Section 8 – Local Service Transformer

SECTION 8

LOCAL SERVICE TRANSFORMERS

Rev. Date Description Prepared by Reviewed by


0 20-01-2016 Initial Version R.S J.A
Updated with Client
1 22-02-2016 R.S J.A
comments

Rev. 1 Ayanunga Hydroelectric Project


Date: 22/02/2016
Electromechanical Water-To-Wire Technical Specifications
Section 8 – Local Service Transformer

TABLE OF CONTENTS
8 LOCAL SERVICE TRANSFORMER ........................................................................................................... 8-1
SCOPE ............................................................................................................................................. 8-1
GENERAL REQUIREMENTS ........................................................................................................... 8-1
DESIGN CRITERIA .......................................................................................................................... 8-1
SUBMITTALS ................................................................................................................................... 8-5
FACTORY ASSEMBLY AND TESTS ............................................................................................... 8-6
SPARE PARTS ................................................................................................................................. 8-7

Rev. 1 8-i Ayanunga Hydroelectric Project


Date: 22/02/2016
Electromechanical Water-To-Wire Technical Specifications
Section 8 – Local Service Transformers

8 LOCAL SERVICE TRANSFORMERS


SCOPE
General
This Section specifies the technical requirements for the local service transformers to be
furnished, complete in accordance with this Technical Specification.

Plant to be Furnished
The Contractor shall design, detail, manufacture, factory test, deliver, install, field test, pre-
commission and commission one (1) local service transformer for Ayanunga powerhouse, one
(1) local service transformer for 8 de Agosto switchyard and one (1) remote site transformer
and appurtenances complete in accordance with this Technical Specification.

The Contractor shall furnish all components and accessories that are usual and required for
the intended use of the transformers, even if they are not specifically called for herein.

The Contractor shall also furnish a complete set of maintenance tools needed for the
adjustment and normal maintenance of the transformer.

GENERAL REQUIREMENTS
The basic materials and methods shall be in accordance with Section 2 - General Technical
Specification.

The station local service transformer shall be of the indoor, dry type, suitable for providing a
ground reference to the medium voltage bus when the generators are not operating.

DESIGN CRITERIA
Ayanunga Local Service Transformer Ratings and Characteristics

The ratings and characteristics of the transformer shall be as follows:

a) Installation Indoor
b) Frequency 60 Hz
c) Number of windings 2 (primary and secondary)
d) Number of phases 3
e) Type of cooling ANAN
f) Continuous rating of windings on all taps, MVA To match Contractors design
demand for plant supplied under
this Contract, plus an allowance
of 150 kVA for Employer loads. Not
less than 250 kVA.
g) Rated Voltage:

Rev. 1 8-1 Ayanunga Hydroelectric Project


Date: 22/02/2016
Electromechanical Water-To-Wire Technical Specifications
Section 8 – Local Service Transformers

 High voltage winding (Primary) 6.6kV


 Low voltage winding (Secondary) 400/230 V
h) Highest System Voltage:
 Primary 12kV
 Secondary 1 kV
i) Basic Impulse Level, Peak:
 High voltage winding (line terminal) 75 kV
j) Power Frequency Withstand Voltage during one minute:
 Primary terminal 28 kV
k) Winding Connections: ZNyn
 High voltage winding (Primary) Zig Zag, resistance grounded
 Low voltage (Secondary) Star, solidly grounded
l) Minimum impedance, on a 100 kVA base, % ~ 6.5%
m) No load taps 5 (±2.5% each)
n) Efficiency, minimum of: 99%
8 de Agosto Local Service Transformer Ratings and Characteristics

The ratings and characteristics of the transformer shall be as follows:

a) Installation Indoor
b) Frequency 60 Hz
c) Number of windings 2 (primary and secondary)
d) Number of phases 3
e) Type of cooling ANAN
f) Continuous rating of windings on all taps, MVA To match Contractors design
demand for plant supplied under
this Contract. Not less than 50 kVA.
g) Rated Voltage:
 High voltage winding (Primary) 13.8 kV
 Low voltage winding (Secondary) 400/230 V
h) Highest System Voltage:
 Primary 17.5 kV
 Secondary 1 kV
i) Basic Impulse Level, Peak:

Rev. 1 8-2 Ayanunga Hydroelectric Project


Date: 22/02/2016
Electromechanical Water-To-Wire Technical Specifications
Section 8 – Local Service Transformers

 High voltage winding (line terminal) 95 kV


j) Power Frequency Withstand Voltage during one minute:
 Primary terminal 38 kV
k) Winding Connections: Dyn
 High voltage winding (Primary) Delta
 Low voltage (Secondary) Star, solidly grounded
l) Minimum impedance, on a 100 kVA base, % ~ 6.5%
m) No load taps 5 (±2.5% each)
n) Efficiency, minimum of: 99%
Remote Site Transformer Ratings and Characteristics

The ratings and characteristics of the transformer shall be as follows:

a) Installation Indoor
b) Frequency 60 Hz
c) Number of windings 2 (primary and secondary)
d) Number of phases 3
e) Type of cooling ANAN
f) Continuous rating of windings on all taps, MVA 100 kVA
g) Rated Voltage:
 High voltage winding (Primary) 13.8 kV
 Low voltage winding (Secondary) 400/230 V
h) Highest System Voltage:
 Primary 17.5 kV
 Secondary 1 kV
i) Basic Impulse Level, Peak:
 High voltage winding (line terminal) 95 kV
j) Power Frequency Withstand Voltage during one minute:
 Primary terminal 38 kV
k) Winding Connections: YNd5
 High voltage winding (Primary) Star, solidly grounded
 Low voltage (Secondary) Delta
l) Minimum impedance, on a 100 kVA base, % ~ 6.5%
m) No load taps 5 (±2.5% each)

Rev. 1 8-3 Ayanunga Hydroelectric Project


Date: 22/02/2016
Electromechanical Water-To-Wire Technical Specifications
Section 8 – Local Service Transformers

n) Efficiency, minimum of: 99%

Standards
The transformers shall be designed, manufactured, and tested in accordance with the
applicable IEC standard.

Impedance
The transformer impedance shall be coordinated with the short circuit current of the
downstream systems and shall have proper short circuit power for motor starting. In any case
minimal impedance values shall be as per IEC 60076-5 Table 1.

Temperature Rise
The observable temperature rise of the transformer or parts thereof as determined by
resistance of the windings, shall be Class B (80°C) in accordance with IEC 60076-11 at rated
kVA on the tap connections that give the highest winding temperature rise, and the winding
hottest spot temperature shall not exceed the requirements of IEC 60076-12.

Short-Circuit Capability
The transformer short-circuit capability shall be in accordance the requirements of IEC 60076-5.

Core
The core of the transformer shall be constructed of the highest quality, non-aging, high-
permeability silicon steel especially suitable for the purpose. The steel shall be in thin
laminations, properly annealed after cutting to suitable size and rolled to ensure smooth
surfaces at the edges. Both sides of each sheet shall be insulated with a durable, heat-resistant
enamel or varnish, baked on. The core shall be carefully assembled and rigidly clamped to
ensure adequate mechanical.

Windings
Windings shall be class F, with temperature rise according to Class B.

Both primary and secondary windings shall be vacuum pressure impregnated. Each coil shall
be cast under vacuum to ensure complete and void-free resin impregnation throughout the
entire insulation system. The top of the sheet steel enclosure shall be solid.

Transformer windings shall be copper. Transformer connections shall be made using insulated
copper bus and bus supports.

Tap Changer
Terminal links shall be provided for changing high-voltage winding taps at no load. They shall
be accessible through a removable section in a panel.

Terminals
The transformer shall have each high-voltage and each low-voltage lead brought out to a
termination pad.

Rev. 1 8-4 Ayanunga Hydroelectric Project


Date: 22/02/2016
Electromechanical Water-To-Wire Technical Specifications
Section 8 – Local Service Transformers

Enclosure
The transformer enclosures shall be sheet-steel-mounted on a structural steel framework. The
panels at the front and rear of the substation and auxiliary transformers shall be removable for
maintenance. All transformers shall have suitable provisions for lifting, jacking, and moving in
any direction, and the base construction shall be suitable for skidding.

The HV and LV terminations shall be at opposite ends of the transformer enclosure and shall
be accessed by separate, lockable doors. The HV door shall be fitted with an electrical
interlock, preventing the door from being opened when the MV fuse switch is closed.

Nameplate
The transformer shall be provided with 2 stainless steel nameplates in accordance with
Standards. One nameplate shall be mounted on the inside of the terminal cabinet door, and
the second nameplate shall be mounted on the transformer tank adjacent to the tap changer.
Nameplates shall in English and Spanish. Instruction plates, warning signs and any marking
on the equipment, parts and accessories shall be provided in appropriate locations and shall
be in English and Spanish.

The details to be shown on the nameplates and markings, and the material to be used, shall
be reviewed by the Employer.

Grounding Pads
Two grounding pads shall be provided for each transformer.

Winding Temperature Indicator/Relay (49T)


A winding temperature indicator/relay (Device 49T) shall be provided for indication of the
simulated hot spot temperature, and for remote alarm of excessive over temperature for the
station service transformers. Two single-pole, double-throw, field-adjustable, alarm contacts
shall be supplied and shall be suitable for 125-V DC ungrounded operation.

Temperature Detector
One standard 100-Ω at 0°C, platinum resistance temperature detector (RTD) shall be provided
for reading the equivalent hot spot temperature of the transformer windings.

Surge Arresters
The station local service transformers shall be equipped with internally mounted distribution
class, metal-oxide-type surge arresters on all 3 phases of the high voltage windings and shall
be grounded to the switchgear ground bus with no less than a 120 mm2 steel cable.

SUBMITTALS
Refer to Clause 2.7.2 - Manuals, Drawings, Diagrams and Information for general requirements
for information submittals.

Rev. 1 8-5 Ayanunga Hydroelectric Project


Date: 22/02/2016
Electromechanical Water-To-Wire Technical Specifications
Section 8 – Local Service Transformers

Basic Design
The following detailed design documents shall be provided in accordance with the
requirements of Clause 2.7.2.1 - Documentation Package A:

a) Drawings
 General arrangement of the transformer, including foundation arrangement, major
outline dimensions and elevations, embedded piping, and control equipment.
b) Documents
 A list of all design codes and standards being used.
 Manufacturing quality control plan.
 Transformer design calculations.
 Type test certificates for the transformer class design.

Detailed Design
The following detailed design documents shall be provided in accordance with the
requirements of Clause 2.7.2.1 - Documentation Package B:

a) Detail Drawings
 General assembly of the transformer in plan and elevation.
 Foundation arrangement, operating forces and anchor bolts including maximum
operating forces on the foundation.
b) Schematic Diagrams, including
 Interface Drawings for Unit control system.
c) Other
 Erection and commissioning quality control plan.
 Protective device settings.

FACTORY ASSEMBLY AND TESTS


The transformer shall be completely assembled in the factory and tested, insofar as
practicable.

General

All measurements, computations, and tests shall be made in accordance with IEC60076. Each
transformer shall be completely assembled at the factory and shall undergo all routine tests
required by IEC60076. As a minimum, the following tests shall be performed:

 Visual inspection and dimensional check of the transformer and housing.


 Ratio.
 Polarity and phase relation.

Rev. 1 8-6 Ayanunga Hydroelectric Project


Date: 22/02/2016
Electromechanical Water-To-Wire Technical Specifications
Section 8 – Local Service Transformers

 Resistance.
 Impedance and load losses.
 No load losses and current.
 Leak test with voltage applied in AC.
 Leak test with voltage induced in AC.
 Measurement of partial discharges.
 Temperature rise.
 Losses and efficiencies.
 Insulation (dielectric) tests.
 Noise.
 Insulation power factor.
 Verification of accessories and components.

SPARE PARTS
Specified Spare Parts

 One complete spare local services transformer.

Mandatory and Optional Spare Parts


The Contractor shall furnish a list of recommended Mandatory and Optional additional spare
parts in accordance with the requirements of Clause 2.28 - Spare Parts.