A) Core type B) Shell type

Single phase transformer construction


전기
공 학
2014-02-21 2
SistemTenaga Elektrik
Ideal transformer
• Winding resistances are zero, no leakage inductance and iron
loss
• Magnetization current generates a flux that induces voltage
in both windings
N p Fm w
Ep =
2
Ns Fm w
Es =
2
Current, voltages and flux in an
unloaded ideal transformer
전기
공 학
2014-02-21 3
SistemTenaga Elektrik
Ideal transformer
• Loaded transformer

Currents and fluxes in a loaded ideal transformer


전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 4 4
SistemTenaga Elektrik
Ideal transformer
• Turn ratio is:
Np Ep
T= =
Ns Es
• The input and output complex powers are equal

E p I *p = S p = S s = E s I *s
Ep Is
T= =
Es Ip
전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 5 5
SistemTenaga Elektrik
5.3.1 Ideal transformer

Ip = Is /T Is
T

Vp Ep Es = V s

V p = Ep = T Es

Figure 5.25 Equivalent circuit of an ideal transformer


전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 6 6
SistemTenaga Elektrik
Ideal transformer
• Transferring impedances through a transformer
VP T VS 2 VS
ZP = =
IP æ IS ö
=T
IS
Z P = T 2 Z load
ç ÷
èT ø
IP IS
T
Thévenin equivalents
Vac VP VS Zload of transformer circuit

a) Original circuit with ideal


전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 7 7
SistemTenaga Elektrik
Transferring impedances through a
transformer
Thévenin equivalents of
IP
transformer circuit

b) Equivalent circuit when


Vac VP T2Zload secondary impedance is
transferred to primary side and
ideal transformer eliminated

(c) Equivalent circuit when primary


source is transferred to secondary
side and ideal transformer
eliminated
전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 8 8
SistemTenaga Elektrik
Real transformer
Fm

Fs_leakage

Fp_leakage

Leakage flux in the real transformer


전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 9 9
SistemTenaga Elektrik
Xp Rp Ist Rs Xs
T
Im
Ip Is
Vp Xm Rc Ep Es Vs

Equivalent circuit of a real transformer

전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 10 10
SistemTenaga Elektrik
Xp Rp Rst Xst Is
T
Im
Ip Ist
Vp Xm Rc Ep Es Vs

Figure 5.32 Modified equivalent circ


uit of a real transformer
전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 11 11
SistemTenaga Elektrik
Determination of transformer parameter
by measurement
• Open circuit test
– Provides magnetizing reactance and core loss
resistance
– Obtain components are connected in parallel

• Short circuit test


– Provides combined leakage reactance and winding
resistance
– Obtain components are connected in series

전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 12 12
SistemTenaga Elektrik
Short Circuit Test
Psh_s
Xp Rp Xs Rs
Figure 5.35 Equiv W I
alent circuit for shor Ish_s
V
t circuit test, measu
Vsh_s
rement at the secon
dary side

Xp / T2 Rp / T 2 Xs Rs Psh_s

Figure 5.36 Simplifi W I


ed equivalent circui Ish_s
V
t for short circuit te
Vsh_s
st

전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 13 13
SistemTenaga Elektrik
Short Circuit Test
Primary and
Psh_s
Xe_s Re_s secondary
W I impedances are
combined
Ish_s
V
Rp
Vsh_s Re _ s = 2
+ Rs
T
Xp
Simplified circuit for calculation of X e _ s = + Xs
2
series impedance T
전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 14 14
SistemTenaga Elektrik
Short circuit test evaluation

Psh_s Vsh_s
Re_s := Zsh_s :=
2 Ish_s
Ish_s

2 2
Xe_s := Zsh_s - Re_s

전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 15 15
SistemTenaga Elektrik
Open circuit test
Po_p
Xp Rp Xs Rs
I W
Io_p
V Xm_p Rc_p
Vo_p

Equivalent circuit for open circuit test, measurement at the


primary side.
Po_p

I W Simplified
equivalent circuit
Io_p
V Xm_p Rc_p
Vo_p

전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 16 16
SistemTenaga Elektrik
Open circuit test evaluation

2
(Vo_p ) Yo_p :=
Io_p
Rc_p := Vo_p
Po_p
1
Xm_p :=
1 1 2 1
Y = 2
+ 2 Yo_p -
R X Rc_p
2

전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 17 17
SistemTenaga Elektrik
Equivalent circuit obtained by measurement
Xe_s Re_s

Xm_p Rc_p

Equivalent circuit for a real transformer resulting from


the open and short circuit tests.

전기
공 학
2/21/2014
2014-02-21 360 Chapter 5 Transformers 18 18
SistemTenaga Elektrik
Very large three-phase network transformer. 전기
SistemTenaga Elektrik 공 학
A B C

VAN VBN VCN N

Vab Vbc Vca

a b c

A three-phase wye-delta transformer with three-legged iron core.


전기
SistemTenaga Elektrik 공 학
wye-wye (Y-Y) seldom used, imbalance and 3rd harmonics
problems
wye-wye-delta frequently used to interconnect high voltage
(Y-Y-Δ) networks (240 kV/345 kV). The delta
winding filters the 3rd harmonics, equalizes
the unbalanced current, and provides a path
for ground current
wye-delta (Y-Δ) frequently used as step down (345 kV/69 kV)
delta-delta (Δ-Δ) used for medium voltage (15 kV), one of the
transformers can be removed (open delta)
delta-wye (Δ-Y) step-up transformer in a generation station

Usual connections for three-phase transformers


전기
SistemTenaga Elektrik 공 학
IA Ia
A a
VAB VAN Van Vab Wye/wye
B VBN N n Vcn b
VCN Vbn
Y
S 3 S
I rate = =
c
Vrate 3 3 Vrate
C

Wye connected three-phase transformer


Np VAN I a VBN I b VCN I c
TY - Y = = = = = = =
Ns Van I A Vbn I B Vcn I C VAB = 3 VAN e j 30°
Np VAN I a Vab = 3 Van e j 30°
TY - Y = = =
Ns Van I A
전기
SistemTenaga Elektrik 공 학
Transformer
Supply
Three-phase network supplies
Load a load through a transformer.
Network
Y-Y

Vnet_AN VAN Van Vload_an


Xnet Xtr_s
A
Ia a
IA
n Equivalent circuit of the wye-
N
wye transformer system

Supply Network Transformer Load

Xnet Xtr_s Single-phase equivalent circuit


for phase A of the three-phase
IA Ia
Vnet_AN VAN Van Vload_an wye-wye transformer system

전기
공 학
2014-02-21
2/21/2014 360 Chapter 5 Transformers 23
SistemTenaga Elektrik
VAN
Transformer
A IA Iba a Ia

AC
VAN Vab Iab
VBN VAB Vab
VCA IB Icb Vca Ib
B b
Ica
Iac
AC
VBN Vbc Ibc
VCN VBC Vbc

C IC Iac c Ic

AC
Load
VCN Vca
Supply N

Wye-delta connected transformer , 5.4.2


전기
SistemTenaga Elektrik 공 학
IA Ia
A a
a Iac D
S 3 S
VAB VAN Vab
I rate = =
Iba c
Ib Vrate 3 Vrate
VCA B VBN VCN b Vca
N Icb
b Vbc
VBC Ic
C c

Figure 5.52 Wye-delta connected transformer , currents and


voltages
Np
VAN I ba
TY -Δ = = =
Ns Vab IA

VAB = VAN - VBN = VAN - VAN e - j 120° = 3 VAN e j 30°

I a = I ba - I ac = I ba - I ba e - j 240° = 3 I ba e - j 30°
전기
공 학
2/21/2014 360 Chapter 5 Transformers 25
SistemTenaga Elektrik
Rtr_p Xtr_p Xtr_s Rtr_s
spe
T

IA Ia
Rc Xm VAN Van Vs_an
Vp_AN

Y-D
Single-phase equivalent circuit of a wye-delta transformer.

Vab = 3 Van e j 30°

T spe
Y -Δ =
VAB VAN 3 e j 30° VAN
= = TYspe-Δ =
*
I
a (
I
= ba
3e )
- j 30° *

Vab Vab Van *


I I *A
A
전기
공 학
2/21/2014 360 Chapter 5 Transformers 26
SistemTenaga Elektrik
IA Ia
A Vbn
a
IAB
VAB Vab
IB n Van Ib
VCA B ICA Vcn b Vca
VBC Ic Vbc
IBC
IC c
C

Figure 5.54 Delta-Wye connected transfor


mer
I A = I AB - I CA = I AB - I AB e - j 240° = 3 I AB e - j 30°

VAB VAB e V - j 30°


I * I *a I *a
TΔspe- Y = = = AN = a TΔspe- Y = * =
Vab Van 3 Van I *
A
IA ( 3 I AB e )
- j 30° *

전기
SistemTenaga Elektrik 공 학
IA Ia

A a
IAB Iba
VAB Vab
B ICA Iac
b

c
C
Delta-Delta connected transformer

Np VAB I a I ba
TΔ -Δ = = = =
Ns Vab I A I AB
전기
SistemTenaga Elektrik 공 학
Transformers
Three-phase Transformer Relations

Windings
Transformer Primary and Secondary Phase
Placed on the
Connection Voltage Phase Relation Shift*
Same Leg
Wye-Wye VAN is in phase with Van Zero A and a

Wye-Delta VAN is in phase with Vab 30° A and ab

Delta-Wye VAB is in phase with Van –30° AB and a

Delta-Delta VAB is in phase with Vab Zero AB and ab

* Note: Phase shift lead between line-to-line voltages, VAB and Vab, and line-to-
neutral voltages, VAN and Van, and line currents, IA and Ia.

2/21/2014 360 Chapter 5 Transformers 29


High Low
voltage voltage C
A W

V
AC AC

AC
V
A W B

Full rated
voltage

Open circuit test for three-phase transformer parameter me


asurement

Vo_ll := 230V Io := 13A Po_3f := 550W


전기
공 학
2014-02-21
2/21/2014 360 Chapter 5 Transformers 30
SistemTenaga Elektrik
Open circuit test
Vo_ll
Vo_ln := Vo_ln = 132.791V
3

Po_3f
Po_1f := Po_1f = 183.333W
3

2
Vo_ln
Rc := Rc = 96.182W
Po_1f
전기
공 학
2014-02-21
2/21/2014 360 Chapter 5 Transformers 31
SistemTenaga Elektrik
Open circuit test

Io
Yo := Yo = 0.098S
Vo_ln

1
Xm :=
2 1 Xm = 10.273W
Yo -
2
Rc

전기
공 학
2014-02-21
2/21/2014 360 Chapter 5 Transformers 32
SistemTenaga Elektrik
High Low
C
voltage voltage
W A

V
AC AC

AC
V

B
W A
Reduced voltage

Short circuit test for three-phase transformer parameter


measurement

Vs_ll := 160V Is := 16A Ps_3f := 1200W


전기
공 학
2014-02-21
2/21/2014 360 Chapter 5 Transformers 33
SistemTenaga Elektrik
Transformers
Short circuit test
Vs_ll
Vs_ln := Vs_ln = 92.376V
3

Ps_3f
Ps_1f := Ps_1f = 400W
3

Ps_1f
Rs := Rs = 1.563W
2
Is
Transformers
Short circuit test

Vs_ln
Zs := Zs = 5.774W
Is

2 2
Xs := Zs - Rs Xs = 5.558W
v George G. Karady & Keith Holbert, Lecture:
EEE 360 Energy Conversion and Transport
v T. Wildi, Electrical Machines, Drives, and
Power Systems, Prentice Hall