Evolis 17.5 kV
0
User
0
Manual
2008
0
E
Ev
Evolis
Evolis description 2
Front 2
Handling 2
Handling 3
Storage 3
Caution 3
Corrective maintenance 20
Foreword 20
Ordering and replacing spare parts 20
Table for basic circuit breaker 20
Table for drawout circuit breaker and cradle 20
Trouble shooting
Upon circuit breaker tripping 21
Table for circuit breaker 21
Table for drawout circuit breaker and cradle 22
DE30355
A
Handling
70 kg
DE30356
200603
200604
Storage
200605
200606
70 ˚C
200607
ok
-40 ˚C
Caution
200608
Risk of burning
Risk of explosion
Before intervening on or in this device, the general power supply must be cut off.
Always use an appropriate voltage detection device to confirm the absence of the
voltage.
Replace all protective covers such as doors and panels before re-energising the
circuit breaker.
You shall refer to the installation guide no. 07897253EN for any information and
recommandation on the installation and connection Evolis.
200591
1 press
O OFF
200612
discharged
Closing cycle
200613
200592
1 press
crack !
indicators move to:
I ON
200615
discharged
Opening-closing cycle
200616
X6
1 charge
200593
crack !
charged
OK
200594
crack !
2 press
I ON
200615
discharged
Preliminary step
X6
200617
200618a
charged
OK
crack !
200594
200615
I ON
discharged
X6
charged
200617
200620a
OK
crack !
Cycle
O OFF
200611
200618
Opening
charged
OK
I ON
200614
200615
Closing
discharged
O OFF
200611
200612
Opening
discharged
O OFF
200611
200618b
X6
200617
200618a
charged
OK
crack !
200622
1
2
charged
OK
Padlocking facility.
200623
charged
OK
DE30357
TEST
TEST
Rack in/out
200627
In cubicle
DE30358
3
200630 1
On the ground
DE30376
1
DE30375
DE30376
2 1
DE30360
Conditions:
earthing switch open
no locking
circuit breaker open.
Conditions:
circuit breaker open
200611
DE30364
3
2
DE30365
DE30366
While pressing on the locking of the low voltage plug, turn the selector to the
operating position so as to lock the circuit breaker to the table.
Close the upper low voltage cover.
1 2
TEST TEST
DE30367
Conditions:
cubicle door closed.
1 Circuit breaker racked-out.
2 Selector in "operating position".
TEST
TEST
DE30368
Conditions:
earthing switch open
circuit breaker open
no locking.
1 Selector in the "movement" position.
2 Rack-in by rotating the handle to the right. End of rack-in is characterised by
the cluster’s force on the fingers up to status change on the indicator of racking
truck and the final stop.
3 Circuit breaker racked-in.
4 Selector in the "operating" position.
201265
2 1
3
B
Operating position
200648
Rack-in
201266
Rack-out
201267
Quick use
201269
1 1 2
+ +
2 2
1
+
2
1
+
2
2
+
1
2
1
+
2
1
+
2
1
+
2
3 3
3 3 3 3 3 3
4 4 4 4 4 4
2 1
3
4 4
201284
201283
Plug in the LV connector, after pushing in and holding down the red button under the
latch. Push the latch. Plug in the connecting lead and latch it.
201291
Before closing the access door to the removable part, raise the panel and check that
it is securely latched in the raised position. Close the door.
201287
201271
Conditions:
cubicle door closed
earthing switch open
no locking
circuit breaker open
2 1
201272
2
201273
3
201274
201276
Conditions:
cubicle door closed
earthing switch open
no locking
circuit breaker open
201277
201278
3
201279
201281
Open the cubicle door.
Unplug the LV auxiliaries connecting lead by pressing the red push-button and
pulling the connector latch (circuit breaker or contactor).
201282
201283
201290
201287
201292
Before closing the removable part access door, lower the panel.
Close the door.
201288
Fit 1 padlock to the flap protecting the mechanical opening push-button 1.
The key is released only if the removable part is in the rack in position and locked.
Operation
Check the operation of:
contact opening
contact closing.
DE30371
DE30372
DE30373
DE30373
The device is designed to operate for 10 years or 10000 operations under normal
conditions of use according to IEC 62271.
Recommended:
1 O-C operation every year at least
1 visual inspection every five years at least to be determined with Schneider group
service centres.
Truck with propulsion version: Interlocking with the cubicle's earthing switch Open the earthing switch or free the locked to
The circuit breaker on its truck is in the test position in or locked to prevent rack-in stemming from prevent rack-in on the cubicle.
the cubicle. the cubicle.
The selector can be turned to 3 positions:
The propulsion handle cannot be inserted all the way into
the truck to allow for the circuit breaker to be racked-in.
The low voltage plug does not fit into the provided space The locking rod for the circuit breaker's truck Raise the hook on the locking rod as much as
on the circuit breaker. and its selector. possible.
Insert the low voltage plug into the hook again
and in the circuit breaker terminals.
(see cradle installation manual).
The shutters are not locked when the circuit breaker is on Shutter lock Adjust the shutter lock and the raising roller
its truck and extracted from the cradle. located on the side of circuit breaker's truck. (see
cradle installation manual).
The circuit breaker's cluster arm touches the shutters. Shutter raising system Re-adjust the operating roller setting for shutter
raising on the side of the circuit breaker truck
(see installation manual).
If the shutters are bent, contact a Schneider
Electric service centre.
The shutter movement does not work. The shutter movement cable The cable is broken.
Shutter padlocking Shutter padlocking was maintained and when
the rack-in operation took place the system was
damaged.
In both cases, contact a Schneider Electric
service centre.
The circuit breaker has just been extracted from the cubicle LV plug interlocking. The low voltage plug interlocking prevents the
on its extraction truck: selector from rotating:
The selector cannot be turned to the operating position Open the circuit breaker's low voltage cover.
that also locks the circuit breaker in the extraction truck. Press the low voltage plug lock.
Turn the selector to the operating position.