Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
COLLEGE OF ENGINEERING
MECHANICAL ENGINEERING DEPARTMENT
CHAPTER 9
SMOKE CONTROL SYSTEMS AND FIRE PROTECTION
SUBMITTED BY:
ACLAN, JONNEL P.
1300313
A. SMOKE-CONTROL SYSTEMS
901.0 Introduction
All fires produce smoke which, If not controlled, will spread throughout the building or
portions of the building, thereby endangering lives and damaging properties.
A smoke-control system should be designed to inhibit the flow of smoke into means of
egress, exit passageways, or other similar areas of a building. Limiting fire size by
providing automatic sprinklers or other means of automatic suppression will generally
be necessary for effective and economical control of smoke in most occupancy.
901.1 Scope This chapter shall recommended practices applied to the design,
installation, testing, operation, and maintenance of new and retrofitted mechanical air
conditioning and ventilation systems for the control of smoke.
(a) Maintain a tenahle environment in the means of egress during the time required for
evacuation.
(b) Control and reduce the migration of smoke from the fire area.
(c) provide conditions outside the fire zone that will assist emergency response
personnel to conduct search and rescue operations and to locate and control the fire.
(e) To provide a standard practices based on the Fire Code of the Philippines.
902.0 Definitions. The following terms for the purposes of this recommended practice
shall have the meanings given in this chapter.
Pressurized Stairtowers. A type of smoke- control system in which stair shafts are
mechanically pressurized with outdoor air to keep smoke from contaminating them
during a fire incident.
Smoke. The airborne solid and liquid particulates and gases evolved when a material
undergoes pyrolysis or combustion, together with the quantity of air that is entrained or
otherwise mixed into the mass.
Smoke Damper. A device that meets the requirements of UL 555S, Standard for
Leakage Rated Dampers for Use in Smoke Control Systems, designed to resist the
passage of air and smoke
Stack Effect. The vertical airflow within buildings caused by temperature differences
between the building interior and exterior.
Zoned Smoke Control. A smoke-control system that includes smoke exhaust for the
smoke zone and pressurization for all contiguous smoke-control zones. The remaining
smoke- control zones in the building also may be pressurized.
903.1 The basic principles of smoke control of this Chapter shall be referred to the
National Fire Protection Association [NFPA] standard requirement NFPA 92A
Recommended Practice of Smoke Control systems.
903.2 Design Parameters. Reference shall be Section 1-6 [NFPA 92A Recommended
Practice of Smoke Control Systems]
904.0 Application. The following shall be applied in smoke control system based on the
present practice and interpretation of the Fire Code of the Philippines 2008.
904.1 Dedicated Smoke Control Systems. Any smoke control system used in
buildings shall be dedicated to smoke control only and shall be separate from any air
moving and distribution system that operates normally. Note : Non-dedicated smoke-
control system such as the HVAC system is still being studied to determine its
advantages.
904.2.2 Stairtower Pressurization. This method shall be used in stairtowers that are
enclosed and pressurized. The stair tower shall be provided with a mechanical
ventilation smoke control system. [ Fire Code of the Philippines 2008 Section 10.2.5.4.I
par. 9]
In compliance with the Fire Code of the Philippines 2008 and NFPA 101 the pressure
difference across the doors shall not exceed the values given in Table 905_1b so that
the doors can operate while the pressurization system is operating. Allowed deviation
depending on tightness of doors, tightness of construction of walls, toxicity of smoke,
airflow rates and the volume of space shall be up to 50 per cent of the minimum design
pressure difference are considered tolerable. [NFPA 92A Section 2-2. 1]
(a) Noncompensated. This system shall not be adopted until further study is done on
its merits. In this system supply air is injected into the stairtower by actuating a single
speed fan.
(b) Compensated. This system shall be adopted in compliance with the Fire Code of
the Philippines Section 10. 2. 5. 4. I par. 9a. The compensated systems adjust to
various combinations of doors open and closed, while maintaining positive pressure
differences across such openings.
(1) Modulating Supply Airflow. In this system, the capacity of the supply fan is sized
to provide at least the minimum air velocity when the design number of doors are open.
The flow rate of air into the stairtower is varied by modulating bypass dampers, which
are controlled by one ot more static pressure sensors that sense the pressure difference
between the stairtower and the building.
In existing buildings, overpressure relief may be discharged into the building. The
effects of this on the integrity of the stairtowers and the interaction with other building
HVAC systems should be closely studied before proposing this method
Overpressure relief may be accomplished by one of four methods
(I) Baromentric dampers with adjustable counter-weights can be used to allow the
damper to open when the maximum interior pressure is reached. This represents the
simplest, least expensive method of overpressure relief since there is no physical
interconnection between the dampers and the fan.
(ii) Motor-operated dampers with pneumatic or electric motor operators are another
option. These dampers are to be controlled by differential pressure controls located in
the stairtower. This method provides more Positive control over the stairtower pressures
than barometric dampers. It requires more control than the barometric dampers and
hence is more complicated and costly.
Possible adverse wind effects are also a concern with a system that uses an open
outside door as a vent. Occasionally, high local wind velocities develop near the exterior
stairtower door. Such local winds are difficult to estimate in the vicinity of new buildings
without expensive modeling. Adjacent objects can act as windbreaks (or windshields).
(iv) An exhaust fan may be used to prevent excessive pressure when all stairtower
doors are closed. The fan should be controlled by a differential pressure sensor so that
it will not operate when the pressure difference between the stairtower and the building
falls below a specified level. This should prevent the fan from pulling smoke into the
stairtower when a number of open doors have reduced stairtower pressurization.
906.3.1 The supply air intake shall be separated from all building exhausts, outlets from
smoke shafts and roof smoke and heat vents, open vents from elevator shafts and other
building openings that might expel smoke from the building in a fire. This separation
shall be as great as is practically possible. Rising hot smoke shall be given
consideration when locating supply air intakes below such critical openings.
906.3.2 When any stairtower pressurization system, has a potential for smoke feedback
into the pressurized stairtower or smoke entering the stairtower through the
pressurization fan intake an automatic shutdown of the pressurization fan shall be
provided. [NFPA 92A Section 2-3. 3. 2]
907. 2 0ther Types of Fans. Centrifugal or in-line axial fans shall be used in ducted
single or multiple injection stairtower pressurization system.
908.1 Single Injection System. Single injection system shall be used in buildings not
more than seven (7) stories or 80 feet (25 meters) high above ground level. [NFPA 92A
Section 2-3. 5. 1]
909.1 A fire floor exhaust shall be provided in in each floor of the building to improve
performance of the stairtower pressurization by increasing the pressure difference
across the stairtower door. The floor exhaust shall discharge the smoke outside the
building either through a fan powered or non-fan powered method. [NFPA 92A Section
2-3. 7]
910.1 General. Due to having elevator doors that are not tightly fitted the elevator
hoistway have been a conduit for the movement of smoke throughout the buildings. The
building stack effect has provided the driving force to easily move the smoke in and out
of the loosely constructed elevator hoistway. The open vent at the top of the elevator
hoistway produces undesirable effect on elevator smoke-control systems.
910.2 To address the concern of smoke migrating in to the elevator lobby two (2)
methods are either proposed to protect the building occupants from smoke, provided
the elevator lobbies are constructed smoketight
(b) Pressurize the elevator lobby through the stairtower pressurization system..
912.1 Automatic Activation. Any operation of any zone of the building protective
signaling system shall cause the activation of all pressurization fans to start. A smoke
detector shall be provided in the air supply of the pressurization fan and upon detection
of smoke shall stop the supply fans. [ NFPA 92A Section 3-4, 4]
912.2 Manual Activation. A manual over-ride switch shall be provided at the Fire
Fighter Smoke Control Station (FFSCS) to re-start the stairtower Pressurization fan
after shut-down from the smoke detector when it was determined that lesser hazard
exist from the smoke entering the fan than the smoke entering through the stairtower
doors.
913.0 Testing
913.1.1 With all building HVAC systems normal operation, measure and record the
Pressure difference across each stairtower door while the door is closed. After
recording the Pressure difference across the door, using spring-type scale. Establish a
consistent procedure for recording data throughout the entire test, such that the
stairtower side of the doors will always be considered as the reference Point [0 lb/sq in,
(0 kg/m 2) ] and the floor side of the doors will always have the pressure difference
value (positive if higher than the stairtower and negative when less than the stairtower).
Since the stairtower pressurization system is intended to produce a positive pressure
within the stairtower, all negative pressure values recorded on th floor side of the doors
are indicative of a potential airflow into the floor.
913.1.2 Verify the proper activation of the stairtower pressurization system (s) in
response to all means of activation, both automatic and manual, as specified in the
contract documents. Where automatic activation is required in response to alarm
signals received from the building's protective signaling system, each separate alarm
signal should be initiated to ensure that proper automatic activation occurs.
913.1.3 With the stairtower pressurization system activated, measure and record the
pressure difference across each stairtower door with all doors closed.
913.1.5 With the stairtower pressurization system activated, open the required
additional doors, one at a time, and measure and record the pressure difference across
each remaining closed stairtower door after the opening of each additional door After
recording the pressure difference across each closed door measure the force necessary
to open each door, using a spring-type scale.
913.1.6 With the stairtower system activated, and all required doors open as covered
by 4-3. 4. 5, determine and record the direction of airflow though each of the open
doors. This can be done by a small amount of smoke at the open doorway or by
temporarily securing a 6-ft (1. 8-m) strip of tissue to the top of the door frame. If velocity
measurements are required, a door opening traverse needs to be performed with the
door fully open.
B. FIRESTOP PROTECTION
914.1 Applicability. All piping penetrations of required fire resistance rated walls,
partitions, floors, floor/ceiling assemblies, roof/ceiling assemblies, or shaft enclosures
shall be protected in accordance with the requirements of the Building Code, and this
chapter.
915.1 Plans and specifications shall indicate with sufficient detail how penetrations of
fire resistance rated assemblies shall be fire stopped prior to obtaining design approval.
916.0 Installation.
916.1 Firestop materials shall be installed in accordance with this chapter, the Building
Code, and the manufacturer's instructions.
917.0 Definitions.
917.2 F Rating. The time period that the penetration firestop system limits the spread of
fire through the penetration, when tested in accordance with ASTM E 814.
917.3 T Rating. The time period that the penetration firestop system, including the
penetrating item, limits the maximum temperature rise of 325 °F above its initial
temperature through the penetration on the non-fire side when tested in accordance
with ASTM E 814.
918.2 When penetrating a fire resistance rated wall, partition, floor, floor ceiling
assembly, roof ceiling assembly, or shaft enclosure, the fire resistance rating of the
assembly shall be restored to its original rating.
918.3 Penetrations shall be protected by an approved penetration firestop system
installed as tested in accordance with ASTM E 119 or ASTM E 814, with a minimum
positive pressure differential of 0.01 inch of water. Systems shall have an F rating of at
least 1 hour but not less than the required fire resistance rating of the assembly being
penetrated Systems protecting noor penetrations shall have a T rating of at least 1 hour
but not less than the required fire resistance rating of the floor being penetrated. Floor
penetrations contained within the cavity of a wall at the location of the floor penetration
do not require a T rating. No T rating shall be required for floor penetrations by piping
that is not in direct contact with combustible material.
918.4 When piping penetrates a rated assembly, combustible piping shall not connect to
non-combustible piping unless it can be demonstrated that the transition complies with
the requirements of Section 905. 3.
918.5 Insulation and Coverings. Insulation and coverings on or in the penetrating item
shall not be permitted unless the specific insulating or covering material has been tested
as part of the penetrating firestop system.
918.6 Sleeves. Where sleeves are used, the sleeves should be securely fastened to the
fire resistance rated assembly. The (inside) annular space between the sleeve and the
penetrating item and the (outside) annular space between the sleeve and the fire
resistance rated assembly shall be firestopped in accordance with the requirements for
a sleeve penetrating item.
919.2 When penetrating a lire resistance rated wall, partition, floor, floor ceiling
assembly, roof ceiling assembly, or shaft enclosure, the fire resistance rating of the
assembly shall be restored to its original rating.
Exceptions
(1) Concrete, mortar, or grout may be used to fill the annular spaces around cast-iron,
copper, or steel piping that penetrates concrete or masonry fire-resistant rated
assemblies. The nominal diameter of the penetrating item should not exceed 6 inches
(15. 2 cm), and the opening size should not exceed 144 inches-(929 cm ). The
thickness of concrete, mortar, or grout should be the full thickness of the assembly or
the thickness necessary to provide a fire resistance rating not less than the required fire
resistance rating of the assembly penetrated, or
(2) The material used to fill the annular space shall prevent the passage of flame and
hot gases sufficient to ignite cotton waste for the time period equivalent to the fire
resistance rating of the assembly, when tested to standard (s) referenced in Section
1506. 3.
919.4 When piping penetrates a rated assembly, combustible piping shall not connect to
non-combustible piping unless it can be demonstrated that the transition complies with
the requirements of Section 1506. 3.
919.5 Unshielded couplings shall not be used to connect noncombustible piping unless
it can be demonstrated that the fire resistive integrity of the penetration is maintained.
919.6 Sleeves. Where sleeves are used, the sleeves should be securely fastened to the
fire resistance rated assembly. The (inside) annular space between the sleeve and the
penetrating item and the (outside) annular space between the sleeve and the fire
resistance rated assembly shall be firestopped in accordance with the requirements for
a sleeve penetrating item.
919.7 Insulation and Coverings. Insulation and coverings on or in the penetrating item
shall not be permitted unless the specific insulating or covering material has been tested
as part of the penetrating firestop system.
920.1 General. Prior to being concealed, piping penetrations shall be inspected by the
Authority having Jurisdiction to verify compliance with the fire resistance rating
prescribed in the Building Code.
920.3 The Authority Having Jurisdiction shall determine the type, size, and quantity of
penetrations to be inspected.
920.4 The Authority Having Jurisdiction shall compare the field installations with the
documentation supplied by the installer to determine the following
(1) The required F ratings (1, 2, 3, or 4 hour) and T ratings (0, 1, 2, 3, or 4 hour) of the
firestop penetration firestop systems are suitable for the assembly being penetrated.
(2) The penetrating firestop systems are appropriate for the penetrating items, as
documented through testing of the systems conducted by an independent testing
agency.