Line and Circuit Protection
fest, Using tap 7 (280A primary) and a time dial of
1.25, we can find the curve points for Figure 12-7:
Multiples of tap Primary current Time to close
setting at 23kV contacts (se)
10 280
20 360 230
25 700 135
30 840 1.00
40 1120 0.600
50 1400 05
10 1860 035
Finally, the IIT of CR-8 is set to 1.3 x 1100, or 14304,
(6A secondary)
1D.3.7. Setting for Relay F to Coordinate with
Relays D and J
Based on the assumption in Section E,3.2 that location
J provides transformer and bus differential protection,
their operations should be high-speed.
The maximum forward-direction load flow current,
will be 125.6 if breakers J and B are opened. The
overcurrent unit at F should be set to 251.2A for this
Toad current, However, the maximum end-zone fault
current is only 200A, Therefore, from the point of
view of protection, operating the system on both
breakers J and B opened at the same time is not
allowed. Based on this conclusion, it can be assumed
that load will not flow through F to E, and since the
relay is directional, then there is no need to set the
overcurrent unit at twice the maximum load current.
It can be set based on 2 continuous rating, The
maximum continuous load is 125.6/40=3.14 A (relay
side), The continuous rating of any HiLo CO tap is
higher than this value. Therefore, choosing a 1-A tap
should be no problem. Since the IIT unit of the D
relay will operate for fault (3) maximum, the critical
fault for relay F is fault (3) minimum. The overcurrent
unit of the D relay will operate in 0.55see (1180)
280 = 4.22 multiple).
For relay F, tap 1 corresponds to 1 x 40, or 404,
primary. The critical fault multiple is 180/40 or 4.5, at
which value the operating time should be 0.55 plus 0.3,
or 0.85sec. From Figure 12D-3, for 2 4.5 multiple and
0.85 see, the time dial is approximately 2. Using tap |
(AOA primary) and a time dial of 2, we can find the
curve points for Figure 12D-8:
317
Multiples of tap Primary current ‘Time to close
setting at BY contacts (see)
10 0
25 100 238
30 120 16s
40 160) 10s
50 200 078
To 280 08
100 400 0.46
16.0 640 0.36
The instantancous-trip unit of the IRV-8 is a
cylinder element, It can be set for 1.10 x 200, or
220A primary (S.SA secondary). A 6-A setting or
240A primary current will provide high-speed, sequen-
tial tripping. After E opens with a fault near B on line
FE, the fault current increases at F to 300 which is
above the instantancous unit pickup of 220.
D.3.8 Setting for Relay H to Coordinate with
Relays K and F
Since relay K operates instantaneously for the max-
mum fault 2), the critical fault is 2) minimum. Critical
fault current is 1550 for relay K and 750A for relay
H, Relay H is set for a minimum pickup of 2 125, or
250A primary (6.25 A secondary) load current. Tap Tis
selected to give a minimum pickup of 7 x 40, or 280A.
The critical fault multiple is 750/280, or 2.68 for
relay H. The operating time of relay K for the critical
fault value of 1550A is 0.70sce (1550/280, or a 5.52
multiple). The set point for relay H should be 0.70 plus
0,30, or Isee at 750A. From Figure 12D-3, for a 2.68
‘multiple and 1 see, the time dial is 1. Using tap 7 (280 A
primary) and a time dial of 1, we can find the curve
points for Figure 120-9:
Multiples of tap Primary current Time to elose
setting at BY contacts (see)
20 560 2
25 700 12
30 os
40 os
50 038
10 030
The instantancous-trip unit of the IRV-8 is a
cylinder element. It can be set for 1.10 x 1000, or
Ms Do
_2T0Nasssn sans New ee New re 6
tha8
Time in Seconds
Chapter 12
26
24
22
20
Pick up at 220 a
18
16
14
12
10
os
os
o4
iT at
Trip at 280 A
02
100 200300 400 +1000 2000-3000
——_>+
— Primary Amperes at 23KV
CRB Tap=7, TD=1.25
Pick up at 7.0(200V5)=260 A
IIT Pick up at 36(200%5)=1430 A
Figure 120-7 Relay D settings
Ms Do
rrrutscnen neecreuatby Ms