TOTAL PROTECTION for POWER SYSTEMS

ASHIDA PROTECTION RELAYS


ANSI terminology
Term Function
2 Time delay starting or closing relay
3 Trip circuits monitoring
ASHIDA is a pioneer in Protection Relays for Power Systems and
21 Distance protection
Substation Automation Systems that enable utility and industry customers 25 Synchrocheck
to improve performance economically. 27 Undervoltage function
27R Additional undervoltage function
ASHIDA Protection Relays for Power Systems: We have complete 37 Undercurrent detection
solutions for Industrial and commercial customers, with a broad range of 46 Unbalance negative sequence
products, systems and services for power transmission & distribution. current protection
47 Voltage unbalance protection
ASHIDA ASCADA-SAS Substation Automation Systems: Blends a 49 Thermal image
robust product and service portfolio with end-user expertise to deliver 50 Phase instantaneous overcurrent
solutions for control, monitoring , protection, and plant integration across function

the full range of substation, process and utility industries. 50C Transformers tank protection
50FA Instantaneous overcurrent with
Our Strength: With our strong R&D team and full-fledged production harmonics restrain
plant, facility to design any emended & DSP base systems, application 50N Neutral / Ground Instantaneous

knowledge and local expertise, we offer products, systems, solutions and overcurrent function
50Ns Sensitive neutral instantaneous
services that allow our customers to improve their operations.
overcurrent function
Our people work together seamlessly to deliver benefits for our 50N/50Ns Sensitive neutral instantaneous
customers. overcurrent unit
Our way of doing business is values-based and performance-oriented. 50Nd/51Nd Neutral unbalance (WYE connection)
50d/51d Current unbalance in double WYE
Some of our Achievements include: Capacitor banks
> Complete Protection solutions, including distance protection for newly 50s+62 Circuit breaker failure protection
converted 25kv traction of prestigious Mumbai suburbs railway 51 Phase overcurrent function

network. 51N Neutral overcurrent function


50N/51Ns Neutral/Sensitive neutral time
> Specialised DC protection systems for Mumbai & Kolkata metro
overcurrent
railway. 51RB Protection against blocked rotor
> Various SCADA systems for upto 400KV sub-stations, integrated with 59 Overvoltage function
various numerical relays, GIS systems, etc for more than 3years. 59N Zero sequence overvoltage function
64 Ground faults protection
35 years of technological service 66 Excessive number of start ups
(motors)
Ashida Electronics Pvt. Ltd is started in 1970 by technocrat
67 Directional phase overcurrent
Mr. Manohar P. Kulkarni. Soon we established our self as 67N Directional neutral overcurrent
reputed manufacturer of non-destructive testing 67NA Directional zero sequence
instrument for Geo-logical application. From 1985 overcurrent (Isolated neutral
onward we started manufacturing of Protection networks)
74TC Tric Circuit Supervision
Relays for Power Systems. In 1998 our company was
79 Recloser
certified with ISO 9001and year 2000 we shifted in our
81 M/m Over/under frequency
new full-fledged production plant of 25000 sq feet. 87 Differential protection
In 2002 we were awarded 1st prize of very prestigious 95 Special neutral overcurrent function
Government of India - Nation Award for special 95N Special neutral overcurrent function.

efforts in R&D.
Instantaneous High Stability
Restricted E/F Relay.
Model ANSI Function
Definite Time Overcurrent Relay
ACAG14 50N Single Pole REF Relay
(Tuned to 50Hz)
Model ANSI Function
ACAG34 3x50N 3 pole version of ACAGl4
(Tuned to 50Hz) ACTU 12 50N+2 Definite Time Earth Relay
ADAG3x 3x51+50 IDMT with 2 O/C + 50HZ
ACTUM 15 50NS Sensitive E/F Relay with
tuned Instant EF with
timer
char. 1 & 2.
ADAG5x 2x51 IDMT with 2 O/C + 50Hz ACTU 32P 3x51+3x2 3 O/C Relay
High speed Biased
+51N tuned Instant EF + High differential relay.
+2x51 Fault with char. 1 & 2. Specification Model ANSI Function
x = IDMT Characteristic (C1-C5)
1. Input C.T. : 1/5 Amp
ACDF31H 3x87 2 winding Tx diff relay
Specification 2. Setting : ACTU 12 : 5% - 80 o far Current with harmonic restrain
1. Input C.T : 1/5 AMP. Inst - 10 sec for timer
ACTU32P : 50 %-200 a for Current ACDT31H 3x87 2 winding Tx diff relay
2. Setting : ACAG 14 : 5%-80%
without harmonic restrain
ACAG 34 : 5%-80% Inst - 25 sec for timer
ADAG 3x : 50 % -200 % for Phase ACTUM15 : 5mA-550mA
5 % - 80 % for EF Specification
for Current
ADAG 5x : 50% - 200% for Phase
Inst - 10 sec for timer 1. Input C.T : 1/5 AMP
5% - 80% for E/F
INST - 20N for HF 3. Pick up : 1.1 times of setting 2. Setting : Bias setting -15%, 30%&45%
3. Pick Up : 1.1 times of Setting 4. Reset time : 200 mS after removal of fault HF setting -2N -20N
4. Reset time : 200mS - 500mS after Removal 3. Pickup : 20% of rated
current
of Fault 4 Reset time : 100mS
5. Operating time : less than 50mS 5. Accuracy : Better than Class 5 as per IS 3231
6. Accuracy : Better than Class 5 as Per IS 3231 6. C.T Burden : 0.2 VA max 5. Operating time : 25mS
7. C.T Burden : Less than 02VA 7. Output : 2 No trip duty contact 6. C.T Burden : 0.2 VA max
8. Aux. DC Supply : 24. 30V, 110 or 220V 8. Insulation : 2.0 Kv as per IS 3231 7. Output : 2No Trip duty contact
9. Burden of Aux. Supply 8. Insulation : 2.0kv as per IS 3231
9. Impulse : 5.0 Kv as per IS 8686
: Less than 10VA
10. Aux. Supply : 18-52 / 77-250V 9. Impulse : 5 0 kv as per IS 8686
10. Insulation : 2.0 KV as per IS 3231
11. Impulse : 5.0 KV as per IS 8686 11. Thermal : Continuous 4 times of rated 3 sec 10. Thermal withstand
12. Thermal withstand withstand 40 times of rated : Continuous d times of rated
: Continuous 4 times of rated For 3 sec 40 Times of rated
For 3 sec 40 times of rated 11. Aux. supply : 18 - 52V and 77 - 250V
13. Output : 2 No trip duty contact
MODEL CASE CUT-OUT 12. Burden on Aux. Supply : Less than 10VA
ACTU 12 CSB - 150 92 x 92 mm
MODEL CASE CUT-OUT MODEL CASE CUT-OUT
ACTU 32P CSA - 150 138 x 138 mm.
ACAG14 CSB - 150 92 x 92 mm. ACDF31H CSD - 120 - V 138 x 280 mm
ACAG34 CSA - 150 138 x 138 mm. ACTUM 15 CSB - 150 92 x 92 mm
ACDT31H CSD - 120 - V 138 x 280 mm
ADAG3x /5x CSA - 150 138 x 138 mm.

IDMT characteristics C4A - Extremely Inverse


IDMT characteristics C4 (Matching to Electro mechanical Relay) IDMT characteristics C5
Extremely Inverse of 10 Times 0.8 sec. of 10 Times 0.6 sec. Long time Inverse of 10 Times 13.3 sec.
100.00 100.00 1000.00
80.00 80.00 800.00
70.00 70.00 700.00
60.00 60.00 600.00
50.00 50.00 500.00
40.00 40.00 400.00
30.00 30.00 300.00

20.00 20.00 200.00

10.00 10.00 100.00


8.00 8.00 80.00
7.00 7.00 70.00
6.00 6.00 60.00
TIME (TIME MULTIPLIER SETTING) FOR IDMT

TIME (TIME MULTIPLIER SETTING) FOR IDMT

TIME (TIME MULTIPLIER SETTING) FOR IDMT


IDMT CURVES

5.00 5.00 50.00


4.00 4.00 40.00
3.00 3.00 30.00

2.00 2.00 20.00


IDMT CURVES
TIME (IN SECONDS)

TIME (IN SECONDS)

TIME (IN SECONDS)


IDMT CURVES

1.00 1.00 10.00


0.80 0.80 8.00
0.70 0.70 7.00 X 1.0
0.60 0.60 6.00 X 0.9
0.50 0.50 5.00 X 0.8
0.40 0.40 4.00 X 0.7
X 0.6
0.30 0.30 X 1.0 3.00 X 0.5
X 0.9 X 0.4
X 0.8
0.20 X 1.0 0.20 X 0.7 2.00 X 0.3
X 0.9 X 0.6
X 0.8 X 0.5
X 0.7 X 0.4 X 0.2
X 0.6 1.00
0.10 X 0.5 0.10
X 0.3
0.08 X 0.4 0.08 0.80
0.07 0.07 0.70
0.06 X 0.3 0.06 X 0.2 0.60 X 0.1
0.05 0.05 0.50
0.04 X 0.2 0.04 0.40
0.03 0.03 X 0.1 0.30 X 0.05

0.02 X 0.1 0.02 0.20


X 0.05

0.01 X 0.05 0.01


1.0 2 3 4 5 6 7 8 9 10 15 20N 1.0 2 3 4 5 6 7 8 9 10 15 20N 1.0 2 3 4 5 6 7 8 9 10 15 20N
N = CURRENT (MULTIPLE OF SETTING) N = CURRENT (MULTIPLE OF SETTING) N = CURRENT (MULTIPLE OF SETTING)
Definite Time
Under/Over Voltage Relay.
Model ANSI Function
Instantaneous Over Current / Inverse time
ASUV 27 Definite time under voltage
Earth Fault Relay Voltage Operated Relay with adjustable time setting

Model ANSI Function Model ANSI Function ASUVF 27 Definite time under voltage
fix time setting
ACAG17 50 Single Pole O/C Relay AVDG 11 59 Inverse Time Over Voltage
Relay ASOV 59 Definite time over voltage
ACAG12 50N Single Pole E/F Relay with adjustable time setting
AVDG 13 27 Inverse Time Under Voltage
APR4H 3x50+50N 3 O/C + EF Relay Relay ASOVF 59 Definite time over voltage
with fix time setting
AVDG 14 50N Inverse Time Neutral
Specification Displacement Relay AOUV 27+59 Definite time under / over
voltage relay with
1. Input C.T : 1/5 AMP adjustable time
2. Setting : ACAG 17 : 100% -800 a Specification
AUV 3P 27 3 Phase under voltage
ACAG 12 : 5% -80 0 1. Input voltage : 110VAC
Relay with adjustable timer
APR4H : 0.5Amp-15.5Amp 2. Setting : AVDG 11 : 110-170%
for phase & E/F AVDG 13 : 30 - 90 % AOV 3P 59 3 Phase over voltage
AVDG 14 : 5.4 - 20V Relay with adjustable timer
3. Operating time : less than 50 mS
4. Accuracy class : Better than Class 5 3. Pick Up : 1.1N of setting
as per IS 3231 4. Resetting Voltage : +/-10 of set value Specification
5. Pick Up : 1.1 times of Setting 5. Operating Time
6. Reset time : 200mS - 500m5 after Removal of : AVDG 11 : At 1.5 lime = 7.0 sec 1. Input : AC or DC 24,30,110 & 220V
Fault Current AVDG 13 : At OV = 5.0 sec 2. Setting : For ASUV & ASUVF 45-95%
7. C.T Burden : Less than 0.1 VA AVDG 14 : At 5 times = 10.5 sec For ASOV & ASOVF 105 - 155 %
8. Aux. Supply : 24, 30V, 110 or 220V 6. Accuracy : Class of 7.5 3. Plck-up : 1.1N of setting-OV / 0.95N-UV
9. Output : 2 No trip duty contact 7. Burden on PT : 1 VA 4. Reset voltage : 5 % of rated
10. Insulation : 2.0 KV as per IS 3231 8. Output : 2 No trip duty contact 5. Aux. Supply : 24,30,110 & 220V
11. Impulse : 5 0 KV as per IS 8686 9. Insulation : 2.0 kv as per IS 3231 6. Burden on Aux. Supply : Less then 5.0VA
12 Thermal withstand : Continuous 4 times of 10. Impulse : 5.0 kv as per IS 8686 7. Burden on monitor supply : Less then 2.0VA
rated For 3sec 40 times of rated 11. Aux. Supply : 18 - 52V and 77 - 250V 8. Thermal with stand : 2 times of normal voltage
12. Burden on Aux. Supply : Less than 10VA continuous
9. Output : Annunciation Duty / Trip Duty, to be
MODEL CASE CUT-OUT specified
ACAG17 / 12 CSB - 150 92 x 92 mm. 10. Insulation : 2.0 KV as per IS 3231
MODEL CASE CUT-OUT
APR 4H CSA - 150 138 x 138 mm. 11. Impulse : 5.0 KV as per IS 8686
AVDG xx CSA - 150 138 x 138 mm.

MODEL CASE CUT-OUT


IDMT Characteristic of 10.5 sec At 5 Time ASUV CSB - 150 92 x 92 mm.
Netral Displacement Voltage Relay Type ASUVF CSB - 150 92 x 92 mm.
50.0 ASOV CSB - 150 92 x 92 mm.
40.0 ASUVF CSB - 150 92 x 92 mm.
30.0 AOUV CSB - 150 92 x 92 mm.
20.0 AUV 3P CSA - 150 138 x 138 mm.
Time / Voltage Characteristic of Over Voltage AOV 3P CSA - 150 138 x 138 mm.
Relay AVDG 11 IDMT 7 Sec At 1.5 Times 10.0
Operating Time In Seconds

9.0
8.0
18.0 7.0 Time / Voltage Characteristic of Under Voltage
6.0
5.0
Relay AVDG 13 IDMT 5 Sec At 0.0 Voltage
16.0 4.0
Operating Time In Seconds

3.0 45.0
14.0 x 1.0
x 0.9
2.0 x 0.8 40.0
x 0.7
12.0 x 0.6
35.0
x 0.5
Operating Time in Seconds

10.0 1.0 x 0.4


0.9 30.0
0.8 x 0.3
0.7 25.0
8.00 0.6
0.5 x 0.2
20.0
6.00
0.4

0.3 15.0
x 0.1
4.00
10.0
0.2
2.00 5.00

0.00 0.00
0 1.0 2.0 3.0 2 3 4 5 6 7 8 9 10 0 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 00.0
Multiple Of Plug Setting Multiple of Plug Setting Percentage of Closing Voltage

5
Auxiliary Relay
Model ANSI Function

AVAJH 13 High Speed Master Trip


Relay (1 Element )

AVAJH 23 High Speed Master Trip


Relay (2 Element )
Trip CIRCUIT Supervisory Relay
AVAJH 33 High Speed Master Trip
Relay (3 Element ) Model ANSI Function

AVAJHM 23 High Speed Tripping Relay ATSR31A 74TC Trip circuit monitor
(2 Element In Series)
Specification
AVAJHM 33 High Speed Tripping Relay
(3 Element In Series) 1. Control Supply : 24 / 30 / 110 / 220 VDC
Specify while ordering
AVA 11 Voltage Operated Auxiliary 2. Aux. annunciation supply
Relay (1 Element ) : 24 / 30 / 110 / 220 VDC.
AVA 21 Voltage Operated Auxiliary Specify while ordering
Relay (2 Element ) 3. Trip coll DC resistance
Auto Recloser Relay. : To be less then 500 Ohms
AVA 33 Voltage Operated Auxiliary
Model ANSI Function 5. Operating Time : 10 sec
Relay (3 Element )
6. Control and auxiliary supply
AEAR1 79 Single shot auto-recloser AVA 21D DC Failure Alarm Relay : can be made parallel If required
Note : For other models Please refer detail technical catalogues 7. Supervision : Pre Closing & Post Closing
AEARM/2S 2x79 2 shot Auto-recloser

APAR4xS2 2x51+51N IDMT 20/c+EF+High Fault Specification MODEL CASE CUT-OUT


+2x50 +2 shot auto recloser
+50N+2x79 1. Operationmits ATSR31 CSB - 150 92 x 92 mm.
: 50 to 120% of rating for AVAJH
20 to 50% for AVA
Specification 2. Operational Time
: 10 - 15 mS at normal rated voltage
1. Input : 1/5 AMP
for AVAJH, 20 - 25 mS for AVA
2. Setting 3. Coil Rating : 24V / 30V / 110V / 220V or AC
APAR4xS2 : 50 %-200 % (or phase 4. Burden : @ 30VDC / 24VDC: 8 watts
5 %-80 % for Earth Fault @ 110 VDC: 8 watts
INST-20N and Bypass for @ 220 VDC: 18 watts
5. Operational Indicator
high fault : Mechanical Flag
Reclaim time 50-300sec (Red for Alarm, white for Normal)
Reclose 1 : 30-60sec 6. Contacts : 4 pair of Hand Reset
Reclose 2 : 60sec Fixed 7. Relay Conforms : IS:3231 fully for all
requirement
AEARM/2S Reclose 1 : 10-60sec
Reclose 2 : 30-180sec 9. Contact Rating
Reclose 3 : 200-300sec Make & Carry Make & Carry
Break
3. Pickup : 1.1 N of setting Continuous For 3.0 ssc.
4. Reset Time : 200mS after removal of fault
AC 1250 VA with 7500 VA with 1250 VA with
current
maxima of maxima of maxima of
5. Accuracy : Within class 2.5 as per IS 3231 5 A & 660 V. 30 A & 660 V. 5 A & 660V.
6. C.T. Burden : Less than 0.2 VA
7. Aux DC Supply : 18-52VDC or 77-250VDC DC 1250 VA with 7500 VA with 100W Resistive
maxima of maxima of 50W Inductive
8. Burden on Aux Supply : Less then 10VA
5 A & 660 V. 30 A & 660V.
9. Insulation : 2.0 KV as per IS 3231
10. Impulse : 5.0 KV as per IS 8686
11. Thermal with Stand MODEL CASE CUT-OUT
: Continuous 4 times of rated AVAJH13 CSB - 80 92 X 92 mm.
for 3 sec 40 times of rated AVA11 /33 CSB - 80 92 X 92 mm.
12. Output : 2 NO trip duty contact AVA21 /21D CSB - 80 92 X 92 mm.
AVAJH23 / 33 CSC - 80 - H 92 X 186 mm.
MODEL CASE CUT-OUT AVAJHM23 /33 CSC - 80 - H 92 X 186 mm.
AEAR1 CSB - 150 92 x 92 mm.
AEARM2S CSC - 150 - H 92 x 192 mm.
APAR42 S2 CSD - 150 - V 138 x 280 mm.
Specification
Current Operated IDMT Relay 1. Input C.T : 1/5 AMP.
2. Setting Phase : 50 % - 200 %
Model ANSI Function
E/F: 5%-80%
APR1xP 51 Single Pole O/C Relay Phase HF : 200 % - 2900% - ¥
with char. 1 or 2. Earth HF : 100 % - 1200 % - ¥
APR1xPH 51+50 APR1xP with Comm. HF : INST - 20N - ¥
Instantaneous High Fault.
Directional setting :
APR1xE 51 N Single Pole Earth Fault Phase : 30degree, 45 deg, or
Relay with char. 1 or 2.
60 deg lead
APR1xEH 51N+50N APR1xE with
Earth : 14deg, 30deg, 45 deg, or
Instantaneous High Fault.
60 deg Lag
APR3x 2x51+51N 2 O/C+1 E/F IDMT Relay
3. Pick Up : 1.1 times of Setting
with char. 1 or 2.
Current Directional 4. Reset time : 200mS after Removal of Fault
APR3xHP 2x50+ APR3x with Instantaneous
current
51Nx50 High Fault for phase. Current Operated IDMT Relay 5. Operating time
APR3xHS 2x51+51N APR3x+Separate High
+2x50 Fault Setting tor phase Model ANSI Function : As per IDMT Characteristic l
+50N & Earth. X = IDMT type
ACDR1xHP 67+50 Single Pole ACDR Relay
APR3xH 2x51+51N APR3x Relay with High 1-5 = C1-C5
for phase and non
+50+50N Fault Setting common directional High Fault with 6. Accuracy : Class 2.5
to phase and Earth Fault. char. 1 or 2. 7. C.T Burden : 0.2 VA max
APR3xP 3x51 3 Pole IDMT over current 8. Output 2 No trip duty contact
Relay. ACDR1xHPD Single Pole ACDR Relay
67+50 for phase and directional 9. Aux. Supply : 18VDC - 52VDC OR
APR3xPH 3x51+3x50 APR3xP with High Fault with Char.1 or2. 77VDC - 250 VDC/AC
Instantaneous High Fault. 10. Burden of Aux. Supply
APR4x 3x51+51N 3 O/C + EF IDMT Relay. ACDR1x HE 67N+50N Single Pole ACDR for
: Less than 10 VA
with char. 1 or 2 Earth Fault and non
directional High Fault with 11. Insulation : 2.0 KV as per IS 3231
APR4xHP 3x51+51N APR4x Relay with High Char. 1 or 2. 12. Impulse : 5.0 KV as per IS 8686
+3x50 Fault for phase
13. Thermal with stand
APR4xHS 3x51+51N APR4x Relay with ACDR1xHED 67N+50N ACDR 1 x HE with
directional High Fault with : Continuous 4 limes of rated
+3x50 separate High Fault for
phase & Earth. char 1 or 2 For 3sec 40 times of rated

APR4xH 3x51+51N APR4x Relay with Hi ACOR4xH 3x67+67N 4Pole directional O/C &
+3x50 Fault Setting common to +3x50+50N E/F relay with non
+50N phase & Earth. Model CASE CUT-OUT
directional HF with char.
Note: Draw-out Cabinet Optional 1 or 2. APRxxx CSA - 150 138 x 138 mm
ACDR1xx CSA - 150 138 x 138 mm
ACDR4xHD 3x67+67N 4 Pole directional O/C &
+3x50+50N E/F relay with directional ACDR4xx CSD - 120 - V 138 x 282 mm
HF with char 1 & 2

IDMT characteristics C2 IDMT characteristics C3


Normal Inverse 10 time 1.3 sec. Very Inverse 10 Times 1.5 sec.
10 100.00
9 80.00
8 70.00
7 60.00
6 50.00
5 40.00
IDMT CURVES

4 30.00

3 20.00
IDMT characteristics C1
Normal Inverse 10 time 3.0 sec. 2
10.00
10 8.00
7.00
9 6.00
TIME (TIME MULTIPLIER SETTING) FOR IDMT

TIME (TIME MULTIPLIER SETTING) FOR IDMT


IDMT CURVES

8 5.00
7 1.00 X 1.0
0.90 X 0.9 4.00
IDMT CURVES

6 0.80 X 0.8
3.00
TIME (IN SECONDS)

5 0.70 X 0.7
4 0.60 X 0.6
2.00
0.50 X 0.5
TIME (IN SECONDS)

3 0.40 X 0.4
TIME (TIME MULTIPLIER SETTING) FOR IDMT

X 1.0 1.00
2 X 0.9 0.30 X 0.3
0.80
X 0.8 0.70
X 0.7 0.60 X 1.0
0.20 X 0.2 X 0.9
X 0.6 0.50 X 0.8
X 0.5 0.40 X 0.7
1.00 X 0.6
0.90 X 0.4 0.30 X 0.5
0.80 X 0.4
TIME (IN SECONDS)

0.70 0.10 X 0.1 0.20


X 0.3 0.09 X 0.3
0.60 0.08
0.50 0.07 X 0.07 X 0.2
X 0.2 0.06
0.40 0.10
0.05
0.08
0.30 0.04 0.07
0.06 X 0.1
X 0.1 0.05
0.03
0.20 0.04
0.03 X 0.05
0.02
0.02
X 0.05
0.10
0.09
0.08
0.07 0.01
1.0 1.3 2 3 4 5 6 7 8 9 10 15 20n 1.0 1.3 2 3 4 5 6 7 8 9 10 15 20N 1.0 2 3 4 5 6 7 8 9 10 15 20N

N = CURRENT (MULTIPLE OF SETTING) N = CURRENT (MULTIPLE OF SETTING) N = CURRENT (MULTIPLE OF SETTING)

3
Numerical Under/Over Frequency
Monitoring Relay- AUOFMR2
Specification
Accurate Frequency monitoring with Crystal
>
Controlled references.
Trip Frequency Point can be selected with 0.01 Hz
>
Resolution.
ASHIDA
Self-Calibration and check ON-Site facility inbuilt.
> RELAY TESTINGTIMER UNIT (ARTU)
Instrument tested to withstand as per IS:3231,
>
ARTU: Micro-Controller based auto ranging timer /
IS:8686-1977 Specification. counter unit of operating / dropout time of time operating
Two Independent set points programmable as Under
> relay.
or Over Frequency.
RS232 & RS485 Communication Port for remote
> Specification ASHIDA ASCADA-SAS System.
SCADA.
1. Power Supply : 250 VAC ASHIDA SCADA Software coupled with ASHIDA's
AC Input from 230 / 110 / 63 V AC PT for Frequency
>
2. Measurement Range FCCM series of modules forms a scalable & flexible
Sensing.
: 1 mS to 99999 Sec. Auto ranging. ASCADA-SAS System This system can be employed to
Frequency setting Range : 49.99 Hz to 40.00 Hz in
>
steps of 0.01 Hz for Under Frequency and 50.01 Hz 3. Measurement Mode make a satellite sub-station completely un-manned,
to 60.00 Hz in steps of 0,01 Hz for Over Frequency. : NO / NC Start. controlled from a central location Such a scheme can
Accuracy Setting : +/- 0.01 Hz Repeat Accuracy
> NO / NC Stop. serve as an Important tool in Energy Management &
better then 0.05 Hz. 4. Accuracy : 0.1 % Audits and also completely encompass the functions of
Delay Time Adjustment : 0 to 99.9 sec Accuracy +/-
> 5. Display : 5 Digits bright 7 segment LEDs. Event Sequence Recording.
5% or +/- 0.02s whichever is Higher. 7. Cabinet : Table Top 110 x 200 x 120 mm.
Programmable Hysterisis.
> This Intuitive GUI based system is built on
This Relay is also available with 2 Stage df/dt and 2
> internationally standard components. Any available
Stage Under/Over Frequency Features. communication medium (ea. PLCC, VHF, dial-up,
Cutout : 186 x 92 mm.
> Dedicated cables, etc.) can be used to link the Sub-
station equipment to the central software using
series appropriate communication interfaces The modular
Feeder Protection Relay A D R 24 1 B
ON
approach gives a benefit of add-on simplicity with
PKP
maximum economic benefit.
FAULT ANSI IEC PROTECTION FUNCTIO
50 N
I>> INSTANTANEOUS OVE RS 232
R CURRENT
50N IE>>
RSP/LC INSTANTANEOUS EART
H FAULT
50, 51 I>t, Ip TIME OVER CURRENT
(PHASE)
50N, 51N IE>t, IEP TIMR OVER CURRENT
TRIP 79
(EARTH)
AUTO RECLOSER
74TC TRIP CIRCUIT PER VI
BREAKER CONSU
TROL
SION.

ASHIDA RELAY TESTING UNIT


VARIABLE FREQUENCY (ARTUVF)
The ARTUVF/S unit is specially designed to suit relay
testing designed of power station testing engineers. The series
ARTUVF/S is a cabinet, which has all the necessary
functions for relay testing viz. Auxiliary source, Time
Interval Meter up to 1ms resolution etc. After adding ASHIDA Numerical Protection Relay
optional phase shifter and phase angle meter, the ADITYA Numerical Relay having Common User
ARTUVF/S become a complete relay-testing unit for Interface & Communication Interface. Various
testing of all available Static / Electromechanical TSS protection such as OC / EF (IDMT / Definite time) / ASHIDA Digital Traction Protection
Transformer differential / Directional / Reverse power /
relays, like IDMT Over Current (OCR- Relays for Railways
1/2/3)/REF/Under-over Voltage/ Power- Directional / UV / OV can be available.
Distance Protection (DPR, WPC)/ Delta-I Protection/ Range of numerical / static protection relays & 01-25 kv
Auxiliary Relays etc. Specification AC traction application.
RS232 and RS485 Communication port for Local /
> ADDR/1: Complete Feeder Protection relay for 25 kv /
Specification Remote SCADA System AC system including Distance / WRC / PT
Variable AC current: - 0-200Amp with 250VA. Load parameter on LCD Display
> Fuse Fault location ETC. elements.
Variable AC voltage : - 0-300 VAC. Latching of fault parameter
> AIDI/1C: Delta-I type high resistive fault selective
Variable DC voltage : - 0-360 VDC. Programming Via local keys as well as remote
> relay. (vectorial)
In-built auxiliary power supply: - 30 / 110 / 220VDC. programming Via communication port .
APFO/1: Digital Pento flash over relay.
Back-lit LCD display for settings & parameter
>
Fix AC voltage : for direction/power relay
testing - 63.5 V / 110 V AC. display ADTR/1: High Resistance fault detection relay for
Pass-word protection
> 1.5kdc / 750vdc protection systems.
Time measuring : Micro-controller based unit
with 1ms resolution. Communication with IEC-870 protocol
> (Refer detail Catalogue)
Special provision : Relays ON Delay / OFF Disturbance recording
>
delay time measurement. Tested as per IEC 60255 standard
>

7
CABINET STYLE ‘A’ CABINET STYLE ‘B’
PANEL CUTOUT PANEL CUTOUT
92
138 FRONT 110

FRONT 160 92 MINIMUM GAP


110 FOR VER.
138 MOUNTING.

MINIMUM GAP CAP 75


160 FOR VER.
MOUNTING.
36
CAP 75
75

36

SIDE
‘D’ MINIMUM GAP FOR HOR.MOUNTING.
75
ALL DIMENSION ARE IN MM.
‘D’ CAB. STYLE
80 CSB - 80
1 3 5 7 9 11 13 15 17
120 CSB - 120
BACK
SIDE ‘D’ MINIMUM GAP FOR HOR.MOUNTING. 30 2 4 6 8 10 12 14 16 18 150 CSB - 150
91 200 CSB - 200
ALL DIMENSION ARE IN MM.

‘D’ CAB. STYLE


1 3 5 7 9 11 13 15 17 A1 3 5 7 9 A11 13 15 17 19 A21 80 CSA- 80
C1 C2 C3 C4 C5 C6 C7 C8 C9 120 CSA - 120
BACK
150 CSA - 150 CABINET STYLE ‘C’ - V
30 2 4 6 8 10 12 14 16 18 A2 4 6 8 10 A12 14 16 18 20 A22
150 CSA -150D
137 200 CSA - 200
TERMINAL TYPE1 TERMINAL TYPE2 PANEL CUTOUT
92

203
FRONT
CABINET STYLE ‘C’ - H
186

PANEL CUTOUT
MINIMUM GAP
FRONT 110 186
110 FOR VER.
MOUNTING.
CAP
75
203 92 MINIMUM GAP 36
FOR VER.
CAP MOUNTING.

75
36 75
‘D’
SIDE

75
SIDE ‘D’

MINIMUM GAP FOR HOR.MOUNTING. 30 MINIMUM GAP FOR HOR.MOUNTING.


91
ALL DIMENSION ARE IN MM.
ALL DIMENSION ARE IN MM.
2 4 6 8 10 12 14 16 18 20 22 24 26 28
1 3 5 7 9 11 13 15 17 19 21 23 25 27

30
184
‘D’ CAB. STYLE
‘D’ CAB. STYLE 80 CSC - V - 80
BACK

80 CSC - H - 80 120 CSC - V - 120


1 3 5 7 9 11 13 15 17 19 21 23 25 27
120 CSC - H - 120 150 CSC - V - 150
BACK 150 CSC - H - 150 200 CSC - V - 200
2 4 6 8 10 12 14 16 18 20 22 24 26 28
200 CSC - H - 200

CABINET STYLE ‘D’ - V


PANEL CUTOUT
CAP 138

36
1 3 5 7 9 11 13 15 17 MINIMUM GAP
282 FOR VER.
2 4 6 8 10 12 14 16 18 MOUNTING.
‘D’ CAB. STYLE
80 CSD - V - 80
FRONT 302 BACK BACK 120 CSD - V - 120 MINIMUM GAP FOR
‘D’ 150 CSD - V - 150 75 HOR. MOUNTING.
SIDE 200 CSD - V - 200
1 3 5 7 9 11 13 15 17 1 3 5 7 9 11 13 15 17

75
2 4 6 8 10 12 14 16 18 2 4 6 8 10 12 14 16 18

30
160 137
Designed by: HEMISPHERE ADVERTISING
Cell: 93200 82678 Tel: 022-2618 6697

ALL DIMENSION ARE IN MM.

ASHIDA
ELECTRONICS PVT. LTD.
‘ASHIDA HOUSE’,
A-308. Road No.21, Wagle Industrial Estate, Thane-400604. INDIA
Tel: 91-22-2582 7524 / 25 / 26, 6577 1076 / 77 / 78
Fax: 91-22-2580 4262 Email: sales@ashidaelectronics.com