K3FP Series
Product Selection
Product Model Input signal Output signal Power supply Reference
voltage page
3-Way Signal Isolator K3FP-YV-I-I 0 (4) to 20 mA DC 0 (4) to 20 mA DC 24 V DC 3
3-Way Signal Isolator K3FP-YV-U-U −10 (0) to 10 V DC −10 (0) to 10 V DC 24 V DC
3-Way Signal Isolator K3FP-VS-UI-UI 0 to 20 mA DC, 4 to 20 mA DC, 0 to 20 mA DC, 4 to 20 mA DC, 24 V DC 6
0 to 10 V DC, 2 to 10 V DC, 0 to 10 V DC, 2 to 10 V DC,
0 to 5 V DC, 1 to 5 V DC 0 to 5 V DC, 1 to 5 V DC
(selected by DIP switch setting) (selected by DIP switch setting)
Dual Output 3-Way Signal K3FP-VS-UI-2I 0 to 20 mA DC, 4 to 20 mA DC, 0 to 20 mA DC, 4 to 20 mA DC 24 V DC 10
Isolator 0 to 10 V DC, 1 to 5 V DC (selected by DIP switch setting)
(selected by DIP switch setting)
Loop-powered Isolator K3FP-SN1-I-I 0 (4) to 20 mA DC 0 (4) to 20 mA DC --- 14
(1-channel)
Loop-powered Isolator K3FP-SN2-I-I 0 (4) to 20 mA DC 0 (4) to 20 mA DC ---
(2-channel)
Thermocouple Transducer K3FP-TS-UI Type J and K Thermocouples 0 to 20 mA DC, 4 to 20 mA DC, 24 V DC 17
(Conforms to IEC 60584-1) 20 to 0 mA DC, 20 to 4 mA DC,
(Input temperature range is 0 to 5 V DC, 1 to 5 V DC,
selected by DIP switch setting.) 0 to 10 V DC, 10 to 0 V DC
(selected by DIP switch setting)
RTD Transducer K3FP-RS-UI PT100 Platinum Resistance 0 to 20 mA DC, 4 to 20 mA DC, 24 V DC 23
Thermometer 20 to 0 mA DC, 20 to 4 mA DC,
(Conforms to IEC 60751) 0 to 5 V DC, 1 to 5 V DC,
(Input temperature range is 0 to 10 V DC, 10 to 0 V DC
selected by DIP switch setting.) (selected by DIP switch setting)
Repeater Power Supply K3FP-DY-I-I 0 (4) to 20 mA DC 0 (4) to 20 mA DC 24 V DC 30
Limit Value Switch K3FP-SL-UI 0 to 20 mA DC, 0 to 10 V DC SPDT output 24 V DC 33
(selected by DIP switch setting)
External device
Field device
Input signal 4 to 20 mA DC
0 to 20 mA DC,
4 to 20 mA DC, Note: Consider the following products for judging non-DC
0 to 10 V DC, signal inputs.
1 to 5 V DC For AC current single-phase signal inputs: K8AB-AS
4 to 20 mA DC For AC voltage single-phase signal inputs:
(switch using
DIP switch) K8AB-VS/K8AB-VW
For AC voltage three-phase signal inputs: K8AB-PW
For thermocouple and platinum resistance
Data Logger
thermometer sensor inputs: K8AB-TH
For details, refer to Measuring and Monitoring Relays K8AB Series/
61F-D21T (Cat. No.: N141).
K3FP-YV-I-I/K3FP-YV-U-U
6.2-mm Ultra-slim Isolator
• Isolates between input, output, and power supply. 1,500 V AC
dielectric strength.
• Close mounting.
• CE Marking compliant.
• UL certified.
20
K3FP-YV-U-U
10
12
0
Name Model
8
DC Current Isolator K3FP-YV-I-I
DC Voltage Isolator K3FP-YV-U-U 4
−10
■ Optional Products
0 4 8 12 16 20 −10 0 10
Input current (mA) Input voltage (V)
Name Model
DIN rail bus connector K3FP-1
Ratings and Specifications
Nomenclature
Translucent cover
Potentiometer for adjustment 1 2 Input signals
3 4 Supply voltage
5 6 Output signals
7 8 Supply voltage
Snap for mounting DIN rail
Note: The potentiometer is for adjustment at the factory. Do not adjust the potentiometer.
+ 3 7 +
Supply voltage Supply voltage
− 4 8 −
K3FP-1
Dimensions
Note: All units are in millimeters unless otherwise indicated.
K3FP-YV-I-I Note: 1. Use solid wire with a diameter
of 2.5 mm2 max. or bar
K3FP-YV-U-U terminals with insulation
93.1 6.2
sleeves for terminal
connections.
To preserve dielectric strength
after connection, the length of
the exposed conductive part
inserted into the terminal must
be 12 mm max.
102.5
For 2.5-mm2 (max.) For bar terminals with
solid wire: insulation sleeves:
12 mm max. 12 mm max.
2. Screw Tightening Torque
Recommended torque:
0.5 N·m
Precautions
Refer to pages 38 and 39 for common precautions.
K3FP-VS-UI-UI
6.2-mm Ultra-slim Isolator with 36 Input and
Output Combinations.
• Input and output ranges can be easily changed using an
external DIP switch.
• Isolates between input, output, and power supply. 1,500 V AC
dielectric strength.
• Close mounting.
• CE Marking compliant.
• UL certified.
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Translucent cover
Potentiometer for adjustment 1 2 Input signals
3 4 Supply voltage
5 6 Output signals
DIP switch S1
DIP switch S2
7 8 Supply voltage
Snap for mounting DIN rail
+ 3 7 +
Supply voltage Supply voltage
− 4 8 −
K3FP-1
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Note: 1. Use solid wire with a diameter
K3FP-VS-UI-UI of 2.5 mm2 max. or bar
terminals with insulation
93.1 6.2 sleeves for terminal
connections.
To preserve dielectric strength
after connection, the length of
the exposed conductive part
inserted into the terminal must
be 12 mm max.
102.5 For 2.5-mm2 (max.) For bar terminals with
solid wire: insulation sleeves:
12 mm max. 12 mm max.
Precautions
Refer to pages 38 and 39 for common precautions.
K3FP-VS-UI-2I
6.2-mm Ultra-slim Dual Output 3-Way Signal
Isolator
• Outputs two isolated signals.
• Isolated between input, output 1, output 2, and between power
supply. 1,500 V AC dielectric strength.
• Close mounting.
• CE Marking compliant.
• UL certified.
Nomenclature
Translucent cover
Diagnostics indicator (red) 1 2 Input signals
DIP switch S1
3 4 Output 2 signal
5 6 Output 1 signal
7 8 Supply voltage
Snap for mounting DIN rail
4 to 20 mA ● ● ● Input: 1 to 5 V
0 1 2 3 4 5 (V)
Analog output limit operation
Below normal Normal operating range Above normal
Limit function disabled ❍ operating range operating range
Limit function enabled ● Note: The following table shows the output values that are held when
Output 1 signal Output 2 signal the measurement range is exceeded while the limit function is
enabled for analog outputs (i.e., pin 4 on DIP switch S1 turned
0 to 20 mA 0 to 20 mA ❍ ❍
ON).
0 to 20 mA 4 to 20 mA ● ❍
4 to 20 mA 4 to 20 mA ❍ ● Output signal Below measurement Above measurement
selection range range
--- --- ● ●
0 to 20 mA The output signal is held The diagnostics indicator
Note: Do not turn ON both pins 5 and 6 at the same time on DIP at 0 mA. is lit (red) if the analog
switch S1. output is 20.5 mA or
higher.
The output signal is held
at 20.5 mA.
4 to 20 mA The output signal is held The diagnostics indicator
at 4 mA. is lit (red) if the analog
The diagnostics indicator output is 20.5 mA or
is lit (red) if the analog higher.
output is 3.5 mA or lower. The output signal is held
at 20.5 mA.
Connections
■ Internal Block Diagram
+ 1 5 +
Input signal Output 1 signal
− 2 6 −
+ 3
Output 2 signal
− 4
7 +
Supply voltage
8 −
K3FP-1
12 mm max. 12 mm max.
Precautions
Refer to pages 38 and 39 for common precautions.
K3FP-SN1-I-I/K3FP-SN2-I-I
6.2-mm Ultra-slim Loop-powered Isolator
• Draws the power required to drive the amplifier from the input
current signal.
• Isolated between input and output. 1,500 V AC dielectric
strength.
• Close mounting.
• CE Marking compliant.
• UL certified.
load
Name Model
Cut-off frequency 75 Hz (3 dB)
DIN rail bus connector K3FP-1
Response time (10% 5 ms max. (for a 600-Ω load)
to 90%)
Insulation resistance 10 M Ω min. between inputs, outputs, and
Model Number Structure Dielectric strength
power supply (at 500 V DC)
1,500 V AC, 50 Hz, 1 min (between inputs,
outputs, and power supply)
K3FP-SN1-I-I Noise resistance Conforms to IEC 61000
K3FP-SN2-I-I Ambient operating −20 to 65°C
1 23 temperature
Ambient storage −40 to 85°C
1. Model temperature
SN1: Channel 1 Ambient operating 95% max. (with no condensation)
SN2: Channel 2 humidity
2. Input signal Ambient storage 95% max. (with no condensation)
I: 0 (4) to 20 mA DC humidity
3. Output signal Connection method Screw connections (M3)
I: 0 (4) to 20 mA DC Tightening torque 0.5 N·m
K3FP-SN@-I-I
20
Output current (mA)
16
12
0 4 8 12 16 20
Input current (mA)
Nomenclature
Translucent cover
1 2 Input 1 signal
1 2 Input signal
5 6 Output 1 signal
K3FP-SN1-I-I
7 8 Output 2 signal
5 6 Output signal
Connections
■ Internal Block Diagram
K3FP-SN1-I-I
+ 1 5 +
Input signal Output signal
− 2 6 −
K3FP-SN2-I-I
+ 1 5 +
Input 1 signal Output 1 signal
− 2 6 −
+ 3 7 +
Input 2 signal Output 2 signal
− 4 8 −
12 mm max. 12 mm max.
Precautions
Refer to pages 38 and 39 for common precautions.
UV = 1.7 V
K3FP-SN1-I-I
K3FP-TS-UI
6.2-mm Ultra-slim Thermocouple Transducer
• Converts measured values for type J and K thermocouple
sensors into analog signals.
• Measurement range can be set between −150 and 1,350°C.
• Isolates between input, output, and power supply. 1,500 V AC
dielectric strength.
• Close mounting.
• CE Marking compliant.
• UL certified.
Nomenclature
Diagnostics indicator (red) Translucent cover
5 6 Output signals
DIP switch S2
DIP switch S1
TC 2 5 +
Output signal
3 6 −
CJC
7 +
Supply voltage
8 −
K3FP-1
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Note: 1. Use solid wire with a diameter
K3FP-TS-UI of 2.5 mm2 max. or bar
terminals with insulation
93.1 6.2
sleeves for terminal
connections.
To preserve dielectric strength
after connection, the length of
the exposed conductive part
inserted into the terminal must
be 12 mm max.
102.5
For 2.5-mm2 (max.) For bar terminals with
solid wire: insulation sleeves:
12 mm max. 12 mm max.
Precautions
Refer to pages 38 and 39 for common precautions.
K3FP-RS-UI
6.2-mm Ultra-slim RTD Transducer
• Converts measured values from PT100 platinum resistance
thermometers into analog signals.
• A 2-conductor, 3-conductor, or 4-conductor PT100 platinum
resistance thermometer can be connected to the input terminal.
• Measurement range can be set between −150 and 850°C.
• Isolates between input, output, and power supply. 1,500 V AC
dielectric strength.
• Close mounting.
• CE Marking compliant.
• UL certified.
Nomenclature
Diagnostics indicator (red) Translucent cover
5 6 Output signals
DIP switch S2
DIP switch S1
Relationship between Output Signal Range Selection and Output Status for Errors
Output Signal Ranges 0 to 20 mA or 20 to 0 mA
Output status DIP switch S2 When disconnected on Above measurement Below measurement When short-circuited on
for errors platinum resistance range range platinum resistance
7 8
thermometer side thermometer side
A ❍ ❍ 21 mA 20.5 mA 0 mA 0 mA
B ● ❍ 21 mA 20.5 mA 0 mA 0 mA
C ❍ ● 21 mA 20 mA 0 mA 21 mA
D ● ● 0 mA 20 mA 0 mA 0 mA
Connections
■ Internal Block Diagram
4-conductor 3-conductor 2-conductor
PT100 PT100 PT100
1
2
5 +
Output signal
3 6 −
7 +
Supply voltage
8 −
K3FP-1
Dimensions
Note: All units are in millimeters unless otherwise indicated.
K3FP-RS-UI Note: 1. Use solid wire with a diameter
of 2.5 mm2 max. or bar
terminals with insulation
93.1 6.2 sleeves for terminal
connections.
To preserve dielectric strength
after connection, the length of
the exposed conductive part
inserted into the terminal must
be 12 mm max.
For 2.5-mm2 (max.) For bar terminals with
102.5
solid wire: insulation sleeves:
12 mm max. 12 mm max.
Connections
2-conductor Connection
• For short distances (less than 10 m)
• Cable resistances RL1 and RL2 are incorporated in the
measurement result directly and falsify the result accordingly.
RL1
1
2
Inputs
3
RL2
4
3-conductor Connection
• For long distances between PT100 platinum resistance
thermometers and K3FP-RS-UI RTD Transducers.
• The value of all cable resistances must be exactly the same to
balance out the PT100 platinum resistance thermometer cable
resistances (RL1 = RL2 = RL3).
RL1
1
2
Inputs
RL2
3
RL3
4
K3FP-DY-I-I
6.2-mm Ultra-slim Repeater Power Supply
• Isolates between input, output, and power supply. 1,500 V AC
dielectric strength.
• Close mounting.
• CE Marking compliant.
• UL certified.
Nomenclature
Translucent cover
1 Input signals
7 8 Supply voltage
Snap for mounting DIN rail
Connections
■ Internal Block Diagram
Input signal + 1 5 +
Output signal
6 −
Sensor
power output 2
GND 3 7 +
Supply voltage
GND 4 8 −
K3FP-1
12 mm max. 12 mm max.
Precautions
Refer to pages 38 and 39 for common precautions.
K3FP-SL-UI
6.2-mm Ultra-slim Limit Value Switch
• Accurate setting of comparative judgment values using the
Unit's potentiometer.
• Isolates between input, output, and power supply. 1,500 V AC
dielectric strength.
• Close mounting.
• CE Marking compliant.
• UL certified.
Nomenclature
Translucent cover
Status indicator (yellow)
Error indicator (red)
1 Not connected
Potentiometer for adjustment
2 3 4 Output: SPDT
5 6 Input signals
DIP switch S1
7 8 Supply voltage
Snap for mounting DIN rail
DIP Switch 1
DIP switch S1 is used to set the input signal range, hysteresis, contact operation (delay time), and contact drive method.
Connections
■ Internal Block Diagram
1 Not connected
2 14
+ 5
Input signal 3 11
− 6
4 12
7 +
Supply voltage
8 −
K3FP-1
12 mm max. 12 mm max.
2. Screw Tightening Torque
Recommended torque:
0.5 N·m
ON
Between terminals 2 and 3
OFF
Potentiometer for adjustment
Input
(%) 0 50 100
Set value
Set value
Hysteresis
ON
Between terminals 2 and 3
OFF
Setting Method
1. Set the input signal, hysteresis, contact operation (delay time),
and contact drive method using the DIP switch.
2. Mount the Unit to DIN rail and wire it.
3. Apply a real input signal, enter the input value (output operation
value) for comparative judgment, and adjust using the
potentiometer.
Note: The output operation can be checked by whether the status
indicator (yellow) is lit or not lit.
Do not touch terminals while power is supplied. Doing so ■ Precautions for Correct Use
may occasionally result in minor or moderate injury.
• A DIN rail bus connector supplies the active devices. No DIN rail
bus connector is necessary to operate the K3FP-SN1-1-1 or K3FP-
SN2-1-1 Passive Loop-powered Isolators. It is, however, possible to
snap the passive loop-powered isolators onto a DIN rail bus
3. Check the mounting direction. connector. An electrically conductive connection is not established
so no existing DIN rail bus connection needs to be disconnected.
• Refer to the Internal Block Diagram for each product for block
diagrams.
• Be sure that the DIN rail is mounted securely with no loose screws.
If the screws are loose, vibration or shock may cause the product or
wiring to become disconnected.
Recommended Drivers
Manufactured by Phoenix Contact
SZS 0.6 × 3.5 (insulated)
SZF 1-0.6 × 3.5 (non-insulated)
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR
COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT,
WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS
UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND
MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in
the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING
THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE
PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty.
It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual
performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with your
OMRON representative at any time to confirm actual specifications of purchased product.