Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Installation Instructions
G6RC Series 90+ Upflow Condensing Furnace
G6RD Series 93+ Upflow Condensing Furnace
G6RL Series 90+ Downflow Condensing Furnace
Exhaust Vent
B
22 1/2"
3/4" 3/4" Combustion Air
Vent C 2 1/4"
19 3/4" (See Fig. 15 3/4" 3/4" 27 5/8"
Figure 1. G6RC, G6RD Unit Dimensions
25 1/4" 25 5/8"
33"
30 1/4"
25 1/4"
20 1/2"
15"
8" Return Air Opening 8"
Return Air Opening (Bottom)
(Side)
1" D
Exhaust Vent A
22 1/2"
3/4" Exhaust
Vent 3/4" B 27 7/8"
3/4"
2"
3/4" 2 1/2"
C
Figure 2. G6RL Unit Dimensions
CL
Combusting 24 7/8"
24 7/8"
Vent
7/8" Dia. Electric (3" for 80/100
43" Connection 7/8" Dia.
2" for 40/60) Electric
Connection
21 7/8"
Model Input Motor Motor 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
** Factory Set Cooling Speed NOTES: 1. Airflow rates of 1800 CFM or more require two return air connections. Data is for operation with filter(s).
** Factory Set Heating Speed 2. Temperature rises in the table are approximate. Actual temperature rises may vary.
- Not Recommended 3. Temperature rises and airflows for external static pressures greater than 0.5 are for reference only.
These conditions are not recommended.
7
9.25"
Sheet 2.0"
Metal
Plenum
16.75"
1.50"
19.63"
18.75" 13.25"
19.75" 3"
Hole in Hole in or 14.25"*
Floor Floor
Figure 7. Downflow Sub-Base Dimensions
G6RL 080/100 G6RL 040/060
If outside air is utilized as return air to the furnace
Figure 5. Opening in Wood Floor
for ventilation or to improve indoor air quality, the
system must be designed so that the return air to
the furnace is not less than 50°F (10°C) during
heating operation. If a combination of indoor and
Wood outdoor air is used, the ducts and damper system
Downflow
Furnace Floor must be designed so that the return air supply to
Sub-base
the furnace is equal to the return air supply under
normal, indoor return air applications.
10
Return Air
The return air ductwork may be connected to
any or all of the following: left side return, right
side return, or bottom return. Tables 1 and 2
show the airflow data for each furnace model.
Where maximum airflow is 1800 CFM or
more two openings must be used.
G6RC/G6RD Protective Screen
VENTING AND COMBUSTION AIR
REQUIREMENTS
NORDYNE condensing furnaces may be in- G6RL
stalled with outdoor combustion air piped di-
rectly to the furnace, or without such special
piping. Codes refer to the former as "direct vent"
or "two pipe" installation. Installation with air
taken from around the furnace is sometimes
referred to as "one pipe" installation - i.e. only Figure 8. Protective Screen for One Pipe
the vent (exhaust) pipe is provided. Installations
11
Furnace
Furnace
--
--
-
12" Max.
12" Max Water Heater
Minimum
Total Input Free Area Round Duct
Water Heater Rating (Btuh) (Each Opening) Diameter
Minimum 40,000 10 sq. in. 4"
60,000 15 sq. in. 5"
Total Input Free Area Round Duct 80,000 20 sq. in. 5"
Rating (Btuh) (Each Opening) Diameter 100,000 25 sq. in. 6"
40,000 100 sq. in. 12" 120,000 30 sq. in. 6"
60,000 100 sq. in. 12" 140,000 35 sq. in. 7"
80,000 100 sq. in. 12" 160,000 40 sq. in. 8"
,,,,,
Heater one square inch
per 4,000 Btuh of
12" Max the total input rat-
Alternate ing of all equipment
Air Inlet Inlet Air in the enclosure.
,,,,,
Water Heater
--
--
-
Minimum
--
--
-
--
--
-
Figure 11. Equipment in a Confined Space Figure 12. Equipment in a Confined Space
with all Combustion Air drawn from with all Combustion Air drawn from
Outdoors through Vertical Ducts – from Outdoors through Ventilated Crawl Space
Ventilated Attic and Ventilated Attic
12
13
Outdoor Air Through Vertical Openings or Ducts The furnace must be vented to the outdoors. It
If combustion air is provided through vertical must not be vented in common with any other
ducts or openings to attics or crawl spaces, the appliance, even if that appliance is of the con-
two openings must each have free area of at densing type. Common venting can result in
least one square inch per 4000 Btuh of total severe corrosion of other appliances or their
appliance input. Ducts must have cross-sec- venting and can allow combustion gases to
tional areas at least as large as the free area of escape through such appliances or vents. Do
their respective openings to the furnace space. not vent the furnace to a fireplace chimney or
Attics or crawl spaces must communicate freely building chase.
with the outdoors if they are the source of air for
combustion and ventilation. (See Figures 11
and 12.) ! WARNING:
Outdoor Air Through Horizontal FURNACE MUST NOT BE COMMON
Openings or Ducts VENTED WITH OTHER APPLIANCES.
If combustion air is taken from outdoors through
horizontal ducts, the openings must each have
free area of at least one square inch per 2000 Vent Pipe Material
Btuh of total appliance input. Ducts must have Vent and combustion air pipe and fittings must
cross-sectional area at least as large as the free be one of the following materials and must
area of their respective openings to the furnace conform to the indicated ANSI/ASTM standards:
space. (See Figure 13.)
Material Standard
Schedule 40 PVC D1785
! CAUTION: PVC-DWV
SDR-21*
D2665
D2241
Do not supply combustion air from an & SDR-26*
attic space that is equipped with power ABS-DWV D2661
ventilation or any other device that Schedule 40 ABS F628
may produce a negative pressure.
Cement and primer must conform to ATSM
Standard D2564 for PVC and Standard D2235
VENTING REQUIREMENTS for ABS. When joining PVC piping to ABS, use
This section specifies installation requirements PVC solvent cement. (See procedure specified
for vent and "2-pipe" combustion air piping. For in ASTM Standard D3138.)
"one pipe" installations, install vent piping per
this section and provide air for combustion and Vent Pipe Length and Diameter
ventilation per the previous section. The capac-
In order for the furnace to operate properly, the
ity table provided in this section applies to the
combustion air and vent piping must not be exces-
total of vent and combustion air piping for either
sively restrictive. To ensure this use Table 5, which
type of installation.
indicates the maximum allowable piping length for
a furnace of specified input rate, when installed
14
APPLICATION SINGLE PIPE LENGTH (ft.) DIRECT VENT, DUAL PIPE LENGTH (ft.)
with 1 long radius elbows*. with 1 long radius elbows on each pipe.*
PVC,CPVC or ABS Outlet Outlet Inlet/Outlet Inlet/Outlet Inlet/Outlet
SCH. 40 Pipe Size 2" 3" 2" 2" 3" 2" 3" 3"
Models
G6RC,D,L 80 150 40 40 50 50 90 90
040
Models
G6RC,D,L 60 150 30 30 35 35 90 90
060 & 080
Models
G6RC,D,L 30 150 15 15 25 25 90 90
100 & 120
*NOTES
1. Subtract 2.5 ft. for each additional 2" elbow and 3.5 ft. for each additional 3" elbow.
2. Two 45 degree elbows are equivalent to one 90 degree elbow.
3. One short radius elbow is equivalent to two long radius elbows
4. Do not include termination elbows in calculation of vent length
5. This table is applicable for elevations from sea level to 2000 ft. For higher elevations decrease
vent pipe lengths by 8% per 1000 ft. of altitude.
6. Only the above pipe materials are approved for use with G6 Condensing Furnaces.
Table 5. Vent Table
15
Inlet Exhaust
5/8" See Vent Table 4
Seal/Caulk
Straps or Other Suitable around Pipe
Supports at Minimum of 5 ft. Intervals at Building
Coupling 90˚ Elbow
Combustion
Offset with
Exhaust Pipe
for Adequate
Dimensional
Clearance Upward Pitch - 1/4" per Foot 12" Min.
Outlet Exhaust Vent 7"
PVC or
ABS Pipe First Support Placed
as Close to Furnace Wall
Connection as Possible
Normal Snow Level
Exhaust Vent
Straight Neoprene Coupling
with 2 Hose Clamps*
(Optional - Not Shown)
Exhaust Inlet
See Vent Table 4 5/8"
Seal/Caulk
around Pipe Straps or Other Suitable
at Building Supports at Minimum of 5 ft. Intervals
* These couplings are field-supplied and can be used if the installation requires breakable
connections in the piping. Note that a maximum of two couplings per pipe are allowed.
16
Combustion Exhaust
Air Pipe Vent
Cabinet
Furnace Front
Exhaust Combustion
Vent Air Pipe
Straight Neoprene
Rubber Couplings Upward Pitch
with 2 Hose Clamps 1/4" per Foot
Cabinet
Furnace Front
Direct vent
terminal
50,000 Btuh
or less
Mechanical
Mechanical draft vent
9 in. draft vent terminal
terminal
Less
than 10 ft.
12
in. 4 ft. min n
mi
n 4 ft mi
.m
in in. 3 ft. min.
12
e
12 ad
Mechanical in.
mi Gr
draft vent n n
terminal mi Forced
in.
12 i n Air Inlet
in.m
Direct vent
12 terminal -
more than
50,000 Btuh
¢
Q
,
Outside
equipment. These distances apply ONLY to Wall 12" Above
U.S. installations. In Canada, the Canadian Normally
Expected
Fuel Gas Code takes precedence. Pipe Snow
Coupling 1/2" Level
7. Avoid areas where condensate drainage
Armaflex
may cause problems by dropping on plant- Insulation or
ers or patios, etc. Also ensure that exhaust Equivalent
gases will not impinge on windows or build-
ing surfaces, which may be compromised
or damaged by condensation. Do not install
the vent terminal such that exhaust is di-
rected into window wells, stairwells, under Figure 18. Alternate Horizontal Vent
decks or into alcoves or similar recessed Installation
areas, and do not terminate above any
public walkways.
For horizontal venting, one of the following kits
8. Select the point of wall penetration where is recommended:
the minimum 1/4 inch per foot of slope up
can be maintained. 2" PVC 3" PVC
Through-the-Wall
! CAUTION: Exterior Vent 9023730 9023750
Mounting Kit
For optimum performance, vent fur- Neutralizer Kit - All
nace through wall which experiences 9023730 9023730
Models
the least exposure to winter winds.
For Canadian installations please refer to the
Canadian Installation Code (CAN/CGA-B149.1
Horizontal Venting or 2) and/or local codes.
Vent and combustion air intake terminations
must be as shown in Figure 19. The kit consists of two face plates and an
insulating gasket to seal the exterior surface. A
hole sized closely to the pipe diameter must first
! WARNING: be cut through the wall. A short length of pipe is
then cut such that it can penetrate the wall and
Ensure that the combustion air vent be held in place by closely fitting standard cou-
and the exhaust vent are configured as plings. The face plates are retained on both
shown in Figure 19. Improper vent sides of the wall by the couplings, and the gasket
termination can cause recirculation of is retained against the wall by the outer face
the flue gases. This may result in fur- plate. Face plates must be fastened to the wall
nace vibration. In severe cases, the and the outside one must be flashed as appro-
priate to prevent entry of water.
furnace will cycle due to the intermit-
tent contact between the flame and the When the above kits are not used the following
flame sensor. If you note oscillations steps are required:
occurring, check the vent configura-
tion. Make sure that the exhaust vent 1. Check the hole size cut through the exterior
does not have a 90 degree termination. wall. Insure that the hole diameter is less than
the diameter of the couplings to be used.
2. Extend the vent pipe through the wall ap-
proximately 1" and seal the area between
the wall and pipe.
19
Exhaust Vent
Option B
Mounting Kit
Faceplate Secured Exhaust Vent
to Wall with Screws 18" Min. Option A
Combustion 36" Max.
8" Min.
Air Inlet
Exhaust Vent
Option C
18" min.
36" max. Grade
18" Min. Level
36" Max. or Normal
12" Min. to Snow
7" Min. Normal Snow Level
Inlet Exhaust
Exhaust
Left
Side
Left Side Drain Rotate clockwise
Rotate counter (Step 2)
Drain clockwise (Step 2) Route to
Route to
floor drain. floor drain.
8" ...OR 8" ...OR
Route to Route to
condensate condensate
Clamp pump. Keep Clamp pump. Keep
"HARD" J "HARD" J downward
(Loosen For Step 1) downward Drain Tube
(Loosen For Step 1)
Drain Tube slope.
(Retighten for Step 3) slope. (Retighten for Step 3)
Ground Joint
Burner Union Some Utilities
Assembly Require Shut-
Some Utilities
Off Valve to
Require Shut- Roll-Out Limit
Burner be 4 to 5 feet
Off Valve to
Assembly Above Floor
be 4 to 5 feet
Above Floor Ground
Shut-Off Valve
Joint
Shut-Off Valve with 1/8" NPT
Union
with 1/8" NPT Denotes field- Plugged Tap
Plugged Tap Automatic Gas Valve provided and
(with manual shut-off) Burner Viewport
installed
components.
NOTE: When pressure testing gas supply lines the installation altitude and the heating value of
at pressures greater than 1/2 psig (14 in. water the gas. The gas heating value based on sea
column), the furnace must be disconnected from level can be obtained from your local gas utility.
the gas supply piping system to prevent damage The heating value of gas at high altitude is
to the gas control valve. always lower than the sea level heating value.
The heating values used in Tables 7 & 8 are
If the test pressure is less than or equal to 1/2 based on sea level values.
psig (14 in. water column), the furnace must be
isolated from the gas supply line by closing the Natural Gas High Altitude
manual shut-off valve.
Conversion
All factory shipped furnaces are ready to operate
between zero and 4999 ft. above sea level. For
! WARNING: higher altitudes (between 5000 and 10,000 ft.
This furnace was equipped at the fac- above sea level), conversion can be achieved
tory for use with natural gas only. A simply by adjusting the furnace manifold pressure
special kit, supplied by the manufac- as shown in Table 7.
turer, is required to convert the fur-
nace to operate on LP/propane gas. LP/Propane Gas Sea Level and
Failure to use the proper conversion High Altitude Conversion
kit can cause fire, explosion, property Conversion of this furnace to utilize LP/propane
damage, carbon monoxide poisoning, gas must be made by qualified service personnel,
personal injury, or death. using factory authorized or approved parts.
Conversion to LP/propane gas can be
accomplished by first replacing the natural gas
Conversion orifices with the appropriate LP/propane orifices
Conversion of this furnace to use LP/propane shown in Table 9 or 10. Note: for installations
gas must be made by qualified service between zero and 5000 ft. above sea level, a
personnel, using only approved parts. #54 or #55 drill size orifice should be used
depending upon the rated firing rate of the unit
High Altitude Application (see Table 9 or 10). However for installations
above 5000 ft. above sea level, a # 55 or #56 drill
High altitude application with this furnace can be size orifice should be used. After changing the
field performed by a simple adjustment of orifices, use Table 8 to determine the appropriate
manifold pressure, and if necessary changing manifold pressure for your installation.
the orifices. The changes required depend on
23
For a Natural Gas Sea Level Heating Value of 800 to 899 Btu/cu.ft.
Elevation (feet above sea level)
zero to 2000 to 5000 to 6000 to 8000 to
1999 4999 5999 7999 10000
Manifold Pressure Setting (in WC) 3.5 3.5 3.5 3.5 3.0
For a Natural Gas Sea Level Heating Value of 900 to 999 Btu/cu.ft.
Elevation (feet above sea level)
zero to 2000 to 5000 to 6000 to 8000 to
1999 4999 5999 7999 10000
Manifold Pressure Setting (in WC) 3.5 3.5 3.5 3.2 2.8
For a Natural Gas Sea Level Heating Value of 1,000 to 1,100 Btu/cu.ft.
Elevation (feet above sea level)
zero to 2000 to 5000 to 6000 to 8000 to
1999 4999 5999 7999 10000
Manifold Pressure Setting (in WC) 3.5 3.5 3.0 2.8 2.5
Table 7. Manifold Pressure (in WC) for Natural Gas at Various Altitudes
Table 8. Manifold Pressure (in WC) for LP/Propane Gas at Various Altitudes
24
Table 9. Natural and LP Gas Orifice Sizes Table 10. Natural and LP gas Orifice Sizes
for Elevations between zero and for Elevations between 5000 and 10,000 ft.
4999 ft. Above Sea Level Above Sea Level
used in this furnace require an earth ground to nace. See Figure 24 for the proper connections
operate properly. Acceptable methods for for heating only (two-wire) and heating/cooling
grounding are electrical wire or conduit ap- (four-wire) applications. The recommended
proved for electrical ground service. Do not use minimum wire gauge for thermostat wiring is
gas piping as an electrical ground. shown in Table 11.
NOTE: Proper line voltage polarity must be The thermostat must not be installed on an
maintained in order for the control system to outside wall or any other location where its opera-
operate correctly. Verify that the incoming tion may be adversely affected. Adverse affects
neutral line is connected to the white wire include radiant loading from fireplaces, sunlight,
and the incoming "hot" line is connected to or lighting fixtures, and convective loading from
the black wire in the furnace junction box. warm air registers or electrical appliances.
These furnaces will not operate unless po-
larity and ground are properly connected. To check the heat anticipator setting either:
See Figure 23.
1. Add the current draw of the system compo-
nents; or
! CAUTION: 2. Measure the current flow on the thermostat
R-W circuit after the circulating blower mo-
Label all wires prior to disconnection tor has started.
when servicing controls. Wiring er- Set the heat anticipator according to the thermo-
rors can cause improper and danger- stat manufacturer's instructions for heat antici-
ous operation. Verify proper opera- pator settings.
tion after servicing.
START-UP AND ADJUSTMENTS
Low Voltage Wiring Prior to start-up, verify that:
1. The line voltage power leads are securely
Install the thermostat per the manufacturer's connected, that the polarity of the connec-
instructions. The low voltage (24 volt) connec- tions is correct, and that the furnace is
tions from the thermostat are made at the properly grounded.
terminal strip on the control board in the fur-
Field Supplied
Fused Service Field Supplied
Panel Connector
Panel Field Line Voltage
Wiring
Black (Hot) Black Black Black
Factory Line
White (Neutral) White White White Voltage Wiring
Green or Bare
(Ground)
Ground Ground Ground
Blower Off
60
90
24 V Fuse
5. The blower door is in place, closing the door
C
Connect TWIN
Y
R&W
switch in the line voltage circuit.
Y
For
G
(Yellow)
Only
W
Status Light
Room (Red)
Thermostat 9 6 3
8 5 2
7 4 1
Start-Up Procedure
1. Set the thermostat to the lowest setting.
NOTE: The "Y"
terminal on the 2. Close the disconnect(s) to provide line volt-
EAC HUM
XFMR
HEAT
HUM
6 3
EAC
Low Voltage
ing instructions label attached to the furnace.
M1
M2
M3
L1
Connections 5 2
4 1
4. Set the thermostat above room tempera-
ture and verify the sequence of operation.
Figure 24. Low Voltage Field, (See the SEQUENCE OF OPERATION.)
Four-wire Heating/Cooling Applications
5. After the furnace has run for approximately
2. The thermostat wires (R, W, Y, and G) are five minutes, set the thermostat below room
securely connected to the correct leads on temperature and verify steps (9) through
the terminal strip of the circuit board. (11) of the SEQUENCE OF OPERATION.
3. The gas line service pressure does not
exceed 10.0 in. water column (0.36 psig), Verifying and Adjusting
and is not less than 4.5 in. water column Firing Rate
(0.16 psig) for natural gas. For LP gas the
The firing rate must be verified for each installa-
line service pressure must not exceed 14 in.
tion to prevent over-firing the furnace.
water column (0.51 psig), and must not be
less than 11.0 in. W.C. (0.40 psig).
NOTE: The firing rate must not exceed the rate
4. The roll-out and vent safety manual reset shown on the furnace rating plate. At altitudes
switches are closed. If necessary, press the above 2000 ft. the firing rate must be adjusted as
red button to reset a switch. See Figure 28 described in the high altitude section.
26
Timing
24 V
C
TWIN
Y
Flame Signal
G
Light (Yellow)
W
Status
9 6 3 Light (Red)
8 5 2
7 4 1
Common
Leads Neutrals
EAC HUM
Unused Motor
Connect Leads
Neutral
COOL
6 3
XFMR
HEAT
M1
M2
M3
HUM
EAC
Lead of
L1
5 2
Electronic
4 1
Air Cleaner
and/or Humidifier
Here.
Electronic Air Tap
(.5A@ 120 VAC)
Humidifier Tap Cooling
(.5A@ 120 VAC) Speed Tap Heating Speed Tap
ORANGE
ORANGE
BLUE
BLUE
WHITE BLACK
WHITE (NEUTRAL)
BLACK 120V
BLOWER DOOR
GROUND
SWITCH
GREEN
ROOM THERMOSTAT
TRANSFORMER
R
WHITE W/ BLK STRIPES WHITE
Y
24 V 120 V
G
BLK W/ WHITE STRIPES BLACK
W
120
180
60
90
BLACK
AIR CONDITIONER
CONDENSING UNIT
YELLOW
BROWN
C
H
MH
GAS
ML
VALVE L
ORANGE
BLACK
WHITE
BLUE
RED
IGNITOR
BLACK
Legend BLACK RED
1
BLACK
Field Wiring R C ORANGE
2
BLUE
Factory Wiring: 3
INDUCER
Low Voltage BLACK BLACK
4
High Voltage 5
WHITE
6
MOTOR
STATUS PLUG
RED
FAULT CONDITION LIGHT THESE WIRES ARE
Power On ON NOT PRESENT
ON 3 SPEED
Limit Circuit Open 1 FLASH
MODELS
Pressure Switch Stuck Open 2 FLASHES
Pressure Switch Stuck Closed 3 FLASHES
Ignition Failure (Check Ground) 4 FLASHES If any of the original wire as supplied with
115 VAC & Neutral Reversed or no Ground 5 FLASHES the furnace must be replaced, it must be
False Flame or Gas Valve Relay Shorted Continuous replaced with wiring material having a
Power Off OFF temperature rating of at least 105 C.
FLAME
YELLOW
FAULT CONDITION LIGHT
Low Flame Sensor Signal Continuous
Flash
Flame Present ON
Figure 26. G6RC, G6RD and G6RL Integrated Control Board System Diagram
30
31
33
Thermostat
W G Y R
Twin Twin
R Terminal R Terminal
C C
Y Y
G G
W W
A/C
Unit
34
35