Sei sulla pagina 1di 7

Energy Conversion and Management 48 (2007) 2604–2610

www.elsevier.com/locate/enconman

Simulation studies on GAX absorption compression cooler


a,* b
A. Ramesh Kumar , M. Udayakumar
a
Department of Mechanical Engineering, Pacheri Sri Nallathangal College of Engineering and Technology, Dindigul 624 622, Tamil Nadu, India
b
Department of Mechanical Engineering, National Institute of Technology, Trichy 620 015, Tamil Nadu, India

Received 10 December 2005; accepted 29 March 2007


Available online 18 May 2007

Abstract

This paper presents simulation studies conducted on a GAX absorption–compression (hybrid) cycle using ammonia–water as working
fluid for air conditioning applications. The degassing range of the cycle has been optimized for maximum COP. The effect of absorber
pressure on the heat duties of the cycle has also been studied. It is found that the maximum COP occurs at an optimum degassing range
of about 0.4 kg of ammonia per kg of strong solution. Comparison of hybrid and conventional GAX cycle was conducted, and it was
found that the hybrid GAX cycle has an average of 30% higher value of COP than the conventional GAX cycle. A reasonable agreement
is observed between the results and performance parameter trends obtained from the present study and the published results available in
the literature.
Ó 2007 Elsevier Ltd. All rights reserved.

Keywords: GAX; Ammonia–water; Degassing range; Compression–absorption; Simulation

1. Introduction readjusted to get the desired results in the final stage.


Experimental validation showed a 0.5 percentage difference
The GAX (generator absorber exchange) absorption of COP value between the simulation and experiment. Sta-
cycle is an elegant way of achieving higher coefficient of icovici [2] introduced a new method to analyze a poly-
performance (COP) with a cycle configuration that essen- branched regenerative GAX cycle. NH3/H2O–LiBr was
tially appears to be a single stage absorption system. In selected as a working fluid due to its increased solubility
the absorber and generator, the pressures and concentra- at elevated temperatures. The author claims that the three
tions are maintained in such a way as to cause a tempera- stage polybranched regenerative GAX cycle gives 1.9 times
ture overlap between the absorber and the generator. This higher COP and 82% of the Carnot cooling efficiency for
provides the possibility that some of the heat of absorption the lift of 47 °C. However, economic analysis for the choice
may be rejected to the generator. Several theoretical and of working fluid was not justified. Also, The Carnot COP
experimental works have been performed on the GAX does not address the internal heat exchange in the GAX
cycle and reported in the literature. Using ABSIM-OSU cycle [3].
software Priedeman and Christensen [1] modeled a GAX Velázquez and Best [4] proposed a methodology to eval-
cycle ammonia–water absorption chiller of 5 ton capacity uate the thermodynamic performance of an air cooled
and calibrated the simulation model using experimental GAX cycle driven by natural gas and solar energy. For
data. In the first stage, the cycle was optimized by paramet- the specified design conditions, they calculated the proper-
ric variations. In the second stage, the model was calibrated ties at different state points and the energy transfer of the
using the experimental data. The calibrated model was components based on external currents. The methodology
also using an iterative procedure for the internal currents
*
Corresponding author. Tel.: +91 451 247 1502; fax: +91 451 255 4249. and convergence was achieved. The model does not con-
E-mail address: aramesh2003@rediffmail.com (A. Ramesh Kumar). sider the pressure losses. A COP value of 0.86 for cooling

0196-8904/$ - see front matter Ó 2007 Elsevier Ltd. All rights reserved.
doi:10.1016/j.enconman.2007.03.013
A. Ramesh Kumar, M. Udayakumar / Energy Conversion and Management 48 (2007) 2604–2610 2605

Nomenclature

Q heat flow (kW) PSE panel heating single effect cycle


f circulation ratio
T temperature (C or K) Greek symbols
P pressure (kPa) g efficiency
C specific heat (kJ/kg K) n degassing range
W power (kW)
U overall heat transfer coefficient (W/m2K) Subscripts
A heat exchanger area (m2) a absorber
CW compressor work (kW) g generator
v specific volume (m3/kg) e evaporator
h specific enthalpy (kJ/kg) p pump
m mass flow rate (kg/s) c condenser
rc refrigerant concentration hf hot fluid
ssc strong solution concentration cf cold fluid
wsc weak solution concentration gt total generator
e effectiveness of heat exchanger rq required
n compression index at total absorber
k clearance ratio av available
RHX condensate pre-cooler r refrigerant
GAX generator absorber heat exchange s strong solution
GAX A GAX absorber w weak solution
GAX D GAX desorber L liquid
PGAX panel heating GAX cycle V vapour

and 1.86 for heating together with an energy integration of technique. They showed that by knowing the closeness of
16.9 kW was obtained for a 10.6 kW cooling capacity. Gar- the state points of the heat recovery processes, an economic
imella et al. [5] studied the performance of a GAX heat design trade off of cycle components could be achieved.
pump for both cooling and heating modes using the Scharfe et al. [9] analyzed the advantages and limitations
OSU-ABSIM simulation program. It was shown that for of the GAX cycle. An equation for the heat of desorption
a given capacity, the gas input based COP can be maxi- was derived, and it showed that at any temperature inter-
mized based on the UA variation of heat exchanging com- val, the heat demand in the desorber is higher than the heat
ponents of the cycle. Also, it was demonstrated that the supplied by the absorber. It was observed that the exergy
choice of desorber bypass fraction primarily depends on losses were high due to the high temperature range of the
the design requirements of the adiabatic analyzer, rather heat exchange process. Kang et al. [10] developed an
than being based on the potential heat duty matching advanced GAX cycle for utilization of waste heat, which
between the GAX absorber and desorber. A performance was called the waste heat GAX (WGAX) cycle. They
simulation considering both the cooling and heating modes reported that the generator outlet could be reduced to
as functions of the operating parameters using ABSIM was 172 °C with a higher COP of the WGAX cycle than that
investigated on a Phillips configuration GAX heat pump of the standard GAX (SGAX) cycle. They presented that
by Grossman et al. [6]. They identified the effect on COP the corrosion problem in the standard GAX cycle at higher
of the heat rejection temperature and equilibrium devia- Tg than 200 °C could be solved by adopting the WGAX
tions. Three control schemes were attempted to maintain cycle. Sabir et al. [11] studied the GAX-resorption refriger-
a fixed COP. With the assistance of a Lorentz type plot, ation cycle model. They showed that the COP of the
they arrived at the optimum flow rate of coolant in the GAX-resorption cycle is higher than that of the simple
GAX heat transfer loop. absorption and resorption cycle. Although the cost analysis
Kang et al. [7] established a theoretical model for the was not reported, it is understood from the discussion that
rectifier in the GAX absorption heat pump. Three different the simple GAX cycle is less expensive and gives a better
rectifier configurations were considered for study in this COP than the GAX-Resorption cycle. Kang and Kashiw-
work. Their investigations revealed that a minimum tem- agi [12] developed a GAX cycle for panel heating, which
perature difference between the interface and bulk regions was called the PGAX cycle. They studied the effects of
and a high heat transfer coefficient in the vapour region UA ratio and coolant split ratio on COP in the PGAX
reduces the size of the rectifier. Hanna et al. [8] analyzed and PSE cycles and concluded that there is an optimum
the GAX cycle processes by introducing the pinch point UA ratio that gives the highest COP in the PGAX cycle
2606 A. Ramesh Kumar, M. Udayakumar / Energy Conversion and Management 48 (2007) 2604–2610

for a given split ratio. For a 17.5 TR capacity, this paper urated vapour (11) passes to the compressor (12) through
provides the optimum UA values of the absorbers for the the condensate pre-cooler. The compressor is placed
split ratio of 0.87. Kang et al. [13] developed four different between the evaporator and the absorber. The compressor
advanced Hybrid GAX cycles. By controlling the pressure increases the absorber pressure (15) higher than the evapo-
of the heat exchanging components, the study showed that rator pressure. In the absorber, the refrigerant vapour is
a higher COP, very low evaporator temperature with rea- absorbed by the weak solution coming from the generator
sonable COP, corrosion minimization at higher generator (3) through an expansion valve (4) and forms the strong
temperatures and an increase of hot water outlet tempera- solution (1). The term ‘‘strong solution’’ represents a solu-
ture can be achieved. tion that is strong with refrigerant (NH3), while ‘‘weak
The above literature review reveals that although many solution’’ represents a solution that is weak with refriger-
works have been conducted to analyze the performance of ant. The strong solution (1) pumped to the generator pres-
the basic GAX cycle, few attempts have been made to mod- sure (2) is introduced into the high temperature part of the
ify it. Also, the cost and economic analysis of the GAX absorber, where it receives heat from the absorber, and the
cycle are rarely reported. Furthermore, the degassing range refrigerant in it is boiled off in the generator. The remaining
(difference between the masses of the strong and weak solu- solution (3) flows back to the absorber and, thus, completes
tions), which has the dominant role in the performance of the cycle. The generator and absorber temperature ranges
the GAX cycle is not well documented. This particular partially overlap. This overlapped heat is internally trans-
issue prompted the present work in which a hybrid GAX ferred from the absorber to the generator. The dotted line
compression–absorption cycle is introduced, and the effect (Qgax in Fig. 1) represents the heat exchange between the
on the COP is investigated in terms of degassing range. absorber and generator.

2. Description of GAX absorption compression cycle 3. Simulation study

Fig. 1 illustrates the main components of the GAX com- Simulation was performed to evaluate the hybrid GAX
pression–absorption refrigeration cycle. The saturated cooling cycle with the assumptions enumerated below:
solution is assumed to leave the absorber (1) and the gen-
erator (3), and saturated ammonia liquid is assumed to 1. Condenser pressure is the equilibrium pressure corre-
leave the condenser (8). Saturated vapour is assumed to sponding to the refrigerant concentration and the
leave the evaporator (11). The condensate pre-cooler sub- condenser temperature.
cools the refrigerant that leaves the condenser (8) by pre- 2. The condition of the refrigerant at the exit of the
heating the vapour entering the compressor (12). The evaporator is saturated vapour, and the evaporator
high pressure cooled liquid refrigerant (8) from the conden- pressure is the saturated pressure at evaporator
sate pre-cooler enters the evaporator (10) through an temperature.
expansion valve that reduces the pressure of the refrigerant 3. The refrigerant pressure at the outlet of the recipro-
to the evaporator pressure. The liquid refrigerant (10) cating compressor is the absorber pressure.
vaporizes in the evaporator by absorbing heat from the 4. The approach temperature at either end of the GAX
room being conditioned, and the resulting low pressure sat- heat exchanger is assumed to 0 K.

Qc Qr Qg

5 14V
7
Condenser Rectifier GAXD Generator

6 14L
3
8 12
Qgax Expansion
17 2 valve
RHX Pump
P 4
R 9 1
E 13V
S GAXA
S Expansion 11
Absorber
U valve 15
13L
R
E 10 Qa
Compr-
Evaporator essor

Qe CW

TEMPERATURE

Fig. 1. Schematic diagram of GAX compression–absorption cycle.


A. Ramesh Kumar, M. Udayakumar / Energy Conversion and Management 48 (2007) 2604–2610 2607

5. The efficiency of the solution pump is 0.5. The circulation ratio of the system can be derived as
6. The effectiveness of the heat exchanger (RHX) is 0.8. f ¼ ðrc  wscÞ=ðssc  wscÞ ð11Þ
7. The temperature of evaporator is assumed as 5 °C.
8. The condenser temperature varies between 45 °C and The degassing range is defined as
30 °C in steps of 5 °C. n ¼ ssc  wsc ð12Þ
9. The generator temperature varies between 110 °C and
170 °C in steps of 10 °C. The strong and weak solutions can be determined as
10. The flow through all the components of the cycle is ms ¼ f  mr ð13Þ
under steady state. mw ¼ ms  mr ð14Þ
11. Pressure drops within the cycle can be neglected
except through the expansion valve. The energy balance for the solution heat exchanger is as
12. The result of the analysis is ignored whenever the follows
mass flow rate of refrigerant becomes zero or an T 9 ¼ T 8  ðe  mcf  C cf  ðT 8  T 11 Þ=ðmhf  C hf ÞÞ ð15Þ
unrealistic value in any of the state points of the
cycle. T 12 ¼ T 11 þ e  ðT 8  T 11 Þ ð16Þ
The pump power is deduced as
A computer program to determine the thermodynamic
properties of the saturated ammonia–water solutions has W p ¼ ðP c  P a Þ  ðvc  mr Þ=gp ð17Þ
been developed based on the correlations of Patek and h17 ¼ h1 þ ðW p =mr Þ ð18Þ
Klomfar [14]. The relation between the saturation pressure,
Energy balances for the condenser yield
solution temperature and ammonia concentration of the
ammonia–water mixture can also be obtained [15]. The Qc ¼ m7  ðh7  h8 Þ ð19Þ
input parameters to the simulation program are the con- The compression of refrigerant vapour is assumed a poly-
centration of the refrigerant leaving the rectifier, degassing tropic process. So the compression work can then be calcu-
ratio, temperatures of condenser, evaporator and genera- lated as
tor, compressor parameters, efficiency of the pump and
the effectiveness of the heat exchanger. For a given degas- CW ¼ mr  ðP e  vr  nÞ=ðgv  ðn  1ÞÞ
sing range and absorber pressure, the simulation program ðn1Þ=n
 ½ðP a =P e Þ  1 ð20Þ
is capable of determining the rate of heat that has to be
added or rejected from each component of the cycle as well The volumetric efficiency can be expressed as
as the COP at different generator temperatures. In the fol- 1=n
gv ¼ 1 þ k  kðP a =P e Þ ð21Þ
lowing section, equations based on the mass, energy and
concentration balance of each component of the cycle is The coefficient of performance of cycle is (COP)
presented. For the desorber, the mass and energy balances COP ¼ Qe =ðQg þ W p þ CWÞ ð22Þ
yield:
m2 þ m6 ¼ m5 þ m3 ð1Þ 4. Validation of the model
m2 h2 þ m6 h6 þ Qgt ¼ m5 h5 þ m3 h3 ð2Þ
To validate the simulation model, the results and the
For the GAX desorber, the mass and energy balances yield:
parameter profiles are compared with the simulation work
m2 þ m6 þ m14V ¼ m5 þ m14L ð3Þ presented in the literature [13]. From Fig. 5, it can be seen
m2 h2 þ m6 h6 þ m14V h14V þ Qrq ¼ m5 h5 þ m14L h14L ð4Þ that at constant desorber and evaporator pressures (1790.3
and 516.87 kPa, respectively), the generator heat supply
For the absorber, the mass and energy balances yield: shows a fast decreasing trend, and the compressor work
m1 ¼ m15 þ m4 ð5Þ shows a gradually increasing trend with absorber pressure
m1 h1 þ m2 h2 þ Qat ¼ m15 h15 þ m4 h4 þ m17 h17 ð6Þ and, hence, cause an increase in the value of COP with
increasing absorber pressure. Kang et al. [13] showed that
For the GAX absorber, the mass and energy balances yield at constant desorber and evaporator pressures (1900 and
m13L ¼ m13V þ m4 ð7Þ 460 kPa, respectively), the cooling COP of the hybrid
GAX system increases with increasing absorber pressure.
m13L h13L þ Qav ¼ m13V h13V þ m4 h4 ð8Þ Thus, it is proved that the simulated COP profiles in this
The mass flow rate of refrigerant is calculated as work match well with the COP profiles obtained from the
OSU-ABSIM simulation work. Though the previous work
mr ¼ ðV p  gv Þ=vr ð9Þ claims that the COP increase that could be achieved is 24%
higher than the standard GAX cycle, the present study pre-
The evaporator heat load is calculated as
dicts it as about 30% higher than the standard GAX cycle.
Qe ¼ mr  ðh11  h10 Þ ð10Þ This difference is mainly due to the number of idealized
2608 A. Ramesh Kumar, M. Udayakumar / Energy Conversion and Management 48 (2007) 2604–2610

assumptions made in the model. Further, the simulation 1.8


Tc = 40 oC Te = 5 oC Pa = 916.87 kPa
model for the conventional GAX cycle also is compared
1.7
with the simulation work presented in literature [16]. For
a given set of input parameters (Tg = 163.3 °C, Tc = Tg = 170 oC
1.6
Tg = 160 oC
40 °C, Ta = 40 °C, Te = 5 °C, Pa = 1548.0 kPa, Pe =
1.5 Tg = 150 oC
478.4 kPa and n = 0.35), the simulation of Ref. [16] pre-
Tg = 140 oC
dicts the COP value of 1.10, and the present simulation 1.4
model for the conventional GAX cycle predicts the COP

COP
value as 1.08. The heat duties of the components are also 1.3

compared and excellent agreement is obtained. 1.2


Tg = 110 oC
5. Results and discussion 1.1 Tg = 120 oC

1.0 Tg = 130 oC
The coefficient of performance is the ratio between the
cooling capacity of the refrigeration system to the heat load 0.2 0.3 0.4 0.5 0.6
added to the generator and power supplied to the pump DEGASING RANGE

and compressor. The mathematical expression is given by Fig. 3. Variation of COP with various generator temperatures.
Eq. (22). Fig. 2 shows the COP variation as a function of
the degasing range for various generator temperatures. 4.5 o o
Tc = 40 C Te = 5 C Pa = 916.87 kPa
The pressures of the desorber, evaporator and absorber
are kept constant as 1555.18 kPa, 516.87 kPa and 4.0
Tg = 170 oC
716.87 kPa, respectively. The degassing range at which
Tg = 160 oC
the COP attains maximum value for each generator tem- 3.5
CIRCULATION RATIO

Tg = 150 oC
perature is denoted as the optimum degassing range.
3.0
Fig. 3 represents the COP variation at higher absorber Tg = 140 oC

pressure (916.87 kPa) keeping all the other parameters con- Tg = 130 oC
2.5
stant. It can be deduced from Figs. 2 and 3 that increasing
the absorber pressure increases the COP for each degassing
2.0 Tg = 120 oC
range, and the higher COP value occurs in the lower degas-
sing range. Along the studied range of absorber pressure Tg = 110 oC
1.5
and evaporator temperature, the optimum degassing range
varies in the amount of ±0.05 about the mean value of 0.4. 1.0
This result is most significant in the context of designing 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65
and running the system. DEGASING RANGE
The circulation ratio is defined as the mass flow rate of Fig. 4. Variation of circulation ratio with various generator temperatures.
the strong solution required to be circulated in the solution
loop in order to circulate a unit mass flow rate in the refrig- Eq. (11). The degassing range affects the value of circulation
erant loop. The mathematical expression is given in ratio. As shown in Fig. 4, at the minimum value of degas-
sing range, the circulation ratio starts with a large value. At
a generator temperature of 110 °C, 0.03826 kg/s of strong
1.50
Tc = 40 oC Te = 5 oC Pa = 716.87 kPa solution is circulated in order to evolve 0.01175 kg/s of
1.45
refrigerant vapour. With rising degassing range, the con-
1.40 Tg = 170 oC
centration of the strong solution increases and the circula-
1.35 Tg = 160 oC
Tg = 150 oC
tion ratio decreases. When Tg increases, the weak solution
1.30
1.25
Tg = 140 oC concentration decreases. At constant degassing range, this
1.20
leads to a decrease in the strong solution concentration.
Further, it increases the absorber temperature. In order
COP

1.15
1.10 to maintain the refrigerant flow rate constant, the mass
1.05 flow rate of the strong solution is to be increased. However,
1.00 Tg = 110 oC the circulation ratio increases with the strong solution flow
Tg = 120 oC
0.95 rate for a constant refrigerant flow rate.
0.90 Tg = 130 oC Increasing the absorber pressure at constant degassing
0.85 range increases the absorber temperature. This increases
0.80 the temperature glide in the absorber and desorber heat
0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65
exchangers, resulting in the rise of heat availability in the
DEGASING RANGE
absorber and the heat required in the desorber as shown
Fig. 2. Variation of COP with various generator temperatures. in Fig. 5.
A. Ramesh Kumar, M. Udayakumar / Energy Conversion and Management 48 (2007) 2604–2610 2609

Qrq Qrq Hybrid Pa = 916.87 kPa Qrq conventional Pa = 516.87 kPa


21
Tg = 150 oC Tc = 45 oC Te = 5 oC Qav Hybrid Pa = 916.87 kPa Qav conventional Pa = 516.87 kPa
18 20
19 Tg = 150 oC Tc = 40 oC Te= 5 oC
16
18
Qav
14 17
16
HEAT DUTY (kW)

12
15

HEAT DUTY (kW)


Qe Qc
10 14
13
8
12
Pe = 516.87 kPa
6 Qa 11
Pc = 1790.3 kPa
10
4 Qg
9
2 CW
8
7
0
600 800 1000 1200 1400 1600 6
ABSORBER PRESSURE (kPa) 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60
DEGASING RANGE
Fig. 5. Variation of heat duty with various absorber pressures.
Fig. 6. Variation of heat duty with various degassing ranges.

The heat availability is the rate of heat supplied to gen- 1.6


Tg = 150 oC Tc = 40 oC Te = 5 oC
erate the refrigerant vapour in the GAX desorber from the
1.5
GAX absorber. The mathematical expression is given in
Eq. (8). The heat required is the rate of heat needed to gen- 1.4

erate the refrigerant vapour in the GAX desorber. The 1.3


mathematical expression is given in Eq. (4). The increases
1.2
of mass flow rate at state point 13v results in the increases
of heat availability in the absorber, and the decreases of 1.1
COP

mass flow rate at state point 14v results in the increases 1.0
of heat required in the desorber. The rate of the incre- 0.9
ment of heat availability is higher than the rate of the incre- Hybrid GAX, Pa = 916.87 kPa
0.8
ment of heat requirement, causing the COP of the hybrid Conventional GAX, Pa = 516.87 kPa
cycle to be high. Although the compression work required 0.7

to run the compressor increases with absorber pressure, the 0.6


internal heat recovered by the GAX cycle subdues the com- 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60
DEGASING RANGE
pressor effect, and the COP increases. The absorber pres-
sure increment reduces the mass flow rate of refrigerant Fig. 7. Variation of COP with various degassing ranges.
and, in turn, causes the reduction of evaporator capacity.
This can also be deduced from Fig. 5. Within the assumed Fig. 7 compares the influence of the degassing range on
range of absorber pressure, the mass flow rate of refriger- the COP for the conventional and hybrid GAX absorption
ant varies from 0.01116 kg/s to 0.01194 kg/s. cycles. Approximately 30% of the average increment in
The dependence of Qav and Qrq on the degassing ranges COP occurs within the degasing range of 0.2–0.55. It is also
for the conventional and hybrid GAX cycles are shown in shown in Fig. 7 that the COP of the hybrid GAX starts
Fig. 6. It can be seen that at constant refrigerant flow rate, decreasing when the degassing ratio crosses the value 0.4.
the Qav value in the hybrid GAX is 8.9 kW higher than that It may be referred to the fact that the required mass flow
in the conventional GAX when the degassing range is 0.2. rate at state point 13v in the cycle initially increases and
Despite the fact that Qrq also increases correspondingly, then decrease with the rise of degassing range, and it, in
the total heat requirement in the generator (Eq. (4)) is turn, decreases the heat availability. Further, as shown in
the same for both the cycles. This results in the low COP Table 1, the rate of decrease in mass flow rate is much
in the conventional GAX cycle. If the concentration of higher at the higher degassing range. These two effects
X13L is less than the weak solution concentration, the mass decrease the COP of the hybrid cycle at higher degassing
flow rate of X13L becomes zero. It decides the lower degas- ranges. In the conventional GAX cycle, the value of COP
sing range in the cycle. of 1.1492 is attained in the degassing range of 0.45. In

Table 1
Variation of mass flow rate at state point 13v with degassing range (Tg = 150 °C, Tc = 40 °C, Te = 5 °C, Pa = 916.87 kPa)
n 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
m13V 0.0054 0.00603 0.00605 0.00603 0.00586 0.00554 0.0052 0.00458
2610 A. Ramesh Kumar, M. Udayakumar / Energy Conversion and Management 48 (2007) 2604–2610

21 Tg = 150 oC Tc = 40 oC Te = 5 oC 3. The circulation ratio changes inversely with the degas-


20 sing range. At constant degassing range, increasing the
19 Qg Conventional GAX, Pa = 516.87 kPa generator temperature increases the circulation ratio,
18 Qa Conventional GAX, Pa = 516.87 kPa and increasing the absorber pressure has no effect on
17 Qg Hybrid GAX, Pa = 916.87 kPa
the circulation ratio.
16 Qa Hybrid GAX, Pa = 916.87 kPa
4. The required COP can be attained in lower degassing
HEAT DUTY (kW)

15
14
ranges in the hybrid cycle, and it can operate success-
13 fully utilizing low temperature energy sources.
12
11 Acknowledgements
10
9 The author thanks K.E. Herold, R. Radermacher and
8
S.A. Klein, the authors of the book ’Absorption Chillers
7
and Heat Pumps’ (CRC Press) for their kindness in supply-
6
0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 ing published papers and program relating to GAX
DEGASING RANGE absorption technology.
Fig. 8. Variation of heat duty with various degassing ranges.
References

the hybrid cycle, almost the same COP of 1.143 is attained [1] Priedeman DK, Christensen RN. GAX absorption cycle design
in the much lower degassing range of 0.2, which is a signif- process. ASHRAE Trans 1999:769–79.
icant factor of the hybrid GAX absorption cycle. [2] Staicovici MD. Polybranched regenerative GAX cooling cycles. Int J
Refrig 1995;18(5):318–29.
Fig. 8 presents the absorber and generator heat duty on [3] Keith Herold. Private communications. www.arameshkumar.blogspot.
the degassing range for the conventional and hybrid GAX com.
absorption cycles. The rate of heat rejection in the absorber [4] Velázquez N, Best R. Methodology for the energy analysis of an air
and the rate of heat supplied to the generator in the conven- cooled GAX absorption heat pump operated by natural gas and solar
tional GAX cycle is high when compared with the hybrid energy. Appl Therm Eng 2002;22:1089–103.
[5] Garimella S, Christensen RN, Lacy D. Performance evaluation of a
GAX cycle at all degassing ranges. From Fig. 8, it can also generator–absorber heat exchange heat pump. Appl Therm Eng
be deduced that the higher rate of rejection in the absorber 1996;16(7):591–604.
at the higher degassing range causes the reduction in COP [6] Grossman G, DeVault R, Creswick F. Simulation and performance
in the hybrid cycle. It obviously decides the higher operating analysis of an ammonia water absorption heat pump based on the
degassing range of the hybrid GAX absorption cycle. generator absorber heat exchange (GAX) cycle. ASHRAE Trans
1995;101(1):1313–23.
For the assumed conditions of n = 0.3, Tc = 40 °C, [7] Kang YT, Chen W, Christensen RN. Development for design model
Te = 5 °C, Tg = 110 °C, Pa = 516.87 kPa, the conventional for a rectifier in GAX absorption heat pump systems. ASHRAE
GAX cycle, which is unrealizable, can be accomplished by Trans 1996;102(1):963–72.
the hybrid GAX cycle by increasing the absorber pressure. [8] Hanna WT, Wilkinson WH, Saunders JH, Philips DB. Pinch-point
This particular result makes the hybrid cycle suitable for analysis: an aid to understanding the GAX absorption cycle.
ASHRAE Trans 1995;101(1):1189–98.
utilizing renewable and waste heat energy sources. [9] Scharfe J, Ziegler F, Radermacher R. Analysis of advantages and
limitations of absorber–generator heat exchange. Int J Refrig
6. Conclusions 1986;9:326–33.
[10] Kang YT, Akisawa A, Kashiwagi T. An advanced GAX cycle for
A hybrid GAX cycle for an aqua ammonia absorption waste heat recovery: WGAX cycle. Appl Therm Eng 1999;19:
933–47.
air conditioning system has been introduced and theoreti- [11] Sabir HM, Chretienneau R, Elhag YBM. Analytical study of a novel
cally analyzed, and the results are validated with published GAX-R heat driven refrigeration cycle. Appl Therm Eng
work. From the obtained theoretical results, the following 2004;24:2083–99.
conclusions are made: [12] Kang YT, Kashiwagi T. An environmentally friendly GAX cycle for
panel heating: PGAX cycle. Int J Refrig 2000;23:378–87.
[13] Kang YT, Hong H, Park KS. Performance analysis of advanced
1. Within the studied range of absorber pressure and gen- hybrid GAX cycles: HGAX. Int J Refrig 2004;27:442–8.
erator temperature the maximum COP occurs at the [14] Patek J, Klomfar J. Simple functions for fast calculations of selected
mean value of the optimum degassing ratio of 0.4 with thermodynamic properties of the ammonia–water system. Int J Refrig
the variation of 0.05. 1995;18(4):228–34.
2. The COP increases with absorber pressure and generator [15] Da-Wen Sun. Comparison of the performances of NH3–H2O, NH3–
LiNO3 and NH3–NaSCN absorption refrigeration systems. Energy
temperature and initially increases then decreases with Convers Manage 1998;39:357–68.
the degassing range. At the chosen operating parameters, [16] Herold KE, Radermacher R, Klein SA. Absorption chillers and heat
a 30% increase in COP occurs in the hybrid GAX cycle. pumps. New York: CRC Press; 1995. pp. 212–32.

Potrebbero piacerti anche