CONCRETE SLABS
1. ALL SLAB REINFORCEMENT SHALL HAVE A MINIMUM CLEAR DISTANCE OF 20mm FROM
THE BOTTOM AND FROM THE TOP OF SLABS.
2. IF SLABS ARE REINFORCED BOTHWAYS, BARS ALONG THE SHORTER SPAN SHALL BE
PLACED BELOW THOSE ALONG THE LONG SPAN AT THE CENTER AND OVER THE
LONGER SPAN BARS NEAR THE SUPPORTS. THE SPACING OF THE BARS AT THE
COLUMN STRIPS SHALL BE APPROXIMATELY ONE AND ONE-HALF (1-1/2) THAT IN
MIDDLE STRIPS BUT IN NO CASE GREATER THAN TWO AND ONE-HALF (2-1/2) SLAB
CONCRETE THICKNESS OR 450mm.
3. TEMPERATURE BARS FOR SLABS SHALL BE GENERALLY PLACED NEAR THE FACE IN
1. CONCRETE MINIMUM ULTIMATE CYLINDER COMPRESSIVE STRENGTHS AT 28 DAYS TENSION AND SHALL NOT BE LESS THAN 0.0018 TIMES THE CROSS AREA OF
SHALL BE : CONCRETE SECTION.
fc' = 20.7 MPa (3000 psi) 4. PROVIDE EXTRA REINFORCEMENT FOR CORNER SLABS (TWO ADJACENT DISCON- REINFORCEMENTS
FOUNDATION, COLUMNS, SLABS, BEAMS, GIRDERS
CONTINUOUS HORIZONTAL
fc' = 20.7 MPa (3000 psi) SLAB ON GRADE DETAIL OF BEAM BLOCK
fc' = 17.5 MPa (2500 psi) 200mm 0.C.
LEAN CONCRETE AND OTHER NON-STRUCTURAL
(BOTTOM BARS)
ELEMENTS
2. AGGREGATE SIZE SHALL BE AS FOLLOWS :
200 W 200
BEAM OR
20mm MAX. SUSPENDED SLABS, BEAMS, GIRDERS, WALLS, AND
COLUMNS SHEAR WALLS
H
TO WEATHER Ld HOOK H 1.3 x Ld 1.7 x Ld SPLICE SPLICE SPLICE
20mm SLABS AND WALLS NOT EXPOSED TO GROUND OR TO DESIGN CRITERIA 1.4 x Ld 1.4 x Ld 1.82 x Ld 2.38 x Ld
WEATHER
CODES & STANDARDS: E = 25 VERTICAL BARS
75mm CONCRETE EXPOSED TO SEWAGE 250 300 400 500 350 350 450 600
1. GOVERNING CODES: H = 150
4. ALL REINFORCING STEEL DOWELS, ANCHOR BOLTS, AND OTHER INSERTS SHALL BE ACI 318-89 BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE
SECURED IN POSITION PRIOR TO POURING CONCRETE. UBC 1994 ED. UNIFORM BUILDING CODE E = 150
NSCP 1992 NATIONAL STRUCTURAL CODE OF THE PHILIPPINES 300 400 500 600 400 400 600 700
5. CONCRETE CYLINDERS SHALL BE TAKEN FOR EACH DAY'S POUR AND EACH 50 CU. M. H = 200
OR FRACTION THEREOF CAST IN ACCORDANCE WITH A.S.T.M. C31 AND TESTED NBCP 1988 NATIONAL BUILDING CODE OF THE PHILIPPINES
IN ACCORDANCE WITH A.S.T.M. C39. 2. GOVERNING STANDARDS: E = 200 DOOR OPENING ELEVATION
400 500 600 700 600 600 700 900
ASTM A36 BUILDING CODE REQUIREMENTS FOR STRUCTURAL STEEL H = 250
REINFORCING STEEL ASTM A611 STEEL, SHEET, CARBON, COLD-ROLLED, STRUCTURAL
QUALITY STRAIGHT
ASTM A615/ SPECIFICATION FOR STEEL BARS FOR CONCRETE STRAIGHT
1. GRADE : PNS 49 REINFORCEMENT S EMBEDMENT EMBEDMENT
A.S.T.M. A615 GRADE 60 ASTM C33 STANDARD SPECIFICATION FOR CONCRETE AGGREGATES CLASS B CLASS C CLASS A CLASS B CLASS C
DEFORMED BARS ASTM C39 STANDARD TEST METHOD FOR COMPRESSIVE STRENGTH K 200 W 200
CLASS A
OF CYLINDRICAL CONCRETE SPECIMENS
(fy = 414 MPa)
E
E
ASTM C150 STANDARD SPECIFICATION FOR PORTLAND CEMENT
A.S.T.M. A615 GRADE 40 PNS 16 PHILIPPINE NATIONAL STANDARD FOR CONCRETE
DEFORMED BARS STIRRUPS, COLUMN TIES & SPIRALS HOLLOW BLOCKS T
(MIN)
SG 671 SPECIFICATION FOR THE DESIGN OF COLD-FORMED
300
(fy = 275 MPa)
STEEL STRUCTURAL MEMBERS BY AMERICAN IRON C H
AND STEEL INSTITUTE
A.S.T.M. A185 OR BS4483 SLAB ON GRADE H STD.90 OR
WELDED WIRE FABRIC 180 HOOK MIN.CONC.
(fy = 500 MPa) DESIGN LOADS: WINDOW
H
2. CON. HOR. REINF.
OPENING
ALL BARS SHALL BE BENT COLD UNLESS PERMITTED BY THE STRUCTURAL 1. ROOF DEAD LOAD: END AN- END AN- FOR COLS. BEAMS FOR BEAM BEAM
3. ENGINEER. TRUSSES 0.24 kN/m^2 CHORAGE CHORAGE VERT.BARS, BOT.BARS BEAMS TOP BARS TOP BARS
4. THE MINIMUM LAP LENGTH ARE SHOWN ON THE TABULATION BELOW. METAL ROOFING & PURLINS 0.14 kN/m^2 R FOR BOT. FOR BOT. BEAM BOT. WHERE WHERE WHERE
CEILING 0.24 kN/m^2 INTO
ALL REINFORCING SHALL BE SUPPORTED IN CONFORMANCE WITH "THE MANUAL
OF STANDARD PRACTICE DETAILING REINFORCED CONCRETE STRUCTURE MECHANICAL AND ELECTRICAL FIXTURES 0.14 kN/m^2 E BARS OF BARS OF TENSILE WALLS TENSILE TENSILE
5. (ACI 315 LATEST EDITION). 2. ROOF LIVE LOAD: M SLAB & SLABS & TENSILE STRESS STRESS STRESS
SILL HEIGHT
ALL REINFORCING BARS SHALL BE CLEANED THOROUGHLY OF ALL LOOSE RUST, UNFACTORED (BASIC) 0.80 kN/m^2
6. SOIL OR OTHER MATERIAL IMMEDIATELY PRIOR TO PLACING CONCRETE. 3. FLOOR DEAD LOAD: A BEAMS BEAMS, STRESS IN IN BARS IN BARS IN BARS
MIN.
600
A FULL WELDED SPLICE SHALL HAVE BARS BUTTED AND WELDED TO DEVELOP PARTITIONS 1.00 kN/m^2 WALL,COL. BARS<0.5fy < 0.5fy < 0.5fy < 0.5fy
VERT. BARS
IN TENSION AT LEAST 125 PERCENT OF THE SPECIFIED YIELD STRENGTH CEMENT TILE FINISH AND R DOWELS
7. fy OF THE BAR. WATER PROOFING ON TOILETS 1.20 kN/m^2 & % OFBAR & % OF & % OF & % OF
ALL WELDING OF REINFORCEMENT SHALL CONFORM TO THE PROVISIONS OF THE 4. MATERIALS UNIT WEIGHT:
K TO FTGS. SPLICE>75% BARS BARS BARS
8. STRUCTURAL WELDING CODE REINFORCING STEEL, AWS D1.4 UNIT WEIGHT OF REINFORCED CONCRETE 24 kN/m^3 S SPLICE SPLICE SPLICE > 50% FLOOR LINE
A FULL MECHANICAL CONNECTION (REBAR SPLICER) SHALL DEVELOP IN UNIT WEIGHT OF STRUCTURAL STEEL 77 kN/m^3 NOTE: OMIT EXTRA REINF. FOR OPENING LESS
TENSION OR COMPRESSION. AS REQUIRED, AT LEAST 125% OF THE SPECIFIED 5. FLOOR LIVE LOAD: > 75% > 50% > 75% > 75% THAN 200 MM VERT. & 400 MM. HOR.
YIELD STRENGTH fy OF THE BAR. IF USED, SUBMIT SAMPLE FOR APPROVAL CLASSROOM 1.9 kN/m^2
OF THE DESIGNER. LIBRARY 2.9 kN/m^2 WINDOW OPENING ELEVATION
REPUBLIC ACT 545 Section 25 (4) DESIGNED : REVISION SHEET CONTENTS : PROJECT TITLE & LOCATION : PROJECT OWNER : SHEET NO. :
DATE
DRAWN: ENL STRUCTURAL NOTES
PROPOSED TWO STOREY
ENGINEER
DATE: 23 March 2018 MR. JOSE M. LIM S-2
P.T.R. DATE:
PRESIDENTIAL DECREE NO. 49 NOTE:
RESIDENTIAL
CHECKED:
SHOULD ANY DISCREPANCIES & INCOHERENCE BE FOUND IN ANY PARTS OF THE PLAN
LOT 15 BLOCK 16
BY: ENL
T.I.N. PRC: AND SPECIFICATION, THE ARCHITECT SHOULD BE NOTIFIED AT ONCE BEFORE ANY
DATE: ADJUSTMENTS HAS TO BE MADE. THE DECISION OF THE ARCHITECT IS FINAL. GENERAL TRIAS, CAVITE CADREF: