Sei sulla pagina 1di 2

The PAXLIT 5 Amp AC Current Meter is configured by simply connecting

the “COMM.” (Terminal 3) and the “5AMP” (Terminal 4) to the external


current transformer. The current carrying wire to be sensed is passed through the
center of the current transformer. The resolution of the display, in this case, is
0.1 Amp, therefore, “Switch #1” is selected.
The meter is now ready to be scaled. The installer has access to a calibrated
portable digital current meter capable of measuring the motor current. Scaling
will be accomplished by adjusting the scaling pot on the PAXLIT meter to agree
with the portable digital current meter. The operator turns on the AC motor and
lifts a large weight to load the motor. The installer then simply adjusts the
scaling adjustment, located at the rear of the unit, until the display is equal to
the value indicated on the portable current meter. The meter will now indicate
the load current of the motor precisely.

El medidor de corriente PAXLIT de 5 amperios se configura simplemente conectando


el "COMM." (Terminal 3) y el "5AMP" (Terminal 4) al externo
transformador de corriente. El cable portador de corriente que se va a detectar pasa a través
del
centro del transformador de corriente. La resolución de la pantalla, en este caso, es
0.1 Amp, por lo tanto, se selecciona "Switch # 1".
El medidor ahora está listo para escalar. El instalador tiene acceso a un calibrado
medidor de corriente digital portátil capaz de medir la corriente del motor. Escalada
se logrará ajustando el potenciómetro en el medidor PAXLIT para acordar
con el medidor de corriente digital portátil. El operador enciende el motor de CA y
levanta un gran peso para cargar el motor. El instalador luego simplemente ajusta el
ajuste de escala, ubicado en la parte posterior de la unidad, hasta que la pantalla sea igual a
el valor indicado en el medidor de corriente portátil. El medidor ahora indicará
la corriente de carga del motor con precisión.

the apollo 5 amp AC current meter is configured by simpy connecting the


COMM (terminal 3) and 5A (terminal 4) to the external current transformer.
the carriying wire to be sensed is passed through the center
of the curren transformer.the resolution of display, in this case, is 0.1 amp,
therefore D.P.I is selected.
the apollo is now ready to be calibrated. the installer has access to portable
digital current meter capable of measuring up to 200 amps.
calibration will be acomplished by causing the apollo indicator to agree whit
the portable digital current meter.
the operator turns on the AC motor and lifts a large weight load
the motor. the installer then simply adjusts the Coarse scaling adjustment,
located at the rear of the unit, until the display is close in value to that indicated
on the portable current meter. he then removes the fine scaling access plug and
adjusts the fine scaling adjustment until the display agrees whit the portable
current meter. he then replaces the access plug to keep dust out of the apollo.
the apollo 5 amp Current meter will now indicate the load current of the motor
precisely.

el medidor de corriente de CA apollo 5 amp se configura simplemente conectando el


COMM (terminal 3) y 5A (terminal 4) al transformador de corriente externo.
el cable que se va a detectar se pasa a través del centro
del transformador de corriente. La resolución de la pantalla, en este caso, es 0.1 amperio,
por lo tanto, se selecciona D.P.I.
el apollo ahora está listo para ser calibrado. el instalador tiene acceso a portátil
medidor de corriente digital capaz de medir hasta 200 amperios.
la calibración se realizará haciendo que el indicador de apolo acepte
el medidor de corriente digital portátil.
el operador enciende el motor de CA y levanta una gran carga de peso
el motor. el instalador luego simplemente ajusta el ajuste de escala gruesa,
ubicado en la parte posterior de la unidad, hasta que la pantalla se acerque al valor indicado
en el medidor de corriente portátil. luego quita el tapón de acceso de escala fina y
ajusta el ajuste fino de escala hasta que la pantalla concuerde con el portátil
medidor de corriente luego reemplaza el enchufe de acceso para mantener el polvo fuera
del apollo.
el medidor de corriente apollo 5 amp ahora indicará la corriente de carga del motor
precisamente.