DEFINITION OF TERMS

AMPERE. The practical unit for measuring flow of current, when one ohm
resistance is connected to one volt source, one ampere will flow.

AMPACITY. The current in amperes that a conductor can carry continuously


under the conditions of use without exceeding its temperature rating.

ASSEMBLY.A combinations of all or of a portion of component parts included in


an electric apparatus, mounted in a supporting frame or panel, and properly
interwired.

AUTOMATIC. Self-acting operating by its own mechanism when actuated by some


impersonal influence.

BUILDING. A structure that stands alone or that is cut-off from adjoining structures
by firewalls with all openings therein protected by approved fire doors.

BUILDING, INSTITUTIONAL. Includes school buildings, hospitals,


museums, display centers, government building and the like.

BUS. A conductor, a group of conductors, in the switchgear assemblies which


serves as a common connection for two or more circuits.

CIRCUIT.

CIRCUIT, BRANCH. The circuit conductors between the final overcurrent


device protecting the circuit and the outlet(s).

CIRCUIT BREAKER. A device design to open and close a circuit by non-


automatic means and to open the circuit automatically on a predetermined
overcurrent without damage to itself when properly applied within its rating.

COVERED. A conductor encased within a material of composition or thickness that


is not recognized by the code as an electrical insulation.

CUT-OUT. An assembly of a fuse support with either a fuse holder, fuse carrier, or
disconnecting blade.

DEMAND FACTOR. The ratio of the maximum demand of a system, or part of a


system, to the total connected load of a system or the part of the system under
consideration.

DISCONNECTING MEANS. A device, or group of devices, or other means by


which the conductors of a circuit can be disconnected from their source of supply.

DROP. The voltage drop that occurs across the resistor due to current flow through
the resistor.
2

DWELLING UNIT, MULTIFAMILY. A building that contain three or more dwelling


unit.

ELECTRIC SIGN. A fixed, stationary, or portable self-contained, electrically


illuminated utilization equipment with words or symbols designed to convey
information or attract attention.

ESTABLISHMENTS.

ESTABLISHMENTS, COMMERCIAL. Include department stores,


stadiums, condominiums, convention centers, restaurants, etc. used for
business of profit.

ESTABLISHMENTS, INDUSTRIAL. A building or part of a building( other


than office or exhibit space) where persons are employed in manufacturing
processes or in the handling of materials, as distinguished from dwelling,
offices and like occupancies.

FEEDER. All circuit conductors between the service equipment, the source of a
separately derived system, or other power supply source and the final branch-
circuit overcurrent device.

FUSE. An overcurrent protective device with a circuit-opening fusible part that is


heated and severed by the passage of overcurrent through it.

GROUND. A conducting connection, whether intentional or accidental, between


an electrical circuit or equipment and the earth or to some conducting body that
serves in place of the earth.

ILLUMINATION. Density of the luminous flux on a surface; it is the quotient of the


flux by the open area of a surface when the latter is uniformly illuminated.

INSTALLATIONS. An assembly of electric equipment in a given location designed


for coordinated operation, and properly erected and wired.

JOINT. A connection between two or more conductors.

LIGHT. For the purpose of illumination, light is visually evaluated as radiant


energy.

LOAD.
LOAD CENTER. A point at which the load of a given area is assumed to be
concentrated.

LOAD, PEAK. The maximum load consumed or produced by a unit or group


of units in a stated period of time. It may be maximum instantaneous load
or the maximum average load over a designated interval of time.
3

MAXIMUM DEMAND. The largest of all demands which have occurred during a
specific period of time.

OVERCURRENT. Any current in excess of the rated current of equipment or the


ampacity of a conductor.

PANELBOARD. A single panel or group of panel units designed for assembly in


the form of a single panel, including buses and automatic overcurrent devices, and
equipped with or without switches for the control of light, heat, or power circuits;
designed to be placed in a cabinet or cut-out box placed in or against a wall,
partition, or other support; and accessible only from the front.

SPLICE. A joint between two wires which possesses mechanical strength as well
as good electrical conductivity.

SPAN. The horizontal distance between two adjacent supporting points of a


conductor.

SYSTEM, ELECTRICAL. An electrical system is one where conductors and


equipment are interconnected to sources of potential difference for distribution
and/or utilization of electrical energy.

UNDERGROUND CABLE. A cable design for operation buried in the ground or


installed in an underground duct or conduit.

VOLT. The unit of electromagnetic force which, steadily applied to a conductor


whose resistance is one ohm, will produce a current of one ampere.

VOLTAGE. The greatest root-mean-square (rms) (effective) difference of potential


between any two conductors of the circuit concerned.

VOLTAGE DROP. The difference between the magnitudes of sending end voltage
and receiving end voltage.

VOLTAGE, NOMINAL. A nominal value assigned to a circuit or system for


the purpose of conveniently designating its voltage.

VOLTAGE, SERVICE. The root mean square phase to phase to neutral


voltage at the point where the electric system of the supplier and the user
are connected.
4
5
6
7
8
9
10

SELECTION OF TRANSFORMERS

TRANSFORMER 01

No. of Consumers Served : 1 (Industrial 02 Load)

KW Demand : 41.472 kW

MDKVA Demand : 51.84 kVA

Recommended Transformer : 3 – 100 kVA

TRANSFORMER 02

No. of Consumers Served : 1 (Industrial 03 Load)

KW Demand : 44.928 kW

MDKVA Demand : 56.16 kVA

Recommended Transformer : 3 – 100 kVA

TRANSFORMER 03

No. of Consumers Served : 12 (B Residential Load)

KW Demand : 29.952 kW

MDKVA Demand : 37.44 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 04

No. of Consumers Served : 24 (B Residential Load)

KW Demand : 44.928 kW

MDKVA Demand : 56.16 kVA

Recommended Transformer : 1 – 100 kVA


11

TRANSFORMER 05

No. of Consumers Served : 1 (Industrial #04 Load)

KW Demand : 51.84 kW

MDKVA Demand : 64.8 kVA

Recommended Transformer : 3 – 100 kVA

TRANSFORMER 06

No. of Consumers Served : 21 (B Residential Load)

KW Demand : 39.312 kW

MDKVA Demand : 49.14 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 07

No. of Consumers Served : 23 (B Residential Load)

KW Demand : 43.056 kW

MDKVA Demand : 53.82 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 08

No. of Consumers Served : 15 (B Residential Load)

KW Demand : 28.08 kW

MDKVA Demand : 35.1 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 09

No. of Consumers Served : 1 (Commercial #34)

KW Demand : 40.32 kW
12

MDKVA Demand : 50.4 kVA

Recommended Transformer : 3 – 75 kVA

TRANSFORMER 10

No. of Consumers Served : 24 (B Residential Load)

KW Demand : 44.928 kW

MDKVA Demand : 56.16 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 11

No. of Consumers Served : 13 (B Residential Load)

KW Demand : 24.336 kW

MDKVA Demand : 30.42 kVA

Recommended Transformer : 1 – 50 kVA

TRANSFORMER 12

No. of Consumers Served : 17 (B Residential Load)

KW Demand : 31.824 kW

MDKVA Demand : 39.78 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 13

No. of Consumers Served : 1 (Commercial #33)

KW Demand : 11.52 kW

MDKVA Demand : 14.4 kVA

Recommended Transformer : 3 – 25 kVA


13

TRANSFORMER 14

No. of Consumers Served : 22 (B Residential Load)

KW Demand : 41.184 kW

MDKVA Demand : 51.48 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 15

No. of Consumers Served : 17 (B Residential Load)

KW Demand : 31.824 kW

MDKVA Demand : 39.78 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 16

No. of Consumers Served : 3 (Comm. #30,31, 32)

KW Demand : 55.08 kW

MDKVA Demand : 68.85 kVA

Recommended Transformer : 3 – 100 kVA

TRANSFORMER 17

No. of Consumers Served : 3 (Comm. #25, 27, 29)

KW Demand : 51.84 kW

MDKVA Demand : 64.8 kVA

Recommended Transformer : 3 – 100 kVA

TRANSFORMER 18

No. of Consumers Served : 3 (Comm. #20, 22, 24)

KW Demand : 56.09 kW

MDKVA Demand : 70 kVA


14

Recommended Transformer : 3 – 100 kVA

TRANSFORMER 19

No. of Consumers Served : 2 (Commercial 12, 23)

KW Demand : 39.74 kW

MDKVA Demand : 49.68 kVA

Recommended Transformer : 3 – 75 kVA

TRANSFORMER 20

No. of Consumers Served : 2 (Commercial 26, 28)

KW Demand : 25.92 kW

MDKVA Demand : 32.4 kVA

Recommended Transformer : 3 – 50 kVA

TRANSFORMER 21

No. of Consumers Served : 17 (A Residential Load)

KW Demand : 42.432 kW

MDKVA Demand : 53.04 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 22

No. of Consumers Served : 17 (A Residential Load)

KW Demand : 42.432 kW

MDKVA Demand : 53.04 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 23

No. of Consumers Served : 18 (A Residential Load)


15

KW Demand : 44.928 kW

MDKVA Demand : 56.16 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 24

No. of Consumers Served : 20 (A Residential Load)

KW Demand : 49.92 kW

MDKVA Demand : 62.4 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 25

No. of Consumers Served : 14 (A Residential Load)

KW Demand : 34.944 kW

MDKVA Demand : 43.68 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 26

No. of Consumers Served : 14 (A Residential Load)

KW Demand : 34.944 kW

MDKVA Demand : 43.68 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 27

No. of Consumers Served : 13 (A Residential Load)

KW Demand : 32.448 kW

MDKVA Demand : 40.56 kVA

Recommended Transformer : 1 – 75 kV
16

TRANSFORMER 28

No. of Consumers Served : 17 (A Residential Load)

KW Demand : 42.432 kW

MDKVA Demand : 53.04 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 29

No. of Consumers Served : 17 (A Residential Load)


1 (Commercial 26)

KW Demand : 49.504 kW

MDKVA Demand : 61.88 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 30

No. of Consumers Served : 2 (Commercial #1, 2)

KW Demand : 16.704 kW

MDKVA Demand : 20.88 kVA

Recommended Transformer : 3 – 37.5 kVA

TRANSFORMER 31

No. of Consumers Served : 15 (A Residential Load)

KW Demand : 37.44 kW

MDKVA Demand : 46.8 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 32

No. of Consumers Served : 3 (Comm. #7, 9, 10)


17

KW Demand : 46.354 kW

MDKVA Demand : 57.942 kVA

Recommended Transformer : 3 – 100 kVA

TRANSFORMER 33

No. of Consumers Served : 2 (Commercial #5, 8)

KW Demand : 16.128 kW

MDKVA Demand : 20.16 kVA

Recommended Transformer : 3 – 37.5 kVA

TRANSFORMER 34

No. of Consumers Served : 1 (Institutional: Elem.)

KW Demand : 51.12 kW

MDKVA Demand : 63.9 kVA

Recommended Transformer : 3 – 100 kVA

TRANSFORMER 35

No. of Consumers Served : 2 (Commercial #11, 13)

KW Demand : 18.576 kW

MDKVA Demand : 23.22 kVA

Recommended Transformer : 3 – 37.5 kVA

TRANSFORMER 36

No. of Consumers Served : 2 (Commercial #14, 15)

KW Demand : 17.28 kW

MDKVA Demand : 21.6 kVA

Recommended Transformer : 3 – 37.5 kVA


18

TRANSFORMER 37

No. of Consumers Served : 2 (Commercial #16, 17)

KW Demand : 27.36 kW

MDKVA Demand : 34.2 kVA

Recommended Transformer : 3 – 50 kVA

TRANSFORMER 38

No. of Consumers Served : 1 (Commercial #21)

KW Demand : 38.304 kW

MDKVA Demand : 47.88 kVA

Recommended Transformer : 3 – 75 kVA

TRANSFORMER 39

No. of Consumers Served : 18 (C Residential Load)

KW Demand : 22.464 kW

MDKVA Demand : 28.08 kVA

Recommended Transformer : 1 – 50 kVA

TRANSFORMER 40

No. of Consumers Served : 2 (Commercial #18, 19)

KW Demand : 18.432 kW

MDKVA Demand : 23.04 kVA

Recommended Transformer : 3 – 50 kVA

TRANSFORMER 41

No. of Consumers Served : 16 (C Residential Load)

KW Demand : 19.968 kW
19

MDKVA Demand : 24.96 kVA

Recommended Transformer : 1 – 37.5 kVA

TRANSFORMER 42

No. of Consumers Served : 19 (C Residential Load)

KW Demand : 23.712 kW

MDKVA Demand : 29.64 kVA

Recommended Transformer : 1 – 50 kVA

TRANSFORMER 43

No. of Consumers Served : 21 (C Residential Load)

KW Demand : 26.208 kW

MDKVA Demand : 32.76 kVA

Recommended Transformer : 1 – 50 kVA

TRANSFORMER 44

No. of Consumers Served : 29 (C Residential Load)

KW Demand : 36.192 kW

MDKVA Demand : 45.24 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 45

No. of Consumers Served : 33 (C Residential Load)

KW Demand : 41.184 kW

MDKVA Demand : 51.28 kVA

Recommended Transformer : 1 – 100 kVA


20

TRANSFORMER 46

No. of Consumers Served : 20 (C Residential Load)

KW Demand : 24.96 kW

MDKVA Demand : 31.2 kVA

Recommended Transformer : 1 – 50 kVA

TRANSFORMER 47

No. of Consumers Served : 22 (C Residential Load)

KW Demand : 27.456 kW

MDKVA Demand : 34.32 kVA

Recommended Transformer : 1 – 50 kVA

TRANSFORMER 48

No. of Consumers Served : 30 (C Residential Load)

KW Demand : 37.44 kW

MDKVA Demand : 46.8 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 49

No. of Consumers Served : 21 (C Residential Load)

KW Demand : 26.208 kW

MDKVA Demand : 32.76 kVA

Recommended Transformer : 1 – 50 kVA

TRANSFORMER 50

No. of Consumers Served : 24 (C Residential Load)


1 (Institutional)

KW Demand : 44.928 kW
21

MDKVA Demand : 56.16 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 51

No. of Consumers Served : 30 (C Residential Load)

KW Demand : 37.44 kW

MDKVA Demand : 46.8 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 52

No. of Consumers Served : 2 (Commercial #35,39)


1 (Institutional)

KW Demand : 54 kW

MDKVA Demand : 67.5 kVA

Recommended Transformer : 3 – 100 kVA

TRANSFORMER 53

No. of Consumers Served : 31 (C Residential Load)

KW Demand : 38.688 kW

MDKVA Demand : 48.36 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 54

No. of Consumers Served : 42 (C Residential Load)

KW Demand : 52.416 kW

MDKVA Demand : 65.52 kVA


22

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 55

No. of Consumers Served : 23 (B Residential Load)

KW Demand : 43.056 kW

MDKVA Demand : 53.82 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 56

No. of Consumers Served : 1 (Industrial #01)

KW Demand : 56.52 kW

MDKVA Demand : 70.65 kVA

Recommended Transformer : 3 – 100 kVA

TRANSFORMER 57

No. of Consumers Served : 17 (A Residential Load)

KW Demand : 42.432 kW

MDKVA Demand : 53.04 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 58

No. of Consumers Served : 8 (A Residential Load)

KW Demand : 19.968 kW

MDKVA Demand : 24.96 kVA

Recommended Transformer : 1 – 50 kVA


23

TRANSFORMER 59

No. of Consumers Served : 20 (A Residential Load)

KW Demand : 49.92 kW

MDKVA Demand : 62.4 kVA

Recommended Transformer : 1 – 100 kVA

TRANSFORMER 60

No. of Consumers Served : 16 (A Residential Load)

KW Demand : 49.92 kW

MDKVA Demand : 62.4 kVA

Recommended Transformer : 1 – 75 kVA

TRANSFORMER 61

No. of Consumers Served : 8 (A Residential Load)

KW Demand : 19.968 kW

MDKVA Demand : 24.96 kVA

Recommended Transformer : 1 – 50 kVA

TRANSFORMER 62

No. of Consumers Served : 8 (A Residential Load)

KW Demand : 24.96 kW

MDKVA Demand : 31.2 kVA

Recommended Transformer : 1 – 50 kVA

TRANSFORMER 63

No. of Consumers Served : 2 (Commercial #4, 6)

KW Demand : 16.848 kW
24

MDKVA Demand : 21.06 kVA

Recommended Transformer : 3 – 25 kVA

TRANSFORMER 64

No. of Consumers Served : 3 (Comm. #36, 37, 38)

KW Demand : 29.376 kW

MDKVA Demand : 36.72 kVA

Recommended Transformer : 3 – 50 kVA

TRANSFORMER 65

No. of Consumers Served : 9 (B Residential Load)

KW Demand : 16.848 kW

MDKVA Demand : 21.06 kVA

Recommended Transformer : 1 – 37.5 kVA


25

VOLTAGE DROP COMPUTATION

𝑉𝑏 = Base Voltage @ 240 V 𝑉𝑠 = Sending Voltage

𝑉𝑟 = Receiving Voltage 𝑉𝑑 = Voltage Drop

%𝑉𝑑 = Percentage Voltage

Z = Total Series Impedance in L = Length


Phase

𝑉𝑏 = 𝑉𝑠 𝑉𝑟 = 𝑉𝑟 + 𝐼 𝑋𝐿

Note: Voltage Drop Limitation: 3%

Voltage Drop at Pole No. 012 @ Transformer 01

No. of consumer served in this section : 1 (Industrial #02 Load)

KW Demand : 41.472 kW

𝑉𝑟 : 232.93 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km


26

Voltage Drop at Pole No. 013 @ Transformer 02

No. of consumer served in this section : 1 (Industrial #03 Load)

KW Demand : 44.928 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No. 001 @ Transformer 03

No. of consumer served in this section : 1 (Residential B Loads)

KW Demand : 29.952 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 015 @ Transformer 04

No. of consumer served in this section : 24(Residential B Loads)

KW Demand : 44.928 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km


27

Voltage Drop at Pole No. 014 @ Transformer 05

No. of consumer served in this section : 1 (Industrial #04 Load)

KW Demand : 51.84 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No. 016 @ Transformer 06

No. of consumer served in this section : 21 (Residential B Load)

KW Demand : 39.312 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 018 @ Transformer 07

No. of consumer served in this section : 23 (Residential B Load)

KW Demand : 43.056 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 32 mm ACSR


28

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 017 @ Transformer 08

No. of consumer served in this section : 15 (Residential B Load)

KW Demand : 28.08 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 011 @ Transformer 09

No. of consumer served in this section : 1(Comm. #34 Load)

KW Demand : 40.32 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 020 @ Transformer 010

No. of consumer served in this section : 24 (Residential B Load)

KW Demand : 44.928 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V
29

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No. 019 @ Transformer 011

No. of consumer served in this section : 13 (B Residential Load)

KW Demand : 24.336 kW

𝑉𝑟 : 232.86 V

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 022 @ Transformer 12

No. of consumer served in this section : 17 (Residential B Load)

KW Demand : 31.824 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.94 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 021 @ Transformer 13

No. of consumer served in this section : 1 (Comm. #33 Load)

KW Demand : 11.52 kW

𝑉𝑟 : 232.66 V
30

𝑉𝑑 : 6.336 V

%𝑉𝑑 : 2.64 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 023 @ Transformer 14

No. of consumer served in this section : 22 (Residential B Load)

KW Demand : 41.184 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 024 @ Transformer 15

No. of consumer served in this section : 17 (Residential B Load)

KW Demand : 31.824 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.94 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 027 @ Transformer 16

No. of consumer served in this section : 3(Comm.#30-32 Load)

KW Demand : 55.08 kW
31

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No. 028 @ Transformer 17

No. of consumer served in this section : 3 (Comm. #25-29 Load)

KW Demand : 51.84 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No. 029 @ Transformer 18

No. of consumer served in this section : 3 (Comm.#20-24 Load)

KW Demand : 56.009 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km


32

Voltage Drop at Pole No. 030 @ Transformer 19

No. of consumer served in this section : 2 (Comm. #12,23 Load)

KW Demand : 39.744 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 031 @ Transformer 20

No. of consumer served in this section : 2(Comm. #26,28 Load)

KW Demand : 25.92 kW

𝑉𝑟 : 233.86 V

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 032 @ Transformer 21

No. of consumer served in this section : 17 (Residential A Load)

KW Demand : 42.432 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km


33

Voltage Drop at Pole No. 033 @ Transformer 22

No. of consumer served in this section : 17 (Residential A Load)

KW Demand : 42.432 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 035 @ Transformer 23

No. of consumer served in this section : 18 (Residential A Load)

KW Demand : 44.928 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No. 034 @ Transformer 24

No. of consumer served in this section : 20 (Residential A Load)

KW Demand : 44.92 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km


34

Voltage Drop at Pole No. 036 @ Transformer 25

No. of consumer served in this section : 14 (Residential A Load)

KW Demand : 34.944 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 037 @ Transformer 26

No. of consumer served in this section : 14 (Residential A Load)

KW Demand : 34.944 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 038 @ Transformer 27

No. of consumer served in this section : 13 (Residential A Load)

KW Demand : 34.944 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km


35

Voltage Drop at Pole No. 039 @ Transformer 28

No. of consumer served in this section : 17 (Residential A Load)

KW Demand : 42.432 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 041 @ Transformer 29

No. of consumer served in this section : 17(Residential A Load)


1 (Comm. #26 Load)

KW Demand : 42.432 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 040 @ Transformer 30

No. of consumer served in this section : 1( Comm. #1,2 Loads)

KW Demand : 16.704 kW

𝑉𝑟 : 233.71 V

𝑉𝑑 : 6.288 V

%𝑉𝑑 : 2.62 %

Size of Wire : 19 mm ACSR


36

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 42-A @ Transformer 31

No. of consumer served in this section : 15 (Residential A Load)

KW Demand : 37.44 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 045 @ Transformer 32

No. of consumer served in this section : 3 (Comm. #7-10 Loads)

KW Demand : 46.354 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No. 043 @ Transformer 33

No. of consumer served in this section : 2 (Comm. #5,8 Loads)

KW Demand : 16.128 kW

𝑉𝑟 : 233.71 V

𝑉𝑑 : 6.288 V

%𝑉𝑑 : 2.62 %
37

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 044 @ Transformer 34

No. of consumer served in this section : 1 (Institutional)

KW Demand : 51.12 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No. 046 @ Transformer 35

No. of consumer served in this section : 2(Comm. #11,13 Load)

KW Demand : 18.576 kW

𝑉𝑟 : 233.71 V

𝑉𝑑 : 6.288 V

%𝑉𝑑 : 2.62 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 048 @ Transformer 36

No. of consumer served in this section : 2 (Comm. #14,15 Load)

KW Demand : 17.28 kW

𝑉𝑟 : 233.71 V

𝑉𝑑 : 6.288 V
38

%𝑉𝑑 : 2.62 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 047 @ Transformer 37

No. of consumer served in this section : 2 (Comm. #16,17 Load)

KW Demand : 27.36 kW

𝑉𝑟 : 233.86 V

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 050 @ Transformer 38

No. of consumer served in this section : 1 (Comm. #21 Load)

KW Demand : 38.304 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 051 @ Transformer 39

No. of consumer served in this section : 18 (Residential C Load)

KW Demand : 22.464 kW

𝑉𝑟 : 233.86 V
39

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56%

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 049 @ Transformer 40

No. of consumer served in this section : 2 (Comm. #18,19 Load)

KW Demand : 18.432 kW

𝑉𝑟 : 233.71 V

𝑉𝑑 : 6.288 V

%𝑉𝑑 : 2.62 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 053 @ Transformer 41

No. of consumer served in this section : 16 (Residential C Load)

KW Demand : 19.968 kW

𝑉𝑟 : 233.71 V

𝑉𝑑 : 6.288 V

%𝑉𝑑 : 2.62 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 052 @ Transformer 42

No. of consumer served in this section : 19 (Residential C Load)

KW Demand : 23.712 kW
40

𝑉𝑟 : 233.86 V

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 054 @ Transformer 43

No. of consumer served in this section : 21 (Residential C Load)

KW Demand : 26.208 kW

𝑉𝑟 : 233.86 V

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 055 @ Transformer 44

No. of consumer served in this section : 29 (Residential C Load)

KW Demand : 36.192 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 056 @ Transformer 45

No. of consumer served in this section : 33 (Residential C Load)


41

KW Demand : 41.184 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 009-A @ Transformer 46

No. of consumer served in this section : 20 (Residential C Load)

KW Demand : 24.96 kW

𝑉𝑟 : 233.86 V

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No.008 @ Transformer 47

No. of consumer served in this section : 22 (Residential C Load)

KW Demand : 27.456 kW

𝑉𝑟 : 233.86 V

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km


42

Voltage Drop at Pole No. 007 @ Transformer 48

No. of consumer served in this section : 33 (Residential C Load)

KW Demand : 37.44 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No.006 @ Transformer 49

No. of consumer served in this section : 21 (Residential C Load)

KW Demand : 26.208 kW

𝑉𝑟 : 233.86 V

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 005 @ Transformer 50

No. of consumer served in this section : 24 (Residential C Load)


1 (Institutional Load)

KW Demand : 44.928 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR


43

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No. 004 @ Transformer 51

No. of consumer served in this section : 33 (Residential C Load)

KW Demand : 37.44 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 010 @ Transformer 52

No. of consumer served in this section : 2(Comm.#35,39 Load)


1 (Institutional Load)

KW Demand : 54 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No. 003 @ Transformer 53

No. of consumer served in this section : 31 (Residential C Load)

KW Demand : 38.688 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %
44

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 002 @ Transformer 54

No. of consumer served in this section : 42 (Residential C Load)

KW Demand : 52.416 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No. 025 @ Transformer 55

No. of consumer served in this section : 23 (Residential B Load)

KW Demand : 43.056 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No. 026 @ Transformer 56

No. of consumer served in this section : 1 (Industrial #01 Load)

KW Demand : 56.52 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V
45

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No. 033-B @ Transformer 57

No. of consumer served in this section : 17 (Residential B Load)

KW Demand : 42.432 kW

𝑉𝑟 : 232.97 V

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 0.91698 Ω / km

Voltage Drop at Pole No.035-B @ Transformer 58

No. of consumer served in this section : 8 (Residential A Load)

KW Demand : 19.968 kW

𝑉𝑟 : 233.86 V

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No.037-A @ Transformer 59

No. of consumer served in this section : 20 (Residential A Load)

KW Demand : 49.92 kW

𝑉𝑟 : 232.97 V
46

𝑉𝑑 : 7.032 V

%𝑉𝑑 : 2.93 %

Size of Wire : 58 mm ACSR

Conductor Resistance : 0.50694 Ω / km

Voltage Drop at Pole No.038-B @ Transformer 60

No. of consumer served in this section : 16 (Residential A Load)

KW Demand : 39.936 kW

𝑉𝑟 : 232.94 V

𝑉𝑑 : 7.056 V

%𝑉𝑑 : 2.94 %

Size of Wire : 32 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No.039-C @ Transformer 61

No. of consumer served in this section : 8 (Residential A Load)

KW Demand : 19.968 kW

𝑉𝑟 : 233.71 V

𝑉𝑑 : 6.288 V

%𝑉𝑑 : 2.62 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No.041-B @ Transformer 62

No. of consumer served in this section : 10 (Residential A Load)


47

KW Demand : 24.96 kW

𝑉𝑟 : 233.86 V

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No.041-B @ Transformer 63

No. of consumer served in this section : 2 (Comm. #4,6 Load)

KW Demand : 16.848 kW

𝑉𝑟 : 233.66 V

𝑉𝑑 : 6.336 V

%𝑉𝑑 : 2.64 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km

Voltage Drop at Pole No.009 @ Transformer 64

No. of consumer served in this section : 3 (Comm. #36-38 Load)

KW Demand : 39.376 kW

𝑉𝑟 : 233.86 V

𝑉𝑑 : 6.144 V

%𝑉𝑑 : 2.56 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km


48

Voltage Drop at Pole No.016-A @ Transformer 65

No. of consumer served in this section : 9 (Residential B Load)

KW Demand : 16.848 kW

𝑉𝑟 : 233.71 V

𝑉𝑑 : 6.288 V

%𝑉𝑑 : 2.62 %

Size of Wire : 19 mm ACSR

Conductor Resistance : 1.5504 Ω / km


49

DESIGN FOR STREET LIGHTING

A. Highways

Staggered Arrangement

𝐸 = 6.46 lux

𝑤 = 10 meters

𝑑 = 20 meters

𝑚. 𝑓. = 0.8

𝑐. 𝑢. = 0.36 (type A fixture, more than 9.15)

ℎ = 1.60 meters

Calculate Average Lumens:

𝐸×𝑑×𝑤 6.46 × 20 × 10
𝐴𝑣𝑒𝑟𝑎𝑔𝑒 𝐿𝑢𝑚𝑒𝑛𝑠 = =
𝑚. 𝑓.× 𝑐. 𝑢. 0.36 × 0.8

𝑨𝒗𝒆𝒓𝒂𝒈𝒆 𝑳𝒖𝒎𝒆𝒏𝒔 = 𝟒, 𝟔𝟔𝟕 ≈ 𝟕𝟐𝟎𝟎

Therefore, use 175 Watts, H39, E-28 or BT-28, HID Lamp.


50

B. Minor Roads

Staggered Arrangement

𝐸 = 6.46 lux

𝑤 = 6 meters

𝑑 = 20 meters

𝑚. 𝑓. = 0.8

𝑐. 𝑢. = 0.36 (type A fixture, more than 9.15)

ℎ = 1.60 meters

Calculate Average Lumens:

𝐸×𝑑×𝑤 6.46 × 20 × 6
𝐴𝑣𝑒𝑟𝑎𝑔𝑒 𝐿𝑢𝑚𝑒𝑛𝑠 = =
𝑚. 𝑓.× 𝑐. 𝑢. 0.36 × 0.8

𝑨𝒗𝒆𝒓𝒂𝒈𝒆 𝑳𝒖𝒎𝒆𝒏𝒔 = 𝟐, 𝟔𝟗𝟐 ≈ 𝟑, 𝟐𝟎𝟎

Therefore, use 100 Watts, H38, ED 23 ½ , HID Lamp.


51

C. Residential Roads

Staggered Arrangement

𝐸 = 2.91 lux

𝑤 = 6 meters

𝑑 = 20 meters

𝑚. 𝑓. = 0.8

𝑐. 𝑢. = 0.29

ℎ = 1.60 meters

Calculate Average Lumens:

𝐸×𝑑×𝑤 2.91 × 20 × 6
𝐴𝑣𝑒𝑟𝑎𝑔𝑒 𝐿𝑢𝑚𝑒𝑛𝑠 = =
𝑚. 𝑓.× 𝑐. 𝑢. 0.29 × 0.8

𝑨𝒗𝒆𝒓𝒂𝒈𝒆 𝑳𝒖𝒎𝒆𝒏𝒔 = 𝟏, 𝟓𝟎𝟓 ≈ 𝟐, 𝟐𝟓𝟎

Therefore, use 40 Watts, H43, E-17, HID Lamp.


52

SPECIFICATION FOR CONSTRUCTION

1. General
All construction work shall be done in a thorough and workmanlike manner
in accordance with the Staking Sheets, Plans and Specifications, and the
Construction Drawing.

2. Distribution of Poles
In the distribution of poles, large choice, closed grain poles shall be used
for transformers, dead-end, angle and corner poles.

3. Distribution Transformer
The transformer should be designed and manufactured with latest
applicable provision of ANSI, NEMA, or any recognized equivalent standards

4. Lighting Arrester
Proper selection of an arrester type and rating shall involve the
consideration of the following criteria.
a. Rated Voltage
b. Maximum continuous over voltage capacity
c. Protection absorption capability
d. Energy absorption capacity
e. Pressure relief capability

5. Cut-Out
Cut-out support should have the following
a. Joint less current path
b. Silver to silver contact
c. Copper alloy casting should be used on fuse tube and bottom support
d. Interchange fuse tube
e. Solid porcelain insulator with cemented steel rods on top, bottom, and
back

6. Taps and Jumper


Jumper in other loads connected to line conductor shall have sufficient slack
to allow free movement of the conductor. Where slack is not shown on
construction drawing it will be provided by at least two bonds in vertical plane,
of one in horizontal plane, or the equivalent. In areas where Aeolian vibration
53

occur, special measure to minimize the effect of jumper break shall be used as
specified.

7. Splices and Dead ends


Conductor shall be spliced dead end as shown on the construction drawing.
There shall not be more than one splice per conductor in any span and splicing
sleeves shall be located near conductor support. Maintain also 3050 mm or
more separation between the splice and the conductor support. No splice shall
be located in grade 13 crossing span and preferable not in adjacent spans.

8. Guys and Anchors


Guys shall be placed before the conductor are strung and shall be attached
to the pole as shown in the construction drawing. All anchors and rods shall be
in line with the strain and shall be so installed that approximately 15 cm of the
rod remain out of the ground. In cultivated fields and other location, as deemed
necessary, the projection of the anchor rod above earth may be increased to
maximum of 30 cm thoroughly tamp to the full depth.

9. Locknuts
A locknut shall be installed with each nut, or other fastener on all bolts or
threaded hardware such as insulator pins, upset bolts, double arming bolts, etc.

10. Conductors
Conductor shall be handled with care; conductor shall not be stamped on
nor run over by vehicles. Each reel shall be examined and the wire shall be
inspected for cuts, kinks, or other injuries. Injured portion shall be cut and
conductor spliced. The conductor properly mounted on pulled over suitable
rollers or stringing blocks shall be carefully mounted on pole or cross arm if
necessary to prevent binding while stringing. The neutral conductor shall be
maintained on one side of the pole (preferable the road-side) for tangent
construction and for angles not exceeding 30 degrees.

11. Hot Line Clamp and Connectors


Connector and hot line clamp suitable for the purpose shall be installed as
shown on the guide drawings. On all hot line clamp installations, the clamp and
jumper shall be so installed so that they are perfectly bonded to the load side of
the line, allowing the jumper to be energized when the clamp is disconnected.
This applies in all cases, even when the line layout is such that the trip line is in
54

actually the main back to the power source. Do not install hot line clamp directly
to the power ACSR conductors.

Use tapping armor rods on tap saddles. Before installing hot line clamp to
the surface of tapping armor rods, clean thorough by the wire brushing and apply
a suitable inhibitor to the area of the tapping armor rod coming in all contact with
the hot line clamp.

12. Lighting Arrester Gap Settings


The external gas electrodes of lighting arrester cut out units, and the
transformer mounted arrester shall be adjusted to the manufacturer’s
recommended spacing. Care shall be taken that the adjusted gap is not
disturbed when the equipment is installed.

13. Conductor Ties


Ties shall be in accordance with construction drawings. Hot line ties shall
not be used at grade B crossings.

14. Sagging of Conductors


Conductors shall be sagged with the conductor manufacturer’s
recommendations except that a maximum increase of 7.6 cm of the specified
sag in any span will be acceptable but in no circumstances shall a decrease in
specified sag be allowed.

15. Secondary and Service Drops


Secondary conductor may be bare or covered wire or multi-conductor
service cable. Conductor for secondary under build on primary lines is normally
bared except in those instances where prevailing conditions may limit primary
span length to the extent that covered wire or service cable type. Secondary
and service drop shall be so installed as not to obstruct climbing space. There
shall not be more than one splice per conductor in any span, and splicing
sleeves shall not be located near the conductor support. Where the same
covered conductors or service cables are to be used for the same secondary
and service drop they may be installed in one continuous run.

16. Ground
Ground rod shall be driven in undistributed earth in accordance with the
construction drawing. Where aluminium ground wire is used, it must be
55

terminated above ground at galvanized ground rod or splice by a compression


connector to copper steel ground wire extension to the ground rod of which the
top of the ground rod shall be 30 cm or more below the surface of the earth.
The ground wire shall be spaced two feet (2 ft.) apart except for a distance of
2.40 m above the ground rod and 2.40 m down from the top of the pole where
they shall have at least two connections from the frame case of the tank to the
multi-grounded neutral conductor. The equipment shall be interconnected and
attached to a common ground wire.

TECHNICAL SPECIFICATIONS

The National Grid Corporation of the Philippines (NGCP), Labo Branch

located at Talobatib, Labo, Camarines Norte will be the commercial source of the

distribution system of the 25 Hectares Subdivision. This power source 69 kV, three

phase line came from the said substation.

From the source there will be a process of stepping down the voltage from

69 kV to 13.2 kV to 240 V. Through the distribution transformers situated along the

different strategic location within the subdivision premises. Each distribution

transformer will have a specific number of consumers to be served.

This expanded radial type of distribution system will be effective enough to

meet the expansion and development requirements of the 25 Hectares Subdivision

for the year to come. To effectively meet the said requirements, it shall conform to

the proper choice of equipment for the case of power distribution.


56

DESCRIPTION OF LOAD DETAILS

RESIDENTIAL

Description Land Effective Unit/s Unit Individual Total


Area Area Load Load KVA
Sq. m. Sq. m. (VA) (VA)
A 300 200 238 24 4,800 1,142.4
B 250 150 279 24 3,600 1,004.4
C 150 100 302 24 2,400 724.8
Total 819

COMMERCIAL

Description Land Effective Unit/s Unit Individual Total


Area Area Load Load KVA
Sq. m. Sq. m. (VA) (VA)
Comm. 1 600 500 1 24 12,000 12.00
Comm. 2 755 700 1 16 11,200 11.20
Comm. 3 500 400 1 24 9,600 9.60
Comm. 4 645 600 1 24 14,400 14.40
Comm. 5 590 500 1 16 8,000 8.00
Comm. 6 580 500 1 18 9,000 9.00
Comm. 7 665 600 1 24 14,400 14.40
Comm. 8 690 600 1 24 14,400 14.40
Comm. 9 1300 1100 1 28 30,800 30.80
Comm. 10 970 800 1 24 19,200 19.20
Comm. 11 805 700 1 24 16,800 16.80
Comm. 12 1460 1200 1 28 33,600 33.60
Comm. 13 540 500 1 18 9,000 9.00
Comm. 14 538 500 1 24 12,000 12.00
Comm. 15 546 500 1 24 12,000 12.00
Comm. 16 1010 900 1 16 14,400 14.40
Comm. 17 1155 1000 1 24 24,000 24.00
Comm. 18 735 600 1 24 14,400 14.40
Comm. 19 825 700 1 16 11,200 11.20
Comm. 20 1280 1100 1 28 30,800 30.80
Comm. 21 2375 1900 1 28 53,200 53.20
Comm. 22 1580 1300 1 28 36,400 36.40
Comm. 23 995 800 1 16 12,800 12.80
Comm. 24 1125 900 1 24 21,600 21.60
Comm. 25 1105 900 1 24 21,600 21.60
Comm. 26 1115 900 1 16 14,400 14.40
Comm. 27 1115 900 1 18 16,200 16.20
Comm. 28 1115 900 1 24 21,600 21.60
Comm. 29 1115 900 1 24 21,600 21.60
Comm. 30 655 600 1 16 9,600 9.60
Comm. 31 1435 1200 1 24 28,800 28.80
57

Comm. 32 1275 1100 1 24 26,400 26.40


Comm. 33 1145 1000 1 16 16,000 16.00
Comm. 34 2450 2000 1 28 56,000 56.00
Comm. 35 2755 2300 1 16 36,800 36.80
Comm. 36 540 500 1 24 12,000 12.00
Comm. 37 595 500 1 24 12,000 12.00
Comm. 38 760 700 1 24 16,800 16.80
Comm. 39 745 600 1 24 14,400 14.40

INSTITUTIONAL

Description Land Effective Unit/s Unit Individual Total


Area Area Load Load KVA
Sq. m. Sq. m. (VA) (VA)
Elementary 8,875 1 8 56,800 56.80
Clinic 1,225 1 16 16,000 16.00
Chapel 1,860 1 16 24,000 24.00

INDUSTRIAL

Description Land Effective Unit/s Unit Individual Total


Area Area Load Load KVA
Sq. m. Sq. m. (VA) (VA)
Industrial 1 6,590 1 18 95,400 95.40
Industrial 2 2,975 1 24 57,600 57.60
Industrial 3 3,205 1 24 62,400 62.40
Industrial 4 3,695 1 24 72,000 72.00
Power Plant 30,600 1 24 588,000 588.00

UTILITY

Description Land Effective Unit/s Unit Individual Total


Area Area Load Load KVA
Sq. m. Sq. m. (VA) (VA)
Park 1,805 1
Recreational 2,790 1
Garden 15,650 1
Parking 5,350 1
Area
Road 38,470 1

Over all 248,870


58

TABLE OF GENERAL INFORMATION

Transformer no. Residential Commercial Industrial Institutional


A B C
1 1
2 1
3 12
4 24
5 1
6 21
7 23
8 15
9 1
10 24
11 13
12 17
13 1
14 22
15 17
16 3
17 3
18 3
19 2
20 2
21 17
22 17
23 18
24 20
25 14
26 14
27 13
28 17
29 17 1
30 2
31 15
32 3
33 2
34 1
35 2
36 2
37 2
38 1
39 18
40 2
41 16
42 19
43 21
59

44 29
45 33
46 20
47 22
48 30
49 21
50 24 1
51 30
52 2 1
53 31
54 42
55 23
56 1
57 17
58 8
59 20
60 16
61 8
62 10
63 2
64 3
65 9
Total 238 279 302 39 4 3

TABULATION OF CONNECTION IN POLE

Pole Residential Commercial Industrial Institutional


1 4
1-A 5
1-B 4
2 5
2-A 10
2-B 8
2-C 12
2-D 6
3 5
3-A 9
3-B 10
3-C 7
4 6
4-A 11
4-B 13
5 4
5-A 9
60

5-B 8
5-C 3 1
6 5
6-A 11
6-B 5
7 4
7-A 10
7-B 7
7-C 9
8 2
8-A 5
8-B 5
8-C 4
8-D 3
8-E 3
9 3
9-A 3
9-B 2
9-C 4
9-D 4
9-E 3
9-F 4
10 1 1
10-A 1
11 1
12 1
13 1
14 1
15 2
15-A 4
15-B 8
15-C 4
15-D 6
16 13
16-C 8
16-A 5
16-B 4
17 8
17-A 10
18 7
18-A 7
18-B 8
19 5
19-A 8
20 5
20-A 9
20-B 10
20-C
61

21 1
21-A
22 4
22-A 6
22-B 7
23 11
23-A 11
24 8
24-A 2
24-B 7
25 5
25-A 5
25-B
25-C 6
25-D 7
26 1
27 3
28 2
28-A
28-B 1
29 3
30 2
31 2
32 6
32-A 6
32-B 5
33 6
33-A 5
33-C 2
33-D 3
33-B 17
34 6
34-A 7
34-B 6
35 7
35-A 11
35-B 8
36 3
36-A 5
36-B 6
37 12
37-A 8
37-B 14
38 7
38-A 6
38-B 5
38-C 12
39 2
62

39-A 4
39-B 10
39-C 8
40 2
41 4 1
41-A 10
41-B 10
42 2
43 1
43-A 1
44 1 1
45 2
45-A 2
46 1
47 1
47-A 1
48 1
48-A 2
49 1
50 1
51 6
51-A 7
51-B 5
52 7
52-A 11
53 3
53-A 4
53-B 4
53-C 5
54 10
54-A 6
54-B 6
55 5
55-A 4
55-B 5
55-C
55-D 6
55-E 5
55-F 3
56 6
56-A 5
56-B 12
56-C 10

Total no. of poles 153


Residential 819
Commercial 39
Industrial 4
63

Institutional 3

SUMMARY OF TOTAL KVA

Residential Commercial Industrial Institutional


T/F No. kVA T/F No. kVA T/F No. kVA T/F No. kVA
3 37.44 13 14.4 1 51.84 34 63.9
4 56.16 16 68.85 2 56.16 50 15.45
6 49.14 17 64.8 5 64.8 52 22.6
7 53.82 18 70 56 70.65
8 35.1 19 49.68
9 50.4 20 32.4
10 56.16 29 3.516
11 30.42 30 20.88
12 39.78 32 57.942
14 51.48 33 20.16
15 39.78 35 23.22
21 53.04 36 21.6
22 53.04 37 34.2
24 62.4 38 47.88
25 43.68 40 23.04
26 43.68 52 44.9
27 40.56 63 21.06
28 53.04 64 36.72
29 58.364
31 46.8
39 28.08
41 24.96
42 29.64
43 32.76
44 45.24
45 51.28
46 31.2
47 34.32
48 46.8
49 32.76
50 40.71
51 46.8
53 48.36
54 52.416
55 53.82
57 53.04
58 24.96
59 64.2
60 62.4
61 24.96
64

62 24.96
65 21.06

Total Residential kVA 1,829.01


Total Commercial kVA 655.248
Total Industrial kVA 243.45
Total Intuitional kVA 101.95
Total kVA 2,829.658

PRIMARY DISTRIBUTION
CALCULATION OF PRIMARY LINE FEEDER
TABULATION LOADS

T/F NO. POLE NO. PHASE A PHASE B PHASE C ∅


1 12 100 100 100 3
2 13 100 100 100 3
3 1 75 1
4 15 1
5 14 100 100 100 3
6 16 75 1
7 18 100 1
8 17 75 1
9 11 75 75 75 3
10 20 100 1
11 19 50 1
12 22 75 1
13 21 25 25 25 3
14 23 75 1
15 24 75 1
16 27 100 100 100 3
17 28 100 100 100 3
18 29 100 100 100 3
19 30 75 75 75 3
20 31 50 50 50 3
21 32 100 1
22 33 100 1
23 35 100 1
24 34 100 1
25 36 75 1
26 37 75 1
27 38 75 1
28 39 100 1
29 41 100 1
30 40 37.5 37.5 37.5 3
31 42-A 75 1
65

32 45 100 100 100 3


33 43 37.5 37.5 37.5 3
34 44 100 100 100 3
35 46 37.5 37.5 37.5 3
36 48 37.5 37.5 37.5 3
37 47 50 50 50 3
38 50 75 75 75 3
39 51 50 1
40 49 37.5 37.5 37.5 3
41 53 37.5 1
42 52 75 1
43 54 50 1
44 55 75 1
45 56 75 1
46 9-A 50 1
47 8 50 1
48 7 75 1
49 6 50 1
50 5 100 1
51 4 75 1
52 10 100 100 100 3
53 3 75 1
54 2 100 1
55 25 100 1
56 26 100 100 100 3
57 33-B 100 1
58 35-B 50 1
59 37-A 100 1
60 38-B 75 1
61 39-C 37.5 1
62 41-B 50 1
63 42 25 25 25 3
64 9 50 50 50 3
65 16-A 37.5 1

Total 2637.5 2650 2637.5

Total kVA per phase Solving for the total kVA in the Feeder

Phase A: 2,637.5 kVAT = 3 (Highest kVA/phase)


Phase B: 2,650 kVAT = 3 (2,650)
Phase C: 2,637.5 kVAT = 7,950

Solving for the Feeder Line Current

IL = kVAT / (√3) (13.2)


IL = (7,950) / (√3) (13.2)
IL = 347.73 A

Use 3 – 90 mm ACSR, 6 strands at 3.5 mm Ø each


66

Maximum Current = 530 A

For Fuse Rating For the Rating of Lighting Arrester


If = (I) (300%) ELA = 13.2 / (√3)
If = (347.73) (3.0) ELA = 7.62 kV
If = 1043.73 A
Use 3 – 1200 A

Use 3 – 10 kV station type Lighting Arrester, 127 mm distance from


bushing.

Calculation of Primary Line Fuse Cut-out No. 1 at Pole No. 12


Tabulation of the Load
T/F NO. POLE NO. PHASE A PHASE B PHASE C
1 12 100 100 100
2 13 100 100 100
3 1 75
4 15
5 14 100 100 100
6 16 75
7 18 100
8 17 75
9 11 75 75 75
10 20 100
11 19 50
12 22 75
13 21 25 25 25
14 23 75
15 24 75
16 27 100 100 100
17 28 100 100 100
18 29 100 100 100
19 30 75 75 75
20 31 50 50 50
21 32 100
Total 1100 1100 1075

Total kVA per phase Solving for the total connected load
Phase A = 1100 kVA kVAT = 3 (Highest kVA/phase)
Phase B = 1100 kVA kVAT = 3 (1,100)
Phase C = 1075 kVA kVAT = 3,300 kVA

Solving for the Feeder Line Current For Fuse Rating


IL = kVA T / (√3) (13.2) If = (I) (300%)
67

IL = 48.11 A If = (48.11) (3.0)


If = 144.33 A

Use 200 A Fuse Cut-out at Pole No. 12

Calculation of Primary Line Fuse Cut-out No. 1 at Pole No. 33


Tabulation of the Load
T/F NO. POLE NO. PHASE A PHASE B PHASE C
22 33 100
23 35 100
24 34 100
25 36 75
26 37 75
27 38 75
28 39 100
29 41 100
30 40 37.5 37.5 37.5
31 42-A 75
32 45 100 100 100
33 43 37.5 37.5 37.5
34 44 100 100 100
35 46 37.5 37.5 37.5
36 48 37.5 37.5 37.5
37 47 50 50 50
38 50 75 75 75
39 51 50
40 49 37.5 37.5 37.5
41 53 37.5
TOTAL 787.5 812.5 825

Total kVA per phase Solving for the Feeder Line Current
Phase A = 787.5 kVA IL = kVA T / (√3) (13.2)
Phase B = 812.5 kVA IL = (2,475) / (√3) (13.2)
Phase C = 825 kVA IL = 108.25 A

Solving for the total connected load For Fuse Rating


kVA T = 3 (Highest kVA/phase) If = (I) (300%)
kVA T = 3 (825) If = (108.25) (3.0)
kVA T = 2,475 kVA If = 324.76 A

Use 400 A Fuse Cut-out at Pole No. 33


68

Calculation of Primary Line Fuse Cut-out No. 1 at Pole No. 33


Tabulation of the Load
T/F NO. POLE NO. PHASE A PHASE B PHASE C
42 52 75
43 54 50
44 55 75
45 56 75
46 9-A 50
47 8 50
48 7 75
49 6 50
50 5 100
51 4 75
52 10 100 100 100
53 3 75
54 2 100
55 25 100
56 26 100 100 100
57 33-B 100
58 35-B 50
59 37-A 100
60 38-B 75
61 39-C 37.5
62 41-B 50
63 42 25 25 25
64 9 50 50 50
65 16-A 37.5
Total 737.5 737.5 725

Total kVA per phase Solving for the Feeder Line Current

Phase A = 737.5 kVA IL = kVA T / (√3) (13.2)


Phase B = 737.5 kVA IL = (2,475) / (√3) (13.2)
Phase C = 725 kVA IL = 96.77 A

Solving for the total connected load For Fuse Rating

kVA T = 3 (Highest kVA/phase) If = (I) (300%)


kVA T = 3 (737.5) If = (108.25) (3.0)
kVA T = 2,212.5 kVA If = 290.32 A

Use 350 A Fuse Cut-out at Pole No. 52


69

TABLES

Table 1.1 Electrical Characteristics of a

1- Phase 60-Hz Distribution Transformers

Impedance Percent voltage drop through Cu Core


Size,
Percent Transformer with FL current Loss Loss
1 Ø kVA
Z<Ɵ 97.5% pf 80% pf 50% pf % %
Single-phase transformer, voltage rating: 240/4160 to 120/220
3 2.7<32.90 2.56 2.7 2.4 2.27 0.93
5 2.7<38.40 2.46 2.7 2.51 2.12 0.72
7½ 2.7<43.5 2.35 2.66 5.58 1.96 0.64
10 2.7<45.9 2.29 2.66 5.62 1.88 0.57
15 2.8<51.6 2.21 2.71 2.76 1.74 0.51
25 2.8<56 2.08 2.64 2.79 1.56 0.46
37.5 2.9<61.8 1.95 2.62 2.9 1.37 0.394
50 2.9<64.7 1.84 2.56 2.89 1.24 0.372
75 3.5<69.4 1.99 2.94 3.45 1.24 0.37
100 3.5<69.9 1.96 2.93 3.45 1.2 0.37

Table 1.2 Typical HID Lamps

Watts ANSI Ballast Type Bulb Lumens Design Factor

40 H43 B-17 or ED – 17 2250 0.8


100 H38 ED23 ½ 3200 0.8
175 H39 E-28 or BT-28 7200 0.8
250 H37 E-28 or BT-28 9800 0.8
400 H33 E-37 or BT-37 18200 0.75
1000 H36 BT-56 40000 0.8
70

Table 1.3 Aluminum Conductor Steel Reinforced (ACSR)

Nominal Number & Conductor


Sectional Area Tension
Sectional Weight DC
(mm) Load Ampacity
Area (kg/km) Resistance
(kg)
(mm) Aluminum Steel at 12/km
19 6 / 2.0 1 / 2.0 698 76.12 180 1.52
32 6 / 2.5 1 / 2.5 1400 128.6 230 0.899
58 6 / 3.5 1 / 3.5 1980 233.1 340 0.497
90 6 / 4.2 1 / 4.2 2770 335.5 530 0.345
95 6 / 4.5 7 / 4.5 3180 385.2 530 0.301
120 30 / 2.3 7 / 2.3 5550 573.7 600 0.233
160 30 / 2.6 7 / 2.6 6990 732.6 730 0.182
200 30 / 2.9 7 / 2.9 8620 911.7 780 0.147
240 30 / 3.2 7 / 3.2 10210 1110 900 0.12
330 26 / 4.0 7 / 3.1 10930 1320 1000 0.0888
410 26 / 4.5 7 / 3.5 13890 1673 1100 0.0702
520 54 / 3.5 7 / 3.5 15600 1969 1380 0.0559
610 54 / 3.8 7 / 3.8 18150 2320 1500 0.0474

STANDARD FUSE LINK AMPERE RATING

1, 2, 3, 6, 8, 10, 12, 15, 20, 25, 30, 40, 50, 60, 70, 80, 90, 100, 110, 125, 150,
175, 200, 225,250, 300, 350, 400, 500, 600, 700, 800, 900, 1000, 1200, 1600,
2000, 4000, 5000, 6000

Table 1.4 Roadway Classifications

Number of Vehicle Per Hours


Classification
(Maximum Night Hour, Both Direction)
Very Light Traffic Under 150
Light Traffic 150 – 500
Medium Traffic 500 – 1200
Heavy Traffic 1200 – 2400
Heavy Traffic 2400 – 4000
Heaviest Traffic Over 4000
71

SUMMARY OF FORMULAS

FOR THE AMPACITY OF THE WIRE

𝑀𝐷𝐾𝑉𝐴
𝐼=
𝑣
FOR THE SAG

𝑠2𝑤
𝑑=
8𝑡

FOR ILLUMINATION

𝐸×𝑊×𝑆
𝑓=
𝑐. 𝑢.× 𝑚. 𝑓.

FOR THE TOTAL MDKVA

𝑀𝐷𝐾𝑉𝐴𝑡 = 𝑀𝐷𝐾𝑉𝐴 + 𝑃𝐿

FOR THE SIZE OF THE TRANSFORMER

𝐷 = 𝑀𝐷𝐾𝑉𝐴𝑡 (125%)

FOR THE FUSE CUT-OUT

𝑟𝑎𝑡𝑒𝑑 𝐾𝑉𝐴
𝐼𝐿 =
𝑉𝑝

FOR THE TOTAL KVA IN THE FEEDER

ℎ𝑖𝑔ℎ𝑒𝑠𝑡 𝐾𝑉𝐴
𝐾𝑉𝐴𝑡 = 3 ( )
𝑓

FOR THE FEEDER LINE CURRENT

𝐾𝑉𝐴𝐿
𝐼𝐿 =
√3(𝑉𝑃 )
72

FOR THE LENGTH OF SPAN

8𝐷2
𝐿=𝑆+
3𝑆

FOR THE LINE LOSS

𝑃𝐿 = 𝐼 2 𝑅

FOR THE VOLTAGE DROP

𝑉𝑡 = 𝑉𝐷 − (𝑅𝐴𝐶 )(𝐿)

FOR THE VOLTAGE REGULATION

𝑉𝑡𝑛 − 𝑉𝑡𝑚
𝑉𝑅 =
𝑉𝑡𝑛
73

COMPUTATION

Transformer No. 01 (Tap on Pole No. 012)


Industrial #02 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (51.84 kVA / 240 V) = 216 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (216)2 (1.02 x 0.899) (2 x 0.050000061) = 4.278 kVA

Total MDKVA:

= 51.84 + 4.278 = 56.11 kVA

Size of Transformer:

= (56.11) (1.25) = 70.13 kVA

Use of 3 - 100 kVA 1Ø Transformer at Pole No. 012

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.93) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 3 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
74

Transformer No. 02 (Tap on Pole No. 013)


Industrial #03 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (56.16 kVA / 240 V) = 234 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (234)2 (1.02 x 0.497) (2 x 0.050000061) = 2.775 kVA

Total MDKVA:

= 56.16 + 2.775 = 58.93 kVA

Size of Transformer:

= (58.93) (1.25) = 70.13 kVA

Use of 3 - 100 kVA 1Ø Transformer at Pole No. 013

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 3 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
75

Transformer No. 03 (Tap on Pole No. 001)


B Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (37.44 kVA / 240 V) = 156 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (156)2 (1.02 x 1.52) (2 x 0.050000061) = 3.77 kVA

Total MDKVA:

= 37.44 + 3.77 = 41.21 kVA

Size of Transformer:

= (41.21) (1.25) = 51.51 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 001

V = 240 – (240) (0.0294) = 232.944

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84 (150%)

= 14.76 A

Use : 1 – 15 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
76

Transformer No. 04 (Tap on Pole No. 015)


B Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (56.16 kVA / 240 V) = 234 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (234)2 (1.02 x 0.497) (2 x 0.050000061) = 2.775 kVA

Total MDKVA:

= 56.16 + 2.775 = 58.93 kVA

Size of Transformer:

= (58.93) (1.25) = 73.66 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 015

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.5(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
77

Transformer No. 05 (Tap on Pole No. 014)


Industrial #04 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (64.8 kVA / 240 V) = 270 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (195)2 (1.02 x 0.497) (2 x 0.050000061) = 3.695 kVA

Total MDKVA:

= 64.8 + 3.695 = 68.49 kVA

Size of Transformer:

= (68.49) (1.25) = 85.61 kVA

Use of 3 - 100 kVA 1Ø Transformer at Pole No. 013

V = 240 – (240) (0.0293) = 232.944

% VR = [(240-232.944) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 3 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
78

Transformer No. 06 (Tap on Pole No. 016)


B Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (49.14 kVA / 240 V) = 204.75 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (195)2 (1.02 x 0.899) (2 x 0.050000061) = 3.844 kVA

Total MDKVA:

= 49.14 + 3.844 = 52.98 kVA

Size of Transformer:

= (52.98) (1.25) = 66.22 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 016

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
79

Transformer No. 07 (Tap on Pole No. 018)


B Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (53.82 kVA / 240 V) = 224.25 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (224.25)2 (1.02 x 0.899) (2 x 0.050000061) = 7.796 kVA

Total MDKVA:

= 53.82 + 7.796 = 61.61 kVA

Size of Transformer:

= (61.61) (1.25) = 77.01 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 018

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97 / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
80

Transformer No. 08 (Tap on Pole No. 017)


B Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (35.1 kVA / 240 V) = 146.25 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (146.25 )2 (1.02 x 1.52) (2 x 0.050000061) = 3.316 kVA

Total MDKVA:

= 35.1 + 3.316 = 38.41 kVA

Size of Transformer:

= (38.41) (1.25) = 48.01 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 018

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
81

Transformer No. 09 (Tap on Pole No. 011)


Commercial #34 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (50.4 kVA / 240 V) = 210 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (210)2 (1.02 x 0.899) (2 x 0.050000061) = 4.043 kVA

Total MDKVA:

= 50.4 + 4.043 = 54.44 kVA

Size of Transformer:

= (54.44) (1.25) = 68.05 kVA

Use of 3 - 75 kVA 1Ø Transformer at Pole No. 011

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
82

Transformer No. 10 (Tap on Pole No. 020)


B Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (56.16 kVA / 240 V) = 234 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (234)2 (1.02 x 0.497) (2 x 0.050000061) = 2.775 kVA

Total MDKVA:

= 56.16 + 2.775 = 58.93 kVA

Size of Transformer:

= (58.93) (1.25) = 73.66 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 020

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.944) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV =13.12(150%)= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
83

Transformer No. 11 (Tap on Pole No. 019)


Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (30.42 kVA / 240 V) = 126.75 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (126.75 )2 (1.02 x 1.52) (2 x 0.050000061) = 2.49 kVA

Total MDKVA:

= 30.42 + 2.49 = 32.91 kVA

Size of Transformer:

= (32.91) (1.25) = 41.13 kVA

Use of 1 - 50 kVA 1Ø Transformer at Pole No. 019

V = 240 – (240) (0.0256) = 232.86

% VR = [(240-232.86) / 240] x 100% = 2.56%

FOR 50 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 50 kVA / 7.62 kV = 6.56(150%)

= 9.84 A

Use : 1 – 15 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
84

Transformer No. 12 (Tap on Pole No. 022)


B Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (39.78 kVA / 240 V) = 165.75 A

ACSR Use 19 mm

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (165.75 )2 (1.02 x 1.52) (2 x 0.050000061) = 4.259 kVA

Total MDKVA:

= 39.78 + 4.259 = 44.03 kVA

Size of Transformer:

= (44.03) (1.25) = 55.03 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 022

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
85

Transformer No. 13 (Tap on Pole No. 021)


Commercial #33 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (14.4 kVA / 240 V) = 60 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (165.75 )2 (1.02 x 1.52) (2 x 0.050000061) = 0.558 kVA

Total MDKVA:

= 14.4 + 0.558 = 14.95 kVA

Size of Transformer:

= (14.95) (1.25) = 18.68 kVA

Use of 3 - 25 kVA 1Ø Transformer at Pole No. 021

V = 240 – (240) (0.0264) = 232.66

% VR = [(240-232.66) / 240] x 100% = 2.64%

FOR 25 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 25 kVA / 7.62 kV = 3.28(150%)

= 4.92 A

Use : 1 – 6 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
86

Transformer No. 14 (Tap on Pole No. 023)


B Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (51.48 kVA / 240 V) = 214.5 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (214.5 )2 (1.02 x 0.899) (2 x 0.050000061) = 4.219 kVA

Total MDKVA:

= 51.48 + 4.219 = 55.69 kVA

Size of Transformer:

= (55.69) (1.25) = 69.61 kVA

Use of 75 kVA 1Ø Transformer at Pole No. 023

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
87

Transformer No. 15 (Tap on Pole No. 024)


B Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (39.78 kVA / 240 V) = 165.75 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (165.75 )2 (1.02 x 1.52) (2 x 0.050000061) = 4.259 kVA

Total MDKVA:

= 39.78 + 4.259 = 44.03 kVA

Size of Transformer:

= (44.03) (1.25) = 55.03 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 024

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
88

Transformer No. 16 (Tap on Pole No. 027)


Commercial #30, 31, 32 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (68.85 kVA / 240 V) = 286.87 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (286.87 )2 (1.02 x 0.497) (2 x 0.050000061) = 4.17 kVA

Total MDKVA:

= 68.85 + 4.17 = 73.02 kVA

Size of Transformer:

= (73.02) (1.25) = 91.27 kVA

Use of 3 - 100 kVA 1Ø Transformer at Pole No. 027

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.93) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%) = 19.68 A

Use : 3 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
89

Transformer No. 17 (Tap on Pole No. 028)


Commercial #25, 27, 29 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (64.8 kVA / 240 V) = 270 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (270)2 (1.02 x 0.497) (2 x 0.050000061) = 3.695 kVA

Total MDKVA:

= 64.8 + 3.695 = 68.49 kVA

Size of Transformer:

= (68.49) (1.25) = 85.61 kVA

Use of 3 - 100 kVA 1Ø Transformer at Pole No. 028

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.93) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 3 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
90

Transformer No. 18 (Tap on Pole No. 029)


Commercial #20, 22, 24 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (70.01 kVA / 240 V) = 291.71 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (291.71 )2 (1.02 x 0.497) (2 x 0.050000061) = 4.313 kVA

Total MDKVA:

= 70.01 + 4.313 = 74.32 kVA

Size of Transformer:

= (74.32) (1.25) = 92.9 kVA

Use of 3 - 100 kVA 1Ø Transformer at Pole No. 029

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.93) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 3 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
91

Transformer No. 19 (Tap on Pole No. 030)


Commercial #12, 23 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (49.68 kVA / 240 V) = 207 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (207)2 (1.02 x 0.899) (2 x 0.050000061) = 3.929 kVA

Total MDKVA:

= 49.68 + 3.929 = 53.6 kVA

Size of Transformer:

= (53.6) (1.25) = 67 kVA

Use of 3 - 75 kVA 1Ø Transformer at Pole No. 030

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.94) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 3 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
92

Transformer No. 20 (Tap on Pole No. 031)


Commercial #28, 26 Load (80% pf, 90% DF)

20 CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (32.4 kVA / 240 V) = 135 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (135)2 (1.02 x 0.899) (2 x 0.050000061) = 2.825 kVA

Total MDKVA:

= 32.4 + 2.825 = 35.22 kVA

Size of Transformer:

= (35.22) (1.25) = 44.02 kVA

Use of 3 - 50 kVA 1Ø Transformer at Pole No. 031

V = 240 – (240) (0.0256) = 232.86

% VR = [(240-232.86) / 240] x 100% = 2.56%

FOR 50 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 50 kVA / 7.62 kV = 6.56(150%)

= 9.84 A

Use : 3 – 12 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
93

Transformer No. 21 (Tap on Pole No. 032)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (53.04 kVA / 240 V) = 221 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (221)2 (1.02 x 0.899) (2 x 0.050000061) = 4.478 kVA

Total MDKVA:

= 53.04 + 4.478 = 57.51 kVA

Size of Transformer:

= (57.51) (1.25) = 71.88 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 032

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
94

Transformer No. 22 (Tap on Pole No. 033)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (53.04 kVA / 240 V) = 221 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (221)2 (1.02 x 0.899) (2 x 0.050000061) = 4.478 kVA

Total MDKVA:

= 53.04 + 4.478 = 57.51 kVA

Size of Transformer:

= (57.51) (1.25) = 71.88 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 033

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
95

Transformer No. 23 (Tap on Pole No. 035)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (56.16 kVA / 240 V) = 234 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (221)2 (1.02 x 0.899) (2 x 0.050000061) = 2.775 kVA

Total MDKVA:

= 56.16 + 2.775 = 58.93 kVA

Size of Transformer:

= (58.93) (1.25) = 73.66 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 035

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
96

Transformer No. 24 (Tap on Pole No. 035)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (62.4 kVA / 240 V) = 260 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (260)2 (1.02 x 0.497) (2 x 0.050000061) = 3.426 kVA

Total MDKVA:

= 62.4 + 3.426 = 65.82 kVA

Size of Transformer:

= (65.82) (1.25) = 82.27 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 034

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
97

Transformer No. 25 (Tap on Pole No. 036)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (43.68 kVA / 240 V) = 182 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (182)2 (1.02 x 0.899) (2 x 0.050000061) = 3.037 kVA

Total MDKVA:

= 43.68 + 3.037 = 46.71 kVA

Size of Transformer:

= (46.71) (1.25) = 58.38 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 036

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
98

Transformer No. 26 (Tap on Pole No. 037)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (43.68 kVA / 240 V) = 182 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (182)2 (1.02 x 0.899) (2 x 0.050000061) = 3.037 kVA

Total MDKVA:

= 43.68 + 3.037 = 46.71 kVA

Size of Transformer:

= (46.71) (1.25) = 58.38 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 037

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
99

Transformer No. 27 (Tap on Pole No. 038)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (40.56 kVA / 240 V) = 169 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (169)2 (1.02 x 1.52) (2 x 0.050000061) = 4.428 kVA

Total MDKVA:

= 40.56 + 4.428 = 44.98 kVA

Size of Transformer:

= (44.98) (1.25) = 56.22 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 038

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
100

Transformer No. 28 (Tap on Pole No. 039)


A Residential Load (80% pf, 65% DF)

28 CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (53.04 kVA / 240 V) = 221 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (221)2 (1.02 x 0.899) (2 x 0.050000061) = 4.478 kVA

Total MDKVA:

= 53.04 + 4.478 = 57.51 kVA

Size of Transformer:

= (57.51) (1.25) = 71.88 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 039

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
101

Transformer No. 29 (Tap on Pole No. 041)


A Residential Load and Commercial #26 (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (61.88 kVA / 240 V) = 257.83 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (257.83)2 (1.02 x 0.497) (2 x 0.050000061) = 3.369 kVA

Total MDKVA:

= 61.88 + 3.369 = 65.24 kVA

Size of Transformer:

= (61.88) (1.25) = 81.55 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 041

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
102

Transformer No. 30 (Tap on Pole No. 040)


Commercial #1, 2 (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (20.88 kVA / 240 V) = 87 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (87)2 (1.02 x 1.52) (2 x 0.050000061) = 1.173 kVA

Total MDKVA:

= 20.88 + 1.173 = 22.05 kVA

Size of Transformer:

= (22.05) (1.25) = 27.56 kVA

Use of 3 – 37.5 kVA 1Ø Transformer at Pole No. 040

V = 240 – (240) (0.0262) = 233.71

% VR = [(240-233.71) / 240] x 100% = 2.62%

FOR 37.5 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 37.5kVA / 7.62 kV = 4.92(150%)

= 7.38 A

Use : 3 – 10 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
103

Transformer No. 31 (Tap on Pole No. 039)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (46.8 kVA / 240 V) = 195 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (195)2 (1.02 x 0.899) (2 x 0.050000061) = 3.486 kVA

Total MDKVA:

= 46.8 + 3.486 = 50.28 kVA

Size of Transformer:

= (50.28) (1.25) = 62.85 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 039

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
104

Transformer No. 32 (Tap on Pole No. 045)


Commercial #7, 9, 10 (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (57.942 kVA / 240 V) = 241.42 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (241.42 )2 (1.02 x 0.497) (2 x 0.050000061) = 2.954 kVA

Total MDKVA:

= 57.942 + 2.954 = 60.89 kVA

Size of Transformer:

= (60.89) (1.25) = 76.11 kVA

Use of 3 - 100 kVA 1Ø Transformer at Pole No. 027

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.93) / 240] x 100% = 2.93%

FOR 3 - 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 3 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
105

Transformer No. 33 (Tap on Pole No. 043)


Commercial #5, 8 (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (20.16 kVA / 240 V) = 84 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (84 )2 (1.02 x 1.52) (2 x 0.050000061) = 1.093 kVA

Total MDKVA:

= 20.16 + 1.093 = 21.25 kVA

Size of Transformer:

= (21.25) (1.25) = 26.56 kVA

Use of 3 – 37.5 kVA 1Ø Transformer at Pole No. 043

V = 240 – (240) (0.0262) = 233.71

% VR = [(240-233.71) / 240] x 100% = 2.62%

FOR 37.5 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 37.5kVA / 7.62 kV = 4.92(150%)

= 7.38 A

Use : 3 – 10 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
106

Transformer No. 34 (Tap on Pole No. 043)


Institutional Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (63.9 kVA / 240 V) = 266.25 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (266.25 )2 (1.02 x 0.497) (2 x 0.050000061) = 3.593 kVA

Total MDKVA:

= 63.9 + 3.593 = 67.49 kVA

Size of Transformer:

= (67.49) (1.25) = 84.36 kVA

Use of 3 - 100 kVA 1Ø Transformer at Pole No. 043

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.93) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 3 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
107

Transformer No. 35 (Tap on Pole No. 046)


Commercial #11, 13 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (23.22 kVA / 240 V) = 96.75 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (96.75 )2 (1.02 x 1.52) (2 x 0.050000061) = 1.451 kVA

Total MDKVA:

= 23.22 + 1.451 = 24.67 kVA

Size of Transformer:

= (24.67) (1.25) = 30.83 kVA

Use of 3 – 37.5 kVA 1Ø Transformer at Pole No. 046

V = 240 – (240) (0.0262) = 233.71

% VR = [(240-233.71) / 240] x 100% = 2.62%

FOR 37.5 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 37.5kVA / 7.62 kV = 4.92(150%)

= 7.38 A

Use : 3 – 10 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
108

Transformer No. 36 (Tap on Pole No. 048)


Commercial #14, 15 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (21.6 kVA / 240 V) = 90 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (90 )2 (1.02 x 1.52) (2 x 0.050000061) = 1.255 kVA

Total MDKVA:

= 21.6 + 1.255 = 22.85 kVA

Size of Transformer:

= (22.85) (1.25) = 28.56 kVA

Use of 3 – 37.5 kVA 1Ø Transformer at Pole No. 048

V = 240 – (240) (0.0262) = 233.71

% VR = [(240-233.71) / 240] x 100% = 2.62%

FOR 3 - 37.5 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 37.5kVA / 7.62 kV = 4.92(150%)

= 7.38 A

Use : 3 – 10 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
109

Transformer No. 37 (Tap on Pole No. 047)


Commercial #16, 17 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (34.2 kVA / 240 V) = 142.5 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (142.5 )2 (1.02 x 1.52) (2 x 0.050000061) = 3.148 kVA

Total MDKVA:

= 34.2 + 3.148 = 37.34 kVA

Size of Transformer:

= (37.34) (1.25) = 46.67 kVA

Use of 3 - 50 kVA 1Ø Transformer at Pole No. 047

V = 240 – (240) (0.0256) = 232.86

% VR = [(240-232.86) / 240] x 100% = 2.56%

FOR 50 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 50 kVA / 7.62 kV = 6.56(150%)

= 9.84 A

Use : 3 – 12 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance


110

from bushing.

Transformer No. 38 (Tap on Pole No. 050)


Commercial #21 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (47.88 kVA / 240 V) = 199.5 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (199.5)2 (1.02 x 0.899) (2 x 0.050000061) = 3.649 kVA

Total MDKVA:

= 47.88 + 3.649 = 51.52 kVA

Size of Transformer:

= (51.52) (1.25) = 64.4 kVA

Use of 3 - 75 kVA 1Ø Transformer at Pole No. 050

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 3 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
111

Transformer No. 39 (Tap on Pole No. 051)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (28.08 kVA / 240 V) = 117 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (117)2 (1.02 x 1.52) (2 x 0.050000061) = 2.122 kVA

Total MDKVA:

= 28.08 + 2.122 = 51.52 kVA

Size of Transformer:

= (51.52) (1.25) = 30.2 kVA

Use of 1 - 37.5 kVA 1Ø Transformer at Pole No. 040

V = 240 – (240) (0.0262) = 233.71

% VR = [(240-233.71) / 240] x 100% = 2.62%

FOR 37.5 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 37.5kVA / 7.62 kV = 4.92(150%)

= 7.38 A

Use : 1 – 10 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
112

Transformer No. 40 (Tap on Pole No. 049)


Commercial #18, 19 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (23.04 kVA / 240 V) = 96 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (96)2 (1.02 x 1.52) (2 x 0.050000061) = 1.428 kVA

Total MDKVA:

= 23.04 + 1.428 = 24.46 kVA

Size of Transformer:

= (24.46) (1.25) = 30.57 kVA

Use of 3 – 37.5 kVA 1Ø Transformer at Pole No. 049

V = 240 – (240) (0.0262) = 233.71

% VR = [(240-233.71) / 240] x 100% = 2.62%

FOR 37.5 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 37.5kVA / 7.62 kV = 4.92(150%)

= 7.38 A

Use : 3 – 10 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
113

Transformer No. 41 (Tap on Pole No. 053)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (24.96 kVA / 240 V) = 104 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (104)2 (1.02 x 1.52) (2 x 0.050000061) = 1.676 kVA

Total MDKVA:

= 24.96 + 1.676 = 26.63 kVA

Size of Transformer:

= (26.63) (1.25) = 33.28 kVA

Use of 1 – 37.5 kVA 1Ø Transformer at Pole No. 053

V = 240 – (240) (0.0262) = 233.71

% VR = [(240-233.71) / 240] x 100% = 2.62%

FOR 37.5 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 37.5kVA / 7.62 kV = 4.92(150%)

= 7.38 A

Use : 1 – 10 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
114

Transformer No. 42 (Tap on Pole No. 052)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (29.64 kVA / 240 V) = 123.5 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (123.5)2 (1.02 x 1.52) (2 x 0.050000061) = 2.364 kVA

Total MDKVA:

= 29.64 + 2.364 = 32 kVA

Size of Transformer:

= (32) (1.25) = 40 kVA

Use of 1 - 50 kVA 1Ø Transformer at Pole No. 052

V = 240 – (240) (0.0256) = 232.86

% VR = [(240-232.86) / 240] x 100% = 2.56%

FOR 50 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 50 kVA / 7.62 kV = 6.56(150%)

= 9.84 A

Use : 3 – 12 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
115

Transformer No. 43 (Tap on Pole No. 054)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (32.76 kVA / 240 V) = 136.5 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (136.5)2 (1.02 x 1.52) (2 x 0.050000061) = 2.888 kVA

Total MDKVA:

= 32.76 + 2.888 = 35.64 kVA

Size of Transformer:

= (35.64) (1.25) = 44.55 kVA

Use of 1 - 50 kVA 1Ø Transformer at Pole No. 054

V = 240 – (240) (0.0256) = 232.86

% VR = [(240-232.86) / 240] x 100% = 2.56%

FOR 50 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 50 kVA / 7.62 kV = 6.56(150%)

= 9.84 A

Use : 3 – 12 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
116

Transformer No. 44 (Tap on Pole No. 055)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (45.24 kVA / 240 V) = 188.5 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (188.5)2 (1.02 x 0.899) (2 x 0.050000061) = 3.258 kVA

Total MDKVA:

= 45.24 + 3.258 = 48.49 kVA

Size of Transformer:

= (48.49) (1.25) = 60.61 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 055

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
117

Transformer No. 45 (Tap on Pole No. 056)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (51.48 kVA / 240 V) = 214.5 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (188.5)2 (1.02 x 0.899) (2 x 0.050000061) = 4.219 kVA

Total MDKVA:

= 51.48 + 4.219 = 55.69 kVA

Size of Transformer:

= (48.49) (1.25) = 69.61 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 056

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
118

Transformer No. 46 (Tap on Pole No. 009-A)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (31.2 kVA / 240 V) = 130 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (130)2 (1.02 x 1.52) (2 x 0.050000061) = 2.62 kVA

Total MDKVA:

= 31.2 + 2.62 = 33.82 kVA

Size of Transformer:

= (33.82) (1.25) = 42.27 kVA

Use of 1 - 50 kVA 1Ø Transformer at Pole No. 009-A

V = 240 – (240) (0.0256) = 232.86

% VR = [(240-232.86) / 240] x 100% = 2.56%

FOR 50 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 50 kVA / 7.62 kV = 6.56(150%)

= 9.84 A

Use : 1 – 12 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
119

Transformer No. 47 (Tap on Pole No. 008)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (34.32 kVA / 240 V) = 143 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (143)2 (1.02 x 1.52) (2 x 0.050000061) = 3.17 kVA

Total MDKVA:

= 34.32 + 3.17 = 37.49 kVA

Size of Transformer:

= (37.49) (1.25) = 46.86 kVA

Use of 1 - 50 kVA 1Ø Transformer at Pole No. 008

V = 240 – (240) (0.0256) = 232.86

% VR = [(240-232.86) / 240] x 100% = 2.56%

FOR 50 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 50 kVA / 7.62 kV = 6.56(150%)

= 9.84 A

Use : 1 – 12 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
120

Transformer No. 48 (Tap on Pole No. 007)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (46.8 kVA / 240 V) = 195 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (195)2 (1.02 x 0.899) (2 x 0.050000061) = 3.486 kVA

Total MDKVA:

= 46.8 + 3.486 = 50.28 kVA

Size of Transformer:

= (50.28) (1.25) = 62.85 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 007

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
121

Transformer No. 49 (Tap on Pole No. 006)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (32.76 kVA / 240 V) = 136.5 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (136.5)2 (1.02 x 1.52) (2 x 0.050000061) = 2.888 kVA

Total MDKVA:

= 32.76 + 2.888 = 35.64 kVA

Size of Transformer:

= (35.64) (1.25) = 44.55 kVA

Use of 1 - 50 kVA 1Ø Transformer at Pole No. 006

V = 240 – (240) (0.0256) = 232.86

% VR = [(240-232.86) / 240] x 100% = 2.56%

FOR 50 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 50 kVA / 7.62 kV = 6.56(150%)

= 9.84 A

Use : 1 – 12 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
122

Transformer No. 50 (Tap on Pole No. 005)


C Residential & Institutional Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (56.16 kVA / 240 V) = 234 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (234)2 (1.02 x 0.497) (2 x 0.050000061) = 2.775 kVA

Total MDKVA:

= 56.16 + 2.775 = 58.93 kVA

Size of Transformer:

= (58.93) (1.25) = 73.66 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 005

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.93) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
123

Transformer No. 51 (Tap on Pole No. 004)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (46.8 kVA / 240 V) = 195 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (195)2 (1.02 x 0.899) (2 x 0.050000061) = 3.486 kVA

Total MDKVA:

= 46.8 + 3.486 = 50.28 kVA

Size of Transformer:

= (50.28) (1.25) = 62.85 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 004

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)

= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
124

Transformer No. 52 (Tap on Pole No. 010)


Commercial #35, 39 and Institutional Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (67.5 kVA / 240 V) = 281.25 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (281.25 )2 (1.02 x 0.497) (2 x 0.050000061) = 4 kVA

Total MDKVA:

= 67.5 + 4 = 71.5 kVA

Size of Transformer:

= (71.5) (1.25) = 89.37 kVA

Use of 3 - 100 kVA 1Ø Transformer at Pole No. 010

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.93) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 3 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
125

Transformer No. 53 (Tap on Pole No. 003)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (48.36 kVA / 240 V) = 201.5 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (201.5)2 (1.02 x 0.899) (2 x 0.050000061) = 3.723 kVA

Total MDKVA:

= 48.36 + 3.723 = 52.08 kVA

Size of Transformer:

= (52.08) (1.25) = 65.1 kVA

Use of 1 - 75 kVA 1Ø Transformer at Pole No. 003

V = 240 – (240) (0.0294) = 232.94

% VR = [(240-232.944) / 240] x 100% = 2.94%

FOR 75 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 75 kVA / 7.62 kV = 9.84(150%)


= 14.76 A

Use : 1 – 20 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
126

Transformer No. 54 (Tap on Pole No. 002)


C Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (65.52 kVA / 240 V) = 273 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (273)2 (1.02 x 0.497) (2 x 0.050000061) = 3.778 kVA

Total MDKVA:

= 65.52 + 3.778 = 69.29 kVA

Size of Transformer:

= (69.29) (1.25) = 86.61 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 027

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.93) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
127

Transformer No. 55 (Tap on Pole No. 025)


B Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (53.82 kVA / 240 V) = 224.25 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (224.25)2 (1.02 x 0.899) (2 x 0.050000061) = 4.611 kVA

Total MDKVA:

= 53.82 + 4.611 = 58.43 kVA

Size of Transformer:

= (58.43) (1.25) = 73.03 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 025

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.93) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
128

Transformer No. 56 (Tap on Pole No. 026)


Industrial #01 Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (70.65 kVA / 240 V) = 294.37 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (294.37)2 (1.02 x 0.497) (2 x 0.050000061) = 4.392 kVA

Total MDKVA:

= 70.65 + 4.392 = 75.04 kVA

Size of Transformer:

= (75.04) (1.25) = 93.8 kVA

Use of 3 - 100 kVA 1Ø Transformer at Pole No. 026

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.93) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 3 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance


129

from bushing.

Transformer No. 57 (Tap on Pole No. 033-B)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (53.04 kVA / 240 V) = 221 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (221)2 (1.02 x 0.899) (2 x 0.050000061) = 4.433 kVA

Total MDKVA:

= 53.04 + 4.433 = 57.47 kVA

Size of Transformer:

= (57.47) (1.25) = 71.83 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 033-B

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
130

Transformer No. 58 (Tap on Pole No. 035-B)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (24.96 kVA / 240 V) = 104 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (104)2 (1.02 x 1.52) (2 x 0.050000061) = 1.676 kVA

Total MDKVA:

= 24.96 + 1.676 = 26.63 kVA

Size of Transformer:

= (26.63) (1.25) = 33.28 kVA

Use of 1 – 37.5 kVA 1Ø Transformer at Pole No. 035-B

V = 240 – (240) (0.0262) = 233.71

% VR = [(240-233.71) / 240] x 100% = 2.62%

FOR 37.5 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 37.5kVA / 7.62 kV = 4.92(150%)

= 7.38 A

Use : 1 – 10 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
131

Transformer No. 59 (Tap on Pole No. 037-A)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (62.4 kVA / 240 V) = 260 A

Use 58 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (260)2 (1.02 x 0.497) (2 x 0.050000061) = 3.426 kVA

Total MDKVA:

= 62.4 + 3.426 = 65.82 kVA

Size of Transformer:

= (65.82) (1.25) = 82.27 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 037-A

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%)

= 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
132

Transformer No. 60 (Tap on Pole No. 038-B)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (49.92 kVA / 240 V) = 208 A

Use 32 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (208)2 (1.02 x 0.899) (2 x 0.050000061) = 6.707 kVA

Total MDKVA:

= 49.92 + 6.707 = 56.62 kVA

Size of Transformer:

= (56.62) (1.25) = 70.77 kVA

Use of 1 - 100 kVA 1Ø Transformer at Pole No. 038-B

V = 240 – (240) (0.0293) = 232.97

% VR = [(240-232.97) / 240] x 100% = 2.93%

FOR 100 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 100 kVA / 7.62 kV = 13.1(150%) = 19.68 A

Use : 1 – 25 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
133

Transformer No. 61 (Tap on Pole No. 039-C)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (24.96 kVA / 240 V) = 104 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (104)2 (1.02 x 1.52) (2 x 0.050000061) = 1.676 kVA

Total MDKVA:

= 24.96 + 1.676 = 26.63 kVA

Size of Transformer:

= (26.63) (1.25) = 33.28 kVA

Use of 1 – 37.5 kVA 1Ø Transformer at Pole No. 039-C

V = 240 – (240) (0.0262) = 233.71

% VR = [(240-233.71) / 240] x 100% = 2.62%

FOR 37.5 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 37.5kVA / 7.62 kV = 4.92(150%)

= 7.38 A

Use : 1 – 10 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
134

Transformer No. 62 (Tap on Pole No. 035-B)


A Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (31.2 kVA / 240 V) = 130 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (130)2 (1.02 x 1.52) (2 x 0.050000061) = 2.62 kVA

Total MDKVA:

= 31.2 + 2.62 = 33.82 kVA

Size of Transformer:

= (33.82) (42.27) = 33.28 kVA

Use of 1 - 50 kVA 1Ø Transformer at Pole No. 031

V = 240 – (240) (0.0256) = 232.86

% VR = [(240-232.86) / 240] x 100% = 2.56%

FOR 50 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 50 kVA / 7.62 kV = 6.56(150%)

= 9.84 A

Use : 1 – 12 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing.
135

Transformer No. 63 (Tap on Pole No. 042)


Commercial #4, 6 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (21.06 kVA / 240 V) = 87.75 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (87.75 )2 (1.02 x 1.52) (2 x 0.050000061) = 1.193 kVA

Total MDKVA:

= 21.06 + 1.193 = 22.25 kVA

Size of Transformer:

= (22.25) (1.25) = 27.81 kVA

Use of 3 – 37.5 kVA 1Ø Transformer at Pole No. 042

V = 240 – (240) (0.0262) = 233.71

% VR = [(240-233.71) / 240] x 100% = 2.62%

FOR 37.5 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 37.5kVA / 7.62 kV = 4.92(150%)

= 7.38 A

Use : 3 – 10 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing
136

Transformer No. 64 (Tap on Pole No. 009)


Commercial #36, 37, 38 Load (80% pf, 90% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (36.72 kVA / 240 V) = 153 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (153 )2 (1.02 x 1.52) (2 x 0.050000061) = 3.629 kVA

Total MDKVA:

= 36.72 + 3.629 = 40.34 kVA

Size of Transformer:

= (40.34) (1.25) = 50.42 kVA

Use of 1 - 50 kVA 1Ø Transformer at Pole No. 009

V = 240 – (240) (0.0256) = 232.86

% VR = [(240-232.86) / 240] x 100% = 2.56%

FOR 50 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 50 kVA / 7.62 kV = 6.56(150%)

= 9.84 A

Use : 3 – 12 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 3 – 10 kV lighting arrester, 127 mm distance

from bushing.
137

Transformer No. 65 (Tap on Pole No. 16 - A)


B Residential Load (80% pf, 65% DF)

CALCULATIONS

Ampacity of the Wire

I = (MDKVA / V) = (21.06 kVA / 240 V) = 87.75 A

Use 19 mm ACSR

For the Sag:

D = (𝑤𝑠 2 ) = [(76.12) (0.05)2 ] / [(8) (698)] = 0.00003408 km

For the length of the Span:

L = s + [8𝐷2 / 3S] = (0.05) + [(8) (0.00003408)2 / (3) (0.05)] = 0.050000061 km

For Line Loss (𝑷𝑳 ):

𝑃𝐿 = (87.75 )2 (1.02 x 1.52) (2 x 0.050000061) = 1.193 kVA

Total MDKVA:

= 21.06 + 1.193 = 22.25 kVA

Size of Transformer:

= (22.25) (1.25) = 27.81 kVA

Use of 1 – 37.5 kVA 1Ø Transformer at Pole No. 16 - A

V = 240 – (240) (0.0262) = 233.71

% VR = [(240-233.71) / 240] x 100% = 2.62%

FOR 37.5 KVA 1Ø TRANSFORMER

Primary Voltage : 13.2 / 7.62 kV

Secondary Voltage : 120 / 240 V

For fuse cut-out : 𝐼𝑝 = 37.5kVA / 7.62 kV = 4.92(150%)

= 7.38 A

Use : 1 – 10 A fuse link @ 100 A fuse cut out

RATING OF LIGHTING ARRESTER

𝐸𝐿𝐴 : 𝑉𝑝 /√3 = 13.2 𝑘𝑉𝐴/√3 = 7.621 𝑘𝑉

Use : 1 – 10 kV lighting arrester, 127 mm distance

from bushing
138

A. PERSONAL INFORMATION

NAME : CHRISTOPHER V. CONSULTA

ADDRESS : P-6 SANTOLAN ST. MOTHERLODE, JOSE


PANGANIBAN, CAMARINES NORTE
DATE OF BIRTH : JULY 6, 1983
AGE : 33
PLACE OF BIRTH : DAET, CAMARINES NORTE
E-MAIL ADDRESS : pedrolaonglaan@gmail.com
CIVIL STATUS : SINGLE
CITIZENSHIP : FILIPINO
PARENTS
FATHER : ORLANDO P. CONSULTA
MOTHER : VIRGINIA P. CONSULTA

B. EDUCATIONAL ATTAINMENT

ELEMENTARY : JOSE PANGANIBAN ELEMENTARY


SCHOOL
SY: 1990 - 1996
SECONDARY : JOSE PANGANIBAN NATIONAL HIGH
SCHOOL
SY: 1996-2000
TERTIARY : CAMARINES NORTE STATE COLLEGE
F. PIMENTEL AVE. DAET, CAM. NORTE
SY: 2012 – 2017

C. ELIGIBILITY

1. REGISTERED MASTER ELECTRICIAN


September 4, 2016
139

A. PERSONAL INFORMATION

NAME : VER II G. BALANTA

ADDRESS : P3 – BAGONGBAYAN, JOSE PANGANIBAN,


CAMARINES NORTE
DATE OF BIRTH : MAY 4, 1995
AGE : 21
PLACE OF BIRTH : JOSE PANGANIBAN, CAMARINES NORTE
E-MAIL ADDRESS : verbalanta04@gmail.com
CIVIL STATUS : SINGLE
CITIZENSHIP : FILIPINO
PARENTS
FATHER : SEVERO S. BALANTA
MOTHER : GINA G. BALANTA

A. EDUCATIONAL ATTAINMENT

ELEMENTARY : SAN MAURICIO ELEMENTARY SCHOOL


SY: 2003 - 2008
SECONDARY : THE SISTERS OF MARY SCHOOL
SY: 2008 - 2012
TERTIARY : CAMARINES NORTE STATE COLLEGE
F. PIMENTEL AVE. DAET, CAM 2. NORTE
SY: 2012 – 2017
A. ELIGIBILITY

1. REGISTERED MASTER ELECTRICIAN


September 4, 2016
140

A. PERSONAL INFORMATION

NAME : JOHN NOEL T. BRAVO


ADDRESS : P-4 PARANG, JOSE PANGANIBAN,
CAMARINES NORTE
DATE OF BIRTH : MAY 16, 1995
AGE : 21
PLACE OF BIRTH : P-1 PLARIDEL, JOSE PANGANIBAN
CAMARINES NORTE
E-MAIL ADDRESS : w3llknown01@gmail.com
CIVIL STATUS : SINGLE
CITIZENSHIP : FILIPINO
PARENTS
FATHER : NOEL A. BRAVO
MOTHER : NILDA T. BRAVO

A. EDUCATIONAL ATTAINMENT

ELEMENTARY : JOSE PANGANIBAN ELEMENTARY


SCHOOL
SY: 2003 - 2008
SECONDARY : JOSE PANGANIBAN NATIONAL HIGH
SCHOOL
SY: 2008-2012
TERTIARY : CAMARINES NORTE STATE COLLEGE
F. PIMENTEL AVE. DAET, CAM. NORTE
SY: 2012 – 2017
C. ELIGIBILITY

1. REGISTERED MASTER ELECTRICIAN


September 4, 2016

Potrebbero piacerti anche