Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
CONSULTANT:
SIEMENS CONSORTIUM
SIEMENS AG - SIEMENS WLL
List of Contents
Sl Description Page No
1 LV DC Distribution Board……………………………………………………………………………. 4
2 LV AC Distribution Board……………………………………………………………………………. 5
4 11kV Switchgear…………………………………………………………….…………..…………… 7
5 LCC Panels………………………………………………………….…………..………………………… 8
6 Relay Panels………………………………………………….…………..……………………………… 8
9 RTCC Panel………………………………………………….…………..……………………………… 9
11 Auxiliary Transformer………………………………….…………..……………………………… 11
Reference Documents:
22 LVAC PH12-3A-XX-60-4802 --
23 LVDC PH12-3A-XX-60-4804 --
LV DC DISTRIBUTION BOARD
Nominal Final value to
S.No Description Setting Range
Voltage be Adopted
I Earth Fault Relay Make:-ABB
1ELR,2ELR Model.No:-CM-IWS-1S 24-240V AC/DC 3.0kOhms
Setting Range:0-100
V Timer Model.No:-3RP1505-1BW30
T01 Make:-SIEMENS
Time Delay:- 1s-8Hr 5 sec
CHAR:- A-H, 5 to 100%
VI Thermostat Make:- Schenider Electric
TH Temp:10-60ºC Un:230V AC 30ºC
VII Humidistat Make:- Schenider Electric
HG Humidity:35-100% Un:230V AC 60%
Page 4 of 15
LV AC DISTRIBUTION BOARD
Nominal Final value to be
S.No Description Setting Range
Voltage Adopted
I Under / Over Voltage Relay Model.No:-3UG4615-1CR20
F27, F59, VSR Make:-SIEMENS
1VSR, 2VSR, 4VSR O/V:-105-125% x Un Un:415 V AC 110% x Un
U/V:-75-95% x Un Un:415 V AC 85% X Un
Time :-0.1-20.0Sec 2 sec
II Timer Model.No:-3RP2505-1BW30
2KT0,3KT1,3KT0 Make:-SIEMENS
1KT0, 4KTST Time Delay:- 1 - 5 sec
III Timer Model.No:-3RP1511-1AP30
3KT11,3KT12 Make:-SIEMENS
Time Delay:- 0.5s - 10s 5 sec
IV Timer Model.No:-NMRDV2-60
TST Make:-GE
Time Delay:- 5Sec - 60Sec 5 sec
V Sync Check Relay Model.No:-2SYS212-S
Make:-RMS
Voltage Difference:- 10V
VI MCCB Range: Min-Med-Max
40A 32-34-36-38-40 A
63A 50-53.3-57-60-63 A
80A 64-68-72-76-80 A
125A 100-107-113-119-125 A Refer LVAC co-
160A 125-136-160 A ordination
LT: 200 - 250A document
250A
ST: 5 - 10 In
LT: 500 - 630A
630A
ST: 5 - 10 In
VII Thermostat Make:- SCHNEIDER
TH Temp:10-60ºC Un:230V AC 30ºC
VIII Humidistat Make:- SCHNEIDER
HG Humidity:35-100% Un:230V AC 60%
IX ACB Make:- GE
4 Pole, Withdrawable ACB with Entelliguard N Type Refer LVAC co-
Incomer 1 & 2 3200A, 65kA ordination
Bus Section document
Page 5 of 15
Page 6 of 15
11kV Switchgear
Nominal Final value to
S.No Description Setting Range
Voltage be Adopted
I Spring Charge Timer Make:-SIEMENS 110V DC
KS42 Model.No:-3RP1525-1BW30
Time:-1S-100Hr 15 sec
II Thermostat Make:-
TH1, TH2 Temp:10-60ºC Un:240V AC 30ºC
III Humidistat Make:-
HD1,HD2 Humidity:50-90% Un:240V AC 60%
IV UV Relay make:-DOLD
OG, B/S Model.No:-1P5201 0.55
Range:- 0.55-1.05
Page 7 of 15
LCC Panels
Nominal Final value to be
S.No Description Setting Range
Voltage Adopted
I Under Voltage Relay Make:-BENDER Un:-63.5V AC
In Tx Incomer & OG feeders Model:-VMD420
K405 Setting Range:-10-100 V 10 V (15.8% of 63.5V)
Hys % - 5 - 30% 10%
Function delay:-0-3 sec <3
II Hygrostat Make:-
Temp:0-60ºC Un:240V AC 30ºC
Humidity:50-90% 60%
III Hooter Reset Timer Make:- Siemens Un:240V AC
In Bus Section Panel Model:-2525-1BW30 50Hz
K6 5 - 100 % 50%
E
T = 10 Sec - 10 sec
Relay Panels
I Hygrostat Make:- Un:230V AC
Temp:0-60ºC 30ºC
Humidity:50-90% 60%
Common AlarmPanel
I Hygrostat Make:-
Temp:10-60ºC Un:240V AC 30ºC
Humidity:50-90% 60%
II Hooter Reset Timer Make:- Siemens Un:240V AC
K6 Model:-3RP1505-1AW30 50Hz
5 - 100 % 50%
Char - A - H E
T = 1 Sec - 10 sec
Page 8 of 15
IV
Page 9 of 15
Page 10 of 15
Page 11 of 15
Page 12 of 15
Page 13 of 15
(K9,K10) Model.No:-3UG4513-1BR20
Page 14 of 15