GENERAL NOTES

1. ALL ELECTRICAL WORKS HEREIN SHALL BE IN ACCORDANCE W/ THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE. THE EXISTING LOCAL ORDINANCES RULES & REGULATIONS OF THE MUNICIPAL ELECTRICIAN
& REQ'TS. OF THE UTILITY COMPANY. NO# WIRE SIZES AND NUMBERS CONDUIT

2. THERE SHALL BE ONLY ONE SERVICE DROP TO THE COMMERCIAL ESTABLISHMENT. THE TYPE OF 1 4 – 60 mm2 and 1 – 30 mm2 THHN 50 mm PVC
2 4 – 30 mm2 and 1 – 22 mm2 THHN 32 mm PVC
ELECTRICAL SERVICE TO BE SUPPLIED SHALL BE 3-PHASE, 4-WIRE, 400V, 60 HZ.
3 4 – 125 mm2 and 1 – 30 mm2 THHN 80 mm PVC
4 4 – 8.0 mm2 and 1 – 8.0 mm2 THHN 20 mm PVC
3. WIRING METHODS SHALL BE OF POLYVINYL CHLORIDE (PVC) PIPES FOR ALL BRANCH CIRCUITS/RACEWAYS, 5 4 – 14 mm2 and 1 – 14 mm2 THHN 25 mm PVC
TELEPHONE & CATV. AND PVC FOR SERVICE ENTRANCE. 6 2 sets of 4 – 125 mm2 and 1 – 60 mm2 THHN 80 mm PVC
7 2 – 14 mm2, 1 – 5.5 mm2 and 1 – 5.5 mm2 THHN 25 mm PVC
4. ALL WIRES SHALL BE COPPER, PVC INSULATED & NYLON JACKETED "THHN" UNLESS OTHERWISE INDICATED. 8 4 – 125 mm2 and 1 – 50 mm2 THHN 80 mm PVC
ACU
THE MINIMUM SIZE FOR POWER SHALL BE 3.5mm2/5.5mm2 AND 9 4 – 3.5 mm2 and 1- 5.5 mm2 THHN 15 mm PVC
FOR LIGHTING 3.5mm2 CONTROL WIRES SHALL BE AS INDICATED OR AS SPECIFIED ELSEWHERE IN THE PLAN. 10 4 – 30 mm2 and 1 – 30 mm2 THHN 32 mm PVC
11 2 THHN 25 mm PVC
12 2 2 THHN Free Air
5. THE MOUNTING HEIGHTS OF WIRING DEVICES SHALL BE AS FOLLOWS:
a.) CEILING LIGHT OUTLET - 1.40m ABOVE FLR. FINISH
b.) CONVENIENCE OUTLET - 0.30m do/ ASREQUIRED FAP
CONDUIT SCHEDULE
c.) TEL/CATV OUTLET - 0.30m do TTC

d.) PANELBOARD/TPB/CATVB -1.40m do/ AT CENTER


SB

6. ALL ELECTRICAL EQUIPMENT, MACHINERIES, TRANSFORMERS PANELBOARDS AND ELECTRICAL GUTTER MSB 8
ROOFTOP

BOXES SHALL BE EFFECTIVELY GROUNDED. MCP 7


7
7 7

7. PVC OUTLET BOXES SHALL BE USED,AS FOLLOWS: MTTC


M M M M
a.) CEILING LIGHT OUTLET - 40mm deep, 100mm dia. OCTAGONAL BOX for 1 or 2 raceways entries. MFAP ~ ~ ~ ~
E4 E3 E1 E2

b.) WALL SWITHCHES - 55mm deep, UTILITY BOX for 1 or 2 switches. C


RP 25 HP 25 HP 25 HP 25 HP

c.) WALL RECEPTACLE OUTLET - 5mm deep, UTILITY BOX for 1 or 2 raceways entries. SD V
6 11
5TH FLOOR

C
d.) SPECIAL PURPOSE OUTLET - 20mm deep, 100mm dia. SQUARE BOX w/ cover.
E VICINITY MAP M M M M M M

U12P U10P U8P U6P U4P U2P


8. ALL MATERIALS TO BE USED SHALL BE NEW & SUITABLE FOR PURPOSE & LOCATION. LEGENDS AND SYMBOLS 11

9. THE CONTRACTOR SHALL VERIFY & ORIENT THE ACTUAL LOCATION OF ELECTRICAL/TELEPHONE/CATV 5FMP
M M M M M M M

SYSTEM SERVICE ENTRANCE FOR CONNECTION TO THE LOCAL ELECTRICAL/TELEPHONE/CATV FACILITIES. U1P U3P U5P U7P U9P U11P U13P

6 4TH FLOOR
11
10. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED
ELECTRICAL ENGINEER OR REGISTERED MASTER ELECTRICIAN. M M M M M M

U12P U10P U8P U6P U4P U2P

11. ALL PANELS ARE LOCATED IN ELECTRICAL ROOM. ROOFTOP 11

P P
1.25 mm2 ASWX CABLE 4FMP
20mm DIAMETER PVC M M M M M M M
FA = 6
U1P U3P U5P U7P U9P U11P U13P
ROOFTOP ROOFTOP
5TH FLOOR

P P P 6 3RD FLOOR
11
1.25 mm2 ASWX CABLE
20mm DIAMETER PVC 5TH FLOOR
5TH FLOOR SB CELING
SB5F CELING
M M M M M M
FA = 10 RG – 6 COAXIAL CABLE
20mm DIAMETER PVC U12P U10P U8P U6P U4P U2P

RG – 6 COAXIAL CABLE 4TH FLOOR


20mm DIAMETER PVC TL = 13 11
TV

TV

TV

TV

TV = 13 P P P
1.25 mm2 ASWX CABLE
20mm DIAMETER PVC 4TH FLOOR 3FMP
SB CELING
4TH FLOOR M M M M M M M
SB4F CELING
U1P U3P U5P U7P U9P U11P U13P
FA = 10 RG – 6 COAXIAL CABLE
20mm DIAMETER PVC
RG – 6 COAXIAL CABLE 3RD FLOOR TL = 13 6 2ND FLOOR
11
20mm DIAMETER PVC
TV = 13
TV

TV

TV

TV

P P P
1.25 mm2 ASWX CABLE 3RD FLOOR
20mm DIAMETER PVC SB CELING
M M M M M M
3RD FLOOR
SB3F CELING

RG – 6 COAXIAL CABLE U12P U10P U8P U6P U4P U2P


FA = 10
POWER TELEPHONE/NETWORK 20mm DIAMETER PVC
POLE OR PEDESTAL TL = 13 11
RG – 6 COAXIAL CABLE
2ND FLOOR
20mm DIAMETER PVC
TV = 13 P P P
TV

TV

TV

TV

POWER TELEPHONE/NETWORK 2FMP


1.25 mm2 ASWX CABLE 2ND FLOOR M M M M M M M
POLE OR PEDESTAL SB CELING
20mm DIAMETER PVC
2ND FLOOR U1P U3P U5P U7P U9P U11P U13P
SB2F CELING
RG – 6 COAXIAL CABLE
FA = 10 400 V,

TL = 13
20mm DIAMETER PVC
3 PHASE SOURCE
AC SUPPLY
6 5
GROUND FLOOR

M 4
RG – 6 COAXIAL CABLE GROUND FLOOR 4
20mm DIAMETER PVC
P P GROUND FLOOR
TV = 13
TV

TV

TV

TV

SB CELING M
1.25 mm2 ASWX CABLE C1P C3P AP
M
20mm DIAMETER PVC 2500 Amp. DPST
FA = 8 M 2
GROUND FLOOR RG – 6 COAXIAL CABLE 415 V, 3 Pole 3 4
Safety Switch 1FMP 1 2
20mm DIAMETER PVC
M
TL = 9
M
P P M C2P LP
RG – 11 COAXIAL CABLE RG – 6 COAXIAL CABLE RPA RPB
20mm DIAMETER PVC 20mm DIAMETER PVC BASEMENT
1.25 mm2 ASWX CABLE FA = 6 12
TL = 1
20mm DIAMETER PVC 10
BASEMENT BASEMENT 9
BASEMENT
SB CELING 9 9
P P
RG – 6 COAXIAL CABLE
FA = 8 RG – 11 COAXIAL CABLE 20mm DIAMETER PVC
20mm DIAMETER PVC M M M
MDP
BP TL = 1 ~ ~ ~
MSB MFAP BP MTTC BP FP FP FP
BP
10 HP 10 HP 10 HP
ELECTRICAL ROOM/STAFF LOUNGE ELECTRICAL ROOM/STAFF LOUNGE MAIN ELECTRICAL ROOM/STAFF LOUNGE
ELECTRICAL ROOM/STAFF LOUNGE

FDAS RISER DIAGRAM TELEPHONE RISER ELECTRICAL RISER


CATV RISER DIAGRAM

DESIGNED NO.1 PREPARED BY: PROJECT TITLE SIGNED AND APPROVED BY: SHEET CONTENTS REVISION SCALE SHEET NO.
TECHNOLOGICAL INSTITUTE OF THE
USANA, JUAN CARLO A.
PHILIPPINES LACORTE, LORENZO LUIS M. ENGR. EDGARDO O. DOMNGO GENERAL NOTES
1338 ARLEGUI ST. QUIAPO MANILA
ARCHITECTURAL DESIGN OF MAGLENTE, JAY-AR C.
MENESES, JOSHUA A.
Professional Electrical Engineer
AND NTS
1
PRC NO. 2000 VALID UNTIL SEPT 2117
ELECTRICAL ENGINEERING DEPARTMENT MULTI FAMILY DWELLING UNIT NOGALIZA, REYJIE R.
SO, BRIA RODORA P.
PTR NO. 123456
ISS AT MANILA CITY
ISS ON JAN 2016
TIN NO: 123 - 456 - 789 SPECIFICATIONS