TI/SPC/PSI/HVCB/0120
RESEARCH DESIGNS AND STANDARDS ORGANIZATION
Date TECHNICAL SPECFICATION
Effective No.TI/SPC/PSI/HVCB/0120 Page
From FOR OUTDOOR HV CIRCUIT BREAKER FOR 1 of 70
01.07.2012 RAILWAY ac TRACTION SUB-STATIONS
GOVERNMENT OF INDIA
MINISTRY OF RAILWAYS
SPECFICATION FOR
OUTDOOR HV SWITCHGEAR DP / TP
CIRCUIT BREAKERS
FOR
SPECIFICATION No.
TI/SPC/PSI/HVCB/0120
ISSUED BY
HV CIRCUIT BREAKER
for
Railway ac Traction Sub-Station
1. Scope
1.2 The CB shall be complete with all Parts, Fittings, and SF6 Gas
for the first filling, Vacuum Bottle as the case may be and
accessories necessary for its efficient operation, including
mounting frame work of steel. All such Parts, Fittings and
Accessories shall be deemed to be within the scope of this
Specification, whether specifically mentioned or not. The CB
shall be proven design.
3.1.1 The Single Phase 50Hz Power Supply for Railway Traction at
25kV is obtained from 220/132/110/100/66/22kV Three Phase
Grid System through a Step Down/ Step Up Single Phase Power
Transformer, the Primary Winding of which is connected to two
of the phase of the Three Phase effectively Earthed
Transmission line network of the State Electricity Board. The
Primary Voltage of the Traction Transformer being 220kV or
132kV or 110kV or 100kV or 66kV or 22kV and no load
secondary voltage being 27kV. In order to reduce the
imbalance on the Three-Phase Grid System, the Two Phases of
the Three Phase Transmission Line are tapped in a cyclic order
for feeding the successive traction sub-stations (TSS). The
distance between adjacent TSS is normally between 50km and
DRAFT SPECIFICATION No. TI/SPC/PSI/HVCB/0120
RESEARCH DESIGNS AND STANDARDS ORGANIZATION
Date TECHNICAL SPECFICATION
Effective No.TI/SPC/PSI/HVCB/0120 Page
From FOR OUTDOOR HV CIRCUIT BREAKER FOR 7 of 70
01.07.2012 RAILWAY ac TRACTION SUB-STATIONS
3.2.2 The two sections of OHE fed by different phases are sometimes
inadvertently bridged causing wrong phase coupling.
3.3.1 The faults in the OHE are isolated by the feeder Circuit Breaker
which Operates through either one or more of the following
relays:
3.3.2 The faults in the traction transformer are isolated by one of the
Following relays:
3.3.3 The faults in the shunt capacitor bank are isolated by one of
the following relays:
3.4.1 The fault level for different grid supply voltages based on a
Three Phase symmetrical short circuit fault is between 1000
MVA and 10,000 MVA depending upon the proximity of the
traction sub-station to the generating station. The fault level
DRAFT SPECIFICATION No. TI/SPC/PSI/HVCB/0120
RESEARCH DESIGNS AND STANDARDS ORGANIZATION
Date TECHNICAL SPECFICATION
Effective No.TI/SPC/PSI/HVCB/0120 Page
From FOR OUTDOOR HV CIRCUIT BREAKER FOR 9 of 70
01.07.2012 RAILWAY ac TRACTION SUB-STATIONS
3.5.1 The traction load is of frequent and rapidly varying nature and
Fluctuates between no load and over loads. The load cycle
varies from Day to Day due to non-uniform pattern of traffic.
3.5.4 For improving power factor fixed shunt capacitor bank with
13% series reactor are also installed at some traction sub-
stations, the net kVAR rating of which is generally in the range
of 2000-3500kVAR
1 2 3 4 5 6
(xii) Rated small inductive 10A 10A 10A 10A
breaking current
(xiv) Rated operating
sequence O-0.3 sec-CO-3 min-CO
(xv) Total beak 60 ms 60 ms 60 ms 60 ms
Time
(xvi) Rated short 31.5kA 40kA for 40kA for 40kA for
time current for 1 sec 1 sec 1 sec 1 sec
(xvii) First pole to 1.5 for 2 1.5 for 2 1.3 for 4 1.3 for 4
clear factor paramet paramete paramete paramet
ers rs rs ers
(xviii) Corona 53kV 88kV 106 kV 176 kV
Extinction
Voltage
(xix) Rating of auxiliary
switch contacts
5.2 Clearances
6.1.4.2 The motor for spring charging shall be suitable for operation
from a 110V dc power from a battery. The voltage at motor is
Likely to vary between 110% and 85% of the normal value. The Carbon
Brushes provided shall have copper pigtails for Carrying Motor
Current. A Miniature Circuit Breaker of adequate ratings and
of reputed make Shall be provided in the Motor circuit for
protection of the motor against over current and earth faults.
6.1.4.7 The closing coil and opening coil shall be suitable for operation
from 110V dc power supply from a battery. The closing coil
shall be suitable for operating at a voltage variation of +10% to
-15%, while the opening coil shall be suitable for operating at a
voltage variation of +10% to -30%.
6.1.4.14 In case of drop in pressure of SF6 gas below the set value the
temperature compensated alarm pressure switch shall get
actuated for generating an alarm. If the drop in the pressure
continues, the temperature compensated Lock out pressure
switch shall get actuated to cause the CB to trip and get Locked
in the tripped condition. Separate auxiliary contact from
pressure switches shall be made available for tele-signalling the
alarm condition from the alarm pressure switch and the trip
and Lock out condition from the Lock out pressure switch. The
maximum pressure, normal pressure, alarm actuating pressure
and tripping & Lock out pressure of thee Circuit Breaker shall
be furnished by the Manufacturer on the schematic drawing of
the CB. Maximum and minimum permissible pressure of SF6
shall be indicated on the rating plate also.
6.1.4.17 Shock absorbers used (if any) shall not require any
maintenance during the entire life of the CB.
6.1.4.20 The entry of all Cables into the shall be only through suitable
Cable Glands which shall not allow ingress of Vermin, Insects
etc. into the . The Cable Gland shall be supplied with the CB.
Five Cable Glands shall be provided of which the shall be of
16.5mm outside diameter while the balance two Glands shall
be for cable of 14mm outside diameter.
6.1.4.21 The Wiring inside the shall be with 1100 V grade PVC
insulated single core cable conforming to IS:1554 (Pt.I-
1988), with stranded copper conductors of adequate cross-
section (with min 2.5 sq.mm strand copper) so proportioned as
to reduce voltage drop and I²R losses to minimum. The ends
of wires shall be terminated with crimped eye type lugs. The
wiring of 110V dc control circuit and 240V ac circuit shall
be segregated and properly identified. The positive and
negative wires of dc circuits shall also be segregated. The
length of the cables used shall be kept to the minimum. Wire
inside the shall be properly laid on trays and anchored to avoid
breakage during vibration.
6.1.4.22 The Terminal end of all wires shall be provided with numbered
interlock type ferrules which shall be of PVC or other durable
DRAFT SPECIFICATION No. TI/SPC/PSI/HVCB/0120
RESEARCH DESIGNS AND STANDARDS ORGANIZATION
Date TECHNICAL SPECFICATION
Effective No.TI/SPC/PSI/HVCB/0120 Page
From FOR OUTDOOR HV CIRCUIT BREAKER FOR 22 of 70
01.07.2012 RAILWAY ac TRACTION SUB-STATIONS
6.1.4.25 For earthling of the, two of adequate capacity to carry the rated
short circuit current shall be provided with 17.5 + 1.5/-0.
Diameter stud/hole for fixing the earthling flat.
7.2 Typical design calculations for the steel supporting frame shall
be furnished by the Manfacturer to the RDSO during design
approval stage for checking the safety of the supporting frame
proposed to be used.
7.3 For earthling at least 2 legs of the steel supporting frame shall
be provided with Stud/Hole type of adequate capacity to carry
the rated short circuit current safely. The earthling shall be
provided with 50 x 8 mm MS flat. The Terminal shall be
provided with 17.5 + 0.5/0.0mm diameter stud/hole for fixing
the earthling flat.
8.0 Foundations
9.1 Galvanizing
9.2 Painting
10.0 Fasteners
11.3.7 The Lock for mounting on the isolators shall be a Castle Type
Lock of approved design. However, the Lock for mounting on
the Circuit Breaker is a Bolt Type Lock, with Adopter. The
Internal Mechanism of the Lock shall be of Non-Ferrous
material and the outer housing shall preferably of Mild Steel
Hot Dip Galvanized. The key, when trapped inside the Lock,
shall remain properly secured and it shall nit become loose due
to vibration.
11.3.8 One spare (duplicate) Key shall be supplied for each type of the
Interlocking arrangements.
a) Closing coil
b) Opening coil
c) Motor voltage
13.0 Testing
13.1 General
13.1.1 After all the designs and drawings have been approved
and clearance given to this effect by RDSO, the
Manufacturer shall take up manufacture of the prototype
for inspection/Testing by RDSO. It is to be clearly
understood that any changes to be done on the prototype
as required by RDSO, the same shall be done
expeditiously.
DRAFT SPECIFICATION No. TI/SPC/PSI/HVCB/0120
RESEARCH DESIGNS AND STANDARDS ORGANIZATION
Date TECHNICAL SPECFICATION
Effective No.TI/SPC/PSI/HVCB/0120 Page
From FOR OUTDOOR HV CIRCUIT BREAKER FOR 29 of 70
01.07.2012 RAILWAY ac TRACTION SUB-STATIONS
13.2.3.1
(b) Rated One Minute Power Frequency wet withstand
Voltage Test As per clause 13.2.3.2
13.2.2.1.1 Procedure
Table
13.2.2.2.1 Procedure
13.4 The tenderer may quote separately the charges for short
circuit Test duties, short time withstand current and peak
current withstand Test, line charging breaking current Tests,
Test to prove rated TRV, short line fault Tests, out of phase
making and breaking Tests, capacitor bank breaking current
Test, measurement of RIV level and special electrical Tests
as per clause 13.2.4,13.2.5, 13.2.6,13.2.7, 13.2.8, 13.2.9,
13.2.10, 13.2.11, 13.2.12 . No Test charge shall be payable
for any other Test.
Parts/ Components.
(vi) Type Test report for relevant rating as per RDSO /IEC
Specification.
16.5 After approval, six copies of approved drawings along with 2 set
of reproducible prints shall be supplied to each consignee.
Drawings shall be made in Auto CAD R14, which is window
based for approval to RDSO.Two sets of approved drawings of
hard copies, one copy of RTF and one set of floppies in Auto
CAD R14 shall be sent to RDSO for record.
18.0 Spares
18.1 The tenderer shall furnish along with his offer, a list of spares
(with cost) recommended by him for maintenance of CB for a
period of 10 years. The list should include gaskets/ O rings,
parts which are likely to wear and items requiring replacement/
replenishment, besides other items recommended by the
Manufacturer. The successful tenderer shall give an
undertaking to the effect that he shall supply the required
spares for the total life of the equipment (i.e. 25 years approx.)
18.2 The tenderer shall furnish along with his offer, the cost of gas
filling arrangement, evacuation plant for SF6 gas and cost of
SF6 in 10kg cylinder.
21.0 Warranty
21.2 This warranty shall cover inspection of, payment for and
acceptance of the equipment, but shall expire 30 (thirty)
DRAFT SPECIFICATION No. TI/SPC/PSI/HVCB/0120
RESEARCH DESIGNS AND STANDARDS ORGANIZATION
Date TECHNICAL SPECFICATION
Effective No.TI/SPC/PSI/HVCB/0120 Page
From FOR OUTDOOR HV CIRCUIT BREAKER FOR 49 of 70
01.07.2012 RAILWAY ac TRACTION SUB-STATIONS
21.6 All replacement and repairs that the Purchaser shall upon the
successful tenderer/ Manufacturer to deliver or perform under
this warranty shall be delivered and performed by the
successful tenderer/ Manufacturer, promptly and satisfactorily
and in any case with in 2 (two) months of the date of advice to
this effect.
DRAFT SPECIFICATION No. TI/SPC/PSI/HVCB/0120
RESEARCH DESIGNS AND STANDARDS ORGANIZATION
Date TECHNICAL SPECFICATION
Effective No.TI/SPC/PSI/HVCB/0120 Page
From FOR OUTDOOR HV CIRCUIT BREAKER FOR 50 of 70
01.07.2012 RAILWAY ac TRACTION SUB-STATIONS
21.8 The warranty here in contained shall not apply to any material
which shall have been repaired or altered by the purchaser or
on his behalf in any way without the consent of successful
tenderer/ Manufacturer, so as to affect the strength,
performance or reliability or to any defects to any part due to
misuse, negligence or accident.
Annexure ‘A’
2 Country of Manufacture
A RATING
5 Rated voltage kV
8 Rated frequency Hz
(i) for 1 s kA
(ii) for 3 s kA
17 Rated operating sequence
condition
B CONSTRUCTIONAL FEATURES
25 SF6
per pole Kg
) between poles mm
C OPERATING PARTICULARS
DRAFT SPECIFICATION No. TI/SPC/PSI/HVCB/0120
RESEARCH DESIGNS AND STANDARDS ORGANIZATION
Date TECHNICAL SPECFICATION
Effective No.TI/SPC/PSI/HVCB/0120 Page
From FOR OUTDOOR HV CIRCUIT BREAKER FOR 55 of 70
01.07.2012 RAILWAY ac TRACTION SUB-STATIONS
42 Arcing Time
(i) At rated normal current ms
(ii) At rated short circuit breaking ms
current
(iii) At 60% of short circuit ms
breaking current
(iv) At 30% of short circuit ms
breaking current
(v) At 10% of short circuit ms
breaking current
43 Critical current kA
Closing coil V dc + %
Tripping coil / -%
Contactors ( if any) V dc + %
Any other item ( for which the tenderer / -%
feels that the voltage is to be V dc + %
maintained within certain limits) / -%
V dc + %
/ -%
54 Type of tripping / closing mechanism
58 Porcelain Insulators
Support
(i) Makers name and type Insulator
designation
(ii) Minimum creep age distance Interrupti
ng
Chamber
Insulator
E OTHER DETAILS
Annexure- ‘B’
6 Auxiliary contact
(i) Description and type Designation
(ii) Make
(iii)Identification mark
(iv)Item drawing No.
(v)Governing Specification No.
(vi)Rating
(a)Voltage
(b)Continuous Current
(c)Breaking and making Current
(d)Electrical & life( No. of operations)
8 MCB’s
(i)Description and type
(ii)Type designation
(iii)Make
(iv)Identification mark
(v)Governing Specification No.
(vi) Rating
(a)Voltage
(b)Continuous Current
(c)Breaking and making Current
(d)Electrical & life( No. of operations)
DRAFT SPECIFICATION No. TI/SPC/PSI/HVCB/0120
RESEARCH DESIGNS AND STANDARDS ORGANIZATION
Date TECHNICAL SPECFICATION
Effective No.TI/SPC/PSI/HVCB/0120 Page
From FOR OUTDOOR HV CIRCUIT BREAKER FOR 65 of 70
01.07.2012 RAILWAY ac TRACTION SUB-STATIONS
10 Spring
(ii)Type designation
(iii)Make
(iv)Identification mark
(vi)Rating
(b) Power
12 Operation counter
(ii)Type designation
(iii)Make
(iv)Identification mark
(ii) Make
14 Heater
(i)Description and type
(ii)Type designation
(iii)Make
(iv)Identification mark
V - ac
(v)Governing Specification No W
(vi)Rating
(a) Voltage
(b) Power
15 Interlock
(i)Description and type
(ii)Type designation
(iii)Make
V dc A
(iv)Identification mark
(v)Governing Specification No
16 Terminal connector
(ii)Type designation
(iii)Make
(iv)Identification mark V ac
A
(v)Governing Specification No
(vi)Rating
(a) Voltage
(b) Current
17 Registers
(i)Description and type
(ii)Type designation
(iii)Make
(iv)Identification mark V ac
A/W
(v)Governing Specification No
DRAFT SPECIFICATION No. TI/SPC/PSI/HVCB/0120
RESEARCH DESIGNS AND STANDARDS ORGANIZATION
Date TECHNICAL SPECFICATION
Effective No.TI/SPC/PSI/HVCB/0120 Page
From FOR OUTDOOR HV CIRCUIT BREAKER FOR 69 of 70
01.07.2012 RAILWAY ac TRACTION SUB-STATIONS
(vi) Rating
(a) Voltage
(b) Current/Power
21 Shock absorber
---------------------------