Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or
operating the flame detection system. Any
deviation from the recommendations in this
manual may impair system performance
and compromise safety.
ATTENTION
The X3301 includes the Automatic o i ®
(Optical Integrity) feature — a calibrated
performance test that is automatically
performed once per minute to verify A tri-color LED on the detector faceplate indicates
complete detector operation capabilities. normal condition and notifies personnel of fire
Testing with an external test lamp is not alarm or fault conditions.
approved or required.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
DESCRIPTION
The X3301 housing is available in copper-free
The X3301 is a multispectrum infrared (IR) flame aluminum or stainless steel, with NEMA/Type 4X
detector. It provides unsurpassed detection and IP66/IP67 rating.
of fires from light to heavy hydrocarbon fuels
combined with the highest degree of false alarm OUTPUTS
rejection. The detector has Division and Zone
explosion-proof ratings and is suitable for use in Relays
indoor and outdoor applications. The standard detector is furnished with fire, fault
and auxiliary relays. All three relays are rated 5
The X3301 contains three IR sensors with their
amperes at 30 Vdc.
associated signal processing circuitry. The
standard output configuration includes fire, fault The Fire Alarm relay has redundant terminals
and auxiliary relays. Output options include: and normally open / normally closed contacts,
normally de-energized operation, and latching or
–– 0 to 20 mA output (in addition to the three non-latching operation.
relays)
The Fault relay has redundant terminals and
–– Pulse output for compatibility with existing
normally open contacts, normally energized
Detector Electronics Corporation (Det-Tronics)
operation, and latching or non-latching operation.
controller based systems (with fire and fault
relays) The Auxiliary relay has normally open /
–– Eagle Quantum Premier®
(EQP) compatible normally closed contacts, and is configurable
model (no analog or relay outputs) for energized or de-energized operation, and
latching or non-latching operation to perform as
–– HART communication a secondary relay for fire alarm or fault. All relay
functions can be configured by using the latest
version of Inspector Monitor.
1.1 3 95-8704
GENERAL APPLICATION Non-Carbon Fires
INFORMATION The X3301 is a multiple spectrum IR device
with detection limited to carbonaceous fuels.
RESPONSE CHARACTERISTICS It should not be used to detect fires from fuels
Response is dependent on the detector's that do not contain carbon, such as hydrogen,
sensitivity setting, distance, type of fuel, sulfur, and burning metals.
temperature of the fuel, and time required for
the fire to come to equilibrium. As with all fire
tests, results must be interpreted according to IMPORTANT SAFETY NOTES
an individual application.
See Appendix A for third-party approved fire test WARNING
results. Additional fire test results are available Do not open the detector assembly in a
from Det-Tronics. hazardous area when power is applied.
The detector contains limited serviceable
IMPORTANT APPLICATION CONSIDERATIONS components and should never be opened.
Doing so could disturb critical optical
In applying any type of sensing device as
alignment and calibration parameters,
a fire detector, it is important to know of any
possibly causing serious damage.
conditions that can prevent the device from
responding to fire, and also to know what other
sources besides fire can cause the device to CAUTION
respond. The wiring procedures in this manual are
intended to ensure proper functioning of the
Welding device under normal conditions. However,
It is recommended that the system be because of the many variations in wiring
bypassed during welding operations in codes and regulations, total compliance to
situations where the possibility of a false these ordinances cannot be guaranteed.
alarm cannot be tolerated. Gas welding Be certain that all wiring complies with
mandates system bypass, since the gas torch the NEC as well as all local ordinances.
is an actual fire. Arc welding rods can contain If in doubt, consult the authority having
organic binder materials in the flux that burn jurisdiction before wiring the system.
during the welding operation and are detectable Installation must be done by a properly
by the X3301. Welding rods with clay binders trained person.
do not burn and will not be detected by the
X3301. However, system bypass is always
recommended, since the material being welded CAUTION
may be contaminated with organic substances To prevent unwanted actuation or alarm,
(paint, oil, etc.) that will burn and possibly cause extinguishing devices must be disabled
the X3301 to alarm. prior to per forming system tests or
maintenance.
Due to the possibility of an alarm condition,
arc welding should not be performed within
40 feet (12.2 m) of the detector configured CAUTION
to very high sensitivity, within 10 feet (3.0 m) The multispectrum IR flame detectors are
at medium sensitivity, within 5 feet (1.5 m) at to be installed in places where the risk of
T-Low sensitivity, or at Low sensitivity. mechanical damage is low.
1.1 4 95-8704
INSTALLATION • Dense fog, rain or ice can absorb IR radiation
and reduce the sensitivity of the detector. To
NOTE ensure optimum performance, be certain that the
The recommended lubricant for threads internal optical heater is enabled on detectors
and O-rings is a silicone free grease (p/n that are used in applications where snow, ice,
005003-001) available from Det-Tronics. and condensation are likely to occur.
Under no circumstances should a lubricant • Although IR detectors are less affected by
containing silicone be used. smoke than other detectors, the X3301 should
not be placed where rising combustion products
can obscure its vision. If smoke is expected
DETECTOR POSITIONING
before fire, smoke or other alternative detectors
Detectors should be positioned to provide should be used in conjunction with the X3301.
the best unobstructed view of the area to be For indoor applications, if dense smoke is
protected. The following factors should also be expected to accumulate at the onset of a fire,
taken into consideration: install the detector on a side wall at least a few
feet (approximately 1 meter) down from the
• Identify all high risk fire ignition sources. ceiling.
• Be sure that enough detectors are used to • If possible, fire tests can be conducted to verify
adequately cover the hazardous area. correct detector positioning and coverage.
• Be sure that the unit is easily accessible for • For ATEX/IECEx installations, the X3301 Flame
cleaning and other periodic servicing. Detector housing must be electrically connected
• Verify that all detectors in the system are to earth ground.
properly located and positioned so that any
fire hazards are within both the Field of View
(FOV) and detection range of the detector. DETECTOR ORIENTATION
The Q1201C Laser Aimer is recommended Refer to Figure 2 and ensure that the oi plate
for establishing the detector's FOV. Refer to will be oriented as shown when the X3301 is
the "High Resolution Field of View Diagrams" installed and sighted. This will ensure proper
section for specific information regarding operation of the oi system and will also minimize
detector range and FOV. the accumulation of moisture and contaminants
• The detector should be aimed downward at between the oi plate and the viewing windows.
least 10 to 20 degrees to allow lens openings
to drain. See Figure 1. The detector should IMPORTANT
be positioned so that its FOV does not If removed, the o i plate must be securely
cover areas outside the hazardous area. tightened to ensure proper operation of
This will minimize the possibility of false alarms
the o i system (40 oz./inches [28.2 N . cm]
caused by activities outside the area requiring
recommended).
protection.
• The detector must be mounted on a rigid
surface in a low vibration area.
oi PLATE
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
oi MAGNET
F2068
DETECTOR
STATUS INDICATOR
CORRECT D1974
1.1 5 95-8704
PROTECTION AGAINST MOISTURE DAMAGE NOTE
It is important to take proper precautions during Refer to “Power Consumption” in the
installation to ensure that moisture will not come “Specifications” section of this manual.
in contact with the electrical connections or
components of the system. The integrity of The use of shielded cable is required to protect
the system regarding moisture protection must against interference caused by EMI and RFI.
be maintained for proper operation and is the When using cables with shields, terminate
responsibility of the installer. the shields as shown in Figures 7 through 12,
If conduit is used, we recommend installing drains, and Figure 15. Consult the factory if not using
according to local codes, at water collection shielded cable.
points to automatically drain accumulated
moisture. It is also recommended to install at least In applications where the wiring cable is installed
one breather, according to local codes, at upper in conduit, the conduit must not be used for wiring
locations to provide ventilation and allow water to other electrical equipment.
vapor to escape.
If disconnection of power is required, separate
Conduit raceways should be inclined so that disconnect capability must be provided.
water will flow to low points for drainage and
will not collect inside enclosures or on conduit
seals. If this is not possible, install conduit drains WARNING
above the seals to prevent the collection of water All entries must contain appropriately rated
or install a drain loop below the detector with a plugs or fittings. It is required that each
conduit drain at the lowest point of the loop. plug or fitting be wrench-tightened to an
Conduit seals are not required for compliance appropriate installation torque and meet the
with explosion-proof installation requirements, but minimum thread engagement requirements
are highly recommended to prevent water ingress per the applicable local standards, codes,
in outdoor applications. Units with M25 threads and practices in order to retain the defined
must use an IP66/IP67 washer to prevent water ratings. PTFE sealant or equivalent should
ingress. be used on NPT threads.
WIRING PROCEDURE
IMPORTANT
Wire Size and Type Devices certified for hazardous locations
The system should be wired according to local shall be installed in accordance with EN/
codes. The wire size selected should be based IEC 60079-14 and NEC 505.
on the number of detectors connected, the supply
voltage and the cable length. Typically 16 AWG
or 2.5 mm2 shielded cable is recommended. CAUTION
Wires should be stripped 3/8 inch (9 mm). A Installation of the detector and wiring should
minimum input voltage of 18 Vdc must be present be performed only by qualified personnel.
at the X3301.
4.0
(10.2)
4X ø0.42 3.0 13.1
(1.1) (7.6) (33.3)
4.0
(10.2)
10.6
(27.0)
F2069
1. Make field connections following local 2. Resistor leads should be cut to a length of
ordinances and guidelines in this manual. approximately 1 1/2 inches (40 mm).
3. Bend the leads and install the EOL resistor
–– Figure 4 shows the wiring terminal strip as shown in Figure 6.
located inside the detector’s integral
junction box. 4. Maintain a 3/8 inch (10 mm) minimum gap
between the resistor body and the terminal
–– Figure 5 shows the wiring terminal block or any other neighboring parts.
identification for the X3301 Flame
Detector.
–– Figure 6 shows an EOL resistor installed NOTE
within the integral wiring compartment of The EOL resistor can only be used within the
the detector (refer to “EOL Resistors” for flameproof terminal compartment. Unused
details). conduit entries shall be closed with suitable
blanking elements.
–– Figures 7 and 8 provide examples of
typical installations with a X3301 wired to
a fire alarm panel.
–– If the detector is equipped with a 0 to
20 mA output, refer to Figures 9 through
12.
IMPORTANT
Do not test any wiring connected to the
detector with a meg-ohmmeter. Disconnect
wiring at the detector before checking
system wiring for continuity.
1.1 7 95-8704
Figure 4—X3301 Terminal Block
9 mA + 19 mA – 29 SPARE
E2061
19 18 17 16 15 14 13 12 11
B2126
BULKHEAD
1.1 8 95-8704
X3301 DETECTOR
FIRE ALARM PANEL
9 mA + 19 mA – SPARE 29
oi TEST 3
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
SHIELD
X3301 DETECTOR
FIRE ALARM PANEL
9 mA + 19 mA – SPARE 29
oi TEST 3
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
1.1 9 95-8704
X3301 IR DETECTOR
24 VDC
PLC – + X3301 IR DETECTOR
mA 6 NO FIRE 16 NO AUX 26
5 NC FIRE NC FIRE 15 NC AUX 25 NO FIRE
+
24 VDC 5 NC FIRE 15 25
4 14 24 NC FIRE NC AUX
–
COM FAULT COM FAULT RS485 A +
24 VDC
3 NO FAULT NO FAULT 13 RS485 B 23 4 COM FAULT COM FAULT 14 RS485 A 24
–
Oi TEST1
Oi TEST1
1.1 10 95-8704
EQP Model 5. Check all field wiring to be sure that the
proper connections have been made.
1. Connect external wires to the appropriate
terminals inside the device junction box, 6. Replace the device cover and apply input
shown in Figure 13. See Figure 14 for power.
terminal identification.
7. Make the final sighting adjustments and
2. Connect the shield of the power cable to use a 14 mm hex wrench to ensure that the
“earth ground” at the power source. mounting arm assembly is tight.
3. Connect shields for the LON cable as
NOTE
indicated. See Figure 15.
Refer to the Eagle Quantum Premier
system manual (95-8533) for information
NOTE
regarding power requirements, network
DO NOT ground any shields at the detector
communication cable requirements, and
housing.
configuration.
4. With input power disconnected, set the
device network address (see the “Setting
Device Network Addresses” section of this
manual for switch setting procedure).
6 SHIELD 16 SHIELD
5 COM 1 A 15 COM 2 A
4 COM 1 B 14 COM 2 B
2 +Vin 12 +Vin
1 –Vin 11 –Vin
C2089
1.1 11 95-8704
1.1
+ +
– –
– POWER –
+ DISTRIBUTION +
+
–
+ – + –
CONTROLLER EQP3700DCIO EQP2100PSM EQPX3301 EQPX3301 EQPX3301 EQPX3301
P1 P1
6 SHIELD 3 4 SHIELD 9 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3
52 B 49 5 B 2 11 B 3 14 B 4 14 B 4 14 B 4 14 B 4
53 A 50 4 A 1 10 A 2 15 A 5 15 A 5 15 A 5 15 A 5
P6
BUS BAR P3
C 45 A2207
C 1 N
FAULT NO 46 P4 P3
B 2
NC 47 A + SUPPLY A AC LINE
P9 P8 3
B IN–/OUT+ B + –
CH 1
CH 5
GND 5 57 GND GND 54 24 VDC 4 H
C COMMON C SUPPLY
RXD 2 58 RxD B 55
TXD 3 59 TxD A 56 A + SUPPLY A
12
DB-9 H N
P2 P3
CONNECTION B IN–/OUT+ B AC LINE
CH 6
CH 2
TO COM PORT 5 1+ 5+ 13
OF PC
6 1– 5– 14 C COMMON C
+ –
7 2+ 6+ 15
A + SUPPLY A 24 VDC
8 2– 6– 16 BATTERY
B IN–/OUT+ B
CH 3
CH 7
9 3+ 7+ 17
10 3– 7– 18 C COMMON C
11 4+
DIGITAL INPUTS
8+ 19
A + SUPPLY A
12 4– 8– 20
B IN–/OUT+ B
CH 4
CH 8
P4 P5
21 C C 33 C COMMON C
22 NO NO 34
RELAY 5
RELAY 1
23 NC NC 35
24 C C 36
25 NO NO 37
RELAY 6
RELAY 2
26 NC NC 38
27 C C 39
28 NO NO 40
RELAY 7
RELAY 3
29 NC NC 41
30 C C 42
31 NO NO 43
RELAY 4
RELAY 8
32 NC NC 44
95-8704
ADDRESS SWITCHES SENSOR MODULE
REMOVED FROM HOUSING
A2191
SETTING DEVICE NETWORK ADDRESSES The address number is binary encoded with
(EQP Model Only) each switch having a specific binary value with
Overview of Network Addresses switch 1 being the LSB (Least Significant Bit),
see Figure 17. The device’s LON address is
Each device on the LON must be assigned a equal to the added value of all closed rocker
unique address. Addresses 1 to 4 are reserved switches. All “Open” switches are ignored.
for the controller. Valid addresses for field
devices are from 5 to 250. Example: for node No. 5, close rocker switches
1 and 3 (binary values 1 + 4); for node No. 25,
IMPORTANT close rocker switches 1, 4 and 5 (binary values
If the address is set to zero or an address 1 + 8 + 16).
above 250, the switch setting will be
ignored. NOTE
The field device sets the LON address
Duplicated addresses are not automatically only when power is applied to the device.
detected. Modules given the same address Therefore, it is important to set the switches
will use the number given and report to the before applying power. If an address is
controller using that address. The status word ever changed, system power must be
will show the latest update, which could be cycled before the new address will take
from any of the reporting modules using that effect.
address.
Setting Field Device Addresses After setting address switches, record the
address number and device type.
Selection of the node address is done by
setting rocker switches on an 8 switch “DIP
Switch Assembly” within the detector’s housing.
Refer to Figure 16 for switch location.
ON
WARNING
The network address switches are located 1 2 3 4 5 6 7 8
switches. For hazardous areas, the area Figure 17—Address Switches for X3301
1.1 13 95-8704
STARTUP PROCEDURE 2. Inspect the viewing windows for
contamination and clean as necessary. The
When installation of the equipment is complete, detector is relatively insensitive to airborne
perform the “Fire Alarm Test” below. contaminants, however, thick deposits of
ice, dirt, or oil will reduce sensitivity. (Refer
FIRE ALARM TEST to the “Maintenance” section for complete
1. Disable any extinguishing equipment that is information regarding cleaning of the
connected to the system. detector viewing windows.)
2. Apply input power to the system. 3. Check input power to the unit.
3. Initiate an oi test (see “Magnetic oi / Manual 4. If the fire system has a logging function,
oi” under Optical Integrity in the Description check the fire panel log for output status
section of this manual). information. See Table 3 for information
regarding 0 to 20 mA output.
4. Repeat this test for all detectors in the
system. If a unit fails the test, refer to the 5. Turn off the input power to the detector and
“Troubleshooting” section. check all wiring for continuity. Important:
Disconnect wiring at the detector before
5. Verify that all detectors in the system are
checking system wiring for continuity.
properly aimed at the area to be protected.
(The Q1201C Laser Aimer is recommended 6. If all wiring checks out and cleaning of
for this purpose.) the oi plate/window did not correct the
fault condition, check for high levels of
6. Enable extinguishing equipment when the
background IR radiation by covering the
test is complete.
detector with the factory supplied cover
or aluminum foil. If the fault condition
clears within 6 minutes or less, extreme
TROUBLESHOOTING background IR is present. Re-adjust the
view of the detector away from the IR source
or relocate the detector.
WARNING
The sensor module (“front” half of the If none of these actions corrects the problem,
detector) contains no user serviceable return the detector to the factory for repair.
components and should never be tampered
with. NOTE
It is highly recommended that a complete
1. Disable any extinguishing equipment that is spare be kept on hand for field replacement
connected to the unit. to ensure continuous protection.
Current Level
Status Action
(±0.3 mA)
0 mA Power Fault Check system wiring
1
1 mA General Fault Cycle power
2
2 mA oi Fault Clean windows
3 mA High Background IR Fault Remove IR source or aim detector away from IR source
4 mA Normal Operation
20 mA Fire Alarm
1 If fault continues, return device to factory for repair.
2 See “Maintenance” section for cleaning procedure.
NOTE: For additional troubleshooting guides, refer to the Flame Inspector Monitor manual (95-8581).
1.1 14 95-8704
MAINTENANCE LOOSEN TWO CAPTIVE SCREWS
IMPORTANT
Periodic flamepath inspections are not
recommended, since the product is not
intended to be serviced and provides
proper ingress protection to eliminate
potential deterioration of the flamepaths.
GRASP VISOR AND
REMOVE oi PLATE
WARNING
The sensor module (“front” half of the
detector) contains no user serviceable
components and should never be tampered B2106
Associated Manuals
List of X3301 related manuals:
TITLE FORM NUMBER
Pulse 95-8736
EQP 95-8533
SIL 2 (Safety) 95-8720
HART Addendum 95-8577
Hangar 95-8735
Q9033 Mounting Arm
95-8686
and Collar Attachment
Inspector Monitor Software for
95-8581
X-Series Flame Detectors
Q1130 Flange Mount 95-8662
1.1 16 95-8704
SPECIFICATIONS CURRENT OUTPUT (OPTIONAL)—
0 to 20 milliampere (±0.3 mA) dc current, with a
OPERATING VOLTAGE— maximum loop resistance of 500 ohms from 18 to
24 Vdc nominal (18 Vdc minimum, 30 Vdc 19.9 Vdc and 600 ohms from 20 to 30 Vdc.
maximum). Maximum ripple is 2 volts
peak-to-peak. LON OUTPUT—
Digital communication, transformer isolated (78.5
POWER CONSUMPTION— kbps).
Without heater: 4 watts at 24 Vdc nominal;
5.2 watts at 24 Vdc in alarm. TEMPERATURE RANGE—
4.5 watts at 30 Vdc nominal; Operating: –40°F to +167°F (–40°C to +75°C).
6.5 watts at 30 Vdc in alarm. Storage: –67°F to +185°F (–55°C to +85°C).
Heater only: 8 watts maximum. Hazardous location ratings from –55°C to +125°C.
Total power: 17 watts at 30 Vdc with EOL resistor
installed and heater on maximum. HUMIDITY RANGE—
EOL resistor must be ceramic, wirewound 0 to 95% relative humidity, can withstand 100%
type, rated 5 watts minimum, with actual power condensing humidity for short periods of time.
dissipation not to exceed 2.5 watts.
For HART model, refer to Addendum number CONE OF VISION—
95-8577. The detector has a 90° cone of vision (horizontal)
with the highest sensitivity lying along the central
POWER UP TIME— axis. Unlike conventional detectors, the X3301
Fault indication clears after 0.5 second; device provides full coverage at a minimum of 70% of
is ready to indicate an alarm condition after 30 the maximum detection distance.
seconds.
Perfect cone of vision for methane fire detection
OUTPUT RELAYS— — 100 feet (30.5 m) on and off axis on “very high”
Fire Alarm relay, Form C, 5 amperes at 30 Vdc: setting.
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts, Refer to Appendix A for FM Approved cone of
normally de-energized operation, and latching or vision data.
non-latching operation.
Fault relay, Form A, 5 amperes at 30 Vdc: RESPONSE TIME—
The Fault relay has redundant terminals and Typical response times are under 10 seconds.
normally open contacts, normally energized Models are available that can respond to
operation, and latching or non-latching automotive paint gun fires in under 0.5 seconds.
operation. See Appendix A and “Automotive Addendum”
Auxiliary relay, Form C, 5 amperes at 30 Vdc: (95-8534) for actual response times.
The auxiliary relay has normally open / normally
closed contacts. It is configurable for energized DIMENSIONS—
or de-energized operation and latching or non- See Figure 19.
latching operation to perform as a secondary relay
for fire alarm or fault.
4.7
(11.9)
10.0 4.8
B2067
(25.4) (12.2)
1.1 17 95-8704
ENCLOSURE MATERIAL— CERTIFICATION—
Copper-free aluminum (painted) or Stainless
Steel (316/CF8M Cast). ®
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD VdS
810C (Curve AW), DNV Note 2.4 (Class B).
WIRING—
Field wiring screw terminals are UL/CSA rated
for up to 14 AWG wire, and are DIN/VDE rated
for 2.5 mm2 wire. Screw terminal required torque For complete approval details, refer to the
range is 3.5–4.4 in.-lbs. (0.4-0.5 N·m). appropriate Appendix:
Important: 18 Vdc minimum must be available
Appendix A - FM
at the detector. For ambient temperatures below
Appendix B - CSA
–10°C (14°F) and above +60°C (140°F) use field
Appendix C - ATEX
wiring suitable for both minimum and maximum
Appendix D - IECEx
ambient temperature.
Appendix E - EN54
THREAD SIZE— Appendix F - Offshore
Conduit connection: Four entries, 3/4 inch NPT or Appendix G - Additional approvals
M25. Conduit seal not required. Appendix H - Declaration of Conformity
WARRANTY PERIOD—
5 years.
1.1 18 95-8704
REPLACEMENT PARTS ORDERING INFORMATION
The detector is not designed to be repaired in the When ordering, please specify:
field. If a problem should develop, refer to the
X3301 Multispectrum IR Flame Detector
Troubleshooting section. If it is determined that
the problem is caused by an electronic defect, Refer to the X3301 Model Matrix for details
the device must be returned to the factory for
repair. Q9033 Mounting Arm is required:
–– Q9033A for aluminum detectors only
–– Q9033B for aluminum and stainless steel
REPLACEMENT PARTS LIST
detectors
Part Number Description
oi Replacement kit for X3301 (5 Black Reflector Plates)
009208-001
with Inspector Connector and Monitor ACCESSORIES
oi Replacement kit for X3301 (5 Stainless Steel Reflector
010831-001 Part Number Description
Plates) with Inspector Connector and Monitor
Replacement oi Reflector Plates for X3301 with Black plate 000511-029 Converter RS485 to RS232
007307-001
(requires Inspector Connector to calibrate)
103881-001 Converter RS485 to USB
Replacement oi Reflector Plates for X3301 with Stainless
010830-001
Steel plate (requires Inspector Connector to calibrate) W6300B1002 Serial Inspector Connector
007819-001
NOTE: Refer to instruction manual 95-8530 to determine the correct oi
(Inspector Monitor software included)
Replacement Plate. W6300B1003 USB Inspector Connector
007819-002
(Inspector Monitor software included)
009207-001 Flame Inspector Monitor CD
103922-001 Model 475 HART Communicator
102740-002 Magnet
008082-001 Magnet and Adapter for Extension Pole
DEVICE REPAIR AND RETURN 007739-001
007240-001
Magnet and Extension Pole
Q1116A1001, Air Shield (AL)
Prior to returning devices, contact the nearest 007818-001 Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
local Detector Electronics office so that a Return Q1118S1001 Stainless Steel Air Shield/Flange
007818-002
Mount (SS)
Material Identification (RMI) number can be 009177-001 Q1120A1001 Paint Shield mounting ring (AL)
assigned. A written statement describing the 010857-001 Q1130A1001 Flange Mount Assembly
malfunction must accompany the returned 006097-001 Q1201 Laser
device or component to assist and expedite 102871-001 Laser Battery, 3V Lithium (laser)
finding the root cause of the failure. 007255-001 Q1201C1001 X-Series Laser Holder (AL/Plastic)
007338-001 Q2000A1001 X-Series Weather Shield (AL)
007338-010 Q2033A10R X3301/X3302 FOV Limiter 10° (AL)
Pack the unit properly. Always use sufficient 007338-020 Q2033A20R X3301/X3302 FOV Limiter 20° (AL)
packing material. Where applicable, use an 007338-030 Q2033A30R X3301/X3302 FOV Limiter 30° (AL)
007912-010 Spare Restrictor Plate 10° (AL)
antistatic bag as protection from electrostatic 007912-020 Spare Restrictor Plate 20° (AL)
discharge. 007912-030 Spare Restrictor Plate 30° (AL)
Q9033B Stainless Steel Mounting Arm Assembly
007290-001
is for aluminum and stainless steel detectors
NOTE
Det-Tronics reserves the right to apply a Q9033A Aluminum Mounting Arm Assembly is for
007290-002
aluminum detectors only
service charge for repairing returned 011385-001 Q9033 Collar Attachment
product damaged as a result of improper 101197-001 Stop Plug, 3/4” NPT, AL
packaging. 101197-004 Stop Plug, 3/4” NPT, SS
101197-005 Stop Plug, M25, AL, IP66
101197-003 Stop Plug, M25, SS, IP66
Return all equipment transportation prepaid to the 010816-001 Stop Plug, 20 Pack, 3/4”NPT, AL
factory in Minneapolis. 010817-001 Stop Plug, 20 Pack, 3/4”NPT, SS
010818-001 Stop Plug, 20 Pack, M25, AL, IP66
010819-001 Stop Plug, 20 Pack, M25, SS, IP66
NOTE 103363-001 14 mm Hex Wrench (Steel)
It is highly recommended that a complete 103406-001 Screwdriver
spare be kept on hand for field replacement 001680-001 Window cleaner (6 pack)
to ensure continuous protection. 107427-040 O-ring - Rear Cover (Viton) - black
005003-001 1 oz grease for detectors (silicone-free)
104346-154 O-ring - Rear Cover (Fluorosilicone) - blue
012549-001 1 oz PTFE silicone-free lubricant
1.1 19 95-8704
X3301 MODEL MATRIX
MODEL DESCRIPTION
X3301 Multispectrum IR Flame Detector
TYPE MATERIAL
A Aluminum
S Stainless Steel (316)
TYPE THREAD TYPE
4M 4 Port, Metric M25
4N 4 Port, 3/4" NPT
TYPE OUTPUTS
11 Relay
13 Relay and 0-20 mA
14 Eagle Quantum Premier (EQP)
15 Relay and Pulse
16 Addressable Module Only (Third Party Type)*
21 Relay-Automotive
22 EQP Automotive
23 HART, Relay and 0-20 mA
TYPE APPROVALS**
B INMETRO (Brazil)
R VNIIPO/VNIIFTRI (Russia)
T SIL/FM/CSA/ATEX/IECEx
W FM/CSA/ATEX/IECEx
TYPE CLASSIFICATION
1 Division/Zone Ex d e
2 Division/Zone Ex d
*The Addressable Module Only (Type 16) is not FM approved.
**Type Approvals can use one or more letters to designate
the approvals of the product.
1.1 20 95-8704
HIGH RESOLUTION FIELD OF VIEW DIAGRAMS
0° 0°
15° 265 (80.7) 15° 15° 70 (21.3) 15°
30° 30° 30° 30°
240 (73.1) 60 (18.3)
45° 200 (60.9) 45° 45° 50 (15.2) 45°
40 (12.1) 10 (3.0)
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
n-Heptane at Very High Sensitivity (1 x 1 foot) Isopropanol at Very High Sensitivity (6 in. x 6 in.)
0° 0°
15° 100 (30.5) 15° 15° 175 (53.3) 15°
30° 90 (27.4) 30° 30° 160 (48.7) 30°
80 (24.4) 140 (42.6)
45° 45° 45° 45°
70 (21.3) 120 (36.5)
60 (18.3) 100 (30.4)
50 (15.2)
80 (24.3)
40 (12.2)
30 (9.1)
60 (18.2)
20 (6.1) 40 (12.1)
10 (3.0) 20 (6.1)
10 (3.0)
20 (6.1)
20 (6.1)
30 (9.1)
30° 40 (12.1) 30°
40 (12.2) 60 (18.2)
50 (15.2) 80 (24.3)
15° 15°
60 (18.3) 100 (30.4)
70 (21.3) 120 (36.5)
80 (24.4) 0° 0°
140 (42.6)
90 (27.4) DETECTOR VERTICAL 160 (48.7)
100 (30.5)
15° FIELD OF VIEW 15° DETECTOR VERTICAL
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
n-Heptane at Very High Sensitivity (6 in. x 6 in.) Diesel at Very High Sensitivity (1 x 1 foot)
1.1 21 95-8704
High Resolution Field of View Diagrams – Continued
0°
0° 15° 40 (12.2) 15°
15° 125 (38.1) 15°
30° 120 (36.6) 30° 30° 30°
35 (10.7)
105 (32) 45° 45° 30 (9.1) 45°
45°
90 (27.4)
25 (7.6)
75 (22.9)
60 (18.3) 20 (6.1)
45 (13.7) 15 (4.6)
30 (9.1) 10 (3)
15 (4.6) 5 (1.5)
15 (4.6) 5 (1.5)
30 (9.1) 30°
10 (3) 30°
45 (13.7)
15 (4.6)
60 (18.3) 15°
75 (22.9) 20 (6.1) 15°
90 (27.4) 25 (7.6)
0°
105 (32) 30 (9.1) 0°
120 (36.6) 15° DETECTOR VERTICAL
35 (10.7)
FIELD OF VIEW DETECTOR VERTICAL
125 (38.1) 30° WITH DETECTOR AT
15° FIELD OF VIEW
45° 40 (12.2) WITH DETECTOR AT
45° FROM HORIZONTAL. 30°
45° 45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
Propane at Very High Sensitivity (32 inch plume) Methanol at Very High Sensitivity (6 in. x 6 in.)
0° 0°
15° 210 (64) 15° 15° 150 (45.7) 15°
30° 30° 30° 135 (41.2 30°
180 (54.9)
120 (36.5)
45° 150 (45.7) 45° 45° 45°
105 (32)
120 (36.5) 90 (27.4)
75 (22.9)
90 (27.4)
60 (18.3)
60 (18.3) 45 (13.7)
30 (9.1)
30 (9.1)
15 (4.6)
30 (9.1)
15 (4.6)
60 (18.3) 30° 30 (9.1) 30°
90 (27.4) 45 (13.7)
60 (18.3)
120 (36.5) 15°
75 (22.9) 15°
150 (45.7) 90 (27.4)
0° 105 (32)
180 (54.9) 0°
DETECTOR VERTICAL 120 (36.5)
15° FIELD OF VIEW
210 (64) 135 (41.2 15° DETECTOR VERTICAL
30° WITH DETECTOR AT FIELD OF VIEW
45° 45° FROM HORIZONTAL. 150 (45.7)
30° WITH DETECTOR AT
45° 45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
Ethanol at Very High Sensitivity (1 x 1 foot) Methanol at Very High Sensitivity (1 x 1 foot)
1.1 22 95-8704
High Resolution Field of View Diagrams – Continued
0° 0°
15° 15° 15°
125 (38.1) 15° 235 (71.6)
30° 100 (30.5) 30°
30° 210 (64) 30°
45° 90 (27.4) 45°
80 (24.4) 45° 180 (54.9)
45°
70 (21.3) 150 (45.7)
60 (18.3)
120 (36.5)
50 (15.2)
40 (12.2) 90 (27.4)
30 (9.1)
60 (18.3)
20 (6.1)
10 (3) 30 (9.1)
10 (3)
30 (9.1)
20 (6.1)
30 (9.1) 30° 60 (18.3) 30°
40 (12.2) 90 (27.4)
50 (15.2)
60 (18.3) 15° 120 (36.5) 15°
70 (21.3) 150 (45.7)
80 (24.4) 0° 180 (54.9) 0°
90 (27.4) DETECTOR VERTICAL
100 (30.5) 15° FIELD OF VIEW 210 (64.0) 15° DETECTOR VERTICAL
WITH DETECTOR AT FIELD OF VIEW
125 (38.1) 235 (71.6)
30° 45° FROM HORIZONTAL. 30° WITH DETECTOR AT
45° 45° 45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
Methane at Very High Sensitivity (32 inch plume) JP-5 at Very High Sensitivity (2 x 2 feet)
1.1 23 95-8704
High Resolution Field of View Diagrams – Continued
0° 0°
15° 100 (30.5) 15° 15° 70 (21.3) 15°
30° 30° 30° 30°
90 (27.4) 60 (18.3)
80 (24.4)
45° 45° 45° 50 (15.2) 45°
70 (21.3)
60 (18.3) 40 (12.2)
50 (15.2)
30 (9.1)
40 (12.2)
30 (9.1) 20 (6.1)
20 (6.1)
10 (3)
10 (3)
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
n-Heptane at Medium Sensitivity (1 x 1 foot) Methanol at Medium Sensitivity (1 x 1 foot)
0° 0°
15° 70 (21.3) 15° 15° 15°
70 (21.3)
30° 30° 30° 30°
60 (18.3) 60 (18.3)
45° 50 (15.2) 45° 45° 50 (15.2) 45°
40 (12.2) 40 (12.2)
30 (9.1) 30 (9.1)
20 (6.1) 20 (6.1)
10 (3) 10 (3)
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
Diesel at Medium Sensitivity (1 x 1 foot) Methane at Medium Sensitivity (32 inch plume)
0° 0°
15° 85 (25.9) 15° 15° 150 (45.7) 15°
30° 80 (24.4) 30° 30° 135 (41.2 30°
75 (22.9) 120 (36.5)
45° 45° 45° 45°
65 (19.8) 105 (32)
55 (16.8) 90 (27.4)
45 (13.7) 75 (22.9)
35 (10.7) 60 (18.3)
25 (7.6) 45 (13.7)
15 (4.6) 30 (9.1)
5 (1.5) 15 (4.6)
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
Ethanol at Medium Sensitivity (1 x 1 foot) JP-5 at Medium Sensitivity (2 x 2 feet)
0°
15° 75 (22.8) 15°
30° 70 (21.3) 30°
60 (18.3)
45° 45°
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
• Explosion-proof for Class I, Div. 1, Groups B, C and D (T4A) Hazardous (Classified) Locations per FM 3615.
• Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T4A) Hazardous (Classified) Locations per FM 3615.
• Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations per FM 3611.
• Nonincendive for Class II, Div. 2, Groups F and G (T3C) Hazardous (Classified) Locations per FM 3611.
• Enclosure rating NEMA/Type 4X per NEMA 250.
• Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
• Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
Flameproof per ANSI/ISA 60079-0, -1, -7, -31
for Class I, Zone 1 -
AEx d e IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C)
AEx d IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C)
for Zone 21 -
AEx tb T130°C Db
Tamb –40°C to +75°C
Degree of protection provided by Enclosure IP66/67, Hazardous Locations for use in the U.S.
The following accessories are FM approved for use with the X3301 Flame Detector:
The oi test procedure, as described in the "Magnetic oi / Manual oi" section of this instruction manual,
is the approved external optical test method for this detector to verify end-to-end detector function. This
test replaces the function and need of a traditional external test lamp.
1.1 25 95-8704
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS
Medium Sensitivity
1.1 26 95-8704
FM Approval and Performance Report – Continued
T-Low Sensitivity
Low Sensitivity
1.1 27 95-8704
FM Approval and Performance Report – Continued
Medium Sensitivity
1.1 28 95-8704
FM Approval and Performance Report – Continued
T-Low Sensitivity
Low Sensitivity
1.1 29 95-8704
FM Approval and Performance Report – Continued
Distance
False Alarm Source Modulated Response Unmodulated Response
feet (m)
Sunlight, direct, reflected — No alarm No alarm
Vibration N/A No alarm N/A
Radio frequency interference 1 (0.3) No alarm (keyed) No alarm (steady)
Arc welding 40 (12.2) No alarm No alarm
LED Lamp 5 (1.5) No alarm No alarm
70 w sodium vapor lamp 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 8 (2.4) No alarm No alarm
500 w shielded quartz halogen lamp 8 (2.4) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 5 (1.5) No alarm No alarm
Medium Sensitivity
Distance
False Alarm Source Modulated Response Unmodulated Response
feet (m)
Sunlight, direct, reflected — No alarm No alarm
Vibration N/A No alarm N/A
Radio frequency interference 1 (0.3) No alarm (keyed) No alarm (steady)
Arc welding 10 (3) No alarm No alarm
LED Lamp 3 (0.9) No alarm No alarm
70 w sodium vapor lamp 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm
T-Low Sensitivity
Distance
False Alarm Source Modulated Response Unmodulated Response
feet (m)
Sunlight, direct, reflected — No alarm No alarm
Vibration N/A No alarm No alarm
Arc welding 5 (1.5) No alarm No alarm
LED Lamp 3 (0.9) No alarm No alarm
70 w sodium vapor 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm
1.1 30 95-8704
FM Approval and Performance Report – Continued
Low Sensitivity
Distance Modulated
False Alarm Source Unmodulated Response
feet (m) Response
Sunlight, direct, reflected — No alarm No alarm
Vibration N/A No alarm No alarm
Radio frequency interference — No alarm N/A
Arc welding 5 (1.5) No alarm No alarm
LED Lamp 3 (0.9) No alarm No alarm
70 w sodium vapor lamp 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm
FIELD OF VIEW
Distance Horizontal Avg. Resp Vertical Avg. Resp Vertical Avg. Resp
Fuel Size
feet (m) L, R (°) Time (s)*** Down (°) Time (s)*** Up (°) Time (s)***
1 x 1 foot 190 (57.9) +/– 45 11 +45 11 –30 8
1 x 1 foot 180 (54.9) +/– 45 8 +45 11 –30 3
n-Heptane 1 x 1 foot 180 (54.9) +/– 45 6** +45 6** –30 3**
1 x 1 foot 100 (30.5) +/– 45 4 +45 3 –30 2
6 x 6 inches 100 (30.5) +/– 45 11 +45 11 –30 7
Gasoline 1 x 1 foot 190 (57.9) +/– 45 7 +45 9 –30 5
Kerosene 1 x 1 foot 110 (33.5) +/– 45 5 +45 5 –30 4
Isopropanol 6 x 6 inches 70 (21.3) +/– 45 8 +45 6 –30 5
Diesel 1 x 1 foot 150 (45.7) +/– 45 10** +45 7** –30 7**
Ethanol 1 x 1 foot 150 (45.7) +/– 45 15 +45 13 –30 10
6 x 6 inches 40 (12.2) +/– 45 3 +45 3 –30 2
Methanol 1 x 1 foot 110 (33.5) +/– 45 8 +45 13 –30 3
1 x 1 foot 110 (33.5) +/– 45 8** +45 4** –30 3**
Xylene 1 x 1 foot 150 (45.7) +/– 45 7** +45 6** –30 3**
Toluene 1 x 1 foot 150 (45.7) +/– 45 8** +45 8** –30 4**
Methane 32 inch plume 100 (30.5) +/– 45 7 +45 8 –30 4
Propane 32 inch plume 90 (27.4) +/– 45 7 +45 9 –30 5
Ethane 32 inch plume 90 (27.4) +/– 45 5 +45 6 –30 3
Ethylene 32 inch plume 90 (27.4) +/– 45 7 +45 9 –30 5
Butane 32 inch plume 90 (27.4) +/– 45 5 +45 4 –30 2
Jet A 1 x 1 foot 100 (30.5) +/– 45 4** +45 3** –30 2**
JP-5 2 x 2 feet 180 (54.9) +/– 45 6** +45 4** –30 2**
JP-8 1 x 1 foot 100 (30.5) +/– 45 5** +45 5** –30 3**
Class A Ø12 in. x 7 in. 80 (24.4) +/– 45 4** +45 2** –30 2**
* Outdoor test condition
** Pre-burn from ignition
*** Add 2 seconds for EQP model
Ø Diameter
1.1 31 95-8704
FM Approval and Performance Report – Continued
Medium Sensitivity
Distance Horizontal Avg. Resp Vertical Avg. Resp Vertical Avg. Resp
Fuel Size
feet (m) L, R (°) Time (s)*** Down (°) Time (s)*** Up (°) Time (s)***
1 x 1 foot 75 (22.9) +/– 45 5 +45 4 –30 5
n-Heptane
1 x 1 foot 50 (15.2) +/– 45 3 +45 2 –30 3
Isopropanol 6 x 6 inches 45 (13.7) +/– 45 11 +45 8 –30 6
Diesel 1 x 1 foot 60 (18.2) +/– 45 4** +45 6** –30 4**
Ethanol 1 x 1 foot 60 (18.2) +/– 45 7 +45 8 –30 5
Methanol 1 x 1 foot 50 (15.2) +/– 45 5 +45 2 –30 6
Methane 32 inch plume 50 (15.2) +/– 45 5 +45 6 –30 3
JP-5 2 x 2 feet 110 (33.5) +/– 45 7 +45 4 –30 5
Propane 32 inch plume 55 (16.7) +/– 45 5 +45 4 –30 5
Ethane 32 inch plume 55 (16.7) +/– 45 6 +45 5 –30 5
Ethylene 32 inch plume 55 (16.7) +/– 45 7 +45 5 –30 5
Butane 32 inch plume 55 (16.7) +/– 45 6** +45 4** –30 3**
Class A Ø12 in. x 7 in. 40 (12.2) +/– 45 3** +45 3** –30 3**
** Pre-burn from ignition
*** Add 2 seconds for EQP model
Ø Diameter
T-Low Sensitivity
Distance Horizontal Avg. Resp Vertical Avg. Resp Vertical Avg. Resp
Fuel Size
feet (m) L, R (°) Time (s)*** Down (°) Time (s)*** Up (°) Time (s)***
n-Heptane 1 x 1 foot 35 (10.7) +/– 45 4 +45 4 –30 3
Methanol 1 x 1 foot 20 (6.1) +/– 45 4 +45 4 –30 2
Methane 32 inch plume 20 (6.1) +/– 45 4 +45 4 –30 4
Propane 32 inch plume 20 (6.1) +/– 45 4 +45 4 –30 5
*** Add 2 seconds for EQP model.
Low Sensitivity
Distance Horizontal Avg. Resp Vertical Avg. Resp Vertical Avg. Resp
Fuel Size
feet (m) L, R (°) Time (s)*** Down (°) Time (s)*** Up (°) Time (s)***
n-Heptane 1 x 1 foot 35 (10.7) +/– 45 8 +45 9 –30 10
Methanol 1 x 1 foot 20 (6.1) +/– 45 9 +45 9 –30 9
Methane 32 inch plume 20 (6.1) +/– 45 9 +45 9 –30 8
Propane 32 inch plume 20 (6.1) +/– 45 9 +45 9 –30 11
*** Add 2 seconds for EQP model.
1.1 32 95-8704
APPENDIX B
CSA APPROVAL
Multispectrum IR Flame Detector/Controller X3301 Series, rated 18-30 Vdc, 4.6 Watts to 17 Watts.
Relay contacts rated 30 Vdc, 5 Amps.
NOTE
Hazardous location testing has been successfully completed on the Model X3301 series from an ambient
temperature range of –55°C to +125°C; however, the detector label marking indicates –40°C to +75°C.
The following accessories are CSA approved for use with the X3301 Flame Detector:
DIVISION CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T4A); Class II, Division 1, Groups E, F, and G (T4A);
Class I, Division 2, Groups A, B, C, and D (T3C); Class II, Division 2, Groups F and G (T3C);
Class III; Enclosure NEMA/Type 4X;
Conduit seal not required.
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 0-M91 – General Requirements — Canadian Electrical Code, Part II
CAN/CSA Std C22.2 No. 25-1966 – Enclosures for use in Class II Groups E, F & G Hazardous Locations
CAN/CSA-C22.2 No. 30-M1986 – Explosion-Proof Enclosures for use in Class I Hazardous Locations
CAN/CSA-C22.2 No. 94-M91 – Special Purpose Enclosures
CAN/CSA-C22.2 No. 142-M1987 – Process Control Equipment
CAN/CSA-C22.2 No. 213-M1987 – Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations
ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex d e IIC T5-T6
T6 (Ta -50oC to +60oC)
T5 (Ta -50oC to +75oC)
Seal required adjacent to enclosure
IP66/IP67.
Ex d IIC T4-T6
T6 (Ta -55oC to +60oC)
T5 (Ta -55oC to +75oC)
T4 (Ta -55oC to +125oC)
Seal required adjacent to enclosure
IP66/IP67.
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0:2007 – Electrical apparatus for explosive gas atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1:2011 – Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d"
CAN/CSA-C22.2 No. 60079-7:2012 – Explosive atmospheres. Part 7: Equipment protection by increased safety "e"
1.1 33 95-8704
APPENDIX C
ATEX APPROVAL
Compliance with:
EN 60079-0: 2009
EN 60079-1: 2007
EN 60079-7: 2007
EN 60079-31: 2009
EN/IEC 60529: 2001.
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring
specifications from 14-24 AWG or 2.5-0.2 mm2.
The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given
by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with
the terminal compartment in type of explosion protection flameproof enclosure "d", or in type of explosion
protection increased safety "e" for use with the terminal compartment in type of explosion protection increased
safety "e". They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected
to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and
maximum ambient temperature.
1.1 34 95-8704
NOTE
Operational performance verified from –40°C to +75°C.
NOTE
An optional third party addressable module can only be used within the Ex d flameproof
model unless the addressable module is component certified as Ex e for use within the Ex d e
increased safety model.
NOTE
Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking
elements shall be certified to “E-generation” or “ATEX” standards, in type of explosion protection
increased safety “e” or flameproof enclosure “d” (as applicable), suitable for the conditions of
use and correctly installed. They shall maintain the degree of ingress protection IP66/IP67 for
the apparatus. Unused conduit entries shall be closed with suitable blanking elements.
NOTE
For ATEX installations, the X3301 Flame Detector housing must be electrically connected to earth
ground.
The following accessories are ATEX approved for use with the X3301 Flame Detector:
1.1 35 95-8704
APPENDIX D
IECEx APPROVAL
DEMKO
IECEx ULD 06.0017X
Ex d e IIC T6...T5 Gb Ex d IIC T6...T4 Gb
Ex tb IIIC T130°C Ex tb IIIC T130°C
T6 (Tamb = –50°C to +60°C) or T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C) T5 (Tamb = –55°C to +75°C)
IP66/IP67. T4 (Tamb = –55°C to +125°C)
IP66/IP67.
Compliance with:
IEC 60079-0: 2007, Ed. 5
IEC 60079-1: 2007, Ed. 6
IEC 60079-7: 2006, Ed. 4
IEC 60079-31: 2008, Ed. 1
EN/IEC 60529: 2001.
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are suitable certified and accepts wiring
specifications from
14-24 AWG or 2.5-0.2 mm2.
The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given
by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use
with the terminal compartment in type of explosion protection flameproof enclosure "d" or in type of explosion
protection increased safety "e" for use with the terminal compartment in type of explosion protection increased
safety "e". They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected
to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and
maximum ambient temperature.
The following accessories are IECEx approved for use with the X3301 Flame Detector:
1.1 36 95-8704
APPENDIX E
EN54 APPROVALS
The following accessories are EN54-10, EN54-13, and EN54-17 approved for use with the X3301 Flame Detector:
Part Number Description
102740-002 Magnet
007739-001 Magnet and Extension Pole
007290-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002 Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001 Q9033 Collar Attachment
1.1 37 95-8704
APPENDIX F
OFFSHORE APPROVALS
USCG APPROVAL
Coast Guard Approval No. 161.002/49/0
The scope of this approval is for a fire detection system meeting 46 CFR 161.002, as part of the Eagle Quantum Premier System.
MARINE EQUIPMENT DIRECTIVE
DNV Certificate No. MED-B-9427
Is found to comply with the requirements in the following Regulations / Standards:
Annex A.1, item No. A.1/3.51 and Annex B, Module B in the Directive. SOLAS 74 as amended, Regulation II-2/7 & X/3,
2000 HSC Code 7, FSS Code 9 and IMO MSC.1/Circ. 1242.
The equipment are found to comply with following location / application dependent requirements
(for definition of each of the location classes, see below the table):
MODEL TEMPERATURE VIBRATION EMC ENCLOSURE
X3301 TEM-D VIB-B EMC-B ENC-C
The following accessories are offshore approved to the listed approvals, for use with the X3301 Flame Detector:
1.1 38 95-8704
APPENDIX G
ADDITIONAL APPROVALS
SIL 2
IEC 61508
Certified SIL 2 Capable.
Applies to specific models – refer to the SIL 2 Certified X3301 Safety manual (95-8720) for details.
VNIIFTRI
CERTIFICATE OF CONFORMITY TO TP TC 012/2011
TC RU C-US. ГБ06.B.00418
2ExdeIICT6/T5 IP66
T6 (Tamb = –50°C to +60°C)
T5 (Tamb = –50°C to +75°C)
Ex tb IIIC T130°C Db.
– OR –
1ExdIICT6/T5/T4 IP66
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
T4 (Tamb = –55°C to +125°C)
Ex tb IIIC T130°C Db.
RUSSIA
VNIIPO
CERTIFICATE OF CONFORMITY TO TECHNICAL REGULATIONS, GOST R 53325-2012
C-US.ПБ01.B.02910
BRAZIL
UL-BR 12.0093X
Ex d e IIC T6-T5 Gb IP66/IP67
Ex tb IIIC T130°C
T6 (Tamb = –50°C to +60°C)
T5 (Tamb = –50°C to +75°C).
– OR –
Ex d IIC T6-T4 Gb IP66/IP67
Ex tb IIIC T130°C
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
T4 (Tamb = –55°C to +125°C).
1.1 39 95-8704
APPENDIX H
DECLARATION OF CONFORMITY
1.1 40 95-8704
95-8704
FlexSonic ® Acoustic X3301 Multispectrum PointWatch Eclipse ® IR FlexVu ® Universal Display Eagle Quantum Premier ®
Leak Detector IR Flame Detector Combustible Gas Detector with GT3000 Toxic Gas Detector Safety System