Sei sulla pagina 1di 7

Modular Multilevel Converter for Direct MVDC

Connection of Offshore Wind Farms

Joseph Carr, Debrup Das, Jun Li, Jiuping Pan Stephan Ebner, Oscar Apeldoorn
ABB Corporate Research ABB Power Conversion
ABB ABB
Raleigh, NC Turgi, Switzerland

Abstract—This paper introduces a new concept for offshore The proposed direct MVDC connection requires that each
wind turbine electrical architectures for wind farms with MVDC turbine would produce a high enough DC voltage output, say
collection grids. With the proposed pre-transformer wind turbine 50-80 kVDC, suitable for transmission to shore. TABLE
drivetrain arrangement, the AC output of the wind turbine illustrates two basic potential wind turbine drivetrain options
generator is transformed to a higher voltage by a step-up
capable of doing so. The two-stage arrangement requires a dc-
transformer and then rectified to a corresponding DC voltage by
an active ac-dc converter. A modular multilevel converter dc converter, which is typically composed of three sub-stages
(MMC) is used for the rectifier to achieve the variable frequency - an inverter, a transformer, and a rectifier, results in higher
AC to DC power conversion. The MMC has been shown to have complexity and lower efficiency. The second option is
burdensome design constraints at low frequency. This paper preferred one where the AC output of the wind turbine
demonstrates that these design constraints are not applicable for generator is transformed to a higher voltage by a step-up
the wind turbine application and that the MMC is a good transformer and then rectified to a corresponding DC voltage
candidate for the wind turbine rectifier. by an active ac-dc converter. This arrangement strikes a
balance between the complexity, efficiency, and design
Keywords—Offshore Wind, MMC, Modular Multilevel
Converter, MVDC, wind farm collection grid
requirements.
TABLE I. DC DRIVETRAIN ARRANGEMENT OPTIONS
I. INTRODUCTION
Offshore wind resources are predicted to be a key part of Simplified one-line arrangements Typical generator ratings
the energy portfolio in Europe, North America, and China, Two-stage
Voltage: 0.69…3.3 kV
reaching a total of 153 GW by 2030 [1]. The U.S. Department
~ = ~
~ = ~ = Frequency: 10…120 Hz
of Energy (DOE) unveiled a plan to install 54 GW of offshore
energy by 2030 [2], more than 50% of which is located within Pre-transformer
Voltage: 0.69…3.3 kV
70 km of shore [3]. This is backed by a National Renewable
~
~ = Frequency: 50…120 Hz
Energy Laboratory (NREL) study that showed that it is
feasible to build 54 GW of offshore wind energy in depths less
than 30 meters by 2030 [4]. The generator output in the pre-transformer arrangement
falls within fairly standard ranges for wind turbine generators.
Offshore wind farms present a challenging environment
The transformer increases the voltage to a rated level of 33 to
for construction and maintenance, both for harsh conditions 72 kVAC for input to the rectifier. This high voltage can be
and for remoteness. Capital expenditure (CapEx) and challenging for standard rectifier designs, so a modular
operation and maintenance expenditures (OpEx) are multilevel converter (MMC) is recommended to implement
consequently high. Any reduction in the levelized cost of this system. This converter will be required to adapt to a range
energy (LCOE) is therefore essential, and measures which of voltage and frequency outputs as the wind speed changes. It
reduce the number of offshore components are particularly is known that the MMC has some problems operating at low
valuable. The cost of electrical infrastructure, including cables frequency [7 - 9], but it will be shown in this paper that the
and the offshore substation, approach about 18% of the total MMC can be an appropriate choice for the wind turbine
CapEx of the offshore system [5]. A new direct MVDC generator.
connection for near-to-shore (< 70 km) offshore wind farms
has been proposed which may reduce the electrical II. WIND TURBINE AND PERMANENT MAGNET
infrastructure costs by up to 20 to 25% [6]. This is SYNCHRONOUS GENERATOR
accomplished largely by reducing the cable requirement and Most offshore wind farms make use of permanent magnet
eliminating the offshore substation. Additionally, for the synchronous generators (PMSGs) to convert the mechanical
proposed solution, the on-shore substation components are power collected by the wind turbine to electrical power. This
easier to access and maintain. assembly is shown in the top of Fig. 1. The maximum power

978-1-4673-7151-3/15/$31.00 ©2015 IEEE 976


design requirements for the module capacitor and arm
inductor of the MMC. The design of these passives for
operation with variable wind speed is shown in the following
section.
III. MMC MODULE CAPACITOR AND ARM INDUCTOR DESIGN
The schematic of the MMC is shown in Fig. 2. The
converter is made up of modules on three legs, U, V, and W,
with upper (U) and lower (D) arms. This MMC uses half-
bridge modules with a capacitor, C, which is designed to
provide a portion of the DC bus voltage with a limited ripple,
often less than 5%. Each arm has an inductor, L, which
suppresses the AC components of the circulating currents,
minimizes the current ripple on the phase currents, and limits
the current in the event of a DC bus fault. These components
are designed to have minimum volume, due to the limited
space on available on the wind turbine tower. However, it has
been seen that the volume of these filter components increases
unmanageably at low frequency operation [7 - 9]. This paper
provides a step-by-step design for these components in the
variable frequency and power environment of the offshore
wind farm to show that they maintain a manageable volume.
A. Module Capacitance
Fig. 1: Wind turbine and PMSG schematic (top) and turbine power
(bottom) The module capacitance C is selected in order to limit the
capacitor voltage ripple during normal operation. This ripple
is influenced by the arm current, iARM, and the module control
produced by these turbines is proportional to the cube of the
wind speed, VW, per the relationship in (1), and shown in the (as the current only flows through the capacitor when the
bottom of Fig. 1 [8]. The mechanical speed and fundamental module is in the ON state). The equations for arm current,
electrical frequency at maximum power, ȦM and Ȧ1 modulation index, m, and arm voltage are given in (5) through
respectively, are proportional to the wind speed, as is the (7), respectively.
voltage, EA, produced by the machine. The phase voltage, vߔ, iARM = iCIRC + ½Iĭcos(Ȧ1t – ș) (5)
at the terminal of the machine is therefore also proportional to
the wind speed. The relationship of the electrical frequency and m = 2Vĭ/VDC (6)
phase voltage with the wind speed are shown in (2) and (3),
vARM = Vĭcos(Ȧ1t) (7)
respectively. The electrical power is the product of the voltage
and current and, neglecting losses, is equal to the mechanical The arm current has a component from the AC phase current,
power produced by the turbine. The current, iߔ, can therefore iĭ, and the internal circulating current, iCIRC. Iij is the peak AC
be found from (1) and (3) to be proportional to the square of phase current magnitude, Ȧ1 is the fundamental frequency of
the wind speed, as shown in (4). the generator, and ș is the phase shift angle between the AC
PT = ½ȡACPVW3 (1) phase voltage and current. The peak phase voltage is Vĭ.
Recall that both phase current magnitude and frequency vary
Ȧ1 = k1VW (2) with the wind speed. It is assumed that proper design of the
vĭ = k2VW (3) arm inductor and circulating current controller will eliminate
2
the AC portions of the circulating current, so it does not
iĭ = k3VW (4) contribute to the ripple. The arm current can therefore be
Wind turbines with PMSGs make use of a full converter to considered to be equal to one-half of the AC phase current.
deal with the variable frequency and voltage produced by the The module control can be accounted for by considering
generator as the wind speed varies. This converter is moved to the modulation index m of the converter. The modulation
the high voltage side of the transformer in the pre-transformer index provides a measure of the percentage of time that a
drivetrain shown in TABLE I, so a high voltage converter module is in the ON versus the OFF state, and is given as the
topology is recommended for this topology. Modular ratio between the peak AC phase voltage Vߔ and DC bus
multilevel converters, MMCs, have been successfully applied voltage VDC.
to HVDC applications, but have been shown to have
challenges during low frequency operation [7 - 9]. The ripple can be calculated from the arm current and
Fortunately, low frequency operation for wind turbine systems voltage by considering the change in energy stored in the
corresponds to lower power operations, which reduces the capacitors over one cycle of the generator fundamental

977
Fig. 2 Modular Multilevel Converter Schematic

frequency [9]. This change in energy, or power, is calculated energy stored in the capacitor and the ripple in the capacitor’s
by multiplying the arm current (5) by the voltage across the voltage.
arm (7). It can be assumed that the energy stored in the arm is
eCAP = ½CVCAP2 (12)
evenly divided among the N modules on the arm, such that the
2
capacitor energy eCAP is equal to the arm energy divided by N. eCAP,MAX = ½C(VAVG + ½ǻV) (13)
2
eARM = S /(12mȦ1)*[4sin(Ȧ1t – ș) – msin(2Ȧ1t – ș) (8)
eCAP,MIN = ½C(VAVG – ½ǻV) (14)
– 2m2sin(Ȧ1t)cos(ș)]
ǻeCAP = ǻeARM /N = eCAP,MAX - eCAP,MIN = (15)
ǻeARM = max(eARM) – min(eARM) (9) CǻVVAVG

ǻeCAP= (ǻeARM) /N (10) C = (ǻeARM) /(NǻVVAVG) (16)

VAVG = VDC /(2N) (11) To start, it is noted that the energy stored in the capacitor
is proportional to the square of the voltage across the
The term S is the power of the converter in VA, considering capacitor, as described in (12). The maximum energy stored in
both real and reactive components, and is three times the the capacitor is found then the voltage across the capacitor is
product of the phase voltage and current magnitudes (recall at its maximum value. This occurs when the ripple is at its
that both will vary with the wind speed and that power, S, maximum value, and the voltage across the capacitor is equal
varies with the cube of the wind speed). The stored energy, to its average value, VDC/2N as seen in (10), plus the ripple.
and hence the capacitor ripple, can be seen to depend on the Similarly, the energy in the capacitor is at its minimum when
power S delivered by the generator, the ratio m of the phase the voltage across the capacitor is at its minimum; i.e. when
voltage to the dc bus voltage, the frequency Ȧ1 of the the ripple is at its minimum. The maximum and minimum
generator, and time t. The dependence on frequency Ȧ1 gives energy in the capacitor can be found in (13) and (14).
rise to the difficulty in operating at low frequencies – the
energy ripple is inversely proportional to frequency, so will The change in energy stored in the capacitor over one cycle
of the generator fundamental frequency is found by subtracting
become quite large at low frequency operation. A larger
the minimum energy in the capacitor, (14), from the maximum
capacitance would therefore be required to limit the voltage
energy stored in the capacitor, (13). This gives the relationship
ripple arising from this energy. in (15), which gives an explicit link between the energy stored
The average voltage across the capacitor, Vavg, is equal to in the arm, (9), and the voltage ripple ǻV. The capacitance
the arm voltage, Vdc/2, divided by the number of capacitors, required to achieve a desired ripple can be found by
and the capacitor ripple is defined as ǻV. The desired substituting (11) into (15) and solving for C, resulting in the
capacitor voltage ripple is set by the designer, and is often on relationship shown in (16). An example of the change in stored
the order of 2% to 10% of the average capacitor voltage. energy and associated voltage ripple is shown in Fig..
Equations (11) through (15) show the relationship between the

978
The voltage applied to the inductors during the imbalance
is equal to the average module voltage, (11). The change in
current, di, is some factor, kRIPPLE, of the peak rated phase
current. It was previously assumed that the AC portion of the
arm current was small, so the current ripple factor is selected
to ensure that this assumption is valid. Current ripples less
than 5-15% of the peak rated phase current are typically
sufficient to keep this assumption valid. The change in time,
dt, is equal to the duty cycle D of the module times the module
switching period Tsw (or the inverse of the switching frequency
fsw) divided by the number N of modules in series. The duty
cycle is continuously changing, so the worst case scenario of a
100% duty cycle is assumed. The time is impacted the number
of modules in series because the control phase shifts the pulse
of each module by Tsw/N, so the period of voltage imbalance
only lasts as long as the phase shift duration rather than the
full switching frequency. The value of the arm inductor
required to achieve the target kRIPPLE can be found by
substituting (18), (19), and (20) into (17) and solving for L.
C. Design of the MMC for Low Frequency Motor Drive
To see the impact of the operating frequency on the design
of the MMC, consider the design of an MMC drive for two
synchronous motors with identical operating characteristics
except for output frequency. For the first design, the
permanent magnet synchronous machine has a power S, a DC
bus voltage VDC, an output frequency Ȧ1, and a phase voltage
Fig. 3. Example of energy storage in module capacitors (top) and module Vߔ of 1 p.u. each, with a phase shift ș of 0 degrees. Derived
capacitor voltage ripple (bottom) values of phase current iĭ, modulation index m, energy ripple
ǻeARM, capacitor energy ripple ǻeCAP, and average capacitor
B. Arm Inductance voltage VAVG would also all be 1 p.u. From these, the required
The arm inductance is used to suppress the harmonic capacitance C for a target ripple ǻV would be calculated to be
components of the circulating current, to limit the current 1 p.u. as well. The required inductance L for a desired ripple
ripple due to module switching, and to limit the fault current kRIPPLE would also be 1.0 p.u.
in the event of a fault on the dc bus. Limiting the current Now, consider that the synchronous machine were
ripple due to module switching usually imposes the most designed to operate at the same power S of 1.0 p.u., but at one-
stringent requirements, so that is used to determine the value half of the original rated speed (for instance, a grinding
of the arm inductance. machine for mines). The machine and MMC would be
The voltage loop during module switching can be seen in designed so that the number of modules N, DC bus voltage
Fig. 2. The sum of the upper and lower arm voltages, VARM,U VDCǡ and phase shift ș would all be the same as in the initial
and VARM,L, are equal to the dc bus voltage VDC during steady- design. It is important to note that the design of the machine
state operation, but there is a brief imbalance when one will be changed to ensure that the phase voltage Vĭǡ will
module is switched. The voltage of that module falls across remain the same even at the lower speed, even though phase
the two arm inductances L during this imbalance. The change voltage is usually linearly proportional to speed. The ‘—–’—–
in current due to this voltage can be found from the familiar ˆ”‡“—‡…› Ȧ1 would be 0.5 p.u. The phase current iĭ and the
relationship in (16). The inductance L is doubled since there modulation index m would remain 1.0 p.u. From (8), the
are two arm inductors in series on each leg. energy stored in the arm, eARM, would be:

v = 2Ldi/dt (17) eARM, 0.5 = 1.0/(12*1.0*0.5)*[4sin(0.5t) – 1.0sin(2*0.5t (21)


– ș) – 2*22sin(0.5*t)]
v = VDC /2N (18)
Fig. 4 illustrates the capacitor stored energy for the designs
di = kRIPPLE*iĭ (19) at original and one-half speed. It can be seen that the change
in energy stored in the capacitor for 50% of the original speed
dt = DTSW /N = D /(fSWN) (20) is twice the energy stored at the original speed. It would
follow that the capacitor would need to be twice as large to
L = DVDC /(4kRIPPLE*iĭN2fSW) (21) maintain a capacitor voltage ripple at the same level, so C50% =
2.0 p.u.

979
current iĭ, modulation index m, energy ripple ǻeARM, capacitor
energy ripple ǻeCAP, and average capacitor voltage VAVG would
also all be 1 p.u. Once again, the calculated capacitance and
inductance, C and L, is 1 p.u.
When the wind speed drops, the output frequency of the
permanent magnet synchronous generator will drop as with the
motor drive example. However, unlike that example, the other
parameters change as well. First, because the design of the
machine does not change, the output voltage will drop to 0.5
p.u. The current produced by a wind generator, by (4), is
quadratically related to wind speed, so it drops to 0.25 p.u.
when the wind speed is at 50% of rated value. The output
Fig. 4. Capacitor Stored Energy at Original and 50% Designed Operating
power would then be 0.125 p.u. The DC bus voltage, and the
Speed for Motor Drive module capacitor voltage, stay the same, however, as will the
expected duty cycle D, number of modules N, switching
frequency fSW, the desired change in capacitor voltage, and
desired current ripple will remain at their same values as for
the rated wind speed condition.
The energy stored in the module capacitors for both rated
and one-half rated wind speed are shown in Fig. 5. It may be
expected from the first term in (8) that the stored energy
would decrease as the power, S, decreases, but would increase
as both the phase voltage to DC bus voltage ratio, m, and
fundamental frequency of the generator, Ȧ1, decrease. It may
be expected that the change in power, however, would
dominate since it changes with the cube of wind speed, while
Fig. 5. Capacitor Stored Energy at Rated and 50% Wind Speed
the voltage ratio and fundamental frequency both vary
linearly. This is consistent with the results in Fig. 5, which
show that the change in stored energy in the one-half rated
An examination of (21) reveals that the inductor for the
50% original speed design would remain the same. The duty wind speed case are 68.8% of the change in stored energy for
cycle D, DC bus voltage Vdc, desired ripple kRIPPLE, phase the rated wind speed case. From (16), one could conclude that
current iĭ, number of modules N, and switching frequency fSW the capacitors could be 2/3rd of their size at rated wind speed
remain the same for both designs, so the inductance will and still achieve the desired voltage ripple. The design of the
remain the same. module capacitors at rated wind speed can be considered
adequate, therefore, for the partial wind speed cases. As with
D. Design of the MMC for Variable Wind Speed Generator the motor example, the arm inductance does not change with
Now consider the design of an MMC at the output of a wind speed, since it is based on rated phase current. This
wind turbine synchronous generator. Like the motor drive case, means that the passive components do not need to be larger to
the permanent magnet synchronous machine is designed with a account for low wind speeds for wind turbine applications of
power S, a DC bus voltage VDC, an output frequency Ȧ1, and a the MMC, which is quite different than in other low speed
phase voltage Vߔ of 1 p.u. each, with derived values of phase

Fig. 6. MMC and Permanent Magnet Synchronous Generator Model

980
Fig. 7. Voltage and Current Ripple at Rated and 0.5 p.u. Wind Speed for Wind Turbine Generator

applications of the MMC [7 - 9]. results illustrated that the capacitor voltage and inductor
currents maintained their rated ripple values even at the low
IV. RESULTS wind speed, requiring no special design or control to ensure
A model of the MMC with a permanent magnet operation at the full range of wind speeds. These results
synchronous generator on a wind turbine was built in Matlab© demonstrate that the MMC can be a good fit for MVDC Wind
to test the impact of the change in wind speed on the design of applications. With these results, it can be seen that the Pre-
the MMC, as shown in Fig. 6. The MMC was designed to Trafo wind turbine concept is valid for wind farms with
ensure a capacitor voltage ripple of ± 0.5% at the rated wind MVDC collection systems. This concept minimizes the total
speed. The wind speed was then changed to 0.5 p.u. to cost of the wind turbine by eliminating several conversion
demonstrate that the capacitor voltage ripple remained within stages, enabling operation at high enough voltage to be able to
those limits. Fig. 7 illustrates the power, MMC capacitor transmit power to shore without an offshore substation. This
voltage ripple, and d-axis current at these conditions. It can be design produces an economical and low-maintenance off-
seen that the power falls to one-eighth of its rated value when shore wind farm with lower levelized cost of energy compared
the wind speed falls to one-half of its rated value at t = 3 s. to traditional wind turbine and AC collection and transmission
The current falls to one-quarter of its rated value, while the system designs.
MMC capacitor voltage maintains its rated value with a small
ripple. This ripple is about 0.5% at rated wind speed, and REFERENCES
(after a small transient), actually decreases at the lower wind [1] Global Wind Power Market Forecast: 2013–2030 Fall Update, HIS,
December 2013.
speed. It can be seen that the frequency of the ripple also
[2] Wind Strategy: Creating an Offshore Wind Energy Industry in the
decreases. Both effects are predicted by the design equations United States, DOE and DOI, Feb 2011.
as discussed above. [3] National Offshore Wind Energy Grid Interconnection Study Final
Technical Report, to be published, 2014.
V. CONCLUSIONS [4] Large-scale offshore wind power in the United States: Assessment
of opportunities and barriers. NREL, Sept. 2010.
It has previously been seen that the design of the MMC is [5] E.ON Wind Turbine Technology and Operations Factbook, Global
complicated for operations at low speeds, often requiring Unit Renewables, Sep. 2013.
oversized passive components and the injection of circulating [6] J. Pan, S. Bala, M. Callavik, P. Sandeberg, “DC Connection of
Offshore Wind Power Plants without Platform”, Wind Integration
currents [7 - 9]. The design of the MMC for low wind speed Workshop, Berlin Nov. 2014.
operation was explored in this paper. It was found that the [7] X. Wang, Q. Ge, S. Zhang, R. Gou, X. Yang, Y. Li, “Research on
module capacitor could be designed for full wind speed and Voltage Balance Control of Modular Multilevel Converter for Low
still operate well at low wind speeds, and that the arm inductor Frequency Operation,” International Conference on Electrical
Machines and Systems, 26 – 29 Oct. 2013, pp. 1678 – 1682.
design does not change with wind speed. This is a contrast to [8] K.Johnson, L.Fingersh, M. Balas and L. Pao, “Methods for
other low frequency applications, and is a result of the rapid Increasing Region 2 Power Capture on a Variable Speed Wind
decrease in power as the wind speed decreases. Simulation Turbine,” Journal of Solar Energy Engineering, vol. 126, no. 4, pp.
725-733, Sept 2006.

981
[9] Kalle Ilves, Staffan Norrga, Lennart harnefors, Hans-Peter Nee, “On IEEE Trans. Power electronics, vol. 29, no. 1, pp. 77 – 88, 2014.
Energy Storage Requirements in Modular Multilevel Converters,”

982

Potrebbero piacerti anche