Sei sulla pagina 1di 14

TEMP: CAL

REV.: 0

ROLTA INDIA LIMITED TITLE :


ROLTA TOWER 'B',
ROLTA TECHNOLOGY PARK,
MIDC – MAROL , ANDHERI (EAST),
LIGHTING CALCULATIONS
MUMBAI – 400 093

ENGINEERED ROLTA INDIA LIMITED


BY EDS : Engineering Design Services

CLIENT INDIAN OIL TANKING LIMITED

PROJECT OIL TERMINAL DETAIL ENGINEERING


LOCATION: MUMBAI, INDIA
NUMBER OF SHEETS OF THIS DOCUMENT

ROLTA PROJECT NUMBER ENG – 1

DOCUMENT NUMBER REV DATE

C - E - 0 0 3 - - 0 0 3 0 1 2008

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 1 of 14
TEMP: CAL
REV.: 0

ROLTA INDIA LIMITED TITLE :


ROLTA TOWER 'B',
ROLTA TECHNOLOGY PARK,
MIDC – MAROL , ANDHERI (EAST),
LIGHTING CALCULATIONS
MUMBAI – 400 093

Document Number C - E - 0 0 3 - -

REVISION HISTORY
REV DATE DESCRIPTION PREPARED CHECKED APPROVED

0 3/1/2008 LIGHTING CALCULATIONS SM/TB/VK/MS JRT VKS/RA

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 2 of 14
TEMP: CAL
REV.: 0

ROLTA INDIA LIMITED REPORT FOR : Document no:


ROLTA TOWER 'B', C-E-003
ROLTA TECHNOLOGY PARK, Rev no:
LIGHTING CALCULATIONS
MIDC – MAROL , ANDHERI (EAST), 0
MUMBAI – 400 093

CONTENTS

Cover page

Index

1.0 Scope & purpose

2.0 Design inputs

3.0 Assumptions

4.0 Methodology

5.0 Calculations

6.0 Results

7.0 References

8.0 Attachments

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 3 of 14
TEMP: CAL
REV.: 0

ROLTA INDIA LIMITED REPORT FOR : Document no:


ROLTA TOWER 'B', C-E-003
ROLTA TECHNOLOGY PARK, Rev no:
LIGHTING CALCULATIONS
MIDC – MAROL , ANDHERI (EAST), 0
MUMBAI – 400 093

SCOPE & PURPOSE:-

The calculations are done for the following purposes :

The purpose of this calculation is to determine the proper number of


lighting fixtures for the required lux level.Yhe calculations have been done using
CG Lux lighting software developed by Crompton Greaves Ltd.

PRESCRIBED LUX LEVELS:-

Average Illumination level


SL NO. Area
(Lux)

1 Switchgear Room 200


2 Control Room/DAS Room 450
3 Control Equipment Room 300
4 Pump House 150
5 Staircase ,Corridor,Toilets etc 70
6 Outdoor Area Street lighting 20
7 Cable Cellar 70

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 4 of 14
TEMP: CAL
REV.: 0

ROLTA INDIA LIMITED REPORT FOR : Document no:


ROLTA TOWER 'B', C-E-003
ROLTA TECHNOLOGY PARK, Rev no:
LIGHTING CALCULATIONS
MIDC – MAROL , ANDHERI (EAST), 0
MUMBAI – 400 093

Design Inputs :

Area Dimensions (m)


Name of Area
Sr. No. Length Width Height
1 Canteen Area 10.33 7.51 3.5
2 Kitchen 7.84 2.54 3.5
3 Wash Area 2.54 1.66 3.5
4 Worker's Room 2.86 2.54 3.5
5 Store Room 6.11 2.95 3.5
6 Passage 14 1.5 3.5
7 W.C. & Bath (3nos) 1.2 1 3.5
Office Building
8 Store 4.86 2.3 3.35
9 Pantry 4.27 2.98 3.35
10 Conference Room 6 3 3.35
11 Junior Engineer 2.98 3.1 3.35
12 Library 5 3 3.35
13 Purchase Office 2.98 2.82 3.35
14 UPS 2.98 2 3.35
15 Passage 14.3 1.5 3.35
16 Corridor 9.8 2.5 3.35
17 Passage 10.61 1.2 3.35
18 Site Engineer 3 1.6 3.35
19 Senior Engg 3 3.6 3.35
20 Project manager 3 3.5 3.35
21 Chief Engg 3 4 3.35
22 Reception 4.44 3.31 3.35
23 Chemical Staff 3.8 2.9 3.35
24 Mechanical Staff 3.8 2.9 3.35
25 Civil Staff 4.38 2.9 3.35
26 Utility 2.9 1.3 3.35
27 Passage 21.04 1.2 3.35
28 Ladies Toilet 3.6 1.2 3.35
29 Gents Toilet 3.6 1.2 3.35
30 Steps 3.1 1.5 3.35
31 W.C. & bath (6 nos) 1.5 1.2 3.35
A Block
32 UPS 2.8 2 3.35
33 Conference Room 5.5 2.8 3.35
34 Cabin 1 5.3 2.8 3.35
35 Cabin 2 4.2 3.1 3.35
36 Cabin 3 4 2.8 3.35
37 Cabin 4 3.3 3.1 3.35
38 Pantry 3.1 2 3.35
39 Utility Block 3.1 1.2 3.35
40 Reception 3.3 3.1 3.35
41 Steps 3.1 1.5 3.35
42 Passage 21.1 1.5 3.35
43 Gents Toilet 3.1 2.4 3.35
44 Ladies Toilet 3.1 2 3.35
45 W.C. (5nos) 1.5 1.2 3.35
Security Cabin
46 Security Cabin 3.46 3.28 3
47 Changing Room 3.28 1.86 3
48 Tankfarm Area (Alt 1) 30
48 Tankfarm Area (Alt 2) 30

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 5 of 14
TEMP: CAL
REV.: 0

ROLTA INDIA LIMITED REPORT FOR : Document no:


ROLTA TOWER 'B', C-E-003
ROLTA TECHNOLOGY PARK, Rev no:
LIGHTING CALCULATIONS
MIDC – MAROL , ANDHERI (EAST), 0
MUMBAI – 400 093

ASSUMPTIONS :

For Indoor lighting:-

Work Plane height = 0.80 m


Ceiling Reflectance = 0.5 m
Wall Reflectance = 0.5 m
Floor Reflectance = 0.1 m
Maintenance Factor = 0.7

For Outdoor lighting:-

Maintenance Factor = 0.6

Note- The lamps are mounted 20m from the finish floor level on the tank

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 6 of 14
TEMP: CAL
REV.: 0

ROLTA INDIA LIMITED REPORT FOR : Document no:


ROLTA TOWER 'B', C-E-003
ROLTA TECHNOLOGY PARK,
LIGHTING CALCULATIONS
Rev no:
MIDC – MAROL , ANDHERI (EAST), 0
MUMBAI – 400 093

METHODOLOGY :

Lighting Calculations

Step 1: Understand the utilisation factor table that is


available on most fittings:

Step 2: Calculate Room Index (K)


Room Index:-
The room index is a number that describes
the ratios of the rooms length,width and
height

Formula :
K=LxW
= Hm ( L + W )

Where :
L = Room Length
W = Room Width
Hm = Mounting Height of Fitting (from
working plane)
Work Plane = Desk or Bench Height
The result of this calculation will be a
number usually between 0.75 and 5.

Note :-This formula for K is only valid when


room length is less than 4 times the width or
when the valve is greater than 0.75

Step 3: Using the room index and reflectance


valves in the utilisation factor table

For the horizontal row select the reflectance


that best describes the room
For the vertical column select the room
index valve K as calculated above.
The utilisation factor for this fitting in this
room is where the row and column intersect

Step 4: To calculate the number of fittings required


use the following formula:

N=ExA
= F x uF x LLF

Where:
N = Number of Fittings
E = Lux level required on working plane

A = Area of Room (L x W )
F = Total Flux (Lumens) from all the lamps
in one Fitting

UF = Utilisation Factor from the table for the


fittings to be used
LLF = Light Loss Factor. This takes account
of the depreciation over time of lamp output
and dirt acculation on the fitting and walls of
the building

Step 5: Space the number of fittings uniformly


around thr room drawing and check the
SHK nominal for trh fitting has not been
exceeded

Step 6:
Work out the number of fittings required in
each axis of the room

Number in Length = Sqrt( Total x L/W )


Number in Width = Sqrt( Total x W/L)

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 7 of 14
TEMP: CAL
REV.: 0

ROLTA INDIA LIMITED REPORT FOR : Document no:


ROLTA TOWER 'B', C-E-003
ROLTA TECHNOLOGY PARK,
LIGHTING CALCULATIONS
Rev no:
MIDC – MAROL , ANDHERI (EAST), 0
MUMBAI – 400 093

CALCULATIONS :

Branch Ref. : Mumbai


LAB Design for : ROLTA
Lighting Division Ref no. : W/191/12/07
Kanjurmarg (East) Designed By : SPJ
Mumbai - 400042 Date : 26/12/2007

Su m m ary Sh eet

Area Dimensions (m) No. of No. of Lamp Lamp Lux


Nam e o f Area Type of Luminaire
Sr. No . Length Width Height Luminaires Lamps Type Wattage Level
Can teen
1 Canteen Area 10.33 7.51 3.5 CSBW1124HSB 8 16 FTL 36 W 200
2 Kitchen 7.84 2.54 3.5 IDJ1124HSB 7 14 FTL 36 W 300
3 Wash Area 2.54 1.66 3.5 IDJ1124HSB 2 4 FTL 36 W 200
4 Worker's Room 2.86 2.54 3.5 IGP1424HSB 2 4 FTL 36 W 200
5 Store Room 6.11 2.95 3.5 IGP1424HSB 3 6 FTL 36 W 200
6 Passage 14 1.5 3.5 IGP1414HSB 6 6 FTL 36 W 100
7 W.C. & Bath (3nos) 1.2 1 3.5 TLE211 3 6 CFL 11 W 100
Office B u ild in g
8 Store 4.86 2.3 3.35 IGP1424HSB 2 4 FTL 36 W 200
9 Pantry 4.27 2.98 3.35 CSBW1124HSB 2 4 FTL 36 W 200
10 Conference Room 6 3 3.35 CSBW1124HSB 8 16 FTL 36 W 500
11 Junior Engineer 2.98 3.1 3.35 CSBW1124HSB 4 8 FTL 36 W 300
12 Library 5 3 3.35 CSBW1124HSB 5 10 FTL 36 W 300
13 Purchase Office 2.98 2.82 3.35 CSBW1124HSB 3 6 FTL 36 W 300
14 UPS 2.98 2 3.35 CSBW1124HSB 4 8 FTL 36 W 300
15 Passage 14.3 1.5 3.35 IGP1414HSB 6 6 FTL 36 W 100
16 Corridor 9.8 2.5 3.35 IGP1414HSB 5 5 FTL 36 W 100
17 Passage 10.61 1.2 3.35 IGP1414HSB 4 4 FTL 36 W 100
18 Site Engineer 3 1.6 3.35 CSBW1124HSB 2 4 FTL 36 W 300
19 Senior Engg 3 3.6 3.35 CSBW1124HSB 4 8 FTL 36 W 300
20 Project manager 3 3.5 3.35 CSBW1124HSB 4 8 FTL 36 W 300
21 Chief Engg 3 4 3.35 CSBW1124HSB 4 8 FTL 36 W 300
22 Reception 4.44 3.31 3.35 CSBW1124HSB 6 12 FTL 36 W 300
23 Chemical Staff 3.8 2.9 3.35 CSBW1124HSB 4 8 FTL 36 W 300
24 Mechanical Staff 3.8 2.9 3.35 CSBW1124HSB 4 8 FTL 36 W 300
25 Civil Staff 4.38 2.9 3.35 CSBW1124HSB 6 12 FTL 36 W 300
26 Utility 2.9 1.3 3.35 CSBW1124HSB 2 4 FTL 36 W 300
27 Passage 21.04 1.2 3.35 IGP1414HSB 8 8 FTL 36 W 100
28 Ladies Toilet 3.6 1.2 3.35 IGP1414HSB 2 2 FTL 36 W 100
29 Gents Toilet 3.6 1.2 3.35 IGP1414HSB 2 2 FTL 36 W 100
30 Steps 3.1 1.5 3.35 IGP1414HSB 2 2 FTL 36 W 100
31 W.C. & bath (6 nos) 1.5 1.2 3.35 TLE211 1x6 2x6 CFL 11 W 100
A B lo ck
32 UPS 2.8 2 3.35 CSBW1124HSB 2 4 FTL 36 W 300
33 Conference Room 5.5 2.8 3.35 CSBW1124HSB 6 12 FTL 36 W 300
34 Cabin 1 5.3 2.8 3.35 CSBW1124HSB 6 12 FTL 36 W 300
35 Cabin 2 4.2 3.1 3.35 CSBW1124HSB 4 8 FTL 36 W 300
36 Cabin 3 4 2.8 3.35 CSBW1124HSB 4 8 FTL 36 W 300
37 Cabin 4 3.3 3.1 3.35 CSBW1124HSB 4 8 FTL 36 W 300
38 Pantry 3.1 2 3.35 CSBW1124HSB 2 4 FTL 36 W 200
39 Utility Block 3.1 1.2 3.35 CSBW1124HSB 2 4 FTL 36 W 300
40 Reception 3.3 3.1 3.35 CSBW1124HSB 4 8 FTL 36 W 300
41 Steps 3.1 1.5 3.35 IGP1414HSB 2 2 FTL 36 W 100
42 Passage 21.1 1.5 3.35 IGP1414HSB 9 9 FTL 36 W 100
43 Gents Toilet 3.1 2.4 3.35 IGP1414HSB 2 2 FTL 36 W 100
44 Ladies Toilet 3.1 2 3.35 IGP1414HSB 2 2 FTL 36 W 100
45 W.C. (5nos) 1.5 1.2 3.35 TLE211 1x6 2x6 CFL 11 W 100
Secu rity Cab in
46 Security Cabin 3.46 3.28 3 IGP1424HSB 2 4 FTL 36 W 200
47 Changing Room 3.28 1.86 3 IGP1424HSB 2 4 FTL 36 W 200
48 Tankfarm Area (Alt 1) 30 FAI40H 79 79 HPSV 400 W 20
48 Tankfarm Area (Alt 2) 30 FAI40H 79 79 HPSV 400 W 20

PROJECT SUMMARY -AL T 1 PROJECT SUMMARY -AL T 2


Total
Type of Luminaire Type of Luminaire
Sr. No . No. of Sr. No .
1 TLE211 15 1 TLE211
2 CSBW1124HSB 104 2 CSBW1124HSB
3 IDJ1124HSB 9 3 IDJ1124HSB
4 IGP1414HSB 50 4 IGP1414HSB
5 IGP1424HSB 11 5 IGP1424HSB
6 FAD1314 79 6 FAI40H

No te : We h ave n o t co n sid ered an y kin d o f o b stru ctio n w h ile d esig n .

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 8 of 14
TEMP: CAL
REV.: 0

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 9 of 14
TEMP: CAL
REV.: 0

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 10 of 14
TEMP: CAL
REV.: 0

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 11 of 14
TEMP: CAL
REV.: 0

ROLTA INDIA LIMITED REPORT FOR : Document no:


ROLTA TOWER 'B', C-E-003
ROLTA TECHNOLOGY PARK, Rev no:
LIGHTING CALCULATIONS
MIDC – MAROL , ANDHERI (EAST), 0
MUMBAI – 400 093

RESULTS :

Type of Mounting No. of No. of Lamp Lamp Lux


Sr. No. Nam e of Area
Luminaire Type Luminaires Lamps Type Wattage Level
1 Canteen Area CSBW1124HSB Surface 8 16 FTL 36 W 200
2 Kitchen IDJ1124HSB Surface 7 14 FTL 36 W 300
3 Wash Area IDJ1124HSB Surface 2 4 FTL 36 W 200
4 Worker's Room IGP1424HSB Surface 2 4 FTL 36 W 200
5 Store Room IGP1424HSB Surface 3 6 FTL 36 W 200
6 Passage IGP1414HSB Surface 6 6 FTL 36 W 100
7 W.C. & Bath (3nos) TLE211 Surface 3 6 CFL 11 W 100
Office Building
8 Store IGP1424HSB Surface 2 4 FTL 36 W 200
9 Pantry CSBW1124HSB Surface 2 4 FTL 36 W 200
10 Conference Room CSBW1124HSB Surface 8 16 FTL 36 W 500
11 Junior Engineer CSBW1124HSB Surface 4 8 FTL 36 W 300
12 Library CSBW1124HSB Surface 5 10 FTL 36 W 300
13 Purchase Office CSBW1124HSB Surface 3 6 FTL 36 W 300
14 UPS CSBW1124HSB Surface 4 8 FTL 36 W 300
15 Passage IGP1414HSB Surface 6 6 FTL 36 W 100
16 Corridor IGP1414HSB Surface 5 5 FTL 36 W 100
17 Passage IGP1414HSB Surface 4 4 FTL 36 W 100
18 Site Engineer CSBW1124HSB Surface 2 4 FTL 36 W 300
19 Senior Engg CSBW1124HSB Surface 4 8 FTL 36 W 300
20 Project manager CSBW1124HSB Surface 4 8 FTL 36 W 300
21 Chief Engg CSBW1124HSB Surface 4 8 FTL 36 W 300
22 Reception CSBW1124HSB Surface 6 12 FTL 36 W 300
23 Chemical Staff CSBW1124HSB Surface 4 8 FTL 36 W 300
24 Mechanical Staff CSBW1124HSB Surface 4 8 FTL 36 W 300
25 Civil Staff CSBW1124HSB Surface 6 12 FTL 36 W 300
26 Utility CSBW1124HSB Surface 2 4 FTL 36 W 300
27 Passage IGP1414HSB Surface 8 8 FTL 36 W 100
28 Ladies Toilet IGP1414HSB Surface 2 2 FTL 36 W 100
29 Gents Toilet IGP1414HSB Surface 2 2 FTL 36 W 100
30 Steps IGP1414HSB Surface 2 2 FTL 36 W 100
31 W.C. & bath (6 nos) TLE211 Surface 1x6 2x6 CFL 11 W 100
A Block
32 UPS CSBW1124HSB Surface 2 4 FTL 36 W 300
33 Conference Room CSBW1124HSB Surface 6 12 FTL 36 W 300
34 Cabin 1 CSBW1124HSB Surface 6 12 FTL 36 W 300
35 Cabin 2 CSBW1124HSB Surface 4 8 FTL 36 W 300
36 Cabin 3 CSBW1124HSB Surface 4 8 FTL 36 W 300
37 Cabin 4 CSBW1124HSB Surface 4 8 FTL 36 W 300
38 Pantry CSBW1124HSB Surface 2 4 FTL 36 W 200
39 Utility Block CSBW1124HSB Surface 2 4 FTL 36 W 300
40 Reception CSBW1124HSB Surface 4 8 FTL 36 W 300
41 Steps IGP1414HSB Surface 2 2 FTL 36 W 100
42 Passage IGP1414HSB Surface 9 9 FTL 36 W 100
43 Gents Toilet IGP1414HSB Surface 2 2 FTL 36 W 100
44 Ladies Toilet IGP1414HSB Surface 2 2 FTL 36 W 100
45 W.C. (5nos) TLE211 Surface 1x6 2x6 CFL 11 W 100
Security Cabin
46 Security Cabin IGP1424HSB Surface 2 4 FTL 36 W 200
47 Changing Room IGP1424HSB Surface 2 4 FTL 36 W 200
48 Tankfarm Area (Alt 1) FAI40H Highmast 79 79 HPSV 400 W 20
48 Tankfarm Area (Alt 2) FAI40H Highmast 79 79 HPSV 400 W 20

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 12 of 14
TEMP: CAL
REV.: 0

ROLTA INDIA LIMITED REPORT FOR : Document no:


ROLTA TOWER 'B', C-E-003
ROLTA TECHNOLOGY PARK, Rev no:
LIGHTING CALCULATIONS
MIDC – MAROL , ANDHERI (EAST), 0
MUMBAI – 400 093

REFERENCES :

1) Crompton Greaves - CG Lux Software

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 13 of 14
TEMP: CAL
REV.: 0

ROLTA INDIA LIMITED REPORT FOR : Document no:


ROLTA TOWER 'B', C-E-003
ROLTA TECHNOLOGY PARK, Rev no:
LIGHTING CALCULATIONS
MIDC – MAROL , ANDHERI (EAST), 0
MUMBAI – 400 093

Attachments

Enclousor (1) TANKFARM AREA

a) Layout map
b) Out door Luminaire Location

Enclousor (2) CANTEEN AREA

a) Project Data Sheet


b) Iso-Lux Diagram
c) IIIuminance Tabulation
d) Installation Dta
e) Project layout

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED
and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved.

Page 14 of 14

Potrebbero piacerti anche