inputs are activated by
closing a switch to J1-B24 (XDRG_B). See Figure 1-15.
4 Woodward
Application Note 51331 Replacing the EGS-01 with EGS Full Authority
Circuit Breaker Auxiliary Contact
EGS-01 does not support the use of a generator CB AUX input. EGS Full
Authority CB AUX is closed when the generator circuit breaker is closed and is
used for multiple speed control dynamics such as offline/online.
Fuel On Contact
Both the EGS-01 and EGS Full Authority use this contact input to allow the
throttle and TecJet to open.
Reset Contact
The EGS-01 and EGS Full Authority both use this contact to Reset internal
Faults. However, the EGS-01 triggers this condition when the input current to this
terminal rises above 10 mA. The EGS Full Authority activation of this function is
the same as the other Discrete Inputs; close this terminal to J1-B24 (XDRG_B).
Discrete Outputs
The EGS-01 contains Form C dry contact relays. The EGS-02 utilizes low-side
relay drivers with one side of the coil connected to the power supply positive. An
external relay must be used. See Figure 1-16.
System Devices
The EGS-01 is the main controller that is the integral part of the EGS system.
The EGS Full Authority is compatible with most Woodward/Deltec system
devices supported by the EGS-01. In most cases the EGS Full Authority will
require system device updates to the firmware or reconfiguration of the tunable
settings.
TecJet™
The EGS Full Authority is not compatible with the old Deltec design TecJet
20, 40, and 50.
The EGS Full Authority is compatible with all TecJet 52 (actuated by
F-Series).
The EGS Full Authority is compatible with TecJet 50+, TecJet 50+ Precision
Flow, and TecJet 110 firmware 5418-1232 E or greater.
Woodward 5
Replacing the EGS-01 with EGS Full Authority Application Note 51331
EGS-01 manages the TecJet keyswitch input through terminal 9 for TecJet 1 and
terminal 49 for TecJet 2. EGS Full Authority can be configured to activate the
TecJet Keyswitch input by using a Speed Switch output. These outputs are low-
side drivers, and the TecJet needs its input pulled-up to the power supply
voltage. Thus, a relay is needed to pull the TecJet Keyswitch voltage up (see
Figures 1-2 & 1-3).
The TecJet CAN connection for the EGS Full Authority is the same as the
EGS-01; an external network termination resistor is required.
FireFly™
The EGS-01 communicates to the FireFly via CAN. EGS-01 sends the load
signal and gathers ignition timing information through the proprietary CAN link.
The EGS Full Authority communicates to the FireFly via CAN J1939 proprietary
messages. EGS Full Authority sends the load signal and gathers knock
information through the J1939 CAN link.
The EGS Full Authority is compatible with FireFly Voltage Load input
1752-015 revision E and later.
The EGS Full Authority is compatible with FireFly Current Load input
1752-227 revision D and later.
The EGS Full Authority is compatible with FireFly Current Load input
1752-1033 revision NEW and later.
The FireFly Service Tool will allow firmware update to allow EGS Full Authority
compatibility. Consult the Woodward factory for a copy of the correct firmware
file.
The FireFly physical CAN connection for the EGS Full Authority is the same as
the EGS-01; an external network termination resistor is required on the EGS
side.
External
Ignition Timing Signal
The EGS-01 is not compatible with CAN communication to any ignition product.
The EGS-01 can receive external Ignition timing information from the FireFly for
Gas Quality Closed-Loop Total Efficiency mapping.
The EGS Full Authority cannot take an analog signal from an external Ignition
timing device. The EGS Full Authority communicates with an IC-92x to receive its
timing signal and diagnostics information as well as sending timing advance and
global energy values.
6 Woodward
Application Note 51331 Replacing the EGS-01 with EGS Full Authority
Wiring
The EGS-01 makes use of differential inputs for analog signals; this method
increases immunity to Common Mode noise and reduces the likelihood of signal-
to-signal interference. The EGS Full Authority uses single-ended analog inputs
with a common return; take care to avoid increased noise problems and ground
loops. In some cases, ground-loop isolators and/or ac filters (capacitors) may be
required. This makes shielding and grounding absolutely critical; wire-run
locations and routing may be difficult to fix if problems arise. The design for the
EGS Full Authority was optimized for on-engine mounting with short wire runs; it
is likely that the control specifications for electromagnetic susceptibility, immunity,
and transmission will be degraded if any wire lengths exceed 30 meters or power
supply lines exceed 10 meters.
Location
The EGS-01 is panel-mounted.
Termination
The EGS-01 utilizes Phoenix terminations.
Service Tool
The EGS-01 Service Tool is a DOS-based program and communicates via
RS-232 through a DB-9M connector. The EGS-01 Service Tool is a fixed text-
based tool and is not compatible with Windows 2000, Windows NT, Windows
XP, or Windows Vista.
The EGS Full Authority Service Tool utilizes Woodward Toolkit and
communicates via RS-485 through a RS-232 or USB converter. Toolkit is a
flexible & powerful user adaptable graphical interface tool and is compatible with
Windows Vista, Windows XP, and Windows 2000. Toolkit uses Microsoft.NET
version 2 or greater (supplied on every CD-ROM that also has Toolkit).
Woodward 7
Replacing the EGS-01 with EGS Full Authority Application Note 51331
8 Woodward
Application Note 51331 Replacing the EGS-01 with EGS Full Authority
Woodward 9
Replacing the EGS-01 with EGS Full Authority Application Note 51331
10 Woodward
Application Note 51331 Replacing the EGS-01 with EGS Full Authority
Woodward 11
Replacing the EGS-01 with EGS Full Authority Application Note 51331
12 Woodward
Application Note 51331 Replacing the EGS-01 with EGS Full Authority
Chapter 2.
Product Support and Service Options
OEM or Packager Support: Many Woodward controls and control devices are
installed into the equipment system and programmed by an Original Equipment
Manufacturer (OEM) or Equipment Packager at their factory. In some cases, the
programming is password-protected by the OEM or packager, and they are the best
source for product service and support. Warranty service for Woodward products
shipped with an equipment system should also be handled through the OEM or
Packager. Please review your equipment system documentation for details.
Woodward 13
Replacing the EGS-01 with EGS Full Authority Application Note 51331
Replacement/Exchange: Replacement/Exchange is a premium program
designed for the user who is in need of immediate service. It allows you to
request and receive a like-new replacement unit in minimum time (usually within
24 hours of the request), providing a suitable unit is available at the time of the
request, thereby minimizing costly downtime.
This option allows you to call your Full-Service Distributor in the event of an
unexpected outage, or in advance of a scheduled outage, to request a
replacement control unit. If the unit is available at the time of the call, it can
usually be shipped out within 24 hours. You replace your field control unit with
the like-new replacement and return the field unit to the Full-Service Distributor.
Flat Rate Repair: Flat Rate Repair is available for many of the standard
mechanical products and some of the electronic products in the field. This
program offers you repair service for your products with the advantage of
knowing in advance what the cost will be.
Flat Rate Remanufacture: Flat Rate Remanufacture is very similar to the Flat
Rate Repair option, with the exception that the unit will be returned to you in “like-
new” condition. This option is applicable to mechanical products only.
When shipping the item(s), attach a tag with the following information:
return number;
name and location where the control is installed;
name and phone number of contact person;
complete Woodward part number(s) and serial number(s);
description of the problem;
instructions describing the desired type of repair.
Packing a Control
Use the following materials when returning a complete control:
protective caps on any connectors;
antistatic protective bags on all electronic modules;
packing materials that will not damage the surface of the unit;
at least 100 mm (4 inches) of tightly packed, industry-approved packing
material;
a packing carton with double walls;
a strong tape around the outside of the carton for increased strength.
Replacement Parts
When ordering replacement parts for controls, include the following information:
the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
the unit serial number, which is also on the nameplate.
14 Woodward
Application Note 51331 Replacing the EGS-01 with EGS Full Authority
Engineering Services
Woodward’s Full-Service Distributors offer various Engineering Services for our
products. For these services, you can contact the Distributor by telephone or by
email.
Technical Support
Product Training
Field Service
Technical Support is available from your equipment system supplier, your local
Full-Service Distributor, or from many of Woodward’s worldwide locations,
depending upon the product and application. This service can assist you with
technical questions or problem solving during the normal business hours of the
Woodward location you contact.
You can also contact the Woodward Customer Service Department at one of the
following Woodward facilities to obtain the address and phone number of the
nearest facility at which you can obtain information and service.
For the most current product support and contact information, please visit our
website directory at www.woodward.com/directory.
Woodward 15
Replacing the EGS-01 with EGS Full Authority Application Note 51331
Technical Assistance
If you need to contact technical assistance, you will need to provide the following information.
Please write it down here before contacting the Engine OEM, the Packager, a Woodward
Business Partner, or the Woodward factory:
General
Your Name
Site Location
Phone Number
Fax Number
Number of Cylinders
Type of Fuel (gas, gaseous, diesel,
dual-fuel, etc.)
Power Output Rating
Application (power generation, marine,
etc.)
Control/Governor Information
Control/Governor #1
Serial Number
Control/Governor #2
Serial Number
Control/Governor #3
Serial Number
Symptoms
Description
If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.
16 Woodward