Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Totally
I n t e gr a t e d
sirius
Automation
MOTOR MANAGEMENT
SIMOCODE pro
Safety Guidelines
Table of Contents
Important Notes
System Description 1
Short Instructions for
Configuring a Reversing Starter 2
SIMOCODE pro Motor Protection 3
Motor Control 4
Monitoring Functions 5
Outputs 6
Inputs 7
System Manual
Analog Value Recording 8
3UF50 Compatibility Mode 9
Standard Functions 10
Logic Modules 11
Communication 12
Mounting, Wiring, Interfaces 13
Commissioning and Servicing 14
Alarm, Faults and System
Messages 15
Tables A
Data Formats and Data Records B
Dimension Drawings C
Technical Data D
Example Circuits E
Safety and Commissioning Infor-
mation for EEx Areas F
Index
List of Abbreviations
Glossary
Order Number: 3UF7970-0AA00-0 To
Edition 03/2007
GWA 4NEB 631 6050-22 DS 02
Safety Information
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
Danger
indicates that death or severe personal injury will result if proper precautions are not taken.
Warning
indicates that death or severe personal injury may result if proper precautions are not taken.
Caution
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
Caution
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
Notice
indicates that an unintended result or situation can occur if the corresponding information is not taken into account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and
operation of a device/system may only be performed out by qualified personnel. Within the context of the safety
notes in this documentation qualified persons are defined as persons who are authorized to commission, ground
and label devices, systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
Warning
This device may only be used for the applications described in the catalog or the technical description and only in
connection with devices and components from other manufacturers which have been approved or recommended
by Siemens. Correct, relaible operation of the product requires proper transport, storage, positioning and assembly
as well as careful operation and maintenance.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this
publication is reviewed regularly and any necessary corrections are included in subsequent editions.
SIMOCODE pro
GWA 4NEB631 6050-22 DS 02 i
Table Of Contents
SIMOCODE pro
ii GWA 4NEB 631 6050-22 DS 02
Table Of Contents
6 Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
7 Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 iii
Table Of Contents
12 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
SIMOCODE pro
iv GWA 4NEB 631 6050-22 DS 02
Table Of Contents
A Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 v
Table Of Contents
SIMOCODE pro
vi GWA 4NEB 631 6050-22 DS 02
Table Of Contents
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 vii
Table Of Contents
SIMOCODE pro
viii GWA 4NEB 631 6050-22 DS 02
Table Of Contents
Index
List of Abbreviations
Glossary
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 ix
Table Of Contents
SIMOCODE pro
x GWA 4NEB 631 6050-22 DS 02
Important Information
Topics
This manual consists of instructional chapters for reference purposes. The
following table lists the most relevant topics. Topics with a gray background
correspond largely with the contents of the "SIMOCODE ES"
parameterization and service software:
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 xi
Important Information
Scope of Application
This manual is applicable to the listed SIMOCODE pro system components.
It contains a description of the components applicable at the time of printing
the document. We reserve the right to include updated information about
new components or new versions of components in a product information.
Further documentation
• Please read the operating instructions of the respective components.
• In addition to this system manual, the manual of the deployed DP master will
also be required.
Definitions
• When "SIMOCODE pro" is referred to, both the "SIMOCODE pro C" and the
"SIMOCODE pro V" series are meant.
SIMOCODE pro
xii GWA 4NEB 631 6050-22 DS 02
Important Information
Correction sheet
A correction sheet is included at the end of this manual. Please use it to
enter suggestions for improvements, additions and corrections and send it
back to us. This will help us to improve the next edition.
Disclaimer
The products described here have been developed to carry out safety
oriented functions as part of a complete plant or machine. In general, a
complete safety system consists of sensors, evaluation units, signalling
devices and methods for safe switching off. The manufacturer is responsible
for ensuring safe functioning of the complete plant or machine.
Siemens AG, its subsidiaries and associated companies (herein referred to
as "Siemens") are not in a position to guarantee every characteristic of a
complete plant or machine not designed by Siemens.
Siemens also denies all responsibility for any recommendations that are
made or implied in the following description. No new guarantee, warranty or
liability above those standard to Siemens can be derived from the following
description.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 xiii
Important Information
SIMOCODE pro
xiv GWA 4NEB 631 6050-22 DS 02
System Description 1
In this chapter
In this chapter you will find an introduction and general information about
the SIMOCODE pro system including e.g.
• Characteristics of both the SIMOCODE pro C and the SIMOCODE pro V
device series
• Simplification of SIMOCODE pro circuits
• Overview of functions
• An overview of system components.
Target groups
This chapter is intended for the following target groups:
• Planners and configurators
• People who are now using SIMOCODE DP but wish to use SIMOCODE pro
as a replacement or additional system in the future
• Optional for commissioners, maintenance and service personnel as additional
information "about SIMOCODE pro"
• System integrators / process technology.
Necessary knowledge
You will require the following knowledge:
• Basic knowledge about load feeders
• Basic knowledge about motor protection
• Basic knowledge of control engineering
• Basic knowledge of industrial bus technology.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-1
System Description
1.1 Introduction
Description
SIMOCODE pro (SIRIUS Motor Management and Control Devices) is a
system of motor management and control devices with a PROFIBUS DP
interface. SIMOCODE pro is a further development of the SIMOCODE DP
system.
Device series
SIMOCODE pro can be subdivided into two device series:
• SIMOCODE pro C - a compact system for direct and reversing starters
and
• SIMOCODE pro V - a variable system, which also offers numerous additional
functions in addition to all of the SIMOCODE pro C functions.
Additional control programs are integrated in SIMOCODE pro V for star-delta
starters, Dahlanders, pole-changing starters, soft starters - each also in
combination with reversal of the direction of rotation, as well as valves and
positioners. SIMOCODE pro V is also particularly versatile. Its functionality can
be extended, if required, for example
– the number and type of binary inputs and outputs can be increased in stages
and adapted
– a current/voltage measuring module can be used for additional voltage
measurement and for monitoring power-related measured values (power
management)
– a temperature module enables the evaluation of several analog temperature
sensors
– An earth-fault detection system can be integrated together with a summation
current transformer
– an analog module extends the system by additional analog inputs and
outputs, for example, for fill-level or flow-rate monitoring.
SIMOCODE pro C is upwards-compatible with SIMOCODE pro V. This
means both ranges can be used simultaneously in your plant according to
requirements.
SIMOCODE pro
1-2 GWA 4NEB 631 6050-22 DS 02
System Description
Independent operation
SIMOCODE pro C and pro V protect and control the motor feeder
independently of the automation system. Even if the automation system
(PLC) fails, or if communication is disrupted, the motor feeder remains fully
protected and controllable. SIMOCODE pro can be used without being
connected to PROFIBUS DP. This can easily be connected later, if required.
Typical configuration
The following schematic shows a typical SIMOCODE pro C and
SIMOCODE pro V hardware configuration:
SIMOCODE pro C
Basic unit (BU1)
Current measuring
module (IM)
UF-01129
SIMOCODE pro V Basic unit (BU2)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-3
System Description
Manual/automatic
-Q1
Feedback Control
-F2- commands
Thermistor
1 3 5
-Q1 open
Overload
Current
ON/OFF
Q1
OFF
ON
-F3
2 4 6 -X1
1 3 5 -K11
- K1
2 4 6 Manual Auto
-X2
1 3 5
- F2 Local stop
S1 PLC
2 4 6
Start/stop
Local start
2 -K12
4 A - 20 mA S2 -K1
PE UV W
-K11 -K12
M ϑ 1 -K1 -K1 -F2 -F3 -Q1 D
3~ 2
-X3 -F3 A
Thermistor 1 N
-K1 Switchgear
evaluation
1N
SIMOCODE pro
1-4 GWA 4NEB 631 6050-22 DS 02
System Description
1 3 5
Q1 F11 Control station
Local control station [LC]
2 4 6 S0 S1
T1 T2 OUT 1 1
K1
1 3 5
- K1 N/L–
2 4 6
PE U V W
T1
M Thermistor
J
3~ T2
Fig. 1-3: Configuration of a load feeder (direct starter) with SIMOCODE pro
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-5
System Description
2 4 6 S0 S1
Liquid container
Display
1 3 5 K1
- K1 N/L– Motor current
2 4 6 (unit: % of Is)
Pump
PE Optional:
U V W
laptop with
T1
M Thermistor SIMOCODE ES
3~ ϑ
T2
SIMOCODE pro
1-6 GWA 4NEB 631 6050-22 DS 02
System Description
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-7
System Description
SIMOCODE
SIMOCODE pro
1-8 GWA 4NEB 631 6050-22 DS 02
System Description
SIMOCODE
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-9
System Description
Stalled rotor
See Chapter 3 "Motor Protection".
Thermistor protection
The basic units (BU1 and BU2) enable connection of thermistor sensors
(binary PTC) for monitoring motor temperature.
Earth-fault monitoring
Basic units have
• Internal earth-fault monitoring:
For motors with a 3-cable connection, the basic unit calculates a possible
fault current/earth-fault current from the total current via a current measuring
module or a current/voltage measuring module. Internal earth-fault
monitoring is only possible for motors with a 3-phase connection in networks
that are either grounded directly or grounded with low impedance.
• External earth-fault monitoring by SIMOCODE pro V 1) 5):
In the case of networks that are grounded with a higher impedance, it may be
necessary to set up the earth-fault monitoring for smaller earth-fault currents
using a summation current transformer instead of carrying out internal earth-
fault monitoring via a current measuring module or a current/voltage
measuring module. A maximum of one earth-fault module can be used to
create an additional input on basic unit 2 to connect a 3UL22 summation
current transformer. Rated fault currents of 0.3 A/ 0.5 A/ 1 A can be evaluated
with the summation current transformer.
SIMOCODE pro
1-10 GWA 4NEB 631 6050-22 DS 02
System Description
Voltage monitoring 2)
SIMOCODE pro V allows voltage monitoring of a three-phase current
network or a one-phase network for undervoltage or further availability:
• Monitoring for undervoltage:
Two-phase monitoring for freely-selectable limits. The SIMOCODE pro V
response can be freely parameterized upon reaching a particular pre-warning
or trip level.
• Monitoring for further availability:
Even when the motor is switched off, SIMOCODE pro can display the further
availability of the feeder by measuring the voltage directly at the circuit
breaker or fuses.
Temperature monitoring 1) 3)
The SIMOCODE pro V temperature module allows analog temperature
monitoring of, for example, the motor windings or the bearings of up to 3
sensor measuring circuits.
SIMOCODE pro V supports two-phase monitoring of overtemperature for
freely-selectable limits. The SIMOCODE pro response can be freely
parameterized and delayed upon reaching a pre-warning or trip level.
Temperature monitoring takes into account the highest temperature of all
the sensor measuring circuits in use.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-11
System Description
SIMOCODE pro
1-12 GWA 4NEB 631 6050-22 DS 02
System Description
SIMOCODE
1)
Overload relay ✓ ✓
1)
Direct starter ✓ ✓
1)
Reversing starter ✓ ✓
1)
Circuit breaker (MCCB) ✓ ✓
Star-delta starters, — ✓
combinable with reversal of the direction of
rotation
Dahlanders, — ✓
combinable with reversal of the direction of
rotation
Pole-changing starters — ✓
combinable with reversal of the direction of
rotation
Solenoid valve — ✓
Positioner — ✓
Soft starters, — ✓
combinable with reversal of the direction of
rotation
Table 1-2: Control functions
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-13
System Description
1.5.4 Communication
PROFIBUS DP
SIMOCODE pro has an integrated PROFIBUS DP interface (SUB-D socket or
terminal connection on the basic units).
SIMOCODE pro supports, for example, the following services:
SIMOCODE
Service pro C (BU1) pro V (BU2)
SIMOCODE
Standard function pro C (BU1) pro V (BU2)
Number Number
Test 2 2
Reset 3 3
Test position feedback (TPF) 1 1
External fault 4 6
Operational protection OFF (OPO) — 1
Power failure monitoring (UVO) — 1
Emergency start 1 1
Watchdog (PLC/PCS Monitoring) 1 1
Timestamping — 1
SIMOCODE pro
1-14 GWA 4NEB 631 6050-22 DS 02
System Description
If you need any other additional functions for your application, you can use
the freely-programmable logic modules. These can be used, for example, to
implement logical functions, time relay functions and counter functions.
Furthermore, limit monitors can monitor any value in SIMOCODE pro for
undershooting or overshooting of a freely selected limit.
Depending on the device series, the system offers several, freely-
parameterizable logic modules:
SIMOCODE
Number Number
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-15
System Description
Operating data
• Motor switching state (ON, OFF, LEFT, RIGHT, SLOW, QUICK), derived from
the current flow in the main circuit; thus, feedback via auxiliary contacts of
circuit breakers and contactors is not necessary
• Current in phases 1, 2 and 3 and maximum current in % of set current
• Voltage in phases 1, 2 and 3 in V 2)
• Active power in W 2)
• Apparent power in VA 2)
• Power factor in % 2)
• Phase unbalance in %
• Phase sequence 2)
• Temperature in the sensor measuring circuits 1, 2 and 3, and maximum
temperature in K 1) 4)
• Actual analog signal values 1) 5)
• Time to trip in s
• Heating motor model in %
• Remaining cooling down period of the motor in s, etc.
It is possible to adapt the units via the device-internal conversion of
individual measured values with the help of the logic modules (calculators)
provided by SIMOCODE pro V. For example: the temperature recorded by
SIMOCODE can be calculated in either °F or °C and be transmitted to the
automation system via PROFIBUS.
Service data
Among other things, SIMOCODE pro provides the following for the
maintenance of relevant data:
• Number of motor operating hours, also resettable
• Motor stop times, also resettable
• Number of motor starts, also resettable
• Number of permissible starts remaining
• Number of overload trippings, also resettable
• Feeder power consumption in kWh, also resettable3)
• Internal feeder comments stored in the device, e.g. information regarding
maintenance events, etc.
SIMOCODE pro
1-16 GWA 4NEB 631 6050-22 DS 02
System Description
Diagnostic Data
• Numerous detailed early warning and fault signals, also for further processing
in the device or in the control system
• Internal device error protocolling with timestamp
• Value of the last trip current
• Feedback faults (e.g. no current flow in the main circuit after switch-on
command), etc.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-17
System Description
SIMOCODE
SIMOCODE pro
1-18 GWA 4NEB 631 6050-22 DS 02
System Description
SIMOCODE
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-19
System Description
Accessories
SIMOCODE pro
1-20 GWA 4NEB 631 6050-22 DS 02
System Description
Software
For parameterization, control, diagnostics and testing
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-21
System Description
SIMOCODE pro
1-22 GWA 4NEB 631 6050-22 DS 02
System Description
Test/Reset button:
Enables the device to be reset after tripping or after a fault has occurred and
makes it possible to test the device/motor feeder with or without tripping
the contactor control. If a memory module or addressing plug is plugged in,
the PROFIBUS address can be parameterized or adopted via the Test/Reset
button.
Input supply
See Chapter 13 "Mounting, Wiring, Interfaces".
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-23
System Description
The operator panel is often integrated into the front panels of motor control
centers, thus, enabling the motor feeder to be controlled from the
switchgear cabinet.
It can be used with both the SIMOCODE pro C and the SIMOCODE pro V
device series. It contains all the basic device status LEDs and the
TEST/RESET button, and facilitates access to the system interface outside
the switchgear cabinet.
The following are available:
• 5 buttons, of which 4 are freely-parameterizable
• 10 LEDs, of which 7 are freely-parameterizable
The following figure shows an operator panel:
SIMOCODE pro
1-24 GWA 4NEB 631 6050-22 DS 02
System Description
Labeling strips:
Labeling strips are enclosed for designating buttons 1 to 4 and the yellow
LEDs 1 to 3:
• Buttons 1 to 4:
6 pre-assigned and 1 individually inscribable labeling strips
• LEDs 1 to 3:
1 individually inscribable labeling strip.
ZU AUF
STOP
CLOSE OPEN
AUF ZU
OPEN CLOSE
0
0
I 0 TEST/
RESET
Fig. 1-7: Labeling strips for operator panel buttons and LEDs
Note:
Labeling software for customized labeling of the SIMOCODE pro operator
panel control buttons and LEDs is available at
www.siemens.com/simocode. For printing purposes, three different types
of pre-cut, transparent labeling strips can be ordered as accessories.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-25
System Description
Unused labeling strips can be stored on the back of the operator panel:
Labeling strips
Storage clips
SIMOCODE pro
1-26 GWA 4NEB 631 6050-22 DS 02
System Description
Apart from the standard operator panel (OP), an optional operator panel with
display (OPD) is also available for SIMOCODE pro V. This operator panel can
display current measured values, operating data, diagnostic data or status
information of the motor feeder on the switchgear cabinet. The operator
panel can only be used with a basic unit 2 (SIMOCODE pro V) from product
version *E03*. It contains all the basic device status LEDs and facilitates
access to the system interface outside the switchgear cabinet. The motor
can be controlled via the buttons on the operator panel. Current measured
values, status information, fault messages or the device-internal error
protocol are simultaneously shown on the display.
Notice:
The operator panel can only be used with a basic unit 2 (SIMOCODE pro V)
from product version *E03*.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-27
System Description
The operator panel with display can be connected directly to the basic unit 2
or an expansion module via the rear system interface. Voltage is supplied by
the basic unit. A PC, the memory module or the addressing plug can be
connected to SIMOCODE ES using the PC cable via the front system
interface (with a cover for IP54).
Caution
The operator module with display may not be removed or plugged in during
operation!
Note
When using an operator panel with display, the type and number of
expansion modules that can be connected to a basic device must be
limited! See Chapter 1.7.8.
Labeling strips:
Labeling strips for labeling buttons 1 to 4 are included:
• 6 pre-assigned and 1 individually inscribable labeling strips
Button 1
Button 2
Button 3
Button 4
ZU
CLOSE
AUF AUF
OPEN
I OPEN
0 ZU
STOP
0 0 0 CLOSE
Fig. 1-11: Labeling strips for the buttons of the operator panel with display
SIMOCODE pro
1-28 GWA 4NEB 631 6050-22 DS 02
System Description
Note:
Labeling software for customized labeling of the SIMOCODE pro operator
panel control buttons and LEDs is available at
www.siemens.com/simocode.
For printing purposes, three different types of pre-cut, transparent labeling
strips can be ordered as accessories.
Unused labeling strips can be stored on the back of the operator panel with
display:
Labeling strips
Storage clips
The memory module can be "parked" on the front of the operator panel with
display beneath the system interface:
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-29
System Description
IL1 2.80 A
IL2 2.16 A
IL3 2.00 A 4
8.00A/5/T Menu
1 23
Fig. 1-14: Displays
1
Shows the set current Is / nominal motor current in A.
The corresponding set current ls1 or ls2 is always shown for motors with
two speeds, independent of whether the current speed is slow or fast,
e.g. 2.35 A.
For motors with two speeds, the left-hand softkey can be used when the
motor is stopped to alternate between both set currents. When running, the
set current for the active motor speed is always displayed.
2
Shows the set class interval of the overload protection,
e.g.: 10 = Class 10 (class = tripping class)
3
Indicates that temperature monitoring is taking place, e.g. the temperature
monitoring of the motor via thermistors or analog temperature sensors
(Pt100, Pt1000, KTY, NTC). T = Temperature monitoring taking place.
4
The main display enables customized depiction of different measured
values when running. This is the standard display at the topmost menu
level. Predefined profiles in the display settings can be selected for this
purpose. When the "Menu" softkey is pressed, the submenus of the main
display can be navigated (see "Read and adapt main display").
SIMOCODE pro
1-30 GWA 4NEB 631 6050-22 DS 02
System Description
1 2 3
1
Four freely-parameterizable control buttons.
These control buttons are used to control the motor with integrated status
LEDs for any status feedback. The functions can be user-defined. Labeling
can be either as desired or via the labeling strips incldued in the scope of
supply (see also Chapter 7.3 "Operator Panel Buttons" and/or
Chapter 6.3 "Operator Panel LEDs")
2
Two softkeys.
These softkeys can have different functions, depending upon the menu
depicted (e.g. Open Menu, Leave Menu, Test/Reset). The currently assigned
functions are shown on the lower left or right edge of the display.
3
Two arrow keys (up and down).
These arrows keys can be used for menu navigation or for changing the display
settings, e.g. contrast adjustment or selection of the main display profile.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-31
System Description
Main display The "Main display" is the default SIMOCODE pro display. It displays
the current measured values, which can be selected via predefined
profiles according to user requirements (see also "Read and adapt
main display")
Measured value display The "Measured value display" gives an overview of all values
measured by SIMOCODE pro.
For example, all phase currents, phase voltages, power-related
measured values or temperatures. For detailed information: See
"Display of measured values in the measured value indicator".
Status display The "Status display" shows all higher-level status information, i.e. all
status information relevant to protection and controlling of the
motor.
For detailed information: See: "Motor protection and motor control
status".
Table 1-9: Operator panel with display: menu and menu navigation
SIMOCODE pro
1-32 GWA 4NEB 631 6050-22 DS 02
System Description
Device I/Os The "Device I/Os" menu item gives a complete overview of the
current status of all inputs and outputs of the basic device as well
as any connected expansion modules.
For detailed information: See: "Display of the current status of all
device I/Os"
Display Settings All settings relevant to the operator panel with display can be
carried out via "Display Settings". In addtion to selecting the
language and adjusting the contrast or lighting, it is also possible to
select the profiles here which are relevant for adjusting the main
display.
For detailed information: See: "Adapt display settings"
Status Information The "Status Information" menu item gives an overview of all
pending status information.
For detailed information: See: "Display of all pending status
information"
Table 1-9: Operator panel with display: menu and menu navigation (Cont.)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-33
System Description
Faults The "Faults" menu item gives an overview of all pending faults.
For detailed information: See: "Display of all pending faults"
Fault memory The "Fault Memory" menu item displays the SIMOCODE pro device-
internal fault memory.
For detailed information: See: "Reading out the device-internal error
buffer"
Identification In the "Identification" menu item you will find detailed information
about SIMOCODE pro hardware components (basic unit, operator
panel with display) respectively labeling.
For detailed information: See: "Identification of the motor feeder
and the SIMOCODE pro components"
About SIMOCODE The "About SIMOCODE" menu item displays further information
about SIMOCODE pro.
Table 1-9: Operator panel with display: menu and menu navigation (Cont.)
SIMOCODE pro
1-34 GWA 4NEB 631 6050-22 DS 02
System Description
IL1, IL2, IL3 [A] (example) Displays the currents in all three phases in amperes
Note:
Only possible if a current measuring module or current/voltage
measuring module is being used.
IL1, IL2, IL 3 [%] (example) Displays the currents in all three phases in % of set current
Note:
Only possible if a current measuring module or current/voltage
measuring module is being used.
Imax [A] (example) Displays the maximum current of all three phases in amperes
Note:
Only possible if a current measuring module or current/voltage
measuring module is being used.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-35
System Description
Imax [%] (example) Displays the maximum current of all three phases in % of set
current
Note:
Only possible if a current measuring module or current/voltage
measuring module is being used.
Imax, Cos (example) Displays the maximum current of all three phases in amperes and
the power factor
Note:
Only possible if a current/voltage measuring module is being used.
Imax, UL1, Cos, S (example) Displays the maximum current of all three phases in amperes, the
phase voltage UL1 in V, the power factor and the apparent power
in kVA
Note:
Only possible if a current/voltage measuring module is being used.
Imax, UL1, Cos, P (example) Displays the maximum current of all three phases in amperes, the
phase voltage UL1 in V, the power factor and the active power
in kW
Note:
Only possible if a current/voltage measuring module is being used.
[mA] In1/Output (example) Displays the current value at Input 1 of the analog module and at
the output of the analog module in mA
Note:
Only possible if a analog module is being used.
SIMOCODE pro
1-36 GWA 4NEB 631 6050-22 DS 02
System Description
[mA] In2/Output ((example) Displays the current value at Input 2 of the analog module and at
the output of the analog module in mA
Note:
Only possible if an analog module is being used.
[mA] Inputs (example) Diplays the current value at both inputs of the analog module
in mA
Note:
Only possible if an analog module is being used.
max. Temp. °C (example) Displays the maximum temperature of all used sensor measuring
circuits of the temperature module in °C
Note:
Only possible if a temperature module is being used.
Temperatures °C (example) Displays the individual temperatures of all used sensor measuring
circuits of the temperature module in °C
Note:
Only possible if a temperature module is being used.
Max. Temp. °F (example) Displays the maximum temperature of all used sensor measuring
circuits of the temperature module in °F
Note:
Only possible if a temperature module is being used.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-37
System Description
Temperatures °F (example) Displays the individual temperatures of all used sensor measuring
circuits of the temperature module in °F
Note:
Only possible if a temperature module is being used.
Imax, UL1, Cos (example) Displays the maximum current of all three phases in amperes, the
phase voltage UL1 in V, and the power factor absolute
Note:
Only possible if a current/voltage measuring module is being used.
Imax, UL1 °C (example) Displays the maximum current of all three phases in amperes, the
phase voltage UL1 in V, and the maximum temperature of all used
sensor measuring circuits of the temperature module in °C
Note:
Only possible if a current/voltage measuring module and
temperature module are being used.
Imax, UL1 °F (example) Displays the maximum current of all three phases in amperes, the
phase voltage UL1 in V, and the maximum temperature of all used
sensor measuring circuits of the temperature module in °F
Note:
Only possible if a current/voltage measuring module and
temperature module are being used.
SIMOCODE pro
1-38 GWA 4NEB 631 6050-22 DS 02
System Description
Calculator 1 (example) Displays the calculated result that the function block Calculator 1
provides, unitless in the range of 0 to 65535
Note:
Enables, for example, the depiction on the switchgear display of a
2-byte value sent directly from the automation system, i.e. the
unitless depiction of all 2-byte values available in SIMOCODE pro
Calculator 2 (example) Displays the calculated result that the function block Calculator 2
provides, unitless in the range of 0 to 65535
Note:
Enables, for example, the depiction on the switchgear display of a
2-byte or 4-byte value sent directly from the automation system, i.e.
the unitless depiction of all 2 or 4-byte values available in
SIMOCODE pro
Note
If measured values are not depicted on the main display for a sustained
period of time, a profile has been selected in the display settings that is no
longer supported, due, for example, to a changed system expansion or
changed hardware configuration. The profile must be reselected.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-39
System Description
I max (example) Displays the maximum current of all three phases, switchable
between amperes or % of ls
Note:
Only possible if a current measuring module or current/voltage
measuring module is being used.
IL1, IL2, IL3 (example) Displays the maximum current of all three phases, switchable
between amperes or % of ls
Note:
Only possible if a current measuring module or current/voltage
measuring module is being used.
Note:
Only possible if a current measuring module or current/voltage
measuring module is being used.
SIMOCODE pro
1-40 GWA 4NEB 631 6050-22 DS 02
System Description
Cos phi, P, S (example) Displays the power factor (0...100% or absolute, switchable via the
right-hand softkey), the active power in kW and the apparent power
in kVA
Note:
Only possible if a current/voltage measuring module is being used.
Analog Input 1, Displays the current values at both inputs and the current value at
Analog Input 2, the output of the analog module, switchable between mA or %
Analog Output (example)
Note:
Only possible if an analog module is being used.
max. Temperature (example) Displays the maximum temperature of all used sensor measuring
circuits of the temperature module in °C (switchable to °F)
Note:
Only possible if a temperature module is being used
T1, T2, T3 (example) Displays the maximum temperature of all used sensormeasuring
circuits of the temperature module in °C (or switchable to °F)
Note:
Only possible if a temperature module is being used
Heating Motor Model (example) Displays the current heating of the internal motor model in %
Table 1-11: Display of measured values in the measured value indicator (Cont.)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-41
System Description
Cooling Down Period (example) Displays the cooling down period remaining before the motor can
be switched on again after an overload trip
Last Trip Current (example) Displays the strength of the current that was measured at the
moment of the overload trip, switchable between A or % of ls
Table 1-11: Display of measured values in the measured value indicator (Cont.)
SIMOCODE pro
1-42 GWA 4NEB 631 6050-22 DS 02
System Description
General
Control: The display of the status information can vary according to the control function.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-43
System Description
SIMOCODE pro
1-44 GWA 4NEB 631 6050-22 DS 02
System Description
Protection
Other
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-45
System Description
General
Number of Overload Trips
Motor Operating Hours > Displays exceedance of the stipulated limit for monitoring operating
hours
SIMOCODE pro
1-46 GWA 4NEB 631 6050-22 DS 02
System Description
Motor Stop Time > Displays exceedance of the stipullated limit for monitoring motor
stop time
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-47
System Description
Timer
SIMOCODE pro
1-48 GWA 4NEB 631 6050-22 DS 02
System Description
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-49
System Description
Bus o.k.
Bus Monitoring
PLC/PCS in Run
PLC/PCS Monitoring
SIMOCODE pro
1-50 GWA 4NEB 631 6050-22 DS 02
System Description
Timestamping Active
Compatibility Mode
Compatibility Mode 1
3UF50 Mode
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-51
System Description
Diagnosis Device Fault Displays the diagnosis information sent by SIMOCODE pro to a
Diagnosis Status Info higher-level automation system via PROFIBUS
SIMOCODE pro
1-52 GWA 4NEB 631 6050-22 DS 02
System Description
Basic Unit
Inputs 1 (2, 3, 4)
Outputs 1 (2, 3)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-53
System Description
Current Measuring
I L1, I L2, I L3
Note:
Only possible if a current measuring module or current/voltage
measuring module is being used.
Voltage Measurement
U L1, U L2, U L3
Note:
Only possible if a current/voltage measuring module is being used.
Inputs 1 (2, 3, 4)
Note:
Only possible if a digital module is being used
Outputs 1 (2)
Monostable Outputs
Bistable Outputs
Table 1-15: Display of the current status of all device I/Os (Cont.)
SIMOCODE pro
1-54 GWA 4NEB 631 6050-22 DS 02
System Description
Analog Module
Output (example)
Open Circuit
Temperature Module
Table 1-15: Display of the current status of all device I/Os (Cont.)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-55
System Description
Sensor Type
Pt100
Pt1000
NTC
KTY83
KTY85
Sensor Fault
Sensor Out Of Range
Table 1-15: Display of the current status of all device I/Os (Cont.)
SIMOCODE pro
1-56 GWA 4NEB 631 6050-22 DS 02
System Description
Languages
Example: English
German
French
Polish
Spanish
Portuguese
Italian
Finnish
Contrast
Example: 0%
5%
10 %
15 %
20 %
25 %
30 %
35 %
40 %
45 %
50 %
55 %
60 %
65 %
70 %
75 %
80 %
85 %
90 %
95 %
100 %
Illumination
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-57
System Description
Profiles
See Section Enables selection of the display profiles for the main display.
"Menu of the operator panel If a defined profile is no longer supported by SIMOCODE pro, for
with display and menu example, due to a changed hardware configuration, the start display
navigation" Main Display is shown instead of the default main display.
Warnings
Do Not Display
Display
Faults
Do Not Display
Display
Table 1-16: Displays the current status of all device I/Os (Cont.)
SIMOCODE pro
1-58 GWA 4NEB 631 6050-22 DS 02
System Description
Factory Settings
Table 1-16: Displays the current status of all device I/Os (Cont.)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-59
System Description
Adopt address Only if the Test/Reset button has not been blocked and a password
has not been stipulated.
Program Only if Test/Reset has not been blocked
Clear Always possible
Reading in Only if the Test/Reset button has not been blocked and a password
has not been stipulated.
Restart Only if Test/Reset has not been blocked
Factory settings Only if Test/Reset has not been blocked
Table 1-17: Resetting, testing and parameterizing via commands
SIMOCODE pro
1-60 GWA 4NEB 631 6050-22 DS 02
System Description
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-61
System Description
SIMOCODE pro
1-62 GWA 4NEB 631 6050-22 DS 02
System Description
Marking
Plant Identifier
Location Designation
Date
Comment
Table 1-18: Identification of the motor feeder and the SIMOCODE pro components
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-63
System Description
Basic Unit
Short Code
Manufacturer
Table 1-18: Identification of the motor feeder and the SIMOCODE pro components (Cont.)
SIMOCODE pro
1-64 GWA 4NEB 631 6050-22 DS 02
System Description
System
HW Version
FW Version (example)
Table 1-18: Identification of the motor feeder and the SIMOCODE pro components (Cont.)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-65
System Description
Timestamp (example)
Display
HW Version
FW Version
Table 1-18: Identification of the motor feeder and the SIMOCODE pro components (Cont.)
SIMOCODE pro
1-66 GWA 4NEB 631 6050-22 DS 02
System Description
Current measuring modules are used together with the basic units of the
SIMOCODE pro C and SIMOCODE pro V device series.
The current measuring module must be selected according to the set
current to be monitored (rated operating current of the motor). The current
measuring modules cover current ranges between 0.3 A and 630 A, with
interposing transformers up to 820 A.
The following figure shows the various current measuring modules:
0.3 A - 3 A 10 A - 100 A
2.4 A - 25 A
20 A - 200 A 63 A - 630 A
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-67
System Description
0.3 A - 3 A 10 A - 100 A
2.4 A - 25 A
20 A - 200 A 63 A - 630 A
SIMOCODE pro
1-68 GWA 4NEB 631 6050-22 DS 02
System Description
Note
Utilization of a current/voltage measuring module requires a basic unit 2,
product version *E02* (from 04/2005) or later.
Note
When using current/voltage measuring modules in ungrounded networks
and/or when using insulation monitors for earth-fault / fault current
detection, each current/voltage measuring module should have an
decoupling module (DCM) connected upstream in series at the system
interface.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-69
System Description
Note
When using a decoupling module, the type and number of expansion
modules that can be connected to a basic device must be limited! See
Chapter 1.7.8 "Configuration Information for Using an Operator Panel with
Display and/or a Decoupling Module".
SIMOCODE pro
1-70 GWA 4NEB 631 6050-22 DS 02
System Description
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-71
System Description
Note
If two digital modules are being used, the digital module connected the
closest to the basic unit via the system interface will be identified as Digital
Module 1. The digital module that follows behind will be identified as Digital
Module 2. If one digital module is connected to the front side and another to
the lower system interface of the basic unit, the digital module on the front
system interface of the basic unit will always be identified as Digital
Module 1.
SIMOCODE pro
1-72 GWA 4NEB 631 6050-22 DS 02
System Description
Attention
The inputs of the analog module are passive inputs that have to be supplied
by an external, isolated current source (e.g. isolating transducer). If the
output of the analog module is not being utilized, it can be used as current
source for an input.
Note
The use of an analog module requires basic unit 2, product version *E02*
(from 04/2005) or later.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-73
System Description
Note
The use of an earth-fault module requires basic unit 2, product version
*E02* (from 04/2005) or later.
SIMOCODE pro
1-74 GWA 4NEB 631 6050-22 DS 02
System Description
Notice
The same sensor type must be used in all sensor measuring circuits.
Note
The use of a temperature module requires basic unit 2, product version
*E02* (from 04/2005) or later.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-75
System Description
Table 1-20: Maximum expansion with expansion modules when using an operator panel with display
Operator panel with display and current/voltage measuring module with basic
unit 2 (110 V - 240 V AC/DC):
Digital module Digital module Analog Temperature Earth-fault
module module module
Max. 3 expansion modules applicable, or
X X
Table 1-21: Maximum expansion with expansion modules when using an operator panel with display
and current/voltage measuring with basic unit 2 (110 V - 240 V AC/DC):
Table 1-22: Maximum expansion with expansion modules when using a decoupling module (voltage
measurement in isolated networks) and basic unit 2 (24 V DC)
Table 1-23: Maximum expansion with expansion modules when using a decoupling module (voltage
measurement in isolated networks) and basic unit 2 (110 V - 240 V AC/DC)
SIMOCODE pro
1-76 GWA 4NEB 631 6050-22 DS 02
System Description
Table 1-24: Maximum expansion with expansion modules when using a decoupling module (voltage
measurement in isolated networks) in connection with an operator panel with display
and basic unit 2 (24 V DC)
Table 1-25: Maximum expansion with expansion modules when using a decoupling module (voltage
measurement in isolated networks) in connection with an operator panel with display
and basic unit 2 (110 V - 240 V AC/DC)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-77
System Description
1.7.9 Accessories
The following figure shows accessories that are independent of the device
series:
Memory module
Connecting cable
PC cable
For device parameterization, for connecting a PC to the system interface of
a basic unit via theserial interface of the PC.
Memory module
For plugging onto the system interface and fast reading in or out of the
entire SIMOCODE pro parameterization, e.g. if a device is replaced (see
Chapter 14.3.3 "Replacing SIMOCODE pro Components").
Addressing plug
For the hardware-related allocation of the PROFIBUS DP address to
SIMOCODE pro without a PC/programming device via the system interface.
Setting the PROFIBUS DP address with an addressing plug:
See Chapter 14.2.2 "Setting the PROFIBUS DP Address".
Connecting cable
In various designs and lengths. These are required to connect the basic unit
to its current measuring module and, if applicable, to its expansion modules
or the operator panel. The total length of all connecting cables must not
exceed 3 m per system!
SIMOCODE pro
1-78 GWA 4NEB 631 6050-22 DS 02
System Description
Door adapter
To faciliate access (e.g. front panel) to the system interface of a system
(SIMOCODE pro), thus ensuring fast parameterization.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-79
System Description
1.7.10 Software
Note
Prerequisite for the installation of SIMOCODE ES Graphic is an installed
version of SIMOCODE ES Smart 2004 + Service Pack 1 or
SIMOCODE ES Professional + Service Pack 1 on the PC/programming
device.
Note
SIMOCODE ES is subject to continual maintenance and improvement.
Current Service Packs and Hotfixes can be downloaded at
http://www.siemens.com/simocode -> Support -> Tools & Downloads.
SIMOCODE pro
1-80 GWA 4NEB 631 6050-22 DS 02
System Description
Note
The PCS 7 library is subject to continual maintenance and improvement.
Current Service Packs and Hotfixes can be downloaded at
www.siemens.com/simocode -> Support -> Tools & Downloads
Notice
Observe the respective system versions!
GSD File
For integration into SIMATIC S7 or any DP standard mastersystem
(automation system). The latest version can be found on the internet at
http://www.siemens.com/profibus-gsd.
Further information about the integration of DP slaves can be found in the
automation system documentation.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-81
System Description
Properties
Function blocks are deposited in the SIMOCODE pro system, e.g., for the
administration of various control stations, for the configured control
function, or for motor protection. Every function block has a name and may
be equipped with inputs and outputs. The inputs and outputs are used for
the internal connection of the various funcion blocks and, thus, the setup of
a device-internal logic instead of an externally wired logic in the control
circuit.
The following table shows the possible input and output types of the
internal function blocks of SIMOCODE pro:
SIMOCODE pro
1-82 GWA 4NEB 631 6050-22 DS 02
System Description
1 1
IN1 Standard function OUT1
2 2
IN2 Function block C OUT2
3 3
IN3 OUT3
4 4
IN4
Standard function
Logic function
PROFIBUS DP PROFIBUS DP
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-83
System Description
Note
The plugs and sockets of the function blocks have not already been
connected at the factory with the binary inputs and the relay outputs of the
basic unit.
Internal wiring (connection of plugs and sockets) is determined by the
selected application. 1)
Note
If external wiring has already been carried out, but SIMOCODE pro has not
yet been parameterized:
If you now press a button, the contactors will not be activated! 1)
1) If you select and load a preset application (e.g. the reversing starter) in
SIMOCODE ES, all links and interlocks for the reversing starter arecreated in
the basic unit.
SIMOCODE pro
1-84 GWA 4NEB 631 6050-22 DS 02
System Description
See Chapter 8.
AM Output
AM Inputs
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-85
System Description
OP-LED
SIMOCODE pro
1-86 GWA 4NEB 631 6050-22 DS 02
System Description
OP Buttons
Operation Monitoring
Flashing 1 (2, 3)
OPO
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-87
System Description
DM1(2) Outputs
SIMOCODE pro
1-88 GWA 4NEB 631 6050-22 DS 02
System Description
DM1(2) Inputs
Extended Protection
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-89
System Description
Extended Control
Flickering 1 (2, 3)
SIMOCODE pro
1-90 GWA 4NEB 631 6050-22 DS 02
System Description
BU Outputs
BU Inputs
Emergency Start
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-91
System Description
TPF
Protection/Control
SIMOCODE pro
1-92 GWA 4NEB 631 6050-22 DS 02
System Description
Control Stations
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-93
System Description
Current Limits
Thermistor
SIMOCODE pro
1-94 GWA 4NEB 631 6050-22 DS 02
System Description
Timer 1 (and 2, 3, 4)
TM Inputs
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-95
System Description
Monitoring 0/4 - 20 mA
SIMOCODE pro
1-96 GWA 4NEB 631 6050-22 DS 02
System Description
Earth-Fault Monitoring
Power Monitoring
Voltage Monitoring
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-97
System Description
Temperature Monitoring
UVO
SIMOCODE pro
1-98 GWA 4NEB 631 6050-22 DS 02
System Description
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-99
System Description
Watchdog
Counter 1 (2, 3, 4)
Timestamping
SIMOCODE pro
1-100 GWA 4NEB 631 6050-22 DS 02
System Description
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 1-101
System Description
SIMOCODE pro
1-102 GWA 4NEB 631 6050-22 DS 02
Short Instructions for Configuring
a Reversing Starter 2
In this chapter
In this chapter you will find short instructions for configuring a reversing
starter, with the aid of a practical example. The majority of the parameters
have been appropriately preset at the factory for most applications.
You only need to set a few parameters.
Target groups
This chapter is addressed to the following target groups:
• Planners
• Configurators
• Technicians
• Electricians
• Commissioners.
Necessary knowledge
You will require the following knowledge:
• Basic SIMOCODE pro knowledge (see Chapter 1 "System Description")
• Basic knowledge of SIMOCODE ES parameterization software.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 2-1
Short Instructions for Configuring a Reversing Starter
Fundamental steps
The two fundamental SIMOCODE pro steps are always:
• Implementation of external wiring (for control and feedback of main current
switching devices and control and signaling devices)
• Implementation/activation of internal SIMOCODE pro functions (function
blocks), with control and evaluation of the SIMOCODE pro inputs/outputs
(internal SIMOCODE pro wiring).
Prerequisites
• Load feeder/motor is present
• PLC/PCS control with PROFIBUS DP interface is present
• The main circuit of the reversing circuit, including the current measuring
module, has already been wired. In this case, the 3 cables leading to the
motor must be led through the through-hole openings of the current
measuring module.
• PC/programming device is present
• SIMOCODE ES software is installed
• The Basic Unit has the basic factory settings. You can find out how to
implement the basic factory settings in .
SIMOCODE pro
2-2 GWA 4NEB 631 6050-22 DS 02
Short Instructions for Configuring a Reversing Starter
6 PROFIBUS DP cable
Table 2-1: Components required for this example
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 2-3
Short Instructions for Configuring a Reversing Starter
L1/L+
1 3 5
Q1 F11
2 4 6 S0 S1 S2
3 through-hole
Current Measuring A2 A1 IN1 IN2 IN3 24 V
openings
Module (IM) Basic Unit (BU)
System System
Connecting cable
interface interface
OUT1 OUT2 1
1 3 5 K1 K2
1 3 5 N/L–
- K1 - K2
2 4 6 2 4 6
PE U V W
Motor, motor rated current e.g. 3 A
M J CLASS 10
3~
Optional: Thermistor
Fig. 2-1: Wiring of the main circuit and the control circuit with SIMOCODE pro
SIMOCODE pro
2-4 GWA 4NEB 631 6050-22 DS 02
Short Instructions for Configuring a Reversing Starter
L1/L+ L1/L+
S0 S1 S2
K2 K1
OUT1 OUT2 1
K1 K2 K1 K2
N/L– N/L–
The necessary interlocks and connections are carried out in the Basic Unit
via software.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 2-5
Short Instructions for Configuring a Reversing Starter
2.3 Parameterization
The basics of parameterization
After the external wiring has been carried out (contactor coils connected,
current measuring module integrated in the main circuit), SIMOCODE pro is
then parameterized.
For this you need to know the following points:
Point Description
1 Function blocks are stored internally in the SIMOCODE pro system, e.g. for
control stations, control functions and motor protection.
2 Function blocks have names.
3 Function blocks may have set values, e.g. the type of control function and the
set current for overload protection.
4 Function blocks are equipped with plugs and sockets. These, in turn, are
clearly designated.
5 To achieve the desired functionality, proceed as follows:
• Connect the function blocks by connecting specific plugs to specific
sockets (i.e "plug the plugs into the sockets")
• If required, set values in the function blocks, e.g. the set current, type of
control function.
6 The inputs of the function blocks in the Basic Unit are designated as plugs
and labeled accordingly:
7 The outputs of the function blocks in the Basic Unit are designated as
sockets and labelled accordingly:
8 The plugs and sockets of the device inputs and outputs are not connected as
factory defaults. If you press a button now, the contactors will not be
activated.
Table 2-2: Schematic of the various SIMOCODE pro function blocks
SIMOCODE pro
2-6 GWA 4NEB 631 6050-22 DS 02
Short Instructions for Configuring a Reversing Starter
SIMOCODE pro
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 2-7
Short Instructions for Configuring a Reversing Starter
Proceed as follows:
Step Description
QE2 2
Note
By choosing a preset application (Step 2), other presettings might be made
when assigning the BU outputs to the contactor controls.
6 Open the dialog Device Parameters> Motor Control > Control Stations
and check the following settings:
• Local Control [LC] ON<: BU Input 1
• Local Control [LC] OFF: BU Input 2
• Local Control [LC] ON>: BU Input 3
"BU Inputs" The control station "Local Control"
Protection/Control is now connected with the binary
1 ON< inputs of the Basic Unit.
2 OFF
3 ON>
Check whether the releases for "ON" and "OFF" for operating mode "Local2"
are set.
7 Parameterization is complete. Save the parameter file on your PC/
programming device using Device > Save.
SIMOCODE pro
2-8 GWA 4NEB 631 6050-22 DS 02
Short Instructions for Configuring a Reversing Starter
Step Description
Table 2-4: Transferring the parameters to the Basic Unit and commissioning
Attention
Switching between "RIGHT" and "LEFT" is only possible via "OFF" after the
preset, 5-second interlocking time has expired.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 2-9
Short Instructions for Configuring a Reversing Starter
Prerequisites
The following prerequisites must be fulfilled:
• The motor is switched off
• The supply voltage for the Basic Unit is switched on. The “Device” LED lights
up green
• You have connected the Basic Unit to the PROFIBUS DP. The PROFIBUS DP
interface is on the front side (9-pole SUB-D- socket)
• You have integrated SIMOCODE pro into your automatization system.
Further information about the integration of DP slaves can be found in the
automation system documentation.
SIMOCODE pro
2-10 GWA 4NEB 631 6050-22 DS 02
Short Instructions for Configuring a Reversing Starter
Step Description
Step Description
Table 2-6: Setting the PROFIBUS DP address via the addressing plug
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 2-11
Short Instructions for Configuring a Reversing Starter
SIMOCODE pro
Cyclic Cyclic
PROFIBUS DP Receive Bit 0.0 Status - Send
Bit 0.0
LEFT ON<
Bit 0.1 Bit 0.1
DP
OFF OFF DP
Bit 0.2 Bit 0.2
RIGHT ON>
Bit 0.5w
S1
Fig. 2-4: Schematic of Basic Unit internal components for this example
SIMOCODE pro
2-12 GWA 4NEB 631 6050-22 DS 02
Motor Protection 3
In this chapter
In this chapter you will find information about Motor Protection.
Motor Protection includes
• Overload Protection
• Unbalance Protection
• Stalled Rotor Protection
• Thermistor Protection.
Motor Protection operates alongside Motor Control "at a higher level in the
background". All Motor Protection parameters are explained here. They can
be active or not, according to the control function selected.
Target groups
This chapter is aimed at the following target groups:
• Configurators
• Commissioners.
Necessary knowledge
You will require the following knowledge:
• Good knowledge of SIMOCODE pro
• The principle of connecting plugs to sockets
• Knowledge of electrical drive engineering.
Navigation in SIMOCODE ES
You will find the dialogs in SIMOCODE ES under
Device Parameters > Motor Protection.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 3-1
Motor Protection
3.1 Introduction
Description
The motor protection functions "Overload Protection", "Unbalance
Protection",
"Stalled Rotor Protection" and "Thermistor Protection" are described in
Chapters 3.2 to 3.4
Schematic
The following schematic diagram shows the "Ext. Protection" function block
("Overload Protection", "Unbalance Protection" and "Stalled Rotor Protection")
with optional parameter settings and events.
SIMOCODE pro
3-2 GWA 4NEB 631 6050-22 DS 02
Motor Protection
Protection/Control
Overload Protection
QE1
Set Current Is1 QE2
Tripping
QE3
Is1 Transformation Ratio -
Active 1) QE4
QE5
Is1 Transformation Ratio -
Counter 1)
Pause Time
Unbalance Protection
Fig. 3-1: "Ext. Protection" function block (Overload Protection, Unbalance Protection and
Stalled Rotor Protection)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 3-3
Motor Protection
Notice
Deactivate the Unbalance Protection in SIMOCODE ES when the Type of
Load is set for 1-phase!
SIMOCODE pro
3-4 GWA 4NEB 631 6050-22 DS 02
Motor Protection
Note
This parameter is only available when using Basic Unit 2 from product
version *E03*.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 3-5
Motor Protection
Note
This parameter is only available when using Basic Unit 2 from product
version *E03*.
SIMOCODE pro
3-6 GWA 4NEB 631 6050-22 DS 02
Motor Protection
Note:
In the case of motors with two speeds, the same or different Transformation
Ratios can be set for each speed, depending upon whether the same or two
different interposing transformers is/are used for each speed.
Application examples
Example 1:
Motor Rated Current: 700 A.
A 3UF18 68-3G current transformer (205 to 820 A) is used as interposing
transformer (transformation ratio 820 : 1), the secondary side is carried out
via a Current Measuring Module 0.3 up to 3 A: Transformation Ratio for as =
820: 1; ls = 700 A
Settings:
• Set Current Is1: 700 A
• Is1 Transformation Ratio - Counter 820
• Is1 Transformation Ratio - Denominator: 1
Example 2:
Motor Rated Current: 225 A.
A 3UF18 68-3G current transformer (205 to 820 A) is used as interposing
transformer (Transformation Ratio 820 : 1), the secondary side is carried out
twice via a Current Measuring Module 0.3 up to 3 A: Transformation Ratio
for ls = 820 : 2; ls = 225 A
Settings:
• Set Current Is1: 225 A
• Is1 Transformation Ratio - Counter: 820
• Is1 Transformation Ratio - Denominator: 2.
Example 3:
The motor rating is carried out twice via a Current Measuring Module 0.3 up
to 3 A for a motor with rated motor current 0.25 A: Transformation Ratio for
ls = 1: 2; Is = 0.25 A
Settings:
• Set Current Is1: 0.25 A
• Is1 Transformation Ratio - Counter: 1
• Is1 Transformation Ratio - Denominator: 2
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 3-7
Motor Protection
Class
The class (tripping class) indicates the maximum tripping time within which
SIMOCODE pro must trip cold at 7.2 times the Set Current Is (motor
protection according to IEC 60947). Please take into account that with start-
ups > "Class 10", the admissible AC3 current of the contactor may have to
be reduced (derating), i.e. a larger contactor selected.
The following figure shows Tripping Classes 5, 10, 15, 20, 25, 30, 35 and 40
for 3-pole symmetrical loads:
1.15
SIMOCODE pro
3-8 GWA 4NEB 631 6050-22 DS 02
Motor Protection
The following figure shows Tripping Classes 5, 10, 15, 20, 25, 30, 35 and 40
for 2-pole loads:
0,85
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 3-9
Motor Protection
Response to Overload
In the case of overload, the SIMOCODE pro response can be additionally
adjusted here:
For further information: See "Tables of Responses of SIMOCODE pro" in
Chapter "Important Information" and the "Responses" table in
Chapter 3.1 "Introduction".
Attention
With motors for EEx e applications, the response must remain set to
"Tripping"!
Pause Time
The Pause Time is the specified time for the cooling response of the motor
when switched off under normal operating conditions (not in the case of an
overload trip!). After this interval, the Thermal Memory in SIMOCODE pro is
deleted and a new cold start is possible. This makes frequent start-ups
possible within a short period of time.
SIMOCODE pro
3-10 GWA 4NEB 631 6050-22 DS 02
Motor Protection
The following schematic shows the Cooling Off Response with and without
Pause Time:
Motor
ON
OFF
t
Thermal Memory (Motor Model)
Without Pause Time
Overload Trip
No Overload Trip
Pause Time t
Thermal Memory will be deleted after the Pause Time
elapses
Fig. 3-4: Cooling Down Response with and without Pause Time
Attention
Both the motor and the switching devices must be dimensioned specifically
for this load!
Type of Load
You can select whether SIMOCODE pro is to protect a 1-phase or a 3-phase
load.
For a "1-phase" Type of Load, proceed as follows:
• The Internal Earth-fault Monitoring and the Unbalance Protection must be
deactivated
• Only one of the two cables is to be fed through any through-hole opening in
the Current Measuring Module.
Phase Failure Monitoring is deactivated automatically.
Type of Load: 1-phase, 3-phase
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 3-11
Motor Protection
Pre-alarm Delay
The "Delay" parameter (default: 0.5 s) determines the amount of time that
the Pre-warning Level (1.15 x Is) must be constantly exceeded before
SIMOCODE pro executes the desired response. Otherwise there will be no
reaction.
In the case of phase failure or > 50 % unbalance, this pre-warning will
already be issued at approx. 0.85 x Is.
Reset
If the "Reset" parameter is set to "Auto", the "Overload", "Overload +
Unbalance" and "Thermistor" faults will be acknowledged automatically
• When the Cooling Down Period has expired
• When the thermistor value has dropped back down to the specified resetting
value.
Warning
The "Auto-Reset" mode must not be used for applications where an
unexpected motor restart may cause personal injury or damage to property.
SIMOCODE pro
3-12 GWA 4NEB 631 6050-22 DS 02
Motor Protection
Level
The level of unbalance to which SIMOCODE pro should react when overshot
is set here.
Level: 0 to 100%
Default: 40%
Response
Here you can choose the response of SIMOCODE pro in case of Phase
Unbalance:
See "Tables of Responses of SIMOCODE pro" in Chapter "Important
Information" and the "Responses" table in Chapter 3.1 "Introduction".
Delay
The unbalance level must be exceeded for the period of the set delay time
before SIMOCODE pro executes the desired response. Otherwise there will
be no reaction.
Setting range: 0 - 25.5 s (default: 0.5 s).
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 3-13
Motor Protection
Level
Upon exceeding the Stalled Rotor Level, SIMOCODE pro reacts according to
the selected response.
Range:
Level: 0 to 1020% of ls
Response
Here you can determine the response when the Stalled Rotor Level is
exceeded:
See "Tables of Responses of SIMOCODE pro" in Chapter "Important
Information" and the "Responses" table in Chapter 3.1 "Introduction".
Delay
The "Delay" parameter determines the amount of time that the Stalled Rotor
Level must be constantly exceeded before SIMOCODE pro executes the
desired response. Otherwise there will be no reaction.
Setting range: 0 - 25.5 s (default: 0.5 s).
SIMOCODE pro
3-14 GWA 4NEB 631 6050-22 DS 02
Motor Protection
R QE1
Thermistor
QE2
Tripping
QE3
υ
QE4
Response
• Overtemperature:
Here you can select the SIMOCODE pro response if the temperature exceeds
the trip level.
Attention
For motors for EEx e applications, the response must be set to "Tripping"!
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 3-15
Motor Protection
SIMOCODE pro
3-16 GWA 4NEB 631 6050-22 DS 02
Motor Control 4
In this chapter
In this chapter you will find information on
• Control stations which you can select and enable according to need. The
following related topics are explained:
– How Control Stations, operating modes and Releases work together,
– How Ccontrol commands, e.g. "ON", "OFF", are switched through to the
control function.
• Control functions you can select according to need. The following related
topics are explained:
– How control commands, e.g. "ON", "OFF", are switched through from
the Control Stations to the Contactor Controls/Relay Outputs
– Which parameters apply depending on the control function chosen.
Target groups
This chapter is addressed to the following target groups:
• Configurators
• PLC programmers.
Necessary knowledge
You will require the following knowledge:
• The principle of connecting plugs to sockets
• Electrical drive engineering
• Motor protection.
Navigation in SIMOCODE ES
You will find the dialogs in SIMOCODE ES under
Device parameter > Motor Control.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 4-1
Motor Control
Control stations are places from which control commands can be given to
the motor. The "Control Stations" function block is used for administration,
switching and prioritization of these different Control Stations. With this,
SIMOCODE pro allows the parallel administration of up to four different
Control Stations. Dependent on the specified control function, up to 5
different control commands can be transmitted from every Control Station
to SIMOCODE pro.
• Local, in the direct vicinity of the motor. Control commands are issued via
pushbutton.
• PLC/PCS, switching commands are issued by the automation system
(remote).
• PC, control commands are issued via an Operator Control Station or via
PROFIBUS DPV1 with the SIMOCODE ES software.
• Operator Panel, control commands are issued via the buttons of the
Operator Panel in the switchgear cabinet door.
Control commands can be, e.g:
– Motor ON (ON>), Motor OFF (OFF) for a direct starter
– Motor LEFT (ON<), Motor OFF (OFF), Motor RIGHT (ON>) for a reversing
starter
– Motor SLOW (ON>), Motor FAST (ON>>), Motor OFF (OFF) for a Dahlander
circuit.
The plugs of the "Control Stations" function block must be connected to
arbitrary sockets (e.g. binary inputs on the Basic Unit, control bits from
PROFIBUS DP, etc.) for the control commands to take effect.
Up to 5 different control commands can be sent from each Control Station.
Up to 5 plugs (plug ON<<, ON<, OFF, ON>, ON>>) are available on the
function block per Control Station. The number of active plugs depends on
the chosen control function. With a direct starter, for example, only the
plugs "ON>" and "OFF" are active.
SIMOCODE pro
4-2 GWA 4NEB 631 6050-22 DS 02
Motor Control
Control Stations
• Control Station - Local Control
In this case, the control devices are usually in the direct vicinity of the motor
and are wired to the inputs of SIMOCODE pro. The plugs of the "Control
Stations" function block must be connected to arbitrary sockets (normally the
function blocks for the Basic Units or the Digital Module Inputs, Basic Unit
Inputs, DM Inputs) for the control commands to take effect.
Notice
The OFF command "LC OFF" is 0-active. This ensures that SIMOCODE pro
switches off the motor safely e.g. if a wire break occurs in the supply cable.
The precondition is that the control station is active.
Pushbutton BU Inputs
Local Control
ON << Station [LC] Releases
1
IN1 ON < ON
2
IN2 OFF
IN3 3 OFF
ON >
4
IN4
ON >>
PLC/PCS [DP]
ON << Releases
O
Fig. 4-1: Control Station - Local Control
ON >>
Bit 1.7
PC [DPV1]
ON << Releases
Fig. 4-2: Control Station - PLC/PCS
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-3
Motor Control
• Control Station - PC
This Control Station is primarily intended for switching commands on an
arbitrary PC which, along with the automation system, is used as a second
master on the PROFIBUS DP. The control commands are sent via the
Acyclic Receive telegram from PROFIBUS DPV1.
Note
If the SIMOCODE ES Professional/SIMATIC PDM PC software is connected to
SIMOCODE pro via PROFIBUS DP, its control commands automatically take
effect via the PC[DPV1] Control Station. In this case connection is not required!
Acycl. Receive
PC [DPV1]
Bit 0.0 ON << Releases
PC
ON < ON
OFF
DP Number: 16
OFF
ON >
Notice
Since the Operator Panel only has four buttons for controlling the motor
feeder, one button must be used as a speed switch button for control
functions with two rotational speeds and two directions of rotation.
For this purpose, the button must be assigned to the internal control
command "[OP]<>/ <<>>".
Notice
If the SIMOCODE ES PC software on a programming device is connected to
SIMOCODE pro via the system interface, the control commands
automatically take effect via the Control Station Operator Panel (OP) and
must also be enabled here as applicable.
SIMOCODE pro
4-4 GWA 4NEB 631 6050-22 DS 02
Motor Control
ON >>
Operating modes
You can use the Control Stations either individually or in combination. There
are four different operating modes you can switch between:
• Local 1
• Local 2
• Local 3
• Remote/Automatic: In this operating mode, the communication must be
carried out via PLC.
Not all Control Stations are usually connected. If more than one Control
Station (e.g local and PLC/PCS) is connected, it makes sense and is also
mandatory to operate the Control Stations selectively. Four operating
modes are provided for this purpose which can be selected via two control
signals (mode selectors). For each individual Control Station in every
operating mode, it can be stipulated if "ON commands" and/or "OFF
commands" are to be used. The operating modes are so controlled that only
one operating mode is active at any one time.
Example: There are three operating modes in a system:
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-5
Motor Control
S2 0 1 0 1
The different operating modes for enabling the Control Stations can be used
to specify the switch authorizations for the individual Control Stations
• Local Control Station [LC]
• PLC/PCS [DP]
• PC [DPV1]
• Operator Panel (OP).
S1 0 1 1 1 0
S2 0 1 0 1 0
0 Time t
Fig. 4-5: Example - operating modes
SIMOCODE pro
4-6 GWA 4NEB 631 6050-22 DS 02
Motor Control
Releases
Releases for the control commands "ON" and "OFF", which must be
activated, are assigned to each operating mode or every single Control
Station. This means that depending on the operating mode, it can be
specified for each Control Station whether the motor may only be switched
on, off or both on and off. The corresponding checkbox is activated in the
"Control Stations" dialog in SIMOCODE ES.
Releases and enabled control command schematic
The following schematic shows the "Control Stations" function block and the
operating modes:
Control Stations
PLC/PCS [DP]
ON << Releases
ON < ON
OFF To the control function
OFF "Protection/Control"
ON >
ON <<
ON >> Enabled ON <
control
command OFF
PC [DPV1]
ON << Releases ON >
ON < ON ON >>
OFF
OFF
ON >
ON >>
Op. Panel[OP]
<>/<<>> Releases
ON < ON
OFF
OFF
ON >
ON >>
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-7
Motor Control
In the example, the motor can only be switched on and off in the "Local 2"
operating mode via the buttons (local) connected to the inputs of the Basic
Unit and the Digital Module.
SIMOCODE pro
4-8 GWA 4NEB 631 6050-22 DS 02
Motor Control
OFF
ON >
ON >>
OFF
ON >
ON >>
OFF
ON >
ON >>
Operator Panel [OP] Activates the Control Station via an arbitrary signal
<>/<<>> (arbitrary sockets , but usually Operator Panel
buttons)
ON <
OFF
ON >
ON >>
Operating Mode Selectors For switching between the 4 operating modes Local 1,
S1 Local 2, Local 3 and remote with arbitrary signals
(arbitrary sockets , e.g. device inputs, control bits
S1 from PROFIBUS DP, etc.)
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-9
Motor Control
Control functions (e.g. direct starters, reversing starters) are used for
controlling load feeders.
They have the following important features:
• Monitoring the switch-on/switch-off sequence
• Monitoring the ON/OFF status
For monitoring these statuses, SIMOCODE pro uses the auxiliary control
input "Feedback ON", which is usually derived directly from the current flow
in the main circuit via the current measuring modules.
All necessary interlocks and connections for the corresponding applications
are already implemented in the control functions.
Control functions contain:
• Plugs for
– control commands (ON <<, ON <, OFF, ON >, ON >>) that are usually
connected with the "Enabled Control Command" sockets.
• Auxiliary control inputs (plug ), e.g. Feedback ON
• Sockets for
– Contactor controls QE1 to QE5.
– Displays (lamp controls) QL, QLS.
– Statuses, e.g. "Status - ON <<, Status - ON >>".
– Faults, e.g. "Trip - Feedback (F) ON",
"Trip - Antivalence".
• Settings, e.g. Interlocking Time, Non-maintained Command Mode ON/OFF,
etc.
• A logic component with all necessary interlockings and connections for the
control function
• Like control functions, the motor protection with its parameters and signals is
active "at a higher level in the background". Motor protection and thermistor
protection are independent functions that switch off the motor when
activated via the control functions. For a more detailed description, see
Chapter 3 "Motor Protection".
SIMOCODE pro
4-10 GWA 4NEB 631 6050-22 DS 02
Motor Control
Fig. 4-8: General representation of the control function ("Protection/Control" function block)
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-11
Motor Control
•Timings FB OPEN
•Operating Mode
TQ CLOSED
•Star-delta
TQ OPEN
Trip - FB ON
Trip - FB OFF
Trip - Double 0
Trip - Double 1
Fig. 4-9: General representation of the control function ("Extended Control" function block)
Contactor controls:
SIMOCODE pro
4-12 GWA 4NEB 631 6050-22 DS 02
Motor Control
Note
If the motor is running in test operation, the QLE.../QLA lamp outputs show a
different response (e.g. flashing).
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-13
Motor Control
SIMOCODE
Overload Relay ✓ ✓
Direct Starter ✓ ✓
Reversing Starter ✓ ✓
Circuit Breaker ✓ ✓
Star-delta Starter — ✓
Star-delta Reversing Starter — ✓
Dahlander — ✓
Dahlander Reversing Starter — ✓
Pole-changing Starter — ✓
Pole-changing Reversing Starter — ✓
Solenoid Valve — ✓
Positioner 1 to Positioner 5 — ✓
Soft Starter — ✓
Soft Starter with Reversing Contactor — ✓
Table 4-4: Control functions
SIMOCODE pro
4-14 GWA 4NEB 631 6050-22 DS 02
Motor Control
Application selection
Selection of the control functions to be carried out by SIMOCODE pro:
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-15
Motor Control
Parameters
Parameters Description
ON <<, ON <, OFF, Are usually connected with the "Enabled Control Command"
ON >, ON >> sockets of the "Control Station" function block. From there, the
control commands come from the different control stations. The
number of active inputs depends on the control function chosen.
For example, with a direct starter, only the inputs "ON>" and "OFF"
are active.
Default: Connected
FC, FO, TC, TO Auxiliary Control Inputs for the "Positioner" and "Solenoid Valve"
control function that are normally connected with the inputs of the
Basic Unit or the Digital Module are used to query the present
status of the Torque Switch and the Limit Switches that are wired
to the Inputs.
Non-maintained • Deactivated:
command mode The control command on the corresponding input of the Control
Stations "ON <, ON <<, ON >,ON >>" is saved. It can only be
revoked by an "OFF" control command from the corresponding
Control Station. The auxiliary contact for locking the contactor is
no longer necessary. Motor feeders are usually operated in
locking mode. Locking is preset.
• Activated:
Depending on the control function chosen, the Non-maintained
Command Mode affects the plugs of all Control Stations "ON <,
ON <<, ON >, ON >>".A control command is only effective as
long as there is a "High Signal".
SIMOCODE pro
4-16 GWA 4NEB 631 6050-22 DS 02
Motor Control
Parameters Description
Feedback Time SIMOCODE pro monitors the status of the feeder (ON or OFF) via
FB ON.
If the status of FB ON changes - without a corresponding switching
command - the Trip feedback (FB) switches off the feeder.
Default: 0.5 s.
The feedback time can be used to suppress such "feedback faults"
for a defined period of time, e.g. in the case of network
switches.When the motor is switched off,
SIMOCODE pro continuously controls if FB ON = 0. If the current
flows longer than the set feedback time without the "ON" control
command being issued, fault message "Trip - Feedback (FB) ON" is
issued. The contactor controls can only be connected after the fault
has been rectified.
When the motor is switched on, SIMOCODE pro continuously
controls if FB ON = 1. If the current flows longer than the set
Feedback Time without the "OFF" control command being issued, a
fault message "Trip - Feedback (FB) OFF" is issued. The contactor
controls are deactivated.
Execution Time SIMOCODE pro monitors switching on/switching off. Switching on/
switching off must be completed within this time period.
Default: 1.0 s.
After the "ON" control command is issued, SIMOCODE pro must be
able to detect current in the main circuit within the execution time.
Otherwise, the fault message "Trip - Execution ON Command" will
be issued. SIMOCODE pro deactivates the contactor controls.
After the "OFF" control command is issued, SIMOCODE pro must
not be able to detect any current in the main circuit after the
execution time has elapsed. Otherwise, the fault message "Trip -
Execution STOP command" will be issued. The contactor controls
can only be connected after the fault has been rectified.
Interlocking Time SIMOCODE pro prevents, e.g. in the case of reversing starters,
both contactors from switching on at the same time. Switching
from one direction of rotation to the other can be delayed via the
Interlocking Time.
Default: 0 s.
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-17
Motor Control
Parameters Description
Max. Star Time For the "Star-delta Starter" or the "Star-delta Reversing Starter"
control function:
Time-dependent switching from star to delta.
Max. star time: 0 - 255 s (default: 20 s)
Current Measuring For the "Star-delta Starter" or the "Star-delta Reversing Starter"
Module Installed control function:
The Set Current and the switching levels for star-delta switching
depend on the mounting place of the Current Measuring Module.
• Delta: Set Current Is is reduced to In x 1/ 3
• In supply cable: Set Current
Table 4-5: General settings and definitions (Cont.)
QE
Switch ON ON Tripping
1
OFF OFF
0
Voltage failure,
FB ON e.g. pulsating current conditions
OFF
0
Az Rz Az Rz
Fig. 4-11: Execution Time (Az) and Feedback Time (Rz) in relation to FB ON
Faults
The contactor controls are deactivated.
The following is also issued:
• A flashing signal on the QLS lamp control
• A flashing signal on the "GEN. FAULT" LED
• The "Status - General Fault" signal
• The corresponding signaling bit of the fault.
SIMOCODE pro
4-18 GWA 4NEB 631 6050-22 DS 02
Motor Control
Protection/Control ContactorControls
QE3
Overload Relay
Motor Protection
Displays
Auxiliary Control Inputs
Type of
FB ON* Consumer Load QLS
(Fault)
*Feedback ON
Fig. 4-12: Schematic of the "Overload Relay" control function, "Protection/Control" function block
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
Overload relay Description
FB ON Auxiliary control input "Feedback ON" (connection with arbitrary
socket , usually with "Status - Motor Current Flowing" socket) as
factory default.
Type of Consumer You can choose between
Load • Motor
• Resistive load (see Chapter 4.2.2 "General Settings and
Definitions")
Table 4-6: Overload relay settings
Notice
In the case of overload, the QE3 output is set (=1) and is only reset when
the overload is tripped (=0).
This output closes when the overload function is parameterized.
Note
Monitoring of the number of starts is not possible for this control function.
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-19
Motor Control
Description
SIMOCODE pro can switch a motor on and off with this control function.
Control commands
• Start with "ON >" activates the QE1 internal contactor control.
• Stop with "OFF" deactivates the QE1 internal contactor control.
The control commands can be issued to SIMOCODE pro from
arbitrary control stations (see also the description of "Control Stations").
Thus, the inputs (plugs) must be connected to the corresponding sockets,
preferably to the "Enabled Control Command" sockets.
Every fault signal causes the QE1 contactor control to be deactivated.
Schematic
Type of
Consumer Load QLA (OFF)
Feedback Time QLE >
(ON)
Auxiliary Control Inputs Execution Time
FB ON*
QLS
(Trip )
Status
OFF
ON >
*Feedback ON
Fig. 4-13: Schematic of the "Direct Starter" control function, "Protection/Control" function block
SIMOCODE pro
4-20 GWA 4NEB 631 6050-22 DS 02
Motor Control
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
Non-maintained • Deactivated
Command Mode • Activated
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-21
Motor Control
Description
With this control function, SIMOCODE pro can control the direction of
rotation of the motor (forwards and backwards).
Control commands
• Start with "ON >" activates the QE1 contactor control (clockwise, i.e.
forwards)
• Start with "ON <" activates the QE2 contactor control (counter-clockwise, i.e.
backwards)
• Stop with "OFF" deactivates the QE1 and QE2 internal contactor controls.
The control commands can be issued to SIMOCODE pro from
arbitrary control stations (see also the description of "Control Stations").
Thus, the inputs (plugs) must be connected to the corresponding sockets,
preferably to the "Enabled Control Command" sockets.
Every fault signal causes the QE1 and QE2 contactor controls to be
deactivated.
SIMOCODE pro
4-22 GWA 4NEB 631 6050-22 DS 02
Motor Control
Schematic
Status
ON <
OFF
ON >
Fig. 4-14: Schematic of the "Reversing Starter" control function, "Protection/Control" function block
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-23
Motor Control
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
Non-maintained • Deactivated
Command Mode • Activated
SIMOCODE pro
4-24 GWA 4NEB 631 6050-22 DS 02
Motor Control
Description
SIMOCODE pro can ideally switch circuit breakers (e.g. 3WL, 3VL) ON and
OFF with this control function. The circuit breakers are connected to
PROFIBUS DP via SIMOCODE pro.
Control commands
• Start with "ON >" activates the QE1 contactor control for a pulse of 400 ms.
• Stop with "OFF" activates the QE3 contactor control for a pulse of 400 ms.
• With "Reset", the QE3 contactor control is activated for a pulse of 400 ms
when the circuit breaker is tripped (alarm switch = ON).
The pulse of a control command is always fully executed before the
"Counter Pulse" is set.
The control commands can be issued to SIMOCODE pro from arbitrary
Control Stations (see also the description of "Control Stations"). Thus, the
inputs (plugs) must be connected to the corresponding sockets, preferably
to the "Enabled Control Command" sockets.
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-25
Motor Control
Schematic
Status
OFF
ON >
*Feedback ON
Fig. 4-15: Schematic of the "Circuit Breaker" control function, "Protection/Control" function block
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
SIMOCODE pro
4-26 GWA 4NEB 631 6050-22 DS 02
Motor Control
Description
Star-delta starting is used to limit the starting current and to avoid
overloading the network. In this control function, SIMOCODE pro initially
starts the motor with a star-switched stator winding and then switches it to
delta.
Control commands
• Start with "ON" first activates the QE1 contactor control (star contactor) and
then immediately activates the QE3 contactor control (network contactor)
• Stop with "OFF" deactivates the QE1, QE2 and QE3 contactor controls.
The control commands can be issued to SIMOCODE pro from arbitrary
control stations (see also the description of "Control Stations"). Thus, the
inputs (plugs) must be connected to the corresponding sockets, preferably
to the "Enabled Control Command" sockets. Every fault signal causes the
QE1, QE2 and QE3 contactor controls to be deactivated.
Safety information
Notice
It is recommended to wire the QE Contactor Controls to the Relay Outputs
of the Basic Unit.
Notice
If you use internal earth-fault detection for star-delta circuits, this can lead to
false trippings. During delta operation, the summation current is non-zero
due to harmonics.
Notice
If the Current Measuring Module is switched to delta (normal case),
a current which is 1/√ 3 times smaller must be set for the star-delta starter
control function.
Example: In = 100 A Is = In x 1/√ 3
Is = 100 A x 1/√ 3 = 57.7 A
Current to be set Is = 57.7 A
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-27
Motor Control
Change-over Pause
The switching time from star to delta can be extended by the change-over
pause.
Reason: For motors with a high ratio between starting current and rated
current, the mains voltage plus motor EMF might lead to a very high delta
starting current if the Change-over Pause is too short. The motor EMF
decreases if the pause is longer.
Schematic
Type of
ConsumerLoad QLA (OFF)
FeedbackTime QLE >
(ON)
Auxiliary Control Inputs Execution Time
FB ON*
QLS
Change-over Pause (Trip)
Status
Max. Star Time
Transformer
mounted OFF
ON >
Fig. 4-16: Schematic of the "Star-delta Starter" control function, "Protection/Control" function block
SIMOCODE pro
4-28 GWA 4NEB 631 6050-22 DS 02
Motor Control
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
Non-maintained • Deactivated
Command Mode • Activated
Current Measuring The Set Current and the switching levels for star-delta switching
Module Installed1) depend on the mounting place of the Current Measuring Module.
• in Delta: Set Current Is is reduced to In x 1/√3 (default)
• In Incoming cable: Set Current Is = In (Rated Current of the
motor)
Table 4-10: Star-delta Starter settings
1) Notice
If a current/voltage measuring module is in use, the transformer must be
connected to the supply cable!
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-29
Motor Control
Description
With this control function, a motor can be started in both directions of
rotation in star-delta operation.
Control commands
• Clockwise rotation: start with "ON >" first activates the QE1 (Star Contactor)
Contactor Control and then immediately activates the QE3 Contactor Control
(Network Contactor, clockwise rotation)
• Counter-clockwise rotation: Start with "ON <" first activates the QE1
Contactor Control (Star Contactor) and then immediately activates the QE4
Contactor Control (Line Contactor, left)
• Stop with "OFF" deactivates the QE1, QE2, QE3 and QE4Contactor Controls.
The control commands can be issued to SIMOCODE pro from arbitrary
control stations (see also the description of "Control Stations"). Thus, the
inputs (plugs) must be connected to the corresponding sockets, preferably
to the "Enabled Control Command" sockets.
Every fault signal causes the QE1, QE2, QE3 and QE4 contactor activations
to be deactivated.
SIMOCODE pro
4-30 GWA 4NEB 631 6050-22 DS 02
Motor Control
Safety information
Note
It is recommended to wire the QE1 and QE2 Contactor Controls to the
Relay Outputs of the Basic Unit. You need at least 1 Digital Module for this
control function.
Notice
If you use internal earth-fault detection for star-delta circuits, this can lead to
false trippings. During delta operation, the summation current is non-zero
due to harmonics.
Notice
If the Current Measuring Module is switched to delta (normal case), a
current which is 1/ 3 smaller than normal must be set for the star-delta
starter control function.
Example: In = 100 A Is = In x 1/ 3
Is = 100 A x 1/ 3 = 57.7 A
Current to be set Is = 57.7 A
Change-over Pause
The switching time from star to delta can be extended by the Change-over
Pause.
Reason: For motors with a high ratio between Starting Current and Rated
Current, the mains voltage plus motor EMF might lead to a very high Delta
Starting Current if the Change-over Pause is too short. The motor EMF
decreases if the pause is longer.
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-31
Motor Control
Schematic
Change-over Pause
*Feedback ON Extended Control
Active
Interlocking Time
Active
Fig. 4-17: Schematic of the "Star-delta Reversing Starter" control function, "Protection/Control"
function block
SIMOCODE pro
4-32 GWA 4NEB 631 6050-22 DS 02
Motor Control
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
Star-Delta Description
Reversing Starter
Non-maintained • Deactivated
Command Mode • Activated
1) Notice
If a Current/Voltage Measuring Module is in use, the transformer must be
connected to the supply cable!
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-33
Motor Control
Description
With this function, SIMOCODE pro can control motors with only one stator
winding at two speeds (fast and slow). SIMOCODE pro wires the stator
winding via the contactors so that there is a high pole number at low speed
and a low pole number at high speed.
Control commands
• SLOW: Start with "ON >" first activates the QE2 Contactor Control (slow).
• FAST: start with "ON>>" first activates the QE3 Contactor Control (Star
Contactor, fast) and then immediately activates the QE1 Contactor Control
(Network Contactor, fast).
• STOP with "OFF" deactivates the QE1, QE2 and QE3 Contactor Controls.
The control commands can be issued to SIMOCODE pro from arbitrary
Control Stations (see also the description of "Control Stations"). Thus, the
inputs (plugs) must be connected to the corresponding sockets, preferably
to the "Enabled Control Command" sockets.
Every fault signal causes the QE1, QE2 and QE3 Contactor Controls to be
deactivated.
SIMOCODE pro prevents the contactors for the "FAST" speed from being
switched on at the same time as the contactor for the "SLOW" speed.
Change-over Pause
The "Change-over Pause" parameter can be used to delay switching from
"FAST" to "SLOW" to give the motor enough time to run down.
SIMOCODE pro
4-34 GWA 4NEB 631 6050-22 DS 02
Motor Control
Notice
Two Set Currents are to be set for this control function:
• Is1 for the slower speed
• Is2 for the faster speed.
Depending on the current range, the current can be directly measured at
both speeds with a single current converter. Otherwise you will need two
external current converters according to the corresponding speed (e.g.
3UF18 with a 1 A secondary transformer rated current), whose secondary
cables must lead through the Current Measuring Module with the range 0.3
- 3 A. The Is1/Is2 Set Currents must be converted according to the
secondary currents of the external transformers. For further information see
Chapter 3.2 "Overload Protection".
Schematic
OFF
ON >
ON >>
*Feedback ON
Change-overPause
ExtendedControl
Active
Fig. 4-18: Schematic of the "Dahlander" control function, "Protection/Control" function block
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-35
Motor Control
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
Dahlander Description
Non-maintained • Deactivated
Command Mode • Activated
SIMOCODE pro
4-36 GWA 4NEB 631 6050-22 DS 02
Motor Control
Description
This control function can be used to change the direction of rotation of a
motor at both speeds.
Control commands
• RIGHT - SLOW: Start with "ON >" activates the QE2 Contactor Control (right-
slow)
• RIGHT - FAST: Start with "ON >>" first activates the QE3 Contactor Control
(Fast-star Contactor) and then immediately activates the QE1 Contactor
Control (right-fast)
• LEFT - SLOW: Start with "ON <" activates the QE4 Contactor Control
(left-slow)
• LEFT - FAST: Start with "ON <<" first activates the QE3 Contactor Control
(fast-Star Contactor) and then immediately activates the QE5 Contactor
Control (left-fast)
• STOP with "OFF" deactivates the Contactor Controls.
The control commands can be issued to SIMOCODE pro from arbitrary
Control Stations (see also the description of "Control Stations"). Thus, the
inputs (plugs) must be connected to the corresponding sockets, preferably
to the "Enabled Control Command" sockets.
It does not matter in what order the control commands are given.
Every fault signal causes the contactor activations to be deactivated.
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-37
Motor Control
Change-over Pause
The "Change-over Pause" parameter can be used to delay switching from
"FAST" to "SLOW" to give the motor enough time to run down.
Safety information
Note
You need at least one Digital Module for this control function. This control
function cannot be implemented with bistable relay outputs.
Notice
Two Set Currents are to be set for this control function:
• Is1 for the slower speed
• Is2 for the faster speed.
Depending on the current range, the current can be directly measured at
both speeds with a single current converter. Otherwise you will need two
external current converters according to the corresponding speed (e.g.
3UF18 with a 1 A secondary transformer rated current), whose secondary
cables must lead through the Current Measuring Module with the range 0.3
- 3 A. The Is1/Is2 set currents must be converted according to the
secondary currents of the external transformers. For further information,
see Chapter 3.2 "Overload Protection".
SIMOCODE pro
4-38 GWA 4NEB 631 6050-22 DS 02
Motor Control
Schematic
QLE >
(ON >)
QLE >>
(ON >>)
QLS
(Trip)
Status
ON <<
ON <
OFF
ON >
*Feedback ON ON >>
Change-over Pause
Extended Control
Active
Interlocking Time
Active
Fig. 4-19: Schematic of the "Dahlander Reversing Starter" control function, "Protection/Control"
function block
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-39
Motor Control
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
Dahlander Description
Reversing Starter
Non-maintained • Deactivated
Command Mode • Activated
SIMOCODE pro
4-40 GWA 4NEB 631 6050-22 DS 02
Motor Control
Description
With this function, SIMOCODE pro can control motors with two stator
winding at two speeds (fast and slow).
Control commands
• SLOW: Start with "ON >" activates the QE2 Contactor Control (slow).
• FAST: Start with "ON >>" activates the QE2 Contactor Control (fast).
• STOP with "OFF" deactivates the Contactor Controls.
The control commands can be issued to SIMOCODE pro from arbitrary
Control Stations (see also the description of "Control Stations"). Thus, the
inputs (plugs) must be connected to the corresponding sockets, preferably
to the "Enabled Control Command" sockets.
It does not matter in what order the control commands are given.
Every fault signal causes the contactor activations to be deactivated.
Change-over Pause
The "Change-over Pause" parameter can be used to delay switching from
"FAST" to "SLOW" to give the motor enough time to run down.
Notice
Two Set Currents are to be set for this control function:
• Is1 for the slower speed
• Is2 for the faster speed.
Depending on the current range, the current can be directly measured at
both speeds with a single current converter. Otherwise you will need two
external current converters according to the corresponding speed (e.g.
3UF18 with a 1 A secondary transformer rated current), whose secondary
cables must lead through the Current Measuring Module with the range 0.3
- 3 A. The Is1/Is2 Set Currents must be converted according to the
secondary currents of the external transformers. For further information,
see Chapter 3.2 "Overload Protection".
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-41
Motor Control
Schematic
OFF
ON >
*Feedback ON ON >>
Change-over Pause
Extended Control
Active
Fig. 4-20: Schematic of the "Pole-changing Starter" control function, "Protection/Control" function
block
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions"
Pole-changing Description
Starter
Non-maintained • Deactivated
Command Mode • Activated
Table 4-14: Pole-changing Starter settings
SIMOCODE pro
4-42 GWA 4NEB 631 6050-22 DS 02
Motor Control
Pole-changing Description
Starter
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-43
Motor Control
Description
This control function can be used to change the direction of rotation of a
motor at both speeds.
Control commands
• RIGHT - SLOW: Start with ON > activates the QE2 Contactor Control
(right-slow)
• RIGHT - FAST: Start with ON >> activates the QE1 Contactor Control
(right-fast)
• LEFT - SLOW: Start with ON < activates the QE4 Contactor Control (left-slow)
• LEFT - FAST: Start with ON << activates the QE5 Contactor Control (left-fast)
• STOP with OFF deactivates the Contactor Controls.
The control commands can be issued to SIMOCODE pro from arbitrary
Control Stations. Thus, the inputs (plugs) must be connected to the
corresponding sockets, preferably to the "Enabled Control Command"
sockets.
It does not matter in what order the control commands are given.
Every fault signal causes the contactor activations to be deactivated.
SIMOCODE pro
4-44 GWA 4NEB 631 6050-22 DS 02
Motor Control
Change-over Pause
SIMOCODE pro prevents the contactors for "FAST" and "SLOW" from being
switched on simultaneously. The "Change-over Pause" can be used to delay
switching from "FAST" to "SLOW" to give the motor enough time to run
down.
Safety information
Note
At least one additional Digital Module is required for this control function.
Notice
Two Set Currents are to be set for this control function:
• Is1 for the slower speed
• Is2 for the faster speed.
Depending on the current range, the current can be directly measured at
both speeds with a single current converter. Otherwise you will need two
external current converters according to the corresponding speed (e.g.
3UF18 with a 1 A secondary transformer rated current), whose secondary
cables must lead through the Current Measuring Module with the range 0.3
- 3 A. The Is1/Is2 set currents must be converted according to the
secondary currents of the external transformers. For further information,
see Chapter 3.2 "Overload Protection".
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-45
Motor Control
Schematic
ON <
OFF
ON >
ON >>
Change-over Pause Active
*Feedback ON
Extended Control
Interlocking Time Active
SIMOCODE pro
4-46 GWA 4NEB 631 6050-22 DS 02
Motor Control
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
Pole-changing Description
Reversing Starter
Non-maintained • Deactivated
Command Mode • Activated
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-47
Motor Control
Description
With this control function, SIMOCODE pro can activate a solenoid valve.
The Solenoid Valve is brought into the corresponding end position using the
control commands "OPEN" and "CLOSED". SIMOCODE pro must be
informed via corresponding limit switches (OPEN, CLOSED) when the end
position has been reached.
Control commands
• OPEN: Start with "ON >" activates the QE1 Contactor Control.
• CLOSED: START with "OFF" deactivates the QE1 Contactor Control.
The control commands can be issued to SIMOCODE pro from arbitrary
Control Stations (see also the description of "Control Stations"). Thus, the
inputs (plugs) must be connected to the corresponding sockets, preferably
to the "Enabled Control Command" sockets.
Every fault signal causes the QE1 Contactor Control to be deactivated and
puts the Solenoid Valve into the "CLOSED" position.
Safety information
Notice
The motor protection functions are not active. A Current Measuring Module
is not necessary.
Notice
If both End Position Switches respond at the same time (FO=1 and FC=1),
the Solenoid Valve is immediately switched OFF via the fault message "Trip -
Double 1" (= "CLOSED")
If the End Position Feedback is different to the control command, the
Solenoid Valve is immediately switched OFF via the fault message "Trip -
End Position" (= "CLOSED")
SIMOCODE pro
4-48 GWA 4NEB 631 6050-22 DS 02
Motor Control
Schematic
OFF
Non-maintained
ON > Command Mode
Displays
QLA (CLOSE)
QLE >
(OPEN)
Auxiliary Control Inputs* Execution Time
FB ON
QLS
(Trip)
FC
Status
FO
* Abbreviations
OFF
FC Feedback CLOSED
ON >
FO Feedback OPEN
FC
Extended Control
FO
Fig. 4-22: Schematic of the "Solenoid Valve" control function, "Protection/Control" function block
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
Non-maintained • Deactivated
Command Mode • Activated
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-49
Motor Control
Description
SIMOCODE pro can control positioners/actuators with this control function.
The Positioner is moved into the corresponding End Position with the
"OPEN" and "CLOSED" control commands and is deactivated via its Limit
Switch (1-active) or Torque Switch (0-active).
The response of the Limit/Torque Switch must be passed to SIMOCODE pro
via its inputs.
Control Commands
• OPEN: Start with "ON >" activates the QE1 Contactor Control until "End
Position OPEN" is reached (Feedback OPEN)
• CLOSE: Start with "ON <" activates the QE2 Contactor Control until "End
Position CLOSED" is reached (Feedback CLOSED)
• STOP with "OFF" deactivates the Contactor Controls.
The drive remains in the present position.
The control commands can be issued to SIMOCODE pro from arbitrary
Control Stations (see also the description of "Control Stations"). Thus, the
inputs (plugs) must be connected to the corresponding sockets, preferably
to the "Enabled Control Command" sockets.
Function schematic
Torque Switch
TO TC
Positioner
Gear
OPEN CLOSED
Fig. 4-23: Function schematic of the Torque and Limit Switches when controlling Positioners
SIMOCODE pro
4-50 GWA 4NEB 631 6050-22 DS 02
Motor Control
Notice
The corresponding Torque Switch must not respond before the associated
Limit Switch when the Torque Switch TO (OPEN) and/or TC (CLOSED) is
connected. In this case, the Positioner is switched off immediately with the
fault message "Trip - Blocked Positioner".
If both Limit Switches respond at the same time (FO=1 and FC=1), the
Positioner is immediately switched off via the fault message
"Trip - Double 1".
If both Torque Switches respond at the same time (TO=0 and TC=0), the
Positioner is switched off immediately with the fault message
"Trip - Double 0".
If the End Position Feedback does not correspond to the control command,
the Positioner is switched off with the fault message "Trip - End Position
Fault".
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-51
Motor Control
Schematic
FO Status
FB ON Feedback ON ON <
TC CLOSED
FC Feedback CLOSED
OFF STOP
FO Feedback OPEN TO
TC Torque CLOSED ON >
OPEN
TO Torque OPEN
Positioner Runs
in CLOSE Direction
Positioner Runs
FC In OPEN Direction
Extended Control
FO
TC
TO
Fig. 4-24: Schematic of the "Positioner" control function, "Protection/Control" function block
SIMOCODE pro
4-52 GWA 4NEB 631 6050-22 DS 02
Motor Control
Type
CLOSE OPEN
Tripping
TC FC FO TO
Torque Limit Limit Torque
CLOSED CLOSED OPEN OPEN
Positioner 1 — X X —
After reaching the End Position FO
(OPEN) or FC (CLOSED).
Positioner 2 X X X X
After reaching the End Position FO
(OPEN) or FC (CLOSED) AND
response of the associated Torque
Switch TO (OPEN) or TC (CLOSED)
Positioner 3 X X X —
After reaching the end position FO
(OPEN). After reaching the End
Position 'CLOSED', the respective
Torque Switch TC must also respond
after the Limit Switch FC has
responded.
Positioner 4 — X X X
After reaching the End Position FO
(OPEN). After reaching the End
Position FO (OPEN), the respective
Torque Switch TO must also
respond after the Limit Switch FO
has responded.
Positioner 5 Antivalent Active Antivalent Active
After reaching the End Position or
the torque. The actuator is monitored
by either the Limit Switches or by
the Torque Switches. The switches
are implemented as change-over
contacts and are checked for
antivalence. In the case of Non-
antivalent Feedback (e.g. FC=0 and
TC=0), SIMOCODE pro recognizes a
wire break and deactivates the
Positioner with the fault message
"Trip - Antivalence"
Table 4-17: Types of Positioner Control
Notice
The signals of the Torque Switches and the Limit Switches must be wired to
the inputs of the basic units. Torque Switches must be 0-active, whereas
the Limit Switches must be 1-active.
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-53
Motor Control
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
Positioner Description
Non-maintained • Deactivated
Command Mode • Activated
SIMOCODE pro
4-54 GWA 4NEB 631 6050-22 DS 02
Motor Control
Description
With this control function, SIMOCODE pro can activate the 3RW soft
starter. The 3RW soft starters are connected to PROFIBUS DP via
SIMOCODE pro.
Control commands
• Start with "ON >" activates the QE1 and QE4 Contactor Controls
• Stop with "OFF" first deactivates the QE4 Contactor Control. When the signal
"Feedback ON" has expired, the QE1 Contactor Control is deactivated 3 s later
in order to facilitate a smooth run down via the soft starter.
• With "Reset", the QE3 Contactor Control is activated for 20 ms and sends the
soft starter an acknowledgement signal via a parameterizable relay output.
The control commands can be issued to SIMOCODE pro from arbitrary
Control Stations (see also the description of "Control Stations"). Thus, the
inputs (plugs) must be connected to the corresponding sockets, preferably
to the "Enabled Control Command" sockets.
Every fault signal causes the contactor activations to be deactivated.
Notice
In order to avoid disconnections due to faults, the "Execution Time"
parameter in SIMOCODE pro must be set at least to the Smooth Running
Down Time of the soft starters.
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-55
Motor Control
Schematic
Status
OFF
ON >
*Feedback ON
Fig. 4-25: Schematic of "Soft Starter" control function, "Protection/Control" function block
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
SIMOCODE pro
4-56 GWA 4NEB 631 6050-22 DS 02
Motor Control
Description
With this control function, SIMOCODE pro can activate the 3RW soft starter
including an additional reversing contactor. Thus, the 3RW soft starters are
connected to the PROFIBUS DP via SIMOCODE pro. With this control
function, SIMOCODE pro can also control the direction of rotation of the
motor (forwards and backwards).
Control commands
• Start with "ON >" activates the QE1 and QE4 Contactor Controls (clockwise,
i.e. forwards)
• Start with "ON <" activates the QE2 and QE4 Contactor Controls (counter-
clockwise, i.e. backwards)
• Stop with "OFF" first deactivates the QE4 Contactor Control. When the
"Feedback ON" signal is no longer issued, the QE1 / QE2 Contactor Control is
deactivated 3 s later in order to facilitate a smooth run down via the soft
starter.
• With "Reset", the QE3 Contactor Control is activated for 20 ms and sends the
soft starter an acknowledgement signal via a parameterizable relay output.
The control commands can be issued to SIMOCODE pro from arbitrary
Control Stations (see also the description of "Control Stations"). Thus, the
inputs (plugs) must be connected to the corresponding sockets, preferably
to the "Enabled Control Command" sockets.
Every fault signal causes the contactor activations to be deactivated.
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-57
Motor Control
1) Assign the QE1 Contactor Control to the Relay Output which controls the coil
of the line contactor (right).
2) Assign the QE2 Contactor Control to the Relay Output which controls the coil
of the line contactor (left).
3) Assign the QE4 Contactor Control to an arbitrary Relay Output from which
the "ON input" of the soft starter should be controlled.
4) Assign the QE3 Contactor Control to the Relay Output that supplies the 20
ms acknowledgment signal to the soft starter.
5) Assign the "ON >", "ON <" and "OFF" control commands to the enabled
control commands.
6) Assign the SIMOCODE pro input to which the "Fault" signal output of the soft
starter is connected to the input (socket) of the standard function "External
Fault 1".
7) The "Start-up End" signal of the soft starter can also be wired to one of the
outputs and processed by SIMOCODE pro.
Note
An additional Digital Module may be necessary for this control function.
Schematic
OFF
ON >
*Feedback ON Interlocking Time
Extended Control
Active
Fig. 4-26: Schematic of the "Soft Starter with Reversing Contactor" control function, "Protection/
Control" function block
SIMOCODE pro
4-58 GWA 4NEB 631 6050-22 DS 02
Motor Control
Settings
You will find detailed information about the settings in
Chapter 4.2.2 "General Settings and Definitions".
Non-maintained • Deactivated
Command Mode • Activated
SIMOCODE pro
GWA 4NEB 631,631 6050-22 DS 02 4-59
4.3
4-60
Lamp control
QLE<< QLE< QLA QLE> QLE>>
Specification/ Control station Contactor control
(ON<<) (ON<) (OFF) (ON>) (ON>>)
Motor Control
Control function
Status signal
ON<< ON< OFF ON> ON>> QE1 QE2 QE3 QE4 QE5 ON<< ON< OFF ON> ON>>
Overload 1),2) - - - - - - - Active - - - - - - -
Direct starter 1),2) - - OFF ON - ON - - - - - OFF ON -
Reversing starter 1),2) - Left OFF Right - Right Left - - - Left OFF Right -
Circuit breaker 1),2) - - OFF ON - ON - OFF - - - - OFF ON -
functions
impulse impulse
Star-delta - - OFF ON - Star Delta Network - - - - OFF ON -
starter 2) contactor contactor contactor
Star-delta starter Left OFF Right - Star Delta Right Left - Left OFF Right -
with reversal of the direction contactor contactor network network
of rotation 2) contactor contactor
Dahlander 2) - - OFF Slow Fast Fast Slow Fast - - - - OFF Slow Fast
star
contactor
Dahlander Left Left OFF Right Right Right Right Fast Left Left Left Left OFF Right Right
with reversal of the direction fast slow slow fast fast slow star slow fast fast slow slow fast
of rotation 2) contactor
Pole-changing switch 2) - - OFF Slow Fast Fast Slow - - - - - OFF Slow Fast
Pole-changing switch Left Left OFF Right Right Right Right - Left Left Left Left OFF Right Right
with reversing the direction fast slow slow fast fast slow slow fast fast slow slow fast
of rotation 2)
Valve 2) - - Closed Open - Open - - - - - - Closed Open -
Positioner 1 2) - Closed Stop Open - Open Closed - - - - Closed Stop Open -
Positioner 2 2) - Closed Stop Open - Open Closed - - - - Closed Stop Open -
Positioner 3 2) - Closed Stop Open - Open Closed - - - - Closed Stop Open -
Positioner 4 2) - Closed Stop Open - Open Closed - - - - Closed Stop Open -
Positioner 5 2) - Closed Stop Open - Open Closed - - - - Closed Stop Open -
Soft starter 2) - - OFF ON - ON - Reset ON - - - OFF ON -
network command
contactor
Soft starter with reversing - Left OFF Right - Right Left Reset ON - - Left OFF Right -
and Status Information for the Control Functions
Table 4-21: Active Control Stations, Contactor/Lamp Controls and Status Information for control
2) Basic unit 2, SIMOCODE pro V
Target groups
This chapter is addressed to the following target groups:
• Configurators
• Programmers
• Commissioners
• Service personnel.
Necessary knowledge
You will require the following knowledge:
• SIMOCODE pro
• Motor protection, motor control
• The principle of connecting plugs to sockets
• Knowledge of electrical drive engineering.
Navigation in SIMOCODE ES
You will find the dialogs in SIMOCODE ES under
Device parameters > Monitoring functions.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-1
Monitoring Functions
Note
If you use internal Earth-fault Monitoring for star-delta circuits, false tripping
may occur. During delta operation, the Summation Current is non-zero due
to harmonics.
SIMOCODE pro
5-2 GWA 4NEB 631 6050-22 DS 02
Monitoring Functions
Response
Here you can set the SIMOCODE pro response to an internal earth fault:
See also "Tables of Responses of SIMOCODE pro" in Chapter "Important
Information".
Event "Internal
Earth Fault"
External Earth Fault
Event "Warning
External Earth Fault"
Activity
Unless it has been deactivated, this function is always active, independent
of whether the motor is running or not (operating state "ON").
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-3
Monitoring Functions
Response
Here you can set the response of SIMOCODE pro to an External Earth Fault:
See also "Tables of Responses of SIMOCODE pro" in Chapter "Important
Information".
QE1
QE2
Earth-fault Monitoring Tripping QE3
QE4
Current from QE5
Summation Current Internal Earth Fault
Transformer/ Event "External
Earth-fault Module Earth Fault"
Response/Delay
External Earth Fault see Table 5-2
Event "Warning
External Earth Fault"
Activity
Unless deactivated, this function is always active, independent of whether
the motor is running or not (operating state "ON").
SIMOCODE pro
5-4 GWA 4NEB 631 6050-22 DS 02
Monitoring Functions
QE1
QE2
Current Limits QE3
Tripping
QE4
QE5
Trip Level: I> 1)
See Event
Response when I<
Table 5-6 - Warning Level I<
Delay when I<
Hysteresis
1) Upper Limit
2) Lower Limit
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-5
Monitoring Functions
Hysteresis
Here you can set the Hysteresis for the Current Limits I> (Upper Limit):
Hysteresis 0 to 15% of the threshold value in 1% increments
Default: 5 %
SIMOCODE pro
5-6 GWA 4NEB 631 6050-22 DS 02
Monitoring Functions
Hysteresis
Here you can set the Hysteresis for the Current Limits I< (Lower Limit):
Hysteresis 0 to 15% of the threshold value in 1% increments
Default: 5%
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-7
Monitoring Functions
QE1
QE2
QE3
Voltage Monitoring Tripping
QE4
QE5
Trip Level: U<
Hysteresis 1)
SIMOCODE pro
5-8 GWA 4NEB 631 6050-22 DS 02
Monitoring Functions
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-9
Monitoring Functions
QE1
QE2
Cos phi Monitoring QE3
Tripping
QE4
QE5
Trip Level
Warning Level
Hysteresis 1)
SIMOCODE pro
5-10 GWA 4NEB 631 6050-22 DS 02
Monitoring Functions
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-11
Monitoring Functions
QE1
QE2
QE3
Power Monitoring Tripping
QE4
QE5
Trip Level: P> 1)
See Event
Response when P>
Table 5-11
- Trip Level P>
Delay when P>
Hysteresis 3)
1) Upper Limit
2) Lower Limit
3) Hysteresis for voltage, cos phi, power
(see "Voltage Monitoring" function block)
SIMOCODE pro
5-12 GWA 4NEB 631 6050-22 DS 02
Monitoring Functions
Response when Trip Level P> (Upper Limit), P< (Lower Limit)
Here you can set how SIMOCODE pro should respond if the set Trip Level is
either undershot or overshot:
See also "Tables of Responses of SIMOCODE pro" in Chapter "Important
Information".
Response Trip Level
Deactivated X
Signaling X
Warning -
Tripping X
Delay 0 - 25.5 s (0.5)
Table 5-11: "Trip Level" response for Active Power Monitoring
Response when Warning Level P> (Upper Limit), P< (Lower Limit)
Here you can set how SIMOCODE pro should respond if the set Warning
Level is either undershot or overshot:
See also "Tables of Responses of SIMOCODE pro" in Chapter "Important
Information".
Response Warning Level
Deactivated X
Signaling X
Warning X
Tripping -
Delay 0 - 25.5 s (0.5)
Table 5-12: "Warning Level" response for Active Power Monitoring
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-13
Monitoring Functions
QE1
Monitoring 0/4-20 mA
QE2
QE3
Tripping
Trip Level 0/4-20 mA > QE4
QE5
Trip Level Activity
See
Response at Trip Level Table 5-13
Event
- Trip Level
Trip Delay 0/4-20 mA >
See Event
Response at Warning Level Table 5-14 - Warning Level
0/4-20 mA >
Warning Delay
See
Response at Trip Level Table 5-13
Event
- Trip Level
Trip Delay 0/4-20 mA <
See Event
Response at Warning Level Table 5-14 - Warning Level
0/4-20 mA <
Warning Delay
Hysteresis
SIMOCODE pro
5-14 GWA 4NEB 631 6050-22 DS 02
Monitoring Functions
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-15
Monitoring Functions
Response when Warning Level 0/4-20 mA> (Upper Limit), 0/4-20 mA< (Lower Limit)
Here you can set how SIMOCODE pro should respond if the set Warning
Level is either undershot or overshot:
See also "Tables of Responses of SIMOCODE pro" in Chapter "Important
Information".
Marking
The marking is stored in the device and allocated and displayed in the Faults/
Warnings online dialog. Optional marking for designating the signal, e.g.
"0/4-20>"; range: up to 10 characters.
Note
Monitoring of a second process variable via Input 2 of the Analog Module
can be done, for example, by free Limit Monitors.
SIMOCODE pro
5-16 GWA 4NEB 631 6050-22 DS 02
Monitoring Functions
Note
Operating hours, plant downtimes and the number of motor starts can be
monitored completely in the device and/or transmitted to the automation
system via PROFIBUS.
QE1
Tripping
QE2
Operation Monitoring QE3
QE4
Operating Hours QE5
Number of Starts
Permissible Starts
Permissible Starts
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-17
Monitoring Functions
Response
The Motor Operating Hours monitoring function enables the operating hours
(service life) of a motor to be recorded so that motor maintenance prompts
can be generated in good time as applicable.
Level
If the operating hours exceed the set Response Level, the Monitoring
function will be activated.
Level: 0 to 119,3046 hours (0 h)
Activity
Unless deactivated, this function is always active, independent of whether
the motor is running or not (operating state "ON").
Response
You can set the Response for Overshoot here.
See also "Tables of Responses of SIMOCODE pro" in Chapter "Important
Information" and Table 5-15.
System parts for important processes often have dual drives (A and B
drives). Ensure that these are always operated alternately. This prevents
long Motor Stop Times and reduces the risk of non-availability. The Motor
Stop Time Monitoring function can be used, for example, to generate an
alarm, thus initiating connection of the motor.
Level
The length of the permissible Motor Stop Time is stipulated here; if
exceeded, monitoring will begin.
Level: 0 to 65,535 hours (0 h)
Activity
Unless deactivated, this function is always active, independent of whether
the motor is running or not (operating state "ON").
SIMOCODE pro
5-18 GWA 4NEB 631 6050-22 DS 02
Monitoring Functions
Response
Here you can determine the response for when the Permissible Motor Stop
Time is exceeded: See also "Tables of Responses of SIMOCODE pro" in
Chapter "Important Information" and Table 5-15.
Monitoring the Number of Starts can protect system parts (motor, switching
devices such as soft starters and converters) from too many start processes
within a parameterizable time frame and, thus, prevent damage. This is
particularly useful for commissioning or manual control.
The following schematic illustrates the principle of Monitoring the Number
of Starts.
Pre-warning Overshot
Fig. 5-9: Monitoring the Number of Starts
Permissible Starts
The maximum Number of Starts is set here. The time interval "Time Range
for Starts" commences to run after the first start. After the second to last
permissible start has been executed, the "Just One Start Possible" pre-
warning is generated.
Permissible starts: 1 to 255
Activity
Unless deactivated, this function is always active, independent of whether
the motor is running or not (operating state "ON").
Response at Overshoot
Here you can set the response for when the Number of Starts within the
Time Range for Starts has been overshot:
See also "Tables of Responses of SIMOCODE pro" in Chapter "Important
Information" and Table 5-15.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-19
Monitoring Functions
Response at Pre-warning
Here you can set the response required after the second to last start:
See also "Tables of Responses of SIMOCODE pro" in Chapter "Important
Information" and Table 5-15.
Interlocking Time
If a new start command is issued within the time range for starts after the
last permissible start, this new start command will no longer be executed if
the setting "Response at Overshoot - Tripping" has been set. "Trip - No. of
Starts >" will be displayed and the set Interlocking Time activated.
Interlocking Time: 00:00:00 to 18:12:15 hh:mm:ss
SIMOCODE pro
5-20 GWA 4NEB 631 6050-22 DS 02
Monitoring Functions
Temperature Monitoring
QE1
QE2
Trip Level Tripping
QE3
Hysteresis
Settings
Temperature Description
Trip Level T> - 273 °C - 65,262 °C
Response at Trip Level Setting of response when the temperature is overshot (see the
T> following table and Chapter "Important Information")
Marking Trip Level T > No parameters. Optional marking for designating the event, e.g.
"Temperature >"; range: up to 10 characters
Warning Level T> - 273 °C - 65,262 °C
Response Warning Setting of response when the temperature is overshot (see the
Level T > following table and Chapter "Important Information")
Marking Warning No parameters. Optional marking for designating the event, e.g.
Level T > "Temperature >"; range: up to 10 characters
Hysteresis 0 - 255 °C in 1 °C increments
Default: 5 °C
Table 5-16: "Temperature Monitoring" settings
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-21
Monitoring Functions
Response
See also "Tables of Responses of SIMOCODE pro" in Chapter "Important
Information".
• Overtemperature: Here you can select how SIMOCODE pro should respond
when the temperature has overshot the Warning Level / Trip Level.
Caution
With motors for EEx e applications, the response must remain set to
"Tripping"!
Note
The sensor type, the number of measuring circuits in use and the response
to a sensor fault must be set in the "Temperature Module Inputs
(TM Inputs)" function block if Temperature Monitoring is being used.
Note
To monitor several Sensor Measuring Circuits individually and
independently, a suitable number of free Limit Monitors can be linked to the
"Temperature Module Inputs (TM Inputs)" function block and differing limits
set for the individual temperature sensors, instead of the "Temperature
Monitoring" function block.
SIMOCODE pro
5-22 GWA 4NEB 631 6050-22 DS 02
Monitoring Functions
0HDVXUHG
YDOXH
7ULSOHYHO! +\VWHUHVLV
:DUQLQJOHYHO! +\VWHUHVLV
:DUQLQJOHYHO +\VWHUHVLV
7ULSOHYHO +\VWHUHVLV
7LPH
6LJQDOLQJ
7ULSOHYHO!
7LPH
6LJQDOLQJ
:DUQLQJOHYHO!
7LPH
6LJQDOLQJ
:DUQLQJOHYHO
7LPH
6LJQDOLQJ
7ULSOHYHO
7LPH
7KHK\VWHUHVHVDUHDOZD\VEDVHGRQWKHUHVSHFWLYHO\VHWUHVSRQVHOHYHO
H[FHSWLRQWHPSHUDWXUHPRQLWRULQJ
7KHWULSDQGZDUQLQJOHYHOHYHQWVFDQDOVREHGHOD\HGLQGLYLGXDOO\
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 5-23
Monitoring Functions
SIMOCODE pro
5-24 GWA 4NEB 631 6050-22 DS 02
Outputs 6
In this chapter
In this chapter you will find information about the Outputs of
SIMOCODE pro.
• Relay Outputs on the Basic Unit and the Digital Modules
• Analog Module - Output
• Operator Panel LEDs
• Send Data on the PROFIBUS DP.
Target groups
This chapter is addressed to the following target groups:
• Planners and configurators
• Programmers.
Necessary knowledge
You will require the following knowledge:
• The principle of connecting plugs to sockets
• PROFIBUS DP.
Navigation in SIMOCODE ES
You will find the dialogs in SIMOCODE ES under:
Further Function Blocks > Outputs.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 6-1
Outputs
6.1 Introduction
Description
Schematic
The following schematic shows the general representation of the various
output types:
SIMOCODE pro
SIMOCODE pro
SIMOCODE pro
SIMOCODE pro
6-2 GWA 4NEB 631 6050-22 DS 02
Outputs
SIMOCODE
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 6-3
Outputs
Schematic
The following schematic shows the "BU Outputs" function block:
SIMOCODE pro
BU Outputs
1 1 Terminal Numbers
Out1
2 2
Out2
3
3
6
Out3
7
Output Terminals
Application examples
• Control of the Main Contactor in the Motor Feeder:
You can, e.g., define which Relay Output is used for controlling the Motor
Contactor in the motor feeder. For this, connect the desired Relay Output to
the respective "QE" Contactor Control of the control function.
• Lamp control for displaying operating states:
You can e.g. define which Relay Outputs are to be used for controlling the
lamps/LEDs displaying operating states of the motor (FAULT, ON, OFF,
FAST, SLOW...).
For this, connect the desired Relay Output to the respective "QE..."
Contactor Control of the control function. The following are specifically
intended for controlling lamps and LEDs:
In addition to the status displays, the "QL..." lamp controls automatically
signal via a 2-Hz flash frequency:
– Test mode (QLE.../QLA Lamp Outputs are flashing)
SIMOCODE pro
6-4 GWA 4NEB 631 6050-22 DS 02
Outputs
Settings
BU Outputs Description
Outputs 1 to 3 Control of the "BU Outputs" function block via any signal
(any sockets ,
e.g. device inputs, control bits from PROFIBUS DP, etc.
usually from the QE Contactor Controls)
Table 6-2: Basic Unit Output Settings
The defaults depend on the selected application (template)
See Chapter E "Example Circuits".
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 6-5
Outputs
Note
The "OP LED" function block can only be used if the Operator Panel (OP) is
connected and configured in the device configuration!
TEST/
RESET
SIMOCODE pro
6-6 GWA 4NEB 631 6050-22 DS 02
Outputs
Green 1
Green 2
Green 3
Green 4
Fig. 6-4: LEDs of the Operator Panel with Display for SIMOCODE pro V
Schematic
The following schematic shows the "OP LED" function block:
OP LED LED
Green 1
Green 2
Green 3
Green 4
Yellow 1
Yellow 2
Yellow 3
Note
The three yellow LEDs mentioned in this section are not available for the
Operator Panel with Display. Status information can be read out here
directly via the display. However, the corresponding three plugs can be
connected via the software. Nevertheless, they remain ineffective.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 6-7
Outputs
Application examples
• Display of operating states:
You can, e.g., define which LEDs are to be used for displaying the operating
states (FAULT, ON, OFF, FAST, SLOW).
For this, connect the desired LED to the respective "QL" Lamp Control of the
control function.
In many cases, the LEDs are connected to the QL Outputs. By referring to
Table 4-21on page 4-60 you can determine which QL Outputs are required
for which control functions.
• Transfer of any other information, status information, warnings, faults, etc. to
the yellow LEDs.
Settings
OP LED Description
SIMOCODE pro
6-8 GWA 4NEB 631 6050-22 DS 02
Outputs
Note
"DM Outputs" function blocks can only be used if the corresponding Digital
Modules (DM) are connected and configured in the device configuration!
Schematic
The following schematic shows the "DM Outputs" function block:
Application examples
• Controlling the motor contactor in the motor feeder
You can, e.g., define which Relay Output is to be used for controlling the main
contactor in the motor feeder.
For this, connect the desired Relay Output to the respective "QE" Contactor
Control of the control function.
• Controlling lamps for displaying of operating states:
You can, e.g., define which Relay Outputs are to be used for controlling the
lamps/LEDs displaying operating states of the motor (FAULT, ON, OFF, FAST,
SLOW...).
For this, connect the desired Relay Output to the respective "QL..." Lamp
Control of the control function.
• Transfer of any other information, status information, warnings, faults, etc. to
the Relay Outputs.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 6-9
Outputs
In many cases, the Outputs of the Digital Module will be connected to the
QE Outputs. By referring to Table 4-21on page 4-60 you can determine
which QE Outputs are required for which control functions.
Settings
"DM1/DM2 Description
Outputs"
SIMOCODE pro
6-10 GWA 4NEB 631 6050-22 DS 02
Outputs
Note
The "AM Output" function block can only be used if the Analog Module (AM)
is connected and configured in the device configuration!
Schematic
The following schematic shows the "AM Output" function block:
AM Output
Assigned OUT+
Start Value of Value Range
Analog Output Value
End Value of Value Range OUT-
Output Signal
Settings
Signal/value Range
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 6-11
Outputs
Note
The Outputs of the analog module are passive outputs. Thus, to configure
an Analog Output Circuit, each output will also require an isolated current
source connected in series. If the Output of the Analog Module is not being
used by another application, it can also be used as current source for an
Analog Module Output Circuit. The "Start Value of Value Range" and the "End
Value of Value Range" of the Analog Module Output have to be set to 65535
for this. Thus, the maximum possible current will always be available via the
Analog Module Output.
SIMOCODE pro
6-12 GWA 4NEB 631 6050-22 DS 02
Outputs
Application examples
1) Output of the Effective Motor Current - across the entire motor
current range
The motor current of a motor ranges from 0 to 8 A.
The Rated Current IN of the motor at nominal load is 2 A.
The parameterized Set Current Is in SIMOCODE ES corresponds to the
Rated Current IN (2 A). In SIMOCODE pro, representation of the effective
phase currents or the maximum current (current IL_1, IL_2, IL_3, max.
current I_max) corresponds to the selected range as a percentage of the
parameterized Set Current Is:
– 0 A Motor Current corresponds to 0% of Is
– 8 A Motor Current corresponds to 400% of Is
– The smallest unit for the Effective Motor Current in SIMOCODE pro is
1% (see Chapter B.8 "Data Record 94 - Measured Values")
PRWRUFXUHQW,PD[
>,PD[RI,H@
$
HQWLUHUDQJH
PRWRUFXUUHQWRI,H
,1 ,H $
$,1
W>V@
As a result,
– the "Start Value of Value Range" to be selected is: 0
– the "End Value of Value Range" to be selected is: 400.
AM Output
Assigned
OUT+
Analog Output Value 0 Start Value of Value Range
Max. Current I_max OUT-
400 End Value of Value Range
Fig. 6-9: Application example: Motor Current Output - output values to function block
AM Output
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 6-13
Outputs
2) Output of the Effective Motor Current - only part of the motor current
range (overload range)
The Motor Current of a motor ranges from 0 to 8 A.
The Rated Current IN of the motor at nominal load is 2 A.
The parameterized Set Current Is in SIMOCODE ES corresponds to the
Rated Current IN (2 A). However, only the overload range (2 A - 8 A) is to be
displayed on a pointer instrument via the Analog Module Output.
In SIMOCODE pro, representation of the effective phase currents or the
maximum current (current IL_1, IL_2, IL_3, max. current I_max) corresponds
to the selected range as a percentage of the parameterized Set Current Is:
– 2 A Motor Current corresponds to 100% of Is
– 8 A Motor Current corresponds to 400% of Is
– The smallest unit for the Effective Motor Current in SIMOCODE pro is 1%
(see Chapter B.8 "Data Record 94 - Measured Values").
PRWRUFXUUHQW,PD[
>,PD[RI,H@
$
3DUWLDOUDQJHRIWKHPRWRUFXUUHQW
2YHUORDGUDQJHRI,H
,1 ,H $
$,1
W>V@
As a result,
– the "Start Value of Value Range" to be selected is: 100
– the "End Value of Value Range" to be selected is: 400.
AM Output
Assigned
OUT+
Analog Output Value 100 Start Value of Value Range
Max. Current I_max OUT-
400 End Value of Value Range
Fig. 6-11: Application example: Motor Current Output - output values to function block
AM Output
SIMOCODE pro
6-14 GWA 4NEB 631 6050-22 DS 02
Outputs
AM Output
Assigned
Analog Output Value OUT+
0 Start Value of Value Range
Cyclic Receive 2/3 OUT-
End Value of Value Range
27648
(1 word, cycl. from the PLC)
0-20 mA Output Signal
As a result,
– The "Start Value of Value Range" to be selected is: 0
– The "End Value of Value Range" to be selected is: 27648.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 6-15
Outputs
Schematic
The following schematic shows the "Cyclic Send" function blocks:
Cyclic Send 0 with eight bits Cyclic Send 1 with eight bits
for binary information for binary information
Cyclic Send 2/9 with four words (eight bytes) Cyclic Send 2/3 with one word (two bytes)
for up to four analog values for one analog value
SIMOCODE pro
6-16 GWA 4NEB 631 6050-22 DS 02
Outputs
Cyclic Services
Cyclic Send Data is exchanged once in every DP cycle between the DP
master and the DP slave. The DP master sends the Cyclic Control Data to
SIMOCODE pro. In response, SIMOCODE pro sends the Cyclic Send Data
to the DP master.
Settings
Byte 2/3 Control of one word (two bytes) with any analog values
Basic types 1*, 2 (any sockets
e.g. Maximum Current Imax, remaining Cooling Time, actual value
of timers, etc.)
Byte 4/5, 6/7, 8/9 Control of four words (eight bytes) with any analog values
Basic type 1* (any sockets )
Table 6-6: Cyclic Send Data settings
Byte 0 of the Send Data is already preset. Byte 2/3 is preset with the Max.
Current Imax!
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 6-17
Outputs
Schematic
The following schematic shows the "Acyclic Send" function blocks:
Acyclic Services
Acyclic Send Data will only be transferred on request.
The information (two bytes) can be found in
Chapter B.18 "Data Record 203 - Acyclic Send".
This data record can be read by every master (PLC or PC) that supports the
Acyclic Services of PROFIBUS DPV1.
Settings
SIMOCODE pro
6-18 GWA 4NEB 631 6050-22 DS 02
Inputs 7
In this chapter
In this chapter you will find information on the Inputs of SIMOCODE pro.
The Inputs are:
• Binary Inputs on the Basic Units and Digital Modules
• Operator Panel Buttons
• Temperature Module Inputs
• Analog Module Inputs
• Control Data from PROFIBUS DP.
Target groups
This chapter is addressed to the following target groups:
• Planners and configurators
• Planners.
Necessary knowledge
You will require the following knowledge:
• The principle of connecting plugs to sockets.
Navigation in
SIMOCODE ES
You will find the dialogs in SIMOCODE ES under:
Device parameters > Inputs.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 7-1
Inputs
7.1 Introduction
Description
SIMOCODE pro has various Inputs. These are represented by the different
function blocks in SIMOCODE pro. These function blocks are the ingoing
SIMOCODE pro interfaces. Within SIMOCODE pro, these inputs are
represented as sockets on the corresponding function blocks and can be
assigned via connections to any functions. Inputs can be:
• Input Terminals , located on the outside of the Basic Units and Digital
Modules
• Buttons on the Operator Panel (one Test/Reset button, four freely-
parameterizable buttons), and Basic Units (one Test/Reset button)
• Temperature Module Inputs
• Analog Module Inputs
• Inputs from PROFIBUS DP (Cyclic and Acyclic).
Schematic
The following schematic shows a general representation of the Input types:
SIMOCODE pro
SIMOCODE pro
Buttons
- Control commands Input Sockets
- TEST/RESET
SIMOCODE pro
SIMOCODE pro
7-2 GWA 4NEB 631 6050-22 DS 02
Inputs
SIMOCODE
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 7-3
Inputs
Schematic
The following schematic shows the "BU Inputs" function block:
SIMOCODE pro
7-4 GWA 4NEB 631 6050-22 DS 02
Inputs
Application examples
The Inputs can be used, for example, for connecting the Start and Stop
Buttons of the Local Control Station, which can then be assigned to the
"Local-Control Station" function block.
If assigned accordingly, the input signals can also be used to activate
function blocks such as "Reset" or "External Fault".
Settings
Delay You can set a delay time for the Inputs, if required.
Inputs Range: 6, 16, 26, 36 ms
Table 7-2: Settings for "Basic Unit Inputs"
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 7-5
Inputs
Note
The "OP Buttons" function block can only be used if the operator panel (OP)
is connected and configured in the device configuration!
Note
The operator panel with display does not have a Test/reset button. The
allocated functions can be carried out via the operator panel menu or via
softkeys. Similarly, the corresponding status signal will then be available at
the OP Test/Reset button socket.
SIMOCODE pro
7-6 GWA 4NEB 631 6050-22 DS 02
Inputs
TEST/
RESET
Button 1
Button 2
Button 3
Button 4
Fig. 7-4: Buttons on the operator panel with display for SIMOCODE pro V
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 7-7
Inputs
Schematic
The following schematic shows the "OP Buttons" function block:
Button 2 OP - Button 2
Button 3 OP - Button 3
Button 4 OP - Button 4
SIMOCODE pro
7-8 GWA 4NEB 631 6050-22 DS 02
Inputs
Note
The "DM Inputs" function blocks can only be used if the respective Digital
Module (DM) is connected and configured in the device configuration!
Schematic
The following schematic shows the "DM1/DM2 Inputs" function blocks:
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 7-9
Inputs
Application examples
Digital Modules allow the number of Binary Inputs and Outputs on Basic
Unit 2 to be increased in increments.
SIMOCODE pro V can thus be extended to a maximum of twelve Binary
Inputs and seven Binary Outputs. By allocating accordingly, Input Signals
can be used to activate, for example, function blocks such as "Reset" or
"External Fault". An external fault can be, for example, the Binary Signal of
an External Overspeed Monitor, signaling that the Nominal Speed of a motor
has been undershot.
Settings
Delay Time If required, you can set a Delay Time for the Inputs.
Inputs Range: 6, 16, 26, 36 ms
These values are valid for Digital Modules with a 24 V DC Input
Supply.
For Digital Modules with a 110 to 240 V AC/DC Input Supply, the
values are approx. 40 ms higher.
Table 7-3: "DM1/DM2 Inputs" settings
SIMOCODE pro
7-10 GWA 4NEB 631 6050-22 DS 02
Inputs
Note
The "TM Inputs" function block can only be used if the Temperature Module
(TM) has been connected and configured in the device configuration!
Schematic
The following schematic shows the "TM Inputs" function block:
Inputs: TM Inputs
R PT/KTY
50 1T3
Max. Temperature
51 2T3
Sensor Type Temperature 1
1 2 u Range:
52 3T3 Temperature 2 0 ... 65535 K
Response at Sensor Fault/
R NTC 53 1T2 Out of Range Temperature 3
54 2T2
Number of Act. Sensors Event
1 2 u 55 3T2
- Sensor Fault
56 T1 - Out of Range
Terminal
Numbers 57 T1
Notes on wiring
You can connect up to three 2-wire or 3-wire Temperature Sensors. You will
find further information in Chapter 13.3 "Wiring".
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 7-11
Inputs
Application examples
Among other things, you can monitor the following motor components:
• Motor windings
• Motor bearings
• Motor coolant temperature
• Motor gearbox oil temperature.
The individual temperatures of the three Sensor Measuring Circuits can be
monitored independently of each other by connecting free Limit Monitors.
Settings
1)
Response Sensor Fault / Out of Range
Deactivated X
Signaling X
Warning X
Tripping X
Delay -
Table 7-5: "Sensor Fault / Out of Range" response
SIMOCODE pro
7-12 GWA 4NEB 631 6050-22 DS 02
Inputs
Note
The "AM Inputs" function block can only be used if the respective analog
module (AM) has been connected and configured in the device
configuration!
Schematic
The following schematic shows the "AM Inputs" function block:
AM Inputs
Inputs:
30 IN1+ Input Signal
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 7-13
Inputs
Application examples
Typical applications are e.g.:
• Fill-level monitoring for implementing dry running protection for pumps
• Monitoring of pollution in a filter using a differential pressure transducer.
Settings
Note
Note
The value of the Analog Module Inputs is in S7 format.
Notice
The Inputs of the Analog Module are passive inputs, i.e. to configure an
Analog Input Circuit, each Input will require an additional, potential-free
external current source connected in series. If the Output of the Analog
Module is not being used by another application, it can be used as current
source for an Input Circuit of the Analog Module. The "Start Value of Value
Range" and the "End Value of Value Range" of the Analog Module Output
have to be set to 65535 for this. Thus, the maximum possible current will
always be available via the Analog Module Output.
SIMOCODE pro
7-14 GWA 4NEB 631 6050-22 DS 02
Inputs
Schematic
The following schematic shows the "Cyclic Receive" function blocks:
Cyclic Services
The Cyclic Data is exchanged between DP master and DP slave once every
DP cycle. The DP master sends the Cyclic Receive Data (Cyclic Receive) to
SIMOCODE pro each time. SIMOCODE pro responds by sending the Cyclic
Send Data (Cyclic Send) to the DP master.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 7-15
Inputs
Schematic
The following schematic shows the "Acyclic Receive" function blocks:
Acyclic Services
Acyclic Data is only transferred on request.
The information (4 bytes) can be found in data record 202.
This data record can be read by every master (PLC or PC) that supports the
Acyclic Services of PROFIBUS DPV1. Connection monitoring is activated
every time the data set is received. The content of the data set is deleted
after a 5-second time-out has elapsed.
SIMOCODE pro
7-16 GWA 4NEB 631 6050-22 DS 02
Analog Value Recording 8
In this chapter
This chapter provides information regarding the possibility of recording the
measured curves of different measured values, e.g. the motor current when
the motor is running, using SIMOCODE pro V.
The increasing wear on the motor and the equipment driven by the motor all
cause the motor current to change over time. By recording the motor
current at different points in time and making direct comparisons,
conclusions can be drawn regarding the condition of the motor and the
equipment.
Target groups
This chapter is addressed to the following target groups:
• Configurators
• Programmers
• Commissioners
• Service personnel.
Necessary knowledge
You will require the following knowledge:
• SIMOCODE pro
• Motor protection, motor control
• The principle of connecting plugs to sockets
• Knowledge of electrical drive engineering.
Navigation in SIMOCODE ES
You will find the dialogs in SIMOCODE ES under:
Device parameters > Analog Value Recording.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 8-1
Analog Value Recording
Description
The "Analog Value Recording" function block can be used to record various
analog values (2 bytes/1word) in SIMOCODE pro over a set period of time.
For example, you can use this function block to record the characteristic
curve of the motor current when the motor is started.
Recording is carried out directly in SIMOCODE pro on the basis of the motor
feeder and independently of PROFIBUS or the automation system. Every
analog value present at the "Allocated Analog Value" analog socket is
recorded and saved. The recording starts on the basis of the edge (positive/
negative) via any binary signal at the Trigger Input of the function block. Up
to 60 values can be saved internally in the device. The time frame of the
recording is indirectly determined by the selected sampling rate:
Sampling time = sampling rate[s] x 60 values.
The Pre-trigger can be used to specify how far in advance the recording
should commence before the Trigger Signal is issued. The Pre-trigger is set
as a percentage of the entire Sampling Time. In addition, with
SIMOCODE ES you can also export the measured curve into a *.csv file for
further processing, for example, in MS Excel.
Functional principle
$OORFDWHGDQDORJYDOXH
HJPRWRUFXUUHQW,PD[>@
WLPH
3UHWULJJHU>@ 6DPSOLQJUDWH>V@
7ULJJHULQSXW 7ULJJHUHGJH SRVLWLYH
WLPH
The old measured curve will be overwritten in SIMOCODE pro each time a
new Trigger Signal is sent to the Trigger Input.
SIMOCODE pro
8-2 GWA 4NEB 631 6050-22 DS 02
Analog Value Recording
Schematic
The following schematic shows the "Analog Value Recording (Record)"
function block:
Record
Trigger Input
Trigger Edge
Assigned
Analog Value Sampling Rate
Pre-trigger
Settings
Signal/Value Range
Application example
Motor Current Recording when the motor starts/Sampling Time = 12 s/Pre-
trigger = 25% (3 s):
Record
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 8-3
Analog Value Recording
SIMOCODE pro
8-4 GWA 4NEB 631 6050-22 DS 02
3UF50 Compatibility Mode 9
In this chapter
In this chapter you will find information on the 3UF50 compatibility mode.
Target groups
This chapter is addressed to the following target groups:
• Configurators
• PLC programmers.
Necessary knowledge
You will require the following knowledge:
• The principle of connecting plugs to sockets
• knowledge about PROFIBUS DP.
Navigation in SIMOCODE ES
You will find the dialogs in SIMOCODE ES under:
Device Parameters > 3UF50 Compatibility Mode.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 9-1
3UF50 Compatibility Mode
Description
The 3UF50 compatibility mode is applied when a SIMOCODE-DP device is
to be replaced by a SIMOCODE pro device without changing the
configuration.
In the 3UF50 compatibility mode you can operate a SIMOCODE pro-V basic
unit 2 with a 3UF50 configuration.
In this case, the communication using SIMOCODE pro behaves the same as
communication using SIMOCODE-DP from the point of view of the PLC
(Master class 1).
SIMOCODE-DP supports cyclic communication (basic types 1-3), diagnosis
as well as DPV1 data records (DR 130, DS 131, DS 133).
Safety information
Notice
Communication with a DP-Master (Master class 2), e.g. with the Win-
SIMOCODE-DP Professional software via PROFIBUS DP, is not covered by
the 3UF50 compatibility mode.
Notice
In the 3UF50 compatibility mode, the start-up parameter block is always set,
i.e. the transmission of the device parameters created using SIMOCODE-
DP-GSD or the object manager SIMOCODE-DP cannot be integrated into
SIMOCODE pro V.
Notice
The 3UF50 compatibility mode supports SIMOCODE-DP projects in which
SIMCODE-DP is integrated via GSD SIEM8031.gs?, SIEM8069.gs? or via the
object manager (OM) SIMOCODE DP.
SIMOCODE pro
9-2 GWA 4NEB 631 6050-22 DS 02
3UF50 Compatibility Mode
Receive
Basic type 1 Basic type 1 Basic type 2 Basic type 2 Basic type 3 Basic type 3
SIMOCODE- SIMOCODE SIMOCODE- SIMOCODE SIMOCODE- SIMOCODE
DP pro V DP pro V DP pro V
0 Cyclic Receive - 0 Cyclic Receive - 0 Cyclic Receive -
1 bit 0. . 1.7 1 bit 0. . 1.7 1 bit 0 1.7 1.7
Receive Data Receive Data Receive Data
2 Not supported 2 Not supported 2 Not supported
3 3 3
Table 9-1: "Receive" configuration
Send
Basic type 1 Basic type 1 Basic type 2 Basic type 2 Basic type 3 Basic type 3
SIMOCODE- SIMOCODE SIMOCODE- SIMOCODE SIMOCODE- SIMOCODE
DP pro V DP pro V DP pro V
0 Cyclic Send 0 Cyclic Send 0 Cyclic Send
1 Send Data Bit[0.0] 1.7 1.7 1 Send Data Bit[0.0] 1.7 1.7 1 Bit[0.0] 1.7 1.7
Send Data
2 Specified: Max. 2 Specified: Max. 2 Acycl. Send
Motor current Current I_max Motor current Current I_max Bit[0.0] 1.7 1.7
3 3 3
4 Number of Number of Starts
5 Starts (Bytes 0 - 3)
6
7 Value Counter 1
8 Counter 1 Actual Value
9 Value Counter 2
10 Counter 2 Actual Value
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 9-3
3UF50 Compatibility Mode
Byte Setup 3UF50 - Device-specific Byte Setup 3UF50 - Device-specific Equivalent in SIMOCODE pro V
Bit diagnosis acc. to DP standard Bit diagnosis acc. to
SIMOCODE-DP DPV1 SIMOCODE-DP
6 0x0B
7 0x81
8 0x04 Same as 3UF50 diagnosis
6 0x0E 9 0x00
7.0 Free 10.0 Free
7.1 Event: DP block 10.1 Event: DP block Event - Start-up Parameter
Block Active
7.2 Event: Emergency Start 10.2 Event: Emergency Start Status - Emergency Start Executed
7.3 Event: HW Test ok 10.3 Event: HW Test ok • No Fault - HW Fault Basic Unit
• No Fault - Module Fault
• No Fault - Temporary Components
7.4 Free 10.4 Free -
7.5 Event: Ext. Event 1 10.5 Event: Ext. Event 1 Event - Ext. Fault 5
7.6 Event: Ext. Event 2 10.6 Event: Ext. Event 2 Event - Ext. Fault 6
7.7 Event: Ext. Fault 3 10.7 Event: Ext. Event 3 -
8.0 Warning: Ext. Warning 11.0 Warning: Ext. Warning Warning - Ext. Fault 3
8.1 Warning: Unbalance > 40% 11.1 Warning: Unbalance > 40% Warning - Unbalance
8.2 Event: Failure PLC-CPU 11.2 Event: Failure PLC-CPU Status - PLC/PCS
8.3 Warning: Sensor Short Circuit 11.3 Warning: Sensor Short Circuit Warning - Thermistor Short Circuit
8.4 Event: Cooling Down Period 11.4 Event: Cooling Down Period Status - Cooling Down Period Active
Active Active
8.5 Status: TPF 11.5 Status: TPF Status - Test Position (TPF)
8.6 Free 11.6 Free -
8.7 Free 11.7 Free -
9.0 Warning: Earth Fault 12.0 Warning: Earth Fault • Warning - Int. Earth Fault
or
• Ext. Warning Earth Fault
9.1 Warning: Overload 12.1 Warning: Overload Warning - Overload
9.2 Warning: Overload + Unbalance 12.2 Warning: Overload + Unbalance Warning - Overload + Phase Failure
9.3 Warning: I1 Response Level 12.3 Warning: I1 Response Level Warning - Warning Level I>
Overshot Overshot
9.4 Warning: I1 Response Level 12.4 Warning: I1 Response Level Warning - Warning Level I<
Undershot Undershot
9.5 Warning: I2 Response Level 12.5 Warning: I2 Response Level -
Overshot Overshot
9.6 Warning: I2 Response Level 12.6 Warning: I2 Response Level -
Undershot Undershot
Table 9-3: Diagram of the Diagnosis Data in the 3UF50 compatibility mode
SIMOCODE pro
9-4 GWA 4NEB 631 6050-22 DS 02
3UF50 Compatibility Mode
Byte Setup 3UF50 - Device-specific Byte Setup 3UF50 - Device-specific Equivalent in SIMOCODE pro V
Bit diagnosis acc. to DP standard Bit diagnosis acc. to
SIMOCODE-DP DPV1 SIMOCODE-DP
9.7 Warning: Thermistor 12.7 Warning: Thermistor • Warning - Thermistor Overload
• Warning - Thermistor Open Circuit
• Warning - TM Warning T>
• Warning - TM Sensor Fault
• Warning - TM Out of Range
10.0 Trip: Earth Fault 13.0 Trip: Earth Fault • Trip - Int. Earth Fault
or
• Trip - Ext. Earth Fault
10.1 Trip: Overload 13.1 Trip: Overload Trip - Overload
10.2 Trip: Overload + Unbalance 13.2 Trip: Overload + Unbalance Trip - Overload + Phase Failure
10.3 Trip: I1 Response Level Overshot 13.3 Trip: I1 Response Level Overshot Trip - Trip Level I>
10.4 Trip: I1 Response Level 13.4 Trip: I1 Response Level Trip - Trip Level I<
Undershot Undershot
10.5 Trip: I2 Response Level Overshot 13.5 Trip: I2 Response Level Overshot -
10.6 Trip: I2 Response Level 13.6 Trip: I2 Response Level -
Undershot Undershot
10.7 Trip: Thermistor 13.7 Trip: Thermistor • Trip - Thermistor Overload
• Trip - Thermistor Short Circuit
• Trip - Thermistor Open Circuit
• Trip - TM Trip T>
• Trip - TM Sensor Fault
• Trip - TM Out of Range
11.0 Trip: F ON 14.0 Trip: F ON Trip - Feedback ON
11.1 Trip: F OFF 14.1 Trip: F OFF Trip - Feedback OFF
11.2 Trip: Motor Blocked 14.2 Trip: Motor Blocked Trip - Stalled Rotor
11.3 Trip: Positioner Blocked 14.3 Trip: Positioner Blocked Trip - Stalled Positioner
11.4 Trip: Double 0 14.4 Trip: Double 0 Trip - Double 0
11.5 Trip: Double 1 14.5 Trip: Double 1 Trip - Double 1
11.6 Trip: End Position 14.6 Trip: End Position Trip - End Position
11.7 Trip: Antivalence 14.7 Trip: Antivalence Trip - Antivalence
12.0 Trip: ESB 15.0 Trip: ESB Trip - Ext. Fault 4
12.1 Trip: OPO 15.1 Trip: OPO Trip - Operational Protection OFF (OPO)
12.2 Trip: UVO 15.2 Trip: OPO Trip - Undervoltage (UVO)
12.3 Trip: Ext. Fault 1 15.3 Trip: Ext. Fault 1 Trip - Ext. Fault 1
12.4 Trip: Ext. Fault 2 15.4 Trip: Ext. Fault 2 Trip - Ext. Fault 2
12.5 Trip: TPF fault 15.5 Trip: TPF fault Trip - Cold Starting (TPF) Error
12.6 Trip: Runtime ON 15.6 Trip: Runtime ON Trip - Execution ON Command
12.7 Trip: Runtime OFF 15.7 Trip: Runtime OFF Trip - Execution STOP Command
13.0 Trip: Parameter Fault 0 16.0 Trip: Parameter Fault 0 Trip - Parameterization
13.1 Trip: Parameter Fault 1 16.1 Trip: Parameter Fault 1 -
13.2 Trip: Parameter Fault 2 16.2 Trip: Parameter Fault 2 -
13.3 Trip: Parameter Fault 3 16.3 Trip: Parameter Fault 3 -
13.4 Trip: Parameter Fault 4 16.4 Trip: Parameter Fault 4 Trip - Configuration Fault
13.5 Trip: Parameter Fault 5 16.5 Trip: Parameter Fault 5 -
13.6 Trip: Parameter Fault 6 16.6 Trip: Parameter Fault 6 -
Table 9-3: Diagram of the Diagnosis Data in the 3UF50 compatibility mode (Cont.)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 9-5
3UF50 Compatibility Mode
Byte Setup 3UF50 - Device-specific Byte Setup 3UF50 - Device-specific Equivalent in SIMOCODE pro V
Bit diagnosis acc. to DP standard Bit diagnosis acc. to
SIMOCODE-DP DPV1 SIMOCODE-DP
13.7 Trip: Parameter Fault 7 16.7 Trip: Parameter Fault 7 Trip - HW Fault Basic Unit
14 - Number of Overload Trips Number of Overload Trips
15
16 - I of the Overload Trip [%/IE)] Last Trip Current
17
18 - Operating Hours [10h] Motor Operating Hours
19
Table 9-3: Diagram of the Diagnosis Data in the 3UF50 compatibility mode (Cont.)
SIMOCODE pro
9-6 GWA 4NEB 631 6050-22 DS 02
Standard Functions 10
In this chapter
In this chapter you will find information about the standard functions stored
as function blocks in SIMOCODE pro. Standard functions are typical motor
functions that can be activated according to need and, as applicable,
individually set for each motor feeder.
Target groups
This chapter is addressed to the following target groups:
• Configurators
• Programmers of application programs for reference purposes.
Necessary knowledge
You will require the following knowledge:
• The principle of connecting plugs to sockets
• Motor protection
• Control functions, Control Stations.
Navigation in SIMOCODE ES
You will find the dialogs in SIMOCODE ES under:
Further function blocks > Standard Functions.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 10-1
Standard Functions
10.1 Introduction
Description
So-called "Standard Functions" in the form of function blocks are also stored
in SIMOCODE pro, and can be used as required. These function blocks may
contain:
• Plugs ( )
• Sockets ( ) in the form of an event
• Setting values, e.g. the response when External Faults occur ("Signaling",
"Warning" or "Tripping").
Schematic
The following schematic shows the general representation of the function
block of a standard function:
SIMOCODE
Test 2 2
Reset 3 3
Test Position Feedback (TPF) 1 1
External Fault 4 6
Operational Protection OFF (OPO) — 1
Power Failure Monitoring (UVO) — 1
Emergency Start 1 1
Watchdog (PLC/PCS Monitoring) 1 1
Timestamping — 1
Table 10-1: Function Blocks
SIMOCODE pro
10-2 GWA 4NEB 631 6050-22 DS 02
Standard Functions
10.2 Test/Reset
Test/Reset description
The function of the "TEST/RESET" button on the Basic Unit is generally
dependent upon the operating status of the device:
• Reset function: if a fault occurs
• Test function: in other operating states.
In addition to the TEST/RESET buttons, SIMOCODE pro allows internal Test/
Reset tripping via the "Test" function block. The "Test" function block consists
of:
• One plug.
Overall, there are:
• Two function blocks, "Test 1" and "Test 2", for BU1 and BU2, whereby each
function block has a slightly different function:
– Test 1: When testing/tripping the Output Relays
– Test 2: Without tripping the Output Relays (normally for testing via the bus).
Schematic
The following schematic shows a general representation of the "Test/Reset"
function blocks:
Test 1
Test 1
Test 2
Test 2
Reset 2
Reset 2
Reset 3
Reset 3
BU "TEST/RESET" Button
Test/Reset - Button Blocked
OP "TEST/RESET" Button*
*) The Operator Panel with Display does not have a Test/Reset button. The
respective functions can be carried out via the Operator Panel menu or via
softkeys.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 10-3
Standard Functions
Testing
Testing can be carried out as follows:
• Via the "TEST/RESET" button on the Basic Unit and on the Operator Panel (can
be deactivated), as well as via PC with SIMOCODE ES software.
• Via the plugs of the internal "Test 1" or "Test 2" function blocks
• Via the menu of the Operator Panel with Display (e.g. the "Commands" menu
item).
Testing can be terminated at any time - it does not influence the Thermal
Motor Model / Overload Function, i.e. after switching off via TEST, the
system can be reset immediately.
Tripping only occurs for Test 1 when the operating mode is set to "Remote".
Reset Function
Resetting can be carried out as follows:
• Via the "TEST/RESET" button on the Basic Unit and on the Operator Panel (can
be deactivated), as well as via PC with SIMOCODE ES software.
• Via the "Reset Input" plug of the internal function blocks via the plugs of the
internal function blocks "Reset 1", "Reset 2" and "Reset 3".
• Via the menu of the Operator Panel with Display (e.g. the "Commands" menu
item).
The "Reset" function block consists of:
• One plug.
Overall, there are:
– Three function blocks, "Reset 1 to Reset 3" for BU1 and BU2.
All Reset Inputs (sockets) are equal (OR function).
Test Function:
A SIMOCODE pro function test can also be initialized via the test function.
The test function comprises the following steps:
• Lamp/LED test (test function < 2 s activated)
• Testing the device functionality (Test Function activated for 2 s - 5 s)
• For the "Test 1" function block only: switching off the QE (Test Function
activated for > 5 s).
SIMOCODE pro
10-4 GWA 4NEB 631 6050-22 DS 02
Standard Functions
Test Phases
The following table shows the test phases when the "TEST/RESET" button is
pressed longer:
Relay Test
Test settings
Test 1 to 2 Description
Test/Reset Button The blue Test/Reset buttons on the Basic Unit and the Operator
Blocked Panel are usually intended for acknowledging faults and for carrying
out a device test.
The buttons can be locked via "Test/Reset Buttons Blocked". They
can then be used for other purposes. On the Operator Panel with
Display, blocking is carried out via the corresponding menu
function.
(Default: unblocked)
Table 10-3: Test settings
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 10-5
Standard Functions
Acknowledgement of faults
Generally, the following applies to the acknowledgement of faults:
• Faults can only be acknowledged
– If the cause of the fault has been eliminated
– If there is no "ON" control command pending.
• A reset will not be possible if the cause of the fault has not been eliminated
or if an "ON" control command is pending. The reset will be saved depending
on the type of fault. Saving a reset is indicated by the "GEN. FAULT" LED on
the Basic Unit and on the Control Panel. The LEDs change from flashing to
continuous signal.
Reset settings
Reset 1 to 3 Description
Test/Reset Button The blue Test/Reset buttons on the Basic Unit and on the Operator
Blocked Panel are intended for acknowledging faults and carrying out device
tests.
The buttons can be locked via "Test/Reset Buttons Blocked". These
can then be used for other purposes. On the Operator Panel with
Display, blocking is carried out via the menu (Default: unblocked).
Table 10-4: Reset settings
SIMOCODE pro
10-6 GWA 4NEB 631 6050-22 DS 02
Standard Functions
Note
When the Test Position is enabled, the QLE/QLA sockets of the control
function are controlled through blinking, e.g. to indicate test operation of the
motor feeder via a blinking LED button.
Schematic
The following schematic shows the "Test Position Feedback" function block:
Status -
TPF Test Position
Input
Type Trip -
Test Position Feedback Fault
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 10-7
Standard Functions
Cold Starting
If the motor feeder is in the test position, its main circuit will be isolated
from the network. However, the control voltage will be connected.
The "Cold Starting" function test is carried out in this status. Cold starting
means the motor feeder is tested without a current in the main circuit.
To differentiate this function from normal operation, it must be enabled via
the socket on the function block.
Feedback stating that the motor feeder is isolated from the mains voltage
can result, for example, via an auxiliary contact of the main switch in the
motor feeder that is connected to any device input (terminal). This is then
internally connected to the "Test Position Feedback (TPF) - Input" plug of the
function block. When using Current/Voltage Measuring Modules, this type
of Auxiliary Contact is entirely unnecessary. The "TPF" function block can be
activated by monitoring for undervoltage ("Voltage Monitoring" function
block).
Thereafter, the Contactor Outputs can be set via the control stations
(see Chapter 4.1 "Control Stations"), enabling the current-free status to be
tested.
If current mistakenly flows during test operation, the Contactor Outputs are
switched off by "Trip - Test Position Feedback".
Notice
"Trip - Test Position Feedback (TPF)" will be generated if:
• "TPF" is activated, although current is flowing in the motor feeder
• "TPF" is activated and current is flowing in the motor feeder.
Settings
Input Control of the "Test Position Feedback (TPF)" function block with
any signal
(any sockets ,
e.g. device input)
SIMOCODE pro
10-8 GWA 4NEB 631 6050-22 DS 02
Standard Functions
Schematic
The following schematic shows the "External Fault" function blocks:
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 10-9
Standard Functions
Settings
SIMOCODE pro
10-10 GWA 4NEB 631 6050-22 DS 02
Standard Functions
Description
The "Operational Protection OFF (OPO)" function block returns the Positioner
to a safe position. In order to do this, the input (plug) must be connected to
the respective socket (e.g. device inputs, control bits from PROFIBUS DP,
etc.).
The "Operational Protection Off" function block consists of
• One plug
• One "Status - OPO" socket. This is set when a signal is pending at the Input.
• One "Trip - OPO Fault" socket. This is set when the respective, safe end
position has been reached.
In total there is:
– One "Operational Protection Off (OPO)" function block for BU2.
Schematic
The following schematic shows the "Operational Protection Off (OPO)"
function block:
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 10-11
Standard Functions
Settings
Operational Description
Protection OFF
(OPO)
Input Control of the "Operational Protection OFF" function block using the
monitored signal (any socket ,
e.g. device inputs, etc.)
Safety information
Note
A "Trip - Operational Protection OFF (OPO)" fault message is not generated if
the "OPO" command attempts to run the Positioner to the end position in
which it is already in, or to which it is heading.
Note
No other control command (counter command or stop command) is carried
out while "Operational Protection OFF (OPO)" is active.
Note
The "Trip - Operation Protection Off (OPO)" fault message must be
acknowledged using the open or closed control command, depending on
the present "OPO" end position.
Note
Acknowledgement is carried out even if the desired end position has not yet
been reached.
Note
The fault message is available as diagnosis via PROFIBUS DP.
SIMOCODE pro
10-12 GWA 4NEB 631 6050-22 DS 02
Standard Functions
Description
For other control functions, the following scenarios can be differentiated
between for OPO:
• Motor in operation: The motor is switched off with a "Trip - Operational
Protection OFF (OPO)" fault.
• The motor is off. Initially no fault. The "Trip - Operational Protection OFF
(OPO)" fault only occurs when an "ON Command" is issued.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 10-13
Standard Functions
Schematic
The following schematic shows the "Power Failure Monitoring (UVO)"
function block
UVO
Trip -
Power Failure (UVO)
Input* Type
Power Failure Time
*Activation
Restart Time Delay External Power Failure Monitoring
Fig. 10-6: Schematic of the "Power Failure Monitoring (UVO)" function block
1)
UVO
t
Power Failure Power Failure
2) Time Time
QE
3)
Trip Trip
SIMOCODE pro
10-14 GWA 4NEB 631 6050-22 DS 02
Standard Functions
Settings
Input Control of the "Power Failure Monitoring" function block using the
monitored signal
(any socket ,
e.g. device inputs, control bits from PROFIBUS DP, etc.)
Restart Time Delay The Restart Time Delay can be set so that not all motors restart
(staggered) simultaneously (the mains voltage would otherwise breakdown
again).
Range: 0 to 255 seconds.
Table 10-10: Power Failure Monitoring settings
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 10-15
Standard Functions
Caution
If Emergency Starts are carried out too frequently, Thermal Overloading of
the motor could result!
Status -
Emergency Start Emergency Start
Executed 1)
Input
1) The "Emergency Start Executed" signal is triggered by the Edge (Input) and reset
when the current flows.
Fig. 10-8: Function block "Emergency Start"
Settings
Input Control of the "Emergency Start" function block from any signal
(any sockets ,
e.g. device inputs, control bits from PROFIBUS DP, etc.)
Table 10-11: Emergency Start settings
SIMOCODE pro
10-16 GWA 4NEB 631 6050-22 DS 02
Standard Functions
Schematic
Bus Monitoring:
With this type of monitoring, the "Trip - Bus" fault is generated if
• "Bus Monitoring" is active
• When, in the "Remote" operating mode (mode selector S1=1 and S2=1), the
Cyclic Data transfer between the PLC and SIMOCODE pro is interrupted, e.g.
by the PROFIBUS DP connection being interrupted.
• "Status - Bus o.k." can always be evaluated. If SIMOCODE pro is cyclically
exchanging data with the PLC,
"Status - Bus o.k." is set to "1"-
PLC/PCS Monitoring:
With this type of monitoring, "Trip - PLC/PCS" is generated if
• "PLC/PCS Monitoring" is activated.
• The PROFIBUS DP switches to "CLEAR" status when in the "Remote"
operating mode (mode selector S1=1 and S2=1).
• The "Status - PLC/PCS in Run" can always be evaluated. If the PROFIBUS DP
is in the "CLEAR" status, the "Status - PLC/PCS in Run" is set to "0".
If the "PLC/PCS Monitoring - Input" is connected primarily to the "Cyclic
Receive - Bit 0.7" bit, the status of the PLC is deduced from this bit only.
Watchdog
(PLC/PCS Monitoring)
Bus/PLC-Fault - Reset
Cyclic Communication Status - PLC/PCS in Run
Bus Monitoring Status - Bus o.k. (bus is active)
Trip - Bus
PLC/PCS Monitoring
Trip - PLC/PCS
PLC/PCS Monitoring - Input Bus Response
(level sensitive)
Notice
"Bus Monitoring" and "PLC/PCS Monitoring" can only be effective if the DP
slave address monitoring is activated in the DP master system.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 10-17
Standard Functions
Settings
Watchdog Description
Monitoring Control of the "Watchdog" function block using the monitored signal
PLC/PCS Input (any sockets ,
e.g. control bits from PROFIBUS DP, etc.)
PLC/PCS • Activated:
Monitoring If an SPS fault occurs, the "Trip - PLC/PCS" fault message is
generated and must be acknowledged
• Deactivated:
No fault message; however, the "Status - PLC/PCS in Run"
information can be evaluated at anytime.
SIMOCODE pro
10-18 GWA 4NEB 631 6050-22 DS 02
Standard Functions
10.9 Timestamping
Description
SIMOCODE pro V can timestamp up to eight digital signals with high
temporal precision (10 ms). In the process, every change in the state of the
digital signal will be recorded.
Prerequisite
To use SIMOCODE pro-V timestamping, the DP master being used must
support time synchronization functions via PROFIBUS (e.g. DP master
connections for SIMATIC S7-400), or a master clock must be used (e.g.
SICLOCK).
Process in STEP 7
Activation of the time synchronization for SIMOCODE pro V occurs
in STEP 7 HW Config in the slave properties under "Time Synchronization".
Notice
The set synchronization interval must correspond to the configuration of the
clock master.
Note
The "LADDR" parameter contains the diagnosis address of the DP slave
from STEP 7 HW Config.
LADDR2 contains the diagnosis address of slot 2 of SIMOCODE pro in the
DP mode "DPV1" of the DP master (integrated via OM SIMOCODE pro). For
all other configurations, LADDR2 will contain the same address as LADDR.
In contrast to the STEP7 online help of the FB62, when integrating via GSD,
the slot number of the module is transmitted with Slot 1 for signal
messages, and with Slot 0 for special messages.
You will find further information about FB 62 in the STEP7 online help.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 10-19
Standard Functions
Schematic
The "Timestamping" standard function consists of
• Eight sockets "Timestamping - Input 0 to Input 7".
Overall, there is:
• One "Timestamp" function block for BU2.
Timestamp
Input 0
Input 1 Timestamping Active Event - Timestamping Function Active + o.k.
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Settings
You can activate/deactivate the timestamping function via the
"Timestamping Active" checkbox.
SIMOCODE pro
10-20 GWA 4NEB 631 6050-22 DS 02
Logic Modules 11
In this chapter
In this chapter you will find information about the Logic Modules of
SIMOCODE pro. Logic Modules are function blocks which are modeled not
only on standard logic functions, e.g. Truth Tables (AND, OR,...), but also on
Counters and Timers. In addition to the predefined control functions, you
can use this, for example, to implement Logical Functions, Time Relay
Functions and Counter Functions without being dependent on external
components (relays).
Target groups
This chapter is addressed to the following target groups:
• Configurators
• Programmers.
Necessary knowledge
You will require the following knowledge:
• The principle of connecting plugs to sockets
• The basics of digital signal processing, e.g. Timers, Counters, etc.
Navigation in SIMOCODE ES
You will find the dialogs in SIMOCODE ES under:
Further Function Blocks > Logic Modules.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 11-1
Logic Modules
11.1 Introduction
Description
Freely programmable Logic Modules are function blocks that process Input
Signals and provide Binary or Analog Output Signals according to their
internal logic components. Logic Modules can contain:
• Plugs
• An internal logic component
• Sockets
• Settings, e.g. the time for a Timer.
Schematic
The following schematic shows a general representation of a Logic Module:
Plug 1
Logic Module
Plug 1 - n
(Logic component)
Plug n
Setting Value
SIMOCODE
Number Number
SIMOCODE pro
11-2 GWA 4NEB 631 6050-22 DS 02
Logic Modules
Schematic
The following schematic shows the "Truth Table for 3I/1O" Logic Modules:
Input 1 Input 1
Truth Table 1 3I/1O Truth Table 2 3I/1O
Input 2 Output Input 2 Output
Input 3 Input 3
Input 1 Input 1
Truth Table 3 3I/1O Truth Table 4 3I/1O
Input 2 Output Input 2 Output
Input 3 Input 3
Input 1 Input 1
Truth Table 5 3I/1O Truth Table 6 3I/1O
Input 2 Output Input 2 Output
Input 3 Input 3
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-3
Logic Modules
Example
You want to implement the following circuit:
0 0 1 0
0 1 0 0
S3
0 1 1 1
1 0 0 0
K1
1 0 1 1
K1 switches with: 1 1 0 0
(S1 or S2) and S3
or 1 1 1 1
S1 and S2 and S3
SIMOCODE pro
11-4 GWA 4NEB 631 6050-22 DS 02
Logic Modules
L1
Circuit: N
K1
BU Inputs BU Outputs
BU
1
S1 1 Input 1
Truth Table 1 3I/1O
2 Out1
S2 2 Input 2 Output
3
S3 3 Input 3
Fig. 11-4: Example circuit and parameterization for Truth Table for 3I/1O
Settings
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-5
Logic Modules
Schematic
The following schematic shows the "Truth Table for 2I/1O" Logic Modules:
Input 1 Input 1
Truth Table 7 for 2I/1O Truth Table 8 for 2I/1O
Output Output
Input 2 Input 2
Example
You want to implement the following circuit:
Circuit:
Truth Table, input conditions colored in gray:
0 1 1
1 0 1
1 1 1
K1 K1 switches with:
S1 or S2
SIMOCODE pro
11-6 GWA 4NEB 631 6050-22 DS 02
Logic Modules
Schematic
The following schematic shows the "Truth Table for 5I/2O" Logic Modules:
Input 1
Truth Table 9 for 5I/2O
Input 2 Output 1
Input 3
Input 4 Output 2
Input 5
Settings
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-7
Logic Modules
11.5 Counters
Description
Counters are integrated in the SIMOCODE pro system. These are activated
via the plugs "+" or "-".
The Counter Output switches to "1" when the preset limit is reached. The
Counter is reset with "Reset".
The actual value is available as a socket for further processing and can also
be transmitted to the automation system.
• Plug +: increases actual value by 1 (maximum: limit value)
• Plug –: Decreases the actual value by 1 (minimum: 0).
• Reset: resets the actual value to 0.
The Counter consists of
• 3 plugs (input +, input – and reset)
• One logic component
• One socket.
• One "Actual Value" analog socket with the current value in the range between
0 and the limit. It remains even if there is a voltage failure.
Overall, there are:
• two Counters, 1 to 2 for BU1
• four Counters, 1 to 4 for BU2.
Schematic
The following schematic shows the "Counters" Logic Modules:
Input + Input +
Counter 1 Counter 2
Input – Output Input – Output
Input + Input +
Counter 3 Counter 4
Input – Output Input – Output
Note
The time between the events to be counted depends on
- the Input Delay
- the Device Cycle Time.
SIMOCODE pro
11-8 GWA 4NEB 631 6050-22 DS 02
Logic Modules
Note
The actual value remains the same
- During parameterization or failure of the supply voltage
- If there are simultaneous Input Signals at Input + and Input –.
Note
The Output is always 0 if a Reset is pending.
Settings
Counters 1 to 4 - Description
Limit The maximum value that can be reached when counting and where
the counter issues an Output Signal.
Range: 0 - 65535
Table 11-4: Counter settings
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-9
Logic Modules
11.6 Timer
Description
The timer consists of
• 2 plugs (input and reset)
• One socket.
• One "Actual Value" analog socket with the actual value.
The actual value is available as a socket for further internal processing and
can also be transmitted to the automation system.
If an input signal is pending, the timer can issue an Output Signal according
to the chosen Timer type:
• With Closing Delay
• With Closing Delay with Memory
• With OFF Delay
• With Fleeting Closing.
Overall, there are:
– Two timers, 1 to 2 for BU1
– Four timers, 1 to 4 for BU2.
Schematic
The following schematic shows the "Timer" Logic Modules:
Input Input
Timer 1 Timer 2
Output Output
Type Type
Reset Actual Value Reset Actual Value
Value Value
Input Input
Timer 3 Timer 4
Output Output
Type Type
Reset Actual Value Reset Actual Value
Value Value
Note
The Output is always 0 if a Reset is pending.
SIMOCODE pro
11-10 GWA 4NEB 631 6050-22 DS 02
Logic Modules
Note
The response of the sockets of all Timers (Input, Reset) has been
completely changed to level-active for Basic Unit 1 from version *E05* and
higher and Basic Unit 2 from version *E03* and higher. Use of an
unchanged parameter file utilizing integrated Timers may thus result in a
different response if such Basic Units are used. For example, if "Fixed Level
- '1'" is set at the Timer Input, the timer function is automatically restarted
after the Timer Reset occurs. However, in Timers with the parameterized
Type = "Fleeting Closing" there is no change in the response.
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-11
Logic Modules
Input
Reset
Time
t t
Output
Input
Reset
Time
t t t
Output
Input
Reset
Time
t t t
Output
Input
Reset
Time
t
Output
Fig. 11-10: Output Response, Timer (Basic Unit 1 before version *E05* and Basic Unit 2 before
version *E03*)
SIMOCODE pro
11-12 GWA 4NEB 631 6050-22 DS 02
Logic Modules
Input
Reset
Time
t t t
Output
Input
Reset
Time
t t t t
Output
Input
Reset
Time
t t t t
Output
Input
Reset
Time
t t t
Output
Fig. 11-11: Output Response, Timer (Basic Unit 1 from version *E05* onwards and Basic Unit 2 from
version *E03* onwards)
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-13
Logic Modules
Settings
Timers 1 to 4 - Description
Value Time during which the Timer provides an Output Signal when
activated, depending on the Output Response (type).
Range: 0 to 65535, unit 100 ms
Table 11-5: Timer settings
SIMOCODE pro
11-14 GWA 4NEB 631 6050-22 DS 02
Logic Modules
Schematic
The following schematic shows the "Signal Conditioner" Logic Modules:
Input Input
Signal Conditioner 1 Signal Conditioner 2
Output Output
Reset Reset
Type Type
Input Input
Signal Conditioner 3 Signal Conditioner 4
Output Output
Reset Reset
Type Type
Note
The Output is always 0 if a Reset is pending.
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-15
Logic Modules
Input
Reset
Output
Level Inverted
Input
Reset
Output
Input
Reset
Output
Reset
Output
SIMOCODE pro
11-16 GWA 4NEB 631 6050-22 DS 02
Logic Modules
NOR function
You can implement a NOR function with the "Level Inverted" type of signal:
0 0 1
Input
1 0 0 Output
Reset
> 1
0 1 0 =
1 1 0
Table 11-6: NOR function
Settings
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-17
Logic Modules
Input Input
Non-vol. Elem. 1 Non-vol. Elem. 2
Output Output
Reset Reset
Type Type
Input Input
Non-vol. Elem. 1 Non-vol. Elem. 2
Output Output
Reset Reset
Type Type
Note
The Output is always 0 if a Reset is pending.
SIMOCODE pro
11-18 GWA 4NEB 631 6050-22 DS 02
Logic Modules
Input
Reset
Output
Level Inverted
Input
Reset
Output
Input
Reset
Output
Input
Reset
Output
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-19
Logic Modules
NOR function
You can implement a NOR function with the "Level Inverted" type of signal:
0 0 1
Input
1 0 0 Output
Reset
> 1
0 1 0 =
1 1 0
Table 11-8: NOR function
Settings
Non-volatile Description
Elements
1 to 4 -
SIMOCODE pro
11-20 GWA 4NEB 631 6050-22 DS 02
Logic Modules
11.9 Flashing
Description
If an Input Signal is pending at its plug, the "Flashing" logic module issues a
signal to its socket, which alternates between binary 0 and 1 with a fixed
frequency of 1 Hz. You can use this to make the LEDs on the Operator Panel
flash.
The Logic Module consists of
• One plug
• One logic component
• One socket.
Overall, there are:
– three "Flashing 1 to 3" Logic Modules for BU1 and BU2.
Schematic
The following schematic shows the "Flashing" Logic Modules:
Flashing 1 Flashing 2
Input Output Input Output
Flashing 3
Input Output
Settings
Flashing 1 to 3 - Description
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-21
Logic Modules
11.10 Flickering
Description
You can use the "Flickering" Logic Modules to assign the "Flickering" function
to the Operator Panel LEDs (for example).
If an Input Signal is pending, the "Flickering" function block issues an Output
Signal with a frequency of 4 Hz.
The function block consists of
• One plug
• One logic component
• One socket.
Overall, there are:
– three "Flickering 1 to 3" Logic Modules for BU1 and BU2.
Schematic
The following schematic shows the "Flickering" Logic Modules:
Flickering 1 Flickering 2
Input Output Input Output
Flickering 3
Input Output
Settings
Flickering 1 to 3 - Description
SIMOCODE pro
11-22 GWA 4NEB 631 6050-22 DS 02
Logic Modules
Schematic
The following schematic shows the "Limit Monitor" Logic Modules:
Response
Response Limit Value 1 to 4
Tripping -
Warning -
Signalling X
Disabled -
Delay 0 - 25.5 s (0.5)
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-23
Logic Modules
Functional principle
The Limit Signal issued depends on
• The operating state of the motor
• The TPF function
• The parameterized "Activity":
– ON
– ON+
– RUN
– RUN+.
The following display shows a flow chart with the different "Activity"
parameters.
Activity
Class-time
"ON"
Time
1) TPF: There is Test Position Feedback, the motor feeder is in the test
position, i.e. its main circuit is isolated from the network. However, the
control voltage is connected.
SIMOCODE pro
11-24 GWA 4NEB 631 6050-22 DS 02
Logic Modules
Settings
Input Analog plug of the Limit Monitor to be connected with the analog
value (2 bytes) which is to be monitored,
(e.g. Maximum Current Imax, Remaining Cooling Time, Actual
Value of Timers, etc.).
Delay Specifies the time period for which the limit must be constantly
overshot before the "Signal - Limit" output is set.
Range: 0 - 25.5 s (0.5).
Note
When using Limit Monitors, always ensure that the correct range and unit
are used for the analog values connected to the Limit Input. These always
have a direct influence on the unit of the Limit Value to be set. The units and
the ranges of all relevant analog values can be found in Chapter B.8 "Data
Record 94 - Measured Values" and Chapter B.9 "Data Record 95 - Service
Data / Statistical Data".
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-25
Logic Modules
Unit Range
Thus, for example, a Limit Value of 473 (K) should be parameterized for a
Limit Monitor to monitor a maximum temperature of 200 °C.
SIMOCODE pro
11-26 GWA 4NEB 631 6050-22 DS 02
Logic Modules
Schematic
The following schematic shows the "Calculator" Logic Modules:
Calculator 1
Input Counter
Output
Denominator
Range: 0 - 65535
Offset
Calculator 2
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-27
Logic Modules
SIMOCODE pro
11-28 GWA 4NEB 631 6050-22 DS 02
Logic Modules
Settings
Calculator - Description
Calculator 1 - Input Any value (2 bytes/1 word)
Range: 0 - 65535
Calculator 1 - Output Calculated value /(2 bytes/1 word)
Range: 0 - 65535
Calculator 1 - Counter Range: -32766 to +32767, increment 1
Calculator 1 - Denominator Range: 0 - 255, increment 1
Calculator 1 - Offset Range: -32766 to +32767, increment 1
Calculator 2 - Input 1 Any value (2 bytes/1 word)
Range: 0 - 65535
Calculator 2 - Input 2 Any value (2 bytes/1 word)
Range: 0 - 65535
Calculator 2 - Output Calculated value (2 bytes/1 word)
Range: 0 - 65535
Calculator 2 - Counter 1 Range: -127 to +128, increment 1
Calculator 2 - Denominator 1 Range: 0 - 255, increment 1
Calculator 2 - Counter 2 1) Range: 0 - 255, increment 1
Calculator 2 - Denominator 2 1) Range: -127 to +128, increment 1
Calculator 2 - Offset Range: -32766 to +32767, increment 2
Calculator 2 - Operating Mode 1 or 2
Calculator 2 - Operator 1) +, -, *, /
1) only relevant for Operating Mode = 1
Table 11-15: Calculator settings
Formulae
Calculator 1
Input Output
Counter
* Input + Offset
Denominator
Calculator 2
* Input 1 Operator
* Input 2 + Offset
Input 2 Denom. 1 Denom. 2
Oper. Mode 1
Calculator 2
Input 1
(High) Counter 1 Output
Input 2 * Input 1, Input 2 + Offset
(Low) Denom. 1
Oper. Mode 2
SIMOCODE pro
GWA 4NEB 6050-22 DS 02 11-29
Logic Modules
Examples
Example 1
• Conversion of the maximum temperature of the Temperature Module from K
to °C
TM Inputs Calculator 1
Max. Temperature 1
* Input + -273 0 ... 65535 °C
Unit = 1 K
Sensor Type 1
Response at
Sensor Fault/
Out of Range
Number of
Act. Sensors
Example 2
• Conversion of the maximum temperature of the Temperature Module from K
to °F
TM inputs Calculator 1
Max. Temperature 9
* Input + -460 0 ... 65535 °F
Unit = 1 K
Sensor Type 5
Response at
Sensor Fault/
Out of Range
Number of
Act. Sensors
Example 3
• Conversion of the motor current I max. from % to A (e.g. Set Current
Is = 3.36 A)
(only possible for motors with one rotational speed)
Calculator 1
336
Max. Current I_max * Input + 0 0 ... 3427 (0 ... 34.72 A)
Unit = 1 % 100
SIMOCODE pro
11-30 GWA 4NEB 631 6050-22 DS 02
Communication 12
In this chapter
In this chapter you will find information about the options of SIMOCODE
pro communication, e.g. communication with a PLC. The presetting of the
Receive, Send and Diagnosis Data is sufficient for almost all applications so
that the parameterization only has to be changed to a small extent.
Otherwise, you can adapt the settings of the individual bits specifically for
your application.
Target groups
This chapter is addressed to the following target groups:
• Configurators
• PLC programmers.
Necessary knowledge
You will require the following knowledge:
• The principle of connecting plugs to sockets
• knowledge about PROFIBUS DP.
Navigation in SIMOCODE ES
You will find the following dialogs in SIMOCODE ES:
Device Parameters > Bus Parameters
Further Function Blocks > Outputs > Acyclic Send Data
Further Function Blocks >Outputs > Cyclic Send Data.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-1
Communication
12.1 Definitions
PROFIBUS DP
PROFIBUS bus system with the DP protocol. DP stands for decentralized
periphery. The main task of PROFIBUS DP is fast Cyclic Data exchange
between the central DP master and the periphery devices.
PROFIBUS DPV1
PROFIBUS DPV1 is an extension of the DP protocol. It enables Acyclic Data
exchange of Parameter, Diagnosis, Receive and Test Data.
DP master
A master is designated as a DP master if it works with the DP protocol
according to the EN 50 170 standard, Volume 2, PROFIBUS.
Class 1 master
A class 1 master is an active station on the PROFIBUS DP. The Cyclic Data
exchange with other stations is characteristic for this type of master. Typical
class 1 masters are, for example, PLCs with a PROFIBUS DP connection.
Class 2 master
A class 2 master is an optional station on the PROFIBUS DP.
Typical class 2 masters are, for example,
• PC/programming devices with the SIMOCODE ES professional software
• SIMATIC PDM (PCS7)
• PC with SIMATIC power control software (power management).
DPV1 slave
A slave is designated as a DPV1 slave if it is operated on the PROFIBUS bus
with the PROFIBUS DP protocol and works according to the EN 50 170
standard, Volume 2, PROFIBUS.
GSD
Device data (GSD) include DP slave descriptions in a uniform format. Using
GSD (device data) makes it easier to parameterize the
DP slaves in a DP master system.
OM SIMOCODE pro
OM SIMOCODE pro (object manager) is used instead of GSD (device data)
to integrate SIMOCODE pro into STEP7.
OM SIMOCODE pro enables the use of SIMOCODE ES Professional (if it is
installed) for parameterization within STEP7.
SIMOCODE pro
12-2 GWA 4NEB 631 6050-22 DS 02
Communication
SIMATIC PDM
Software package for the configuration, parameterization, commissioning
and maintenance of devices (e.g. transducers, controllers, SIMOCODE) and
for configuring networks and PCs.
Writing data
Writing data means that data is transmitted to the SIMOCODE pro system.
Reading data
Reading data means that data is transmitted from the SIMOCODE pro
system.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-3
Communication
Maximum of two
class 2 masters
Communication principle
The following figure shows the communication principle and the way data is
transmitted depending on the master and slave operating modes:
PLC CPU
Cyclic I/O Acyclic Acyclic Acyclic
PC or PCS
e.g.
SIMOCODE ES
Professional
PLC
Communication processor
Configuration GSD
Startup
Parameter
Lock
SIMOCODE pro
3UF7
Diagnosis Alarms Parameter
Data Records Data Records
DPV0
Cycl. Send Data
Cycl. Receive Data DPV1 DPV1
SIMOCODE pro
12-4 GWA 4NEB 631 6050-22 DS 02
Communication
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-5
Communication
SIMOCODE pro
12-6 GWA 4NEB 631 6050-22 DS 02
Communication
Byte 0
Byte 1 Station Status 1 to 3
Byte 2
Standard
Byte 3 Master PROFIBUS address Diagnosis
Byte 8
.
. Status Information
.
Byte 27
Byte 28
Channel-related Diagnosis
Byte 29
(dynamic, n = 0; 3; 6)
Byte 30
Advanced
Diagnosis
Byte 31
Channel-related Diagnosis
Byte 32
(dynamic, n = 0; 3; 6)
Byte 33
Byte 28+n
.
. Diagnosis Alarm (Temporary)
.
Byte 48+n
Byte 28+n
.
. Process Alarm (Temporary)
.
Byte 48+n
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-7
Communication
Station Status 1
SIMOCODE pro
12-8 GWA 4NEB 631 6050-22 DS 02
Communication
Station Status 2
Bit Meaning
0 The DP slave must be parameterized again.
1 There is a diagnosis message. The DP slave will not function until the error is
rectified (static diagnosis message).
2 The bit is always "1" when the DP slave with this PROFIBUS address is present.
3 The address monitoring is activated for this DP slave.
4 The DP slave received the "FREEZE" control command 1).
5 The DP slave received the "SYNC" control command 1) .
6 0: Bit is always "0".
7 The DP slave is deactivated, i.e. it is decoupled from the current processing.
1) Bit is only updated if another diagnosis message also changes.
Table 12-4: Configuration of Station Status 2 (byte 1)
Station Status 3
Station Status 3 is not relevant for the slave diagnosis.
Bit Meaning
0 to 7 Bits are always "0".
Table 12-5: Configuration of Station Status 3
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-9
Communication
7 6 5 0 Bit number
Byte 6 0 1 0 0 0 0 1 0 = 0x42
7 6 5 0 Bit number
Byte 7 0 0 0 0 0 0 0 x GSD
7 6 5 0 Bit number
Byte 7 0 0 0 0 x 0 0 0 OM SIMOCODE pro
SIMOCODE pro
12-10 GWA 4NEB 631 6050-22 DS 02
Communication
7 6 5 0 Bit number
Byte 8 0 0 0 1 0 1 0 0 = 0x14
7 0
Byte 10 x Slot number GSD: 0x01
OM SIMOCODE pro: 0x04
Byte 11 0x00
7 6 5 4 3 2 1 0 Bit number
..
Byte 12
. Detailed messages
Byte 27
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-11
Communication
7 6 5 0 Bit number
Byte 28 1 0 0 0 0 0 x x
0x80 GSD
0x83 OM SIMOCODE pro
Code for Channel-related Diagnosis
7 6 5 0 Bit number
Byte 29 1 1 0 0 0 0 0 0
Input/output channel
7 6 5 0 Bit number
Byte 30 0 0 0
Channel type:
000B: No special channel type
The block for the Channel-related Diagnosis, which has a length of 3 bytes,
is either missing (if there is no Channel-related Diagnosis) or is available
once or twice.
Error types
The diagnosis message is output on channel 0.
SIMOCODE pro
12-12 GWA 4NEB 631 6050-22 DS 02
Communication
7 0
Byte 29+n 0x01 Diagnosis Alarm
7 0
Byte 30+n x Slot number GSD: 0x01
OM SIMOCODE pro: 0x04
Byte 31+n 0x00
7 6 5 4 3 2 1 0 Bit number
Byte 32+n
Byte 48+n
n = 0; 3; 6
The first byte of the block for Diagnosis Alarms can be moved by 3 or 6
bytes depending on the number of blocks for the Channel-related Diagnosis.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-13
Communication
7 6 5 0 Bit number
Byte 28+n 0 0 0 1 0 1 0 0 = 0x14
7 0
Byte 29+n 0x02 Process Alarm
7 0
Byte 30+n x Slot number GSD: 0x01
OM SIMOCODE pro: 0x04
Byte 31+n 0x00
7 6 5 4 3 2 1 0 Bit number
Byte 32+n
Detailed messages
Byte 48+n
n = 0; 3; 6
The first byte of the block for Process Alarms can be moved by 3 or 6 bytes
depending on the number of blocks for the Channel-related Diagnosis.
SIMOCODE pro
12-14 GWA 4NEB 631 6050-22 DS 02
Communication
The following table shows an overview of the slave operating modes which
SIMOCODE pro can be operated with on the class 1 master:
Class 1 master
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-15
Communication
Notice
If you want to utilize the complete functionality of SIMOCODE pro (e.g.
timestamping), your configuration tool must support GSD files - Rev. 5 such
as e.g. STEP7 V5.3 and higher.
The following table describes how to integrate the GSD file in SIMATIC S7
and SIMOCODE pro from the hardware catalog.
Table 12-9: Integration of SIMOCODE pro as DPV1 slave via GSD in the Configuration Software
SIMOCODE pro
12-16 GWA 4NEB 631 6050-22 DS 02
Communication
12.4.4 Integration of SIMOCODE pro as SIMATIC PDM Object (DPV-1 Slave via
GSD) in STEP7-HW Config
3 Enter
"SIMOCODE pro C (PDM)" or
"SIMOCODE pro V (PDM)" on the PROFIBUS.
Only for SIMOCODE pro V:
SIMOCODE pro V can be connected in two basic types (basic type 1 or
basic type 2). See Chapter 12.3.1 "Cyclic Data".
Enter the desired basic type "Basic type 1" or "Basic type 2" as a module.
4 Check the set DP alarm mode (DPV0 or DPV1) as well as the enable of the
DPV-1 alarms in the properties of the DP slave.
These settings influence the evaluation of the diagnosis data and the
alarms (see Chapter 12.5 "Evaluating Diagnosis Data" and Chapter 10.9
"Timestamping").
Table 12-10: Integration of SIMOCODE pro as SIMATIC PDM Object (DPV-1 Slave via GSD) in
STEP7-HW Config
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-17
Communication
Step STEP7
3 Enter
SIMOCODE pro C, SIMOCODE pro V (basic type 1) or
SIMOCODE pro V (basic type 2) on the PROFIBUS.
Only for SIMOCODE pro V:
SIMOCODE pro V can be connected in two basic types (basic type 1 or
basic type 2). See Chapter 12.3.1 "Cyclic Data".
Insert the desired basic type "Basic type 1" or "Basic type 2" as a module.
SIMOCODE pro
12-18 GWA 4NEB 631 6050-22 DS 02
Communication
Note
The interface of the SFB 54 "RALRM" is identical to the interface of the FB
"RALRM" as defined in the "PROFIBUS Guideline PROFIBUS
Communication and Proxy Function Blocks according to IEC 61131-3"
standard.
You will find further information about SFB 54 in the STEP7 online help.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-19
Communication
The Diagnosis Data about the Diagnosis Alarms and Process Alarms is
transmitted and evaluated during the integration of SIMOCODE pro as an
S7 slave.
DP masters which are operated in "S7 compatible" DP mode (e.g. all older SIMATIC
S7-300/400-DP master systems)
Response and process in STEP7:
A Diagnosis Alarm (OB 82) is triggered in the CPU for every new diagnosis
of a device error, whereas a Process Alarm (OB 40) is triggered for every
new diagnosis triggered by Trips/Warnings/Events.
If the OB 82 or the OB 40 is not programmed, the CPU goes into the "STOP"
mode.
You will find more information about device errors in the start information of
the OB 82 in the "OB82_MDL_DEFECT" variable.
The start information of the OB 40 contains the "OB40_POINT_ADDR"
variable, which in turn contains the data of the Process Alarm that is
SIMOCODE pro
12-20 GWA 4NEB 631 6050-22 DS 02
Communication
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-21
Communication
Note
The interface of the SFB 52 "RDREC" and the SFB 53 "WRREC" is identical to
the FB "RDREC" and "WRREC" as defined in the "PROFIBUS Guideline
PROFIBUS Communication and Proxy Function Blocks according to IEC
61131-3" standard.
You will find further information about SFB and SFC in the STEP7 online
help.
SIMOCODE pro
12-22 GWA 4NEB 631 6050-22 DS 02
Communication
Note
A PC with a system connection for PROFIBUS (e.g. SIMATIC NET CP 5512
or CP 5611) is required to carry out online functions via PROFIBUS DP, e.g.
transfer of SIMOCODE pro parameters.
Notice
The startup parameter block (Device Parameter > Bus Parameter) must
always be set for this form of parameterization to avoid overwriting the
device parameters with any existing parameter data during startup.
The standard version of SIMATIC PDM (PDM Basic) provides you with a
comparable functionality to SIMOCODE ES Professional for
parameterization of SIMOCODE pro via PROFIBUS:
The following additional functions are available with the PDM option
"Integration in STEP7":
• "Offline Saving" of SIMOCODE pro parameter data in the STEP7 project and
manual transmission (no automatic transfer of parameter data during
startup!)
• "Routing via S7 Stations".
Example: Parameterization of all SIMOCODE pro devices from a central
engineering station, together with hardware components which provide a
data record gateway (CP443-5 Extended, IE/PB link), also in connection with
different networks.
Notice
The startup parameter block (Device Parameter > Bus Parameter) must
always be set for this form of parameterization to avoid overwriting the
device parameters with any existing parameter data during startup.
You will find further information about SIMATIC PDM in the SIMATIC-PDM
manual.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 12-23
Communication
Notice
In order to be able to carry out the device parameterization during startup,
the startup parameter block ("Device Parameter > Bus Parameter") must
remain unset.
SIMOCODE pro is then parameterized with the device-specific parameters
stored in the DP master, and any existing parameters in the device are
overwritten.
SIMOCODE pro
12-24 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces 13
In this chapter
This chapter contains information about mounting and wiring individual
SIMOCODE pro components.
Target groups
This chapter is addressed to the following target groups:
• Technicians
• Electricians
• Maintenance and service personnel.
Necessary knowledge
You will require the following knowledge:
• Basic general knowledge about SIMOCODE pro.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-1
Mounting, Wiring, Interfaces
Warning
Dangerous electrical voltage! Can cause electric shock and
burning. Ensure the system and the device are disconnected from voltage
before beginning work.
Notice
Observe the information contained in the operating instructions.
Notice
For technical reasons, there are two different mounting lugs for the screw
attachment:
For Basic Units, Expansion Modules,
Decoupling Module: Order No. 3RP1903
For Current Measuring Modules and
Current/Voltage Measuring Modules,
45 mm and 55 mm width: Order No. 3RP1900-0B
Removable terminals
Notice
The removable terminals are mechanically coded and will only fit in a certain
position!
SIMOCODE pro
13-2 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
13.2 Mounting
13.2.1 Basic Units, Expansion Modules and Decoupling Module
BU1 BU2
Screw attachment
3RP1903 3RP1903
Ø 5 mm
Ø 5 mm
Fig. 13-1: Mounting of Basic Unit, Expansion Modules and the Decoupling Module
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-3
Mounting, Wiring, Interfaces
45 mm width 55 mm width
Screw attachment
3RP1900-0B 25-mm spacer 3RP1900-0B
SIMOCODE pro
13-4 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
45 mm width 55 mm width
Screw attachment
3RP1900-0B 25-mm spacer 3RP1900-0B
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-5
Mounting, Wiring, Interfaces
Step Description
1 Make a cutout, e.g. in the front panel or switchgear cabinet door. Dimensions
(see Fig. 13-4 and 13-5).
2 Position the operator Panel or the Operator Panel with Display in the cutout.
4 Lock the Operator Panel in position by tightening the four mounting bracket
screws.
Table 13-1: Sequence for installing the Operator Panel / Operator Panel with Display
Cutout
90+0.5
Front panel
30+0.5
switchgear
cabinet door, etc.
SIMOCODE pro
13-6 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
Cutout
91,5+0.5
54,5+0.5
Warning
To ensure IP54 tightness and the correct functionality of the Operator Panel,
the tightening torque of the screws provided should not be set too high
when mounting.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-7
Mounting, Wiring, Interfaces
Step Description
1 Unscrew the four mounting bracket screws and remove the 3UF52 Operator
Panel from the front panel or switchgear cabinet door.
2 Ensure that the dimensions of the cutout in the front panel or switchgear
cabinet door measure 91.5 +0.5 mm (width) and 54.5+0.5 mm (height)
(see Fig. 13-6).
3 Slide the seal provided onto the Operator Panel Adapter (see Fig. 13-6).
7 Lock the Operator Panel in position by tightening the four mounting bracket
screws (see Fig. 13-7 and safety guidelines!).
Table 13-2: Exchanging a 3UF52 Operator Panel for a 3UF720 Operator Panel
4x
SIMOCODE pro
13-8 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
IP 54
Warning
To ensure IP54 tightness and the correct functionality of the Operator Panel,
the tightening torque of the screws provided should not be set too high
when mounting.
Notice
A SIMOCODE pro 3UF7 system operator panel can not be used with
SIMOCODE-DP 3UF5, and vice versa.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-9
Mounting, Wiring, Interfaces
13.3 Wiring
13.3.1 Basic Units, Expansion Modules and Decoupling Module
Basic Units, Expansion Modules and the Decoupling Module have
removable terminals. You do not have to detach the wiring to exchange
these devices!
Removable terminals
Basic Units Expansion Modules/
Decoupling Module
D D
C C
A A
A, C, D: Coding
Fig. 13-8: Removable terminals on Basic Units, Expansion Modules and the Decoupling Module
Notice
The removable terminals are mechanically coded and will only fit in a certain
position!
Cables
The cable cross sections are the same for all devices. The following table
shows cable cross sections, stripping lengths and tightening torques of the
cables for the removable terminals:
Table 13-3: Cable cross sections, stripping lengths and tightening torques of the cables
SIMOCODE pro
13-10 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
a) b) c)
24 V DC internal, 4 Inputs usable 24 V DC external, 3 Inputs usable 24 V DC external, 4 Inputs usable
Basic Unit (BU) Basic Unit (BU) Basic Unit (BU)
BU Inputs BU Inputs BU Inputs
A1
24 V DC
A2
All inputs work reactionless, i.e. the signal statuses on neighboring inputs
do not influence each other.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-11
Mounting, Wiring, Interfaces
Connection Assignment
Upper terminals
PROFIBUS DP
RESET
T1 Thermistor connection (binary PTC)
Lower terminals
A PROFIBUS DP Pin A
SPE/PE Shielded/PE
Table 13-4: Pin assignment for the removable terminals of the Basic Unit
Step Description
1 Connect the cables to the upper and lower terminals.
2 If you wish to use the A/B terminals for PROFIBUS DP, connect the
PROFIBUS DP cable-shielding to the SPE/PE terminal.
Notice
The A/B terminals are an alternative to the 9-pole SUB-D connection! Baud
rates of up to 1.5 MBit/s are possible!
SIMOCODE pro
13-12 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
b)
a)
T1 T2 9 10 4 5 8
IN1 IN2 IN3 IN4 24 V
1
OUT1
Device 2
OUT2
Bus
3
Gen. Fault
6
OUT3
7
PROFIBUS DP
A1 A2 A B SPE/PE
Max. 1.5 MBd
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-13
Mounting, Wiring, Interfaces
N/M
DM Inputs N/M
DM Inputs
~
IN1 1 IN1 1
IN2 2 IN2 2
IN3 3 IN3 3
IN4 4 IN4 4
Connection Assignment
Upper terminals
Lower terminals
PE PE
READY
26 IN3 IN4 27 PE
Table 13-6: Pin assignment of the removable terminals of the Digital Module
SIMOCODE pro
13-14 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
~ AC
+
DC
–
23 IN1 24 IN2 26 IN3 27 IN4 25 N/M
20
Ready 21
OUT1
22
OUT2
PE
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-15
Mounting, Wiring, Interfaces
Connectio Assignment
n
Upper terminals
Lower terminals
PE PE
READY
EM
3UF7 500–1AA00–0
G/YYMMDD *Exx*
PE
Table 13-7: Pin assignment of the removable terminals of the Earth-fault Module
SIMOCODE pro
13-16 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
L1
L2
L3
N
Z2
3UL22
Z1
*) *) Cable shielding recommended
40 43
C1 C2
Ready
PE
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-17
Mounting, Wiring, Interfaces
Connectio Assignment
n
Upper terminals
Lower terminals
PE Shielded/PE
READY
TM
3UF7 700–1AA00–0
G/YYMMDD *Exx*
56 T1 57 PE
Table 13-8: Pin assignment of the removable terminals of the Temperature Module
SIMOCODE pro
13-18 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
3 x max. 3 x max.
1) 2)
ϑ ϑ
*) *) *) Cable shielding recommended.
Ready
T1 T1
56 57 PE
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-19
Mounting, Wiring, Interfaces
Connectio Assignment
n
Upper terminals
Lower terminals
PE PE READY
AM
3UF7 400–1AA00–0
G/YYMMDD *Exx*
36 +OUT- 37 PE
Table 13-9: Pin assignment of the removable terminals of the Analog Module
SIMOCODE pro
13-20 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
2 x max. L+
IIN (0/4 mA - 20 mA) + (potential-free current source, e.g. isolating amplifier)
-
*) M
IN1+ IN1-
IN2+ IN2-
30 33 31 34
IN1+ IN1- IN2+ IN2-
Ready
OUT+ OUT-
36 37 PE *) Cable shielding recommended for up to 30 m
*) and for outside of the switchgear cabinet.
+ Cable shielding necessary for over 30 m
RL
IOUT (0/4 A - 20 mA)
-
RL < 500 Ohm
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-21
Mounting, Wiring, Interfaces
Connectio Assignment
n
Upper terminals
Lower terminals
PE PE
READY
DCM
3UF7 150–1AA00–0
G/YYMMDD *Exx*
PE
Table 13-10: Pin assignment of the removable terminals of the Decoupling Module
Ready
Wiring the removable terminals of the Expansion Modules and the Decoupling
Module
Connect the system shielding to the PE terminal.
SIMOCODE pro
13-22 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
3UF7000-1AU00-0 Through-hole
0.3 A - 3 A technology
Ø Through-hole
openings: 7.5 mm
3UF7101-1AA00-0
2.4 A - 25 A
Ø Through-hole
openings: 7.5 mm
3UF7102-1AA00-0
10 A - 100 A L1
L2
Ø Through-hole
Ø
L3
N
openings: 14 mm
3UF7103-1AA00-0
20 A - 200 A L1 L2 L3
Ø Through-hole
openings: 25 mm
section:
16 mm² - 95 mm², M
3~
AWG 5 to 3/0
3UF7104-1BA00-0
63 A - 630 A
Conductor cross
section:
50 mm² - 240 mm²,
AWG 1/0 kcmil to
500 kcmil
Table 13-11: Current Measuring Modules
Notice
Pay attention to the correct assignment and the correct routing direction
when connecting or routing the cables of the single phases of the main
circuit!
Observe the information in the operating instructions!
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-23
Mounting, Wiring, Interfaces
3UF7101-1AA00-0
20 A - 200 A L1 L2 L3 L1 L2 L3
Ø Through-hole
openings: 25 mm
SIMOCODE pro
13-24 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
Safety guidelines
Note
Measuring of measured values relating to voltage or power:
For Current/Voltage Measuring Modules, connect the main circuit L1, L2, L3
with the connection terminals (L1, L2, L3) of the removable terminals via a
3-core cable. The supply cables may have to have additional cable
protection, for example, via short-circuit proof cable or fuses.
Notice
When connecting or routing the cables of the single phases of the main
circuit, ensure correct assignment of the phases on the Current/Voltage
Measuring Modules and correct routing direction! Observe the information
in the operating instructions!
Removable terminals
The following table shows cable cross sections, stripping lengths and
tightening torques of the cables for the removable terminals:
Table 13-13: Cable cross sections, stripping lengths and tightening torques of the cables
The following is a representation of the pin assignment of the removable
terminals:
Lower Upper
L1, L2, L3:
Terminals for connecting the 3-wire
cable of the main circuit
Fig. 13-17: Pin assignment of the terminals of the Current/Voltage Measuring Modules
Caution
The L1 and L3 phases are interchanged on the upper/lower terminals!
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-25
Mounting, Wiring, Interfaces
Description
SIMOCODE pro can be operated with external current transformers. The
secondary cables of the current transformer are looped through the three
through-hole openings of the Current Measuring Module, and short-
circuited. The secondary current of the external current transformer is the
primary current of the SIMOCODE pro Current Measuring Module.
Notice
If the main circuit is using rated current, the secondary current of the
current transformer must be within the setting range of the Current
Measuring Module used!
K1
K2
Current Measuring Basic Unit
K3 Module 3UF 71 3UF 70
L
Transformation ratio
The transformation ratio is calculated using the following formula:
Primary current (external current transformer)
Transformation ratio =
Secondary current x number of loops n
(ext. current transformer) (current measuring module)
In the following examples, the displayed actual current flowing does not
need to be converted, even when an interposing transformer is used, since
SIMOCODE pro only outputs the proportional value, based upon the
parameterized Set Current Is.
SIMOCODE pro
13-26 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
Example 1:
• 3UF1868-3GA00 current transformer:
– Primary current: 820 A at nominal load
– Secondary current: 1 A
• SIMOCODE pro with 3UF7 100-1AA00-0 current measuring module,
Set Current 0.3 to 3 A
This means:
– The secondary current of the current transformer is 1 A at the rated load
and is, therefore, within the 0.3 to 3 A setting range of the Current
Measuring Module used
– The Set Current Is to be parameterized in SIMOCODE pro is 1 A.
K1
Current Measuring
K2
Module 3UF 71 Basic Unit
K3 Setting Range: 3UF 70
L 0.3 A - 3 A
Fig. 13-19: Example (1 of 2) for current measuring with an 3UF18 external current transformer
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-27
Mounting, Wiring, Interfaces
Example 2:
• 3UF1868-3GA00 current transformer:
– Primary current: 205 A at nominal load
– Secondary current: 0.25 A
• SIMOCODE pro with 3UF7 100-1AA00-0 Current Measuring Module,
Set Current 0.3 to 3 A
This means:
– The secondary current of the current transformer is 0.25 A at the rated
load and is, therefore, not within the 0.3 A to 3 A setting range of the
Current Measuring Module used.
– The secondary current must be boosted by multiple looping of the
secondary cables through the through-hole openings of the Current
Measuring Module. Double-looping results in 2 x 0.25 A = 0.5 A.
– The Set Current Is to be parameterized in SIMOCODE pro is 0.5 A.
K1
Current Measuring
K2
Module 3UF 71 Basic Unit
K3 Setting Range: 3UF 70
L 0.3 A - 3 A
Fig. 13-20: Example (2 of 2) for current measuring with an 3UF18 external current transformer
Note
When using Basic Unit 2 (SIMOCODE pro V) from version *E03* onwards,
the Set Current does not have to be converted. It will correspond to the
rated current flowing on the main current side.
Additional entry of the transformation ratio of the current transformer
(interposing transformer) will result in automatic conversion in the device.
SIMOCODE pro
13-28 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
Warning:
Applies to system interfaces on Operator Panels and on door adapters (IP54
degree of protection):
When using for the first time, press the cover firmly against its stop in the
socket!
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-29
Mounting, Wiring, Interfaces
Fig. 13-21: Closing the system interface using the system interface cover on the door adapter
Fig. 13-22: Closing the system interface using the system interface cover on the Operator Panel
Fig. 13-23: Closing the system interface using the system interface cover on the Operator Panel
with Display
SIMOCODE pro
13-30 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
Example
The following figure shows an example of a SIMOCODE pro V installation:
Outgoing, to Outgoing, to
• Expansion Module • Expansion Module
• Operator Panel • Operator Panel
UF-01130
Incoming, from
• Basic Unit
SIMOCODE pro V
Basic Unit (BU2) Current Measuring
Module (IM)
Expansion Module
Cover
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-31
Mounting, Wiring, Interfaces
Notice
Only connect system interfaces when disconnected from voltage!
System
2 System
interfaces Memory Module,
interfaces
Connecting cable addressing plug
system interface cover
Current Measuring Modules
System
interface
Connecting cable
Removable terminals
System
interface
SIMOCODE pro
13-32 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
Step Description
1 Place the plug in the plug shaft, keeping it is as straight as possible. Ensure
that the catches on the plug shaft above the plug housing audibly click into
place.
For SIMOCODE pro C, the system interfaces on the bottom can only be
used for the Current Measuring Module!
2 Use the cover to close system interfaces that are not in use
1 3
Connecting
Cover cable
Safety Guidelines
Notice
For SIMOCODE pro C, the system interfaces on the bottom can only be
used for the Current Measuring Module!
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-33
Mounting, Wiring, Interfaces
Notice
Only a Current/Voltage Measuring Module may be connected to the system
interface on the right of the Decoupling Module. Memory Module,
addressing plugs or PC cables will not be recognized there.
Notice
Observe the color coding for the connection cable (see diagram)!
SIMOCODE pro
13-34 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
13.4.3 System Interfaces on the Operator Panel and the Operator Panel with
Display
Connecting cable
E.g. Memory Module
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-35
Mounting, Wiring, Interfaces
Sequence for connecting cables to the system interface of the Operator Panel and the
Operator Panel with Display
Proceed as follows:
Step Description
1 Place the plug in the plug shaft, keeping it is as straight as possible. Ensure
that the catches on the plug shaft above the plug housing audibly click into
place.
The incoming connecting cable is connected to the rear side.
2 Use the cover to close system interfaces that are not in use
Notice
In order to ensure IP54 degree of protection, press the cover firmly against
its stop in the socket when using for the first time (see figure!).
When mounting the Operator Panel using the screws provided, ensure the
tightening torque is not set too high.
Note
Throughout connection, you can place the cover on one of the two "park
positions" (see Fig. 13-29).
Notice
Observe the color coding for the connection cable (see diagram)!
SIMOCODE pro
13-36 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
Front
Rear
Catches
1
1
2
Catches 0
Color coding
Connecting cable
Fig. 13-29: Sequence for connecting cables to the system interface of the Operator Panel
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-37
Mounting, Wiring, Interfaces
Front
Cover
Park position
Rear
Fig. 13-30: Sequence for connecting cables to the system interface of the Operator Panel with
Display
SIMOCODE pro
13-38 GWA 4NEB 631 6050-22 DS 02
Mounting, Wiring, Interfaces
Notice
The 9-pole SUB-D connection is an alternative to the A/B terminals!
Step Description
1 Connect the PROFIBUS DP cable with the 9-pole SUB-D plug to the
PROFIBUS DP interface.
9-pole
SUB-D plug
PROFIBUS DP interface
9-pole SUB-D socket
PROFIBUS DP cable
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 13-39
Mounting, Wiring, Interfaces
Publisher:
PROFIBUS User Organization e. V.
Haid-und-Neu-Strasse 7
76131 Karlsruhe, Germany
SIMOCODE pro
13-40 GWA 4NEB 631 6050-22 DS 02
Commissioning and Service 14
In this chapter
In this chapter you will find information about how SIMOCODE pro is
commissioned, how components are replaced and how statistics are read.
Target groups
This chapter is addressed to the following target groups:
• Commissioners
• Technicians
• Maintenance and service personnel.
Necessary knowledge
You will require the following knowledge:
• General basic knowledge about SIMOCODE pro, e.g. from Chapter 1
• SIMOCODE ES software.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 14-1
Commissioning and Service
Warning
Dangerous electrical voltage! Can cause electric shock and burning. Ensure
the system and the device are disconnected from voltage before beginning
work.
Notice
Observe the information contained in the operating instructions.
Prerequisites
The following prerequisites must be fulfilled for commissioning and
servicing:
• SIMOCODE pro is already mounted and wired
• The motor is switched off.
Notes on parameterizing
You can parameterize SIMOCODE pro as follows:
• With the Memory Module in which the parameters of a Basic Unit have
already been saved. The Memory Module is plugged into the system
interface. If the Memory Module is connected to the system interface and
the supply voltage returns to the Basic Unit, the Basic Unit will be
automatically parameterized by the Memory Module. The parameters can
also be loaded into the Basic Unit from the Memory Module by briefly
pressing the Test/Reset button.
• With the SIMOCODE ES software via serial interface.
The PC/programming device is connected to the system interface with the
PC cable.
• With an automation system and/or SIMOCODE ES software via
PROFIBUS DP. For this, the PROFIBUS DP cable should be connected to the
PROFIBUS DP interface of the Basic Unit.
Commissioning options
There are two commissioning options:
1. Normal case: SIMOCODE pro has not yet been parameterized and still has
the factory settings:
When connected to PROFIBUS DP, the "bus" LED flashes green when a
DP-master is connected.
2. SIMOCODE pro has already been parameterized:
– The parameters have already been loaded into the Basic Unit.
– The parameters from a previous application still exist. Check whether
the parameters (e.g. the set current) apply to the new application.
Change these accordingly, if necessary.
SIMOCODE pro
14-2 GWA 4NEB 631 6050-22 DS 02
Commissioning and Service
14.2 Commissioning
14.2.1 Sequence
Step Description
1 Switch on the supply voltage. In a fault-free state, the following LEDS should
light up or flash green:
• "Device" (lights up)
• "Bus" if PROFIBUS DP is connected (lights up or flashes).
Continue with Step 2.
Otherwise, carry out diagnosis according to the LED display.
You will find further information in Chapter 14.2.3 "Diagnosis via LED Display".
Try to rectify the fault.
2 If you wish to make SIMOCODE pro available on the PROFIBUS DP, set the
PROFIBUS DP address. You will find further information about this in Chapter
"Setting the PROFIBUS DP Address" on Page 14-4.
Notice
For basic unit 1 (SIMOCODE pro C), only use the front system interface!
PC cable,
Order No. 3UF7940-0AA00-0
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 14-3
Commissioning and Service
Note:
This setting cannot be carried out if the Test/Reset button has been blocked.
Proceed as follows:
Step Description
Table 14-2: Setting the PROFIBUS DP address via the addressing plug
Step Description
SIMOCODE pro
14-4 GWA 4NEB 631 6050-22 DS 02
Commissioning and Service
The Basic Units and the Operating Panel have three LEDs for displaying
specific device states:
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 14-5
Commissioning and Service
14.3 Service
14.3.1 Preventive Maintenance
SIMOCODE pro
14-6 GWA 4NEB 631 6050-22 DS 02
Commissioning and Service
Saving parameters from the Basic Unit into the Memory Module
Note:
This function will not be available if the Test/Reset button has been blocked.
Proceed as follows:
Step Description
1 Plug the Memory Module into the system interface. The "Device" LED lights
up yellow for approx. 10 seconds. During this time, press the "Test/Reset"
button for approx. 3 seconds. The parameters will be saved in the Memory
Module. After successful data transfer, the "Device" LED flickers yellow for
approx. 3 seconds.
If necessary, unplug the Memory Module from the system interface.
Note:
This function will not be available if the Test/Reset button has been blocked.
Proceed as follows:
Step Description
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 14-7
Commissioning and Service
Saving parameters from the Memory Module into the Basic Unit
Note:
This function will not be available if the Test/Reset button has been blocked.
Proceed as follows:
Step Description
1 Plug the memory module into the system interface. The "Device" LED lights up
yellow for approx. 10 seconds. During this time, briefly press the "Test/Reset"
button. The parameters will be transferred to the Basic Unit. After successful
data transfer, the "Device" LED flickers yellow for approx. 3 seconds.
2 If necessary, unplug the Memory Module from the system interface.
Table 14-7: Saving parameters from the Memory Module into the Basic Unit
Notice
If the Memory Module is plugged in, the parameters will be transferred
from the Memory Module to the Basic Unit when the supply voltage is
switched on.
Step Description
SIMOCODE pro
14-8 GWA 4NEB 631 6050-22 DS 02
Commissioning and Service
Safety Guidelines
Warning
The main power for the feeder and the supply voltage for the Basic Unit
must be switched off before replacing Current Measuring Modules and
Current/Voltage Measuring Modules.
Notice
Please observe the information contained in the operating instructions!
Notice
It is not necessary to detach the wiring from the removable terminals to
replace the components!
Step Description
1 Save the parameters. See Chapter "Securing and Saving Parameters" on Page
14-7.
2 Switch off the main power for the feeder and the supply voltage for the Basic
Unit.
3 If necessary, pull the PC cable, the cover or the connecting cable out of the
system interface.
4 Remove the removable terminals. You do not need to detach the wiring.
5 Demount the Basic Unit.
6 Remove the removable terminals of the new Basic Unit.
7 Mount the new Basic Unit.
8 Plug in the wired removable terminals.
9 Plug the connecting cable into the system interface.
10 Switch on the supply voltage for the Basic Unit.
11 Save the parameters into the Basic Unit. See Chapter "Securing and Saving
Parameters" on Page 14-7.
12 Switch on the main power for the feeder.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 14-9
Commissioning and Service
Step Description
1 Switch off the main power for the feeder and the supply voltage for the Basic
Unit.
2 If necessary, pull the PC cable, the cover or the connecting cable out of the
system interface.
3 Remove the removable terminals. You do not need to detach the wiring.
4 Demount the Expansion Module or the Decoupling Module.
5 Remove the removable terminals of the new Expansion or Decoupling
Module.
6 Mount the new Expansion Module or Decoupling Module.
7 Plug in the wired removable terminals.
8 Plug the connecting cable into the system interface.
9 Switch on the supply voltage for the Basic Unit.
10 Switch on the main power for the feeder.
SIMOCODE pro
14-10 GWA 4NEB 631 6050-22 DS 02
Commissioning and Service
Replacing the Current Measuring Module and the Current/Voltage Measuring Module
Proceed as follows:
Step Description
1 Switch off the main power for the feeder and the supply voltage for the Basic
Unit.
3 Pull out the removable terminal from the module as illustrated below
(Current/Voltage Measuring Modules only).
4 Disconnect the three cables of the three phases of the main circuit.
5 Replace the module (see Chapter 13.2.2 "Current Measuring Modules" and
Chapter 13.2.3 "Current/Voltage Measuring Modules").
6 Connect the three cables of the main circuit, leading them through the
through-hole openings.
Table 14-11: Replacing the Current Measuring Module and the Current/Voltage Measuring Module
Upper terminals
Lower terminals
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 14-11
Commissioning and Service
With the factory settings, all parameters are reset to the factory values.
Resetting the factory settings with the Test/Reset button on the Basic Unit
Proceed as follows (also deletes any previous password setting!):
Step Description
Table 14-12: Resetting factory settings with the Test/Reset button on the Basic Unit
Notice
If any one of the steps is not carried out correctly, the Basic Unit will revert
to normal operation.
Notice
This function is always active, independent of the "Test/Reset - Button
Blocked" parameter.
Step Description
Table 14-13: Resetting the factory settings with the SIMOCODE ES software
SIMOCODE pro
14-12 GWA 4NEB 631 6050-22 DS 02
Commissioning and Service
Example:
Screenshot
Fig. 14-4: Example of event logging using the "SIMOCODE ES" software
SIMOCODE pro has an error buffer, in which the 21 most recent errors/
faults, "Mains On" events and time information are recorded. The time
information is based upon the operating hours of the device (resolution 1 s),
i.e. the amount of time that the device is supplied with control supply
voltage.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 14-13
Commissioning and Service
Example:
The most recent "Mains ON" event was logged at a device operating time of
17 days, 21 hours and 31 minutes. Therefore, at the moment of "Mains ON",
the device was operating (supplied with voltage) for 17d21h31min. The
"No. of Starts >" fault was logged at a device operating time of 18 days,
22 hours, 17 minutes, i.e. 24h 46min after the most recent "Mains ON".
SIMOCODE pro
14-14 GWA 4NEB 631 6050-22 DS 02
Alarm, Fault and System Events 15
In this chapter
In this chapter you will find information about troubleshooting.
Target groups
This chapter is addressed to the following target groups:
• Commissioners
• Maintenance and service personnel.
• Configurators
• PLC programmers.
Necessary knowledge
You will require the following knowledge:
• Basic general knowledge about SIMOCODE pro
• Knowledge about SIMOCODE ES software
• Knowledge about PROFIBUS DP.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 15-1
Alarm, Fault and System Events
Analog Module There is a wire break in the Check the Transducer Reset
Open Circuit Analog Value Measuring Circuit. and the Measuring
Circuit.
Configuration The configured device • Please check whether Rectify the Tripped
Fault configuration does not match the all configured fault; reset
existing configuration. components are
present.
• Check the actual
-configuration using
"Configuration".
Execution The motor feeder could not be • Main circuit is Reset Tripped
ON-Command turned on after an ON command interrupted (fuse,
is issued. circuit breaker)
• Motor Contactor or
Contactor Control is
defective
• Parameter Execution
Time is too short.
Execution The motor feeder could not be • The Contactor Contact Reset; counter Tripped
STOP-Command turned off after a STOP command is welded command
was issued. • Parameter Execution
Time is too short
• The "OPEN" End
Position has not been
reached during the
parameterized runtime
(only for the
"Positioner" and
"Solenoid Valve" control
functions).
External Earth External Earth-fault Monitoring Please check the motor Reset Tripped
Fault has activated. An impermissibly connection cable for
high Fault Current is flowing. damage.
External Fault A signal is pending at the Input Check the motor feeder According to Tripped
1, 2, 3, 4, 5 or 6 (socket) of the "External Fault 1, 2, parameterizatio
3, 4, 5 or 6" standard function. n
SIMOCODE pro
15-2 GWA 4NEB 631 6050-22 DS 02
Alarm, Fault and System Events
Feedback OFF The Current Flow in the motor • The main circuit has Reset Tripped
feeder has been interrupted been interrupted (fuse,
without the motor feeder being circuit breaker, main
turned off. switch).
• The Motor Contactor
or Contactor Control is
defective
Feedback ON Current is flowing in the motor • Contactor Contacts Reset; counter Tripped
feeder without the motor feeder have been manually command
being switched on activated
• Contactor has not been
switched on via
SIMOCODE
Hardware Faults The SIMOCODE pro basic device Please replace the Basic Rectify the fault Tripped
hardware is defective. Unit.
See Chapter 13
"Mounting, Wiring,
Interfaces".
Internal Earth Internal Earth-fault Monitoring Please check the motor Reset Tripped
Fault has been activated. connection cable for
An impermissibly high Fault damage.
Current is flowing.
Module Fault At least one SIMOCODE pro • The connecting cable Rectify the Tripped
module is not ready for use. is defective or has not fault; reset
been plugged in
correctly.
• Module is defective.
Please replace the
module.
For this, see
Chapter 13 "Mounting,
Wiring, Interfaces".
Motor Operating The configured Limit Value for the Please adopt the
Hours > Motor Operating Hours has been maintenance measures
exceeded. intended for the feeder.
Motor Stop The configured Limit Value for Please adopt the
Time > Motor Stop Time Monitoring has maintenance measures
been exceeded. intended for the feeder.
If possible, switch on the
feeder.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 15-3
Alarm, Fault and System Events
Overload The motor feeder has been Please check the motor Reset, auto- Tripped
overloaded. and the application that reset
is driven by the motor.
The motor can only be
switched on again after
the Cooling Down Period
has expired or after an
Emergency Start.
Overload and The motor feeder has been Check the motor feeder Reset or Tripped
Unbalance asymmetrically overloaded. and the motor. auto-reset
Possible causes: The motor can only be
• Phase Failure switched on again after
• Fault in the motor windings. the Cooling Down Period
has expired or after an
Emergency Start.
Parameter is The parameter data is faulty. The designation of the Rectify the Tripped
faulty ("General faulty parameter can be fault; reset
Fault" category) found via the number
(byte No.) in the system
manual, Chapter A
"Tables".
SIMOCODE pro
15-4 GWA 4NEB 631 6050-22 DS 02
Alarm, Fault and System Events
PhaseUnbalance The Limit Value for Phase Check the motor feeder Reset Tripped
Unbalance has been exceeded. A and the motor.
Phase Unbalance can cause an
overload.
Possible causes:
• Phase Failure
• Faults in the motor windings.
Stalled Positioner The Torque Switch has activated • The Positioner may be "OPEN/ Tripped
before or without the respective blocked. CLOSED"
Limit Switch. • Acknowledge the fault counter
via "Free-wheeling" command.
with the
"OPEN/CLOSED"
counter command.
• Please check the
Positioner application
and the Limit
Switches.
Stalled Rotor The Maximum Motor Current has Please check the Reset Tripped
exceeded the threshold for application that is being
Stalled Rotor Protection. driven by the motor.
Possible cause: The motor is
blocked.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 15-5
Alarm, Fault and System Events
Status - Cooling The motor feeder has been The motor can only be
Down Period switched off due to overload. switched on again after
active the Cooling Down Period
has expired.
Temperature Either a Short Circuit or a Wire Check the Temperature Rectify the Tripped
Module Sensor Break (Open Circuit) has occurred Sensor and the sensor fault; reset
Fault in the Temperature Sensor cable.
Circuit.
Test Position Current is flowing in the motor The main circuit is not Reset Tripped
Feedback (TPF) feeder although the motor feeder interrupted in test
is in the Test Position (TPF). operation.
SIMOCODE pro
15-6 GWA 4NEB 631 6050-22 DS 02
Alarm, Fault and System Events
Thermistor Open A wire break has occurred in the Check the Thermistor Rectify the Tripped
Circuit Thermistor Sensor Cable. Sensor Cable and the fault; reset
Thermistor.
Thermistor Short A Short Circuit has occurred in Check the Thermistor Rectify the Tripped
Circuit the Thermistor Sensor Cable. Sensor Cable and the fault; reset
Thermistor.
Thermistor Trip Thermistor Protection has been Please check the motor Reset or auto- Tripped
Level activated. The temperature of the and the application that reset
motor is too high. is driven by the motor.
The motor cannot be
switched back on until
the temperature has
reached the Switch-back
Point of the thermistor.
Trip - Bus PROFIBUS DP communication Check the PROFIBUS Reset, auto- Tripped
has been interrupted or is connection (plugs, reset
interrupted cables, etc.)
Trip - PLC/PCS The PLC controlling the feeder Please check the Reset, auto- Tripped
was or is in the STOP-state. operating state of the reset
PLC.
Trip Antivalence The Limit Switches are not • Limit Switch Open Counter Tripped
reporting any Antivalent Signals. Circuit command
• Please check the "OPEN/
Positioner application CLOSED"
and the Limit Switches
Trip End Pos. Positioner / Solenoid Valve has Acknowledge the fault Reset; counter Tripped
left the End Position without a via "Free-wheeling" with command
command being issued. The the counter command
motor feeder has been switched "OPEN/CLOSED".
off.
Trip Temporary One of the following components Please replace the Rectify the Tripped
Components is defective: defective components. fault; reset
(e.g. memory • Addressing plug For this, see
module) • Memory module Chapter 13 "Mounting,
• PC cable. Wiring, Interfaces".
Warning Level The Power Factor cos phi has Please check the
cos phi < undershot the Warning Level. application that is being
Possible cause: The motor is driven by the motor.
being operated without a load.
Warning Level I< The Maximum Current has Please check the
Undershot undershot the Warning Level. application that is being
driven by the motor.
Warning Level I> The Maximum Current has Please check the
Overshot overshot the Warning Level. application that is being
driven by the motor.
Warning Level P< The Active Power of the motor Please check the
Undershot has undershot the Warning Level. application that is being
driven by the motor.
Warning Level The Active Power of the motor Please check the
P> Overshot has overshot the Warning Level. application that is being
driven by the motor.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 15-7
Alarm, Fault and System Events
Warning Level U< The Voltage in the motor feeder Check the motor feeder.
Undershot has undershot the Warning Level.
Possible causes:
• Undervoltage in the network
• Fuse has tripped.
Warning Level The measured value at the Analog Check the Measuring
0/4 - 20 mA< Input has undershot the Warning Station.
Undershot Level.
Warning Level The measured value at the Analog Check the Measuring
0/4 - 20 mA> Input has overshot the Warning Station.
Overshot Level.
Wrong Password SIMOCODE pro parameters are Please use the correct
protected by a password. password for changing
An attempt has been made to the parameters.
change the parameters without If you do not know the
entering the password. password, new
parameters can only be
entered after the factory
settings have been
restored.
For a description of
factory settings, please
refer to Chapter 14.3.4
"Resetting the Factory
Settings".
SIMOCODE pro
15-8 GWA 4NEB 631 6050-22 DS 02
Tables A
In this chapter
In this chapter you will find various tables which can help you when working
with SIMOCODE pro.
Target groups
This chapter is addressed to the following target groups:
• Configurators.
Necessary knowledge
You will require the following knowledge:
• Thorough knowledge of SIMOCODE pro.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 A-1
A-2
A.1
Tables
Lamp control
QLE<< QLE< QLA QLE> QLE>>
Specification/ Control station Contactor control
(ON<<) (ON<) (OFF) (ON>) (ON>>)
Control function
Status signal
ON<< ON< OFF ON> ON>> QE1 QE2 QE3 QE4 QE5 ON<< ON< OFF ON> ON>>
Overload 1),2) - - - - - - - Active - - - - - - -
Direct starter 1),2) - - OFF ON - ON - - - - - OFF ON -
Reversing starter 1),2) - Left OFF Right - Right Left - - - Left OFF Right -
Circuit breaker 1),2) - - OFF ON - ON - OFF - - - - OFF ON -
impulse impulse
Star-delta - - OFF ON - Star Delta Network - - - - OFF ON -
starter 2) contactor contactor contactor
Star-delta starter Left OFF Right - Star Delta Right Left - Left OFF Right -
with reversal of the direction contactor contactor network network
of rotation 2) contactor contactor
Dahlander 2) - - OFF Slow Fast Fast Slow Fast - - - - OFF Slow Fast
star
contactor
Dahlander Left Left OFF Right Right Right Right Fast Left Left Left Left OFF Right Right
with reversal of the direction fast slow slow fast fast slow star slow fast fast slow slow fast
of rotation 2) contactor
Pole-changing switch 2) - - OFF Slow Fast Fast Slow - - - - - OFF Slow Fast
Pole-changing switch Left Left OFF Right Right Right Right - Left Left Left Left OFF Right Right
with reversing the direction fast slow slow fast fast slow slow fast fast slow slow fast
of rotation 2)
Valve 2) - - Closed Open - Open - - - - - - Closed Open -
Positioner 1 2) - Closed Stop Open - Open Closed - - - - Closed Stop Open -
Positioner 2 2) - Closed Stop Open - Open Closed - - - - Closed Stop Open -
Positioner 3 2) - Closed Stop Open - Open Closed - - - - Closed Stop Open -
Positioner 4 2) - Closed Stop Open - Open Closed - - - - Closed Stop Open -
Positioner 5 2) - Closed Stop Open - Open Closed - - - - Closed Stop Open -
Soft starter 2) - - OFF ON - ON - Reset ON - - - OFF ON -
Status Information for the Control Functions
network command
contactor
Soft starter with reversing - Left OFF Right - Right Left Reset ON - - Left OFF Right -
contactor 2) network- network- command
Table A-1: Active control stations, contactor/lamp controls and status information for control functions
contactor contactor
Abbreviation Meaning
OP Operator Panel
AM Analog Module
EM Earth-Fault Module
TM Temperature Module
Th Thermistor
CF Control Function
Cycl. Cyclic
Acycl. Acyclic
S Trip
M Event
W Warning
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 A-3
Tables
Specifications
The following specifications apply in the tables:
Example
SIMOCODE pro
A-4 GWA 4NEB 631 6050-22 DS 02
Tables
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 A-5
Tables
SIMOCODE pro
A-6 GWA 4NEB 631 6050-22 DS 02
Tables
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 A-7
Tables
SIMOCODE pro
A-8 GWA 4NEB 631 6050-22 DS 02
Tables
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 A-9
Tables
SIMOCODE pro
A-10 GWA 4NEB 631 6050-22 DS 02
Tables
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 A-11
Tables
SIMOCODE pro
A-12 GWA 4NEB 631 6050-22 DS 02
Tables
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 A-13
Tables
SIMOCODE pro
A-14 GWA 4NEB 631 6050-22 DS 02
Tables
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 A-15
Tables
SIMOCODE pro
A-16 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records B
In this chapter
In this chapter you will find information about the data records of
SIMOCODE pro.
Target groups
This chapter is addressed to the following target groups:
• Configurators
• PLC programmers.
Necessary knowledge
You will require the following knowledge:
• good knowledge about writing and reading data records
• good knowledge of SIMOCODE pro.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-1
Data Formats and Data Records
SIMOCODE pro
B-2 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
Further information
You will find further information on the SFBs
• in the "System Software for S7-300/400, System and Standard Functions"
reference manual
• in the STEP7 online help.
Byte arrangements
When data which is longer than one byte is saved, the bytes are arranged as
follows ("big endian"):
Byte 0 Byte 0
Byte
Byte 1 Byte 1
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-3
Data Formats and Data Records
B.1.2 Abbreviations
Abbreviation Meaning
B.1.3 Specifications
Example
SIMOCODE pro
B-4 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-5
Data Formats and Data Records
SIMOCODE pro
B-6 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
The unit of the measured value is dependent on the assigned analog value.
You will find all the available analog values with their units in
Chapter A.4 "Socket Assignment Table - Analog".
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-7
Data Formats and Data Records
SIMOCODE pro
B-8 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
Timestamp
The operating hours of the device are used as a timestamp (resolution: 1 s).
Type/error number
If the type has the value 71, the entry contains a fault: Refer to the error
numbers for detailed information: You will find the meaning in the "Error
number" column of "Data Record 92 - Diagnostics" in Chapter B.7 "Data
Record 92 - Device Diagnosis".
If the type has the value 255, the entry displays "Power ON". In this case,
the error number contains the number of power ON operations, reduced
by 1 (0 = 1x Power ON, ...).
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-9
Data Formats and Data Records
SIMOCODE pro
B-10 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-11
Data Formats and Data Records
SIMOCODE pro
B-12 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-13
Data Formats and Data Records
SIMOCODE pro
B-14 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
*) The "DP Diagn." column contains the bits which are additionally available
in the diagnosis using PROFIBUS DP:
• S: Trip
• M: Event
• W: Warning
• F9, F16:Error types
See also Chapter A.5 "Detailed Events of the Slave Diagnostics".
**) Event - prm error number (bytes):
If parameterization is not possible, the number of the parameter group (prm
group) which caused the error is transmitted here. You will find the
parameter groups in the parameter data records 130 to 133.
Byte.Bit Designation
(Prm group)
0.0 Reserved
4.0 Device Configuration
(see above) (12) Parameter group 12
...
***) See "Error number" in Chapter B.6 "Data Record 72 - Error Buffer".
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-15
Data Formats and Data Records
1) S7 format:
0/4 mA = 0
20 mA = 27648
2) Representation of the "Thermal Motor Model":
Value always refers to Symm. Trip Level,
Representation in 2% increments in bits 6..0 (range 0 to 254%),
bit 7 shows unbalance (fixed level 50%).
3) Representation in Kelvin.
SIMOCODE pro
B-16 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
Additional abbreviations
r/w: value can be written/changed
r: value can only be read
Byte.Bit Designation Type Range Unit Informati
on
0.0 Reserved Byte[4] 0
4.0 Permissible Starts - Actual Value Byte 0 .. 255 r1) BU1 BU2
5.0 Reserved Byte
8.0 Number of Parameterizations Word 0 .. 65535 r BU1 BU2
10.0 Number of Overload Trips Word 0 .. 65535 r/w BU1 BU2
12.0 Number of Internal Overload Trips Word 0 .. 65535 r BU1 BU2
14.0 Motor Stop Time Word 0 .. 65535 1h r/w BU1 BU2
16.0 Timer 1 - Actual Value Word 0 .. 65535 100 ms r BU1 BU2
18.0 Timer 2 - Actual Value Word 0 .. 65535 100 ms r BU1 BU2
20.0 Timer 3 - Actual Value Word 0 .. 65535 100 ms r BU2
22.0 Timer 4 - Actual Value Word 0 .. 65535 100 ms r BU2
24.0 Counter 1 - Actual Value Word 0 .. 65535 r BU1 BU2
26.0 Counter 2 - Actual Value Word 0 .. 65535 r BU1 BU2
28.0 Counter 3 - Actual Value Word 0 .. 65535 r BU2
30.0 Counter 4 - Actual Value Word 0 .. 65535 r BU2
32.0 Reserved Byte
40.0 Motor Operating Hours D-Word 0 .. 0xFFFFFFFF 1s r/w BU1 BU2
44.0 Int. Motor Operating Hours D-Word 0 .. 0xFFFFFFFF 1s r BU1 BU2
48.0 Device Operating Hours D-Word 0 .. 0xFFFFFFFF 1s r BU1 BU2
52.0 Number of Starts D-Word 0 .. 0xFFFFFFFF r/w BU1 BU2
56.0 Internal Number of Starts Right D-Word 0 .. 0xFFFFFFFF r BU1 BU2
60.0 Internal Number of Starts Left D-Word 0 .. 0xFFFFFFFF r BU1 BU2
64.0 Consumed Energy D-Word 0 .. 0xFFFFFFFF 1 kWh r/w UM
68.0 Reserved Byte[8]
Table B-10: Data Record 95 - Diagnosis - Statistical data
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-17
Data Formats and Data Records
SIMOCODE pro
B-18 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-19
Data Formats and Data Records
SIMOCODE pro
B-20 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-21
Data Formats and Data Records
1) Value range dependent on current range of the IM/UM and the conversion factor
SIMOCODE pro
B-22 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-23
Data Formats and Data Records
SIMOCODE pro
B-24 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-25
Data Formats and Data Records
SIMOCODE pro
B-26 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-27
Data Formats and Data Records
SIMOCODE pro
B-28 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-29
Data Formats and Data Records
SIMOCODE pro
B-30 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-31
Data Formats and Data Records
1) Value range dependent on current range of the IM/UM and the conversion factor
SIMOCODE pro
B-32 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-33
Data Formats and Data Records
SIMOCODE pro
B-34 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-35
Data Formats and Data Records
SIMOCODE pro
B-36 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
Notice
Only the address is relevant for writing. The baud rate is recognized
automatically. The current baud rate is read.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-37
Data Formats and Data Records
SIMOCODE pro
B-38 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-39
Data Formats and Data Records
SIMOCODE pro
B-40 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-41
Data Formats and Data Records
SIMOCODE pro
B-42 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-43
Data Formats and Data Records
Table B-24: Assignment of Cyclic Receive/Send Data - Molded Case Circuit Breaker (MCCB)
SIMOCODE pro
B-44 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-45
Data Formats and Data Records
SIMOCODE pro
B-46 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
B.20.7 Dahlander
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-47
Data Formats and Data Records
SIMOCODE pro
B-48 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-49
Data Formats and Data Records
SIMOCODE pro
B-50 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-51
Data Formats and Data Records
B.20.12 Positioner
SIMOCODE pro
B-52 GWA 4NEB 631 6050-22 DS 02
Data Formats and Data Records
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 B-53
Data Formats and Data Records
Table B-34: Assignment of Cyclic Receive/Send Data - Soft Starter with Reversing Contactor
SIMOCODE pro
B-54 GWA 4NEB 631 6050-22 DS 02
Dimension Drawings C
In this chapter
This chapter contains the technical dimension drawings of the
SIMOCODE pro system components.
Target groups
This chapter is addressed to the following target groups:
• Configurators
• Technicians.
Necessary knowledge
You will require the following knowledge:
• Thorough knowledge of switchgear configuration.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 C-1
Dimension Drawings
12
106
80
5
45 5 36
86 4
45 5 65
115 4
SIMOCODE pro
C-2 GWA 4NEB 631 6050-22 DS 02
Dimension Drawings
84
45 5 40
7,5
T3 T1
38
T2
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 C-3
Dimension Drawings
94
55 5 67
14
T1
T3
65
T2
SIMOCODE pro
C-4 GWA 4NEB 631 6050-22 DS 02
Dimension Drawings
120
95
79
95
7 5 140
78
25
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 C-5
Dimension Drawings
120
95
37 17
9
119
95
79
7 5 47
140
84
SIMOCODE pro
C-6 GWA 4NEB 631 6050-22 DS 02
Dimension Drawings
145
50 25
11
57
147
122
125 85
9
60,5 6
148
60,5
6
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 C-7
Dimension Drawings
45
85
21
5
7
31
11
66
SIMOCODE pro
C-8 GWA 4NEB 631 6050-22 DS 02
Dimension Drawings
55
94
20
5
12
23
60
92
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 C-9
Dimension Drawings
SIMOCODE pro
C-10 GWA 4NEB 631 6050-22 DS 02
Dimension Drawings
37 9 17 79
Ø
119
79
95
95 5 47
140
120
3
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 C-11
Dimension Drawings
48 25
1
Ø1
88
147
122
1
125 Ø1
32
67
149
145
6
SIMOCODE pro
C-12 GWA 4NEB 631 6050-22 DS 02
Dimension Drawings
96
27,9
29
36
8,9
32,3
41,1
26 20,7
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 C-13
Dimension Drawings
10
92
68
22,5 5 115 4
15
110
Versions:
• 3UF73 Digital Modules
• 3UF7500 Earth-fault Module
• 3UF7700 Temperature Module
• 3UF7400 Analog Module
• 3UF715 Decoupling Module
SIMOCODE pro
C-14 GWA 4NEB 631 6050-22 DS 02
Dimension Drawings
C.6 Accessories
C.6.1 Door Adapter
IP54
37 24.5+0.5
ø3
R2
.4
Ø
±0
3
.1
13.5+0.5
17 37±0.1
46
IP54
26.5+0.5
R2
ø3
39
.4
13.5+0.5
37
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 C-15
Dimension Drawings
SIMOCODE pro
C-16 GWA 4NEB 631 6050-22 DS 02
Technical Data D
In this chapter
This chapter contains information about SIMOCODE pro technical data.
Target groups
This chapter is addressed to the following target groups:
• Configurators.
Necessary knowledge
You will require the following knowledge:
• Thorough knowledge of switchgear configuration
• Thorough knowledge of SIMOCODE pro.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 D-1
Technical Data
SIMOCODE pro
D-2 GWA 4NEB 631 6050-22 DS 02
Technical Data
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 D-3
Technical Data
Relay Outputs:
• Number 3 monostable Relay Outputs
• Auxiliary Contacts of the The isolated NO contacts (NC contact response
3 Relay Outputs parameterizable via Internal Signal Conditioning), 2 Relay
Outputs with common root, one Relay Output separate, freely-
assignable to control functions (e.g. Network, Star or Delta
Contactor or Signaling of the Operating State)
• Mandatory Short-circuit Protection • Fuse link, operating class gL/gG 6 A, fast-acting 10 A
for Auxiliary Contacts (Relay (IEC 60947-5-1)
Outputs) • Miniature circuit breaker 1.6 A, C-characteristic
(IEC 60947-5-1)
• Miniature circuit breaker 6 A, C-characteristic (Ik < 500 A)
• Rated Uninterrupted Current 5A
6 A at max. +50 °C
• Rated Switching Capacity AC-15 6 A / 24 V AC 6 A / 120 V AC 3 A / 230 V AC
DC-13 2 A / 24 V DC 0.55 A / 60 V DC 0.25 A / 125 V DC
Inputs (binary) 4 inputs with a common root that are supplied via the device
electronics (24 V DC) for measuring process signals (e.g. Local
Control Station, Key-operated Switch, Limit Switch, etc.),
freely-assignable to control functions.
• 24 V DC
Cable lengths (single) 300 m
Input characteristic Type 1 accord. to EN 61131-2
Thermistor Motor Protection
(PTC binary)
• Total Cold Resistance < 1.5 kOhm
• Response Value 3.4 kOhm - 3.8 kOhm
• Return Value 1.5 kOhm - 1.65 kOhm
• Cable lengths Cross section:2.5 mm2 Length:2 x 250 m
1.5 mm2 2 x 150 m
0.5 mm2 2 x 50 m
Connection
• Tightening torque TORQUE: 7 LB.IN - 10.3 LB.IN
0.8 Nm - 1.2 Nm
• Connection cross sections:
- Solid 2 x 0.5 mm2 - 2.5 mm2 / 1 x 0.5 mm2 - 4 mm2
2 x AWG 20 to 14 / 1 x AWG 20 to 12
- Finely stranded, with end sleeves 2 x 0.5 mm2 - 1.5 mm2 / 1 x 0.5 mm2 - 2.5 mm2
2 x AWG 20 to 16 / 1 x AWG 20 to 14
SIMOCODE pro
D-4 GWA 4NEB 631 6050-22 DS 02
Technical Data
Mounting
• Set Current le = 0.3 A - 3 A; Snap-on mounting onto 35-mm standard mounting rails or
2.4 A - 25 A; 10 A - 100 A screw attachment via additional plug-in lugs
(3UF71.0, 3UF71.1, 3UF71.2)
• Set Current ls = 20 A - 200 A Snap-on mounting onto 35-mm standard mounting rails, screw
(3UF7103, 3UF7 113) attachment onto the mounting plate or direct mounting to the
contactor
• Set Current ls = 63 A - 630 A Screw attachment to the mounting plate or direct mounting to
(3UF7103, 3UF7 114) the contactor
System interface for connection to a Basic Unit or Decoupling Module
Main Circuit
• Set Current Is 3UF71.0: 0.3 A - 3 A 3UF71.1: 20 A - 200 A
3UF71.1:2.4 A - 25 A 3UF71.1: 63 A - 630 A
3UF71.1: 10 A - 100 A
• Rated Insulation Voltage Ui (at 690 V 1)
Degree of Pollution 3)
• Rated Operational Voltage Ue 690 V
• Rated Impulse Withstand Voltage 6 kV 2)
Uimp
• Rated Frequency 50/60 Hz
• Type of current Three-phase current
• Short circuit Additional Short-circuit Protection in Main Circuit
required 3)
• Accuracy of Current Measuring +/- 3 %
(ranging from 1 times the
minimum Set Current Imin to
8 times the maximum Set Current
Imax)
Typical measuring range of the
Voltage Measuring
• Phase-to-phase voltage / line-to- 110 V - 690 V (only the phase voltages are available in the
line voltage (e.g. UL1L2) system as measured values)
• Phase voltage (e.g. UL1) 65 V - 400 V
Accuracy of
• voltage measuring in the range +/- 3 % (typical)
230 V - 400 V
• cos phi measurement (in the +/- 5 % (typical)
nominal load range cos phi =
0.4 ... 0.8) +/- 5 % (typical)
• apparent power measurement (in
the nominal load range)
1) for 3UF7103 and 3UF7104 up to 1000 V
2) for 3UF7103 and 3UF7104 up to 8 kV
3) More information can be found at http://www.siemens.com/simocode and Chapter D.7 "Short-Circuit Protection
with Fuses for Motor Feeders for Short-Circuit Currents up to 50 kA and 690 V" on Page D-14.
4) Screw connection is possible with an appropriate 3RT19... box terminal.
5) When connecting cable lugs complying with DIN 46235 to cables with a cross section larger than 95 mm2, the
3RT19 56-4EA1 terminal cover is required to maintain phase separation.
6) When connecting cable lugs complying with DIN 46234 to cables with a cross section larger than 240 mm 2 and
when connecting cable lugs complying with DIN 46235 to cables with a cross section larger than 185 mm2, the
3RT19 56-4EA1 terminal cover is required to maintain phase separation.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 D-5
Technical Data
SIMOCODE pro
D-6 GWA 4NEB 631 6050-22 DS 02
Technical Data
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 D-7
Technical Data
SIMOCODE pro
D-8 GWA 4NEB 631 6050-22 DS 02
Technical Data
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 D-9
Technical Data
SIMOCODE pro
D-10 GWA 4NEB 631 6050-22 DS 02
Technical Data
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 D-11
Technical Data
SIMOCODE pro
D-12 GWA 4NEB 631 6050-22 DS 02
Technical Data
• 4 green LEDs For freely-assigning any status signals (preferably for feedback
on the switching state, e.g. ON, OFF, LEFT, RIGHT)
Display Graphic display of present measured values, operating and
diagnosis data or status information
Buttons
• Control buttons • Control of the motor feeder, freely assignable
• Arrow keys • Navigation in the display menu
• Softkeys • Various functions, depending upon the menu, e.g. Test, Reset,
operation of Memory Module and Addressing Plug
System interfaces
• Front For connecting a Memory Module, an Addressing Plug or a PC-
Cable for parameterization purposes
• Rear Connection to the Basic Unit or expansion module
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 D-13
D-14
D.7
690V 415V
Technical Data
Short-circuit protection with Fuses for Motor Feeders Fast fuse links 3) British
for Short-circuit Currents up to 50kA and 690V
NH Type 3NA Type 3ND Standards
for 3UF7 and 3RB22/3RB23 inclusive Current Measuring Module 3RB29
DIAZED Type 5SB aM Fuses
NEOZED Type 5SE BS88
Overload relay Contactor CLASS Overload relay Contactor CLASS Overload relay Contactor Operating class
Setting range 5 and10 15 *) 3UF7 only 20 25 *) 3UF7 only Setting range 30 35 *) 3UF7 only 40 *) 3UF7 only Setting range gL(gG)
5)
(Type) Rated operating current Ie/AC-3 in A for (Type) Rated operating current Ie/AC-3 in A for (Type) Type of coordination
400V / 500V / 690V 400V / 500V / 690V 400V / 500V / 690V 400V / 500V / 690V 400V / 500V / 690V 400V / 500V / 690V 400V / 500V / 690V 1 2 2 2
0.3 - 3.0A 3RT1015 3,0 / 3,0 / 3,0 3,0 / 3,0 / 3,0 3,0 / 3,0 / 3,0 3,0 / 3,0 / 3,0 0.3 - 3.0A 3RT1015 3,0 / 3,0 / 3,0 3,0 / 3,0 / 3,0 3,0 / 3,0 / 3,0 0.3 - 3.0A 3RT1015 35 20 20
3RT1016 3,0 / 3,0 / 3,0 3,0 / 3,0 / 3,0 3,0 / 3,0 / 3,0 3,0 / 3,0 / 3,0 3RT1016 3,0 / 3,0 / 3,0 3,0 / 3,0 / 3,0 3,0 / 3,0 / 3,0 3RT1016 35 20 20
2.4 - 25A 3RT1015 7,0 / 5,0 / 4,0 7,0 / 5,0 / 4,0 7,0 / 5,0 / 4,0 7,0 / 5,0 / 4,0 2.4 - 25A 3RT1015 7,0 / 5,0 / 4,0 7,0 / 5,0 / 4,0 7,0 / 5,0 / 4,0 2.4 - 25A 3RT1015 35 20 20
3RT1016 9,0 / 6,5 5,2 9,0 / 6,5 5,2 9,0 / 6,5 5,2 9,0 / 6,5 5,2 3RT1016 9,0 / 6,5 5,2 9,0 / 6,5 / 5,2 8,5 / 6,5 5,2 3RT1016 35 20 20
3RT1017 12,0 / 9,0 / 6,3 11,0 / 9,0 / 6,3 10,0 / 9,0 / 6,3 9,5 / 9,0 / 6,3 3RT1017 9,0 / 9,0 / 6,3 9,0 / 9,0 / 6,3 8,5 / 8,5 / 6,3 3RT1017 35 20 20
3RT1023 9,0 / 6,5 / 5,2 9,0 / 6,5 / 5,2 9,0 / 6,5 / 5,2 3RT1023 3RT1023 63 25 25
3RT1024 12,0 / 12,0 / 9,0 12,0 / 12,0 / 9,0 12,0 / 12,0 / 9,0 12,0 / 12,0 / 9,0 3RT1024 12,0 / 12,0 / 9,0 12,0 / 12,0 / 9,0 12,0 / 12,0 / 9,0 3RT1024 63 25 20 25
3RT1025 17,0 / 17,0 / 13,0 17,0 / 17,0 / 13,0 16,0 / 16,0 / 13,0 15,0 / 15,0 / 13,0 3RT1025 14,0 / 14,0 / 13,0 13,0 / 13,0 / 13,0 12,0 / 12,0 / 12,0 3RT1025 63 25 20 25
3RT1026 25,0 / 18,0 / 13,0 18,0 / 18,0 / 13,0 16,0 / 16,0 / 13,0 15,0 / 15,0 / 13,0 3RT1026 14,0 / 14,0 / 13,0 13,0 / 13,0 / 13,0 12,0 / 12,0 / 12,0 3RT1026 100 35 20 25
3RT1034 25,0 / 25,0 / 20,0 25,0 / 25,0 / 20,0 22,3 / 22,3 / 20,0 20,3 / 20,3 / 20,3 3RT1034 19,1 / 19,1 / 19,1 17,6 / 17,6 / 17,6 16,1 / 16,1 / 16,1 3RT1034 125 63 50 63
3RT1035 25,0 / 25,0 / 24,0 25,0 / 25,0 / 24,0 25,0 / 25,0 / 24,0 25,0 / 25,0 / 24,0 3RT1035 25,0 / 25,0 / 24,0 25,0 / 25,0 / 24,0 23,5 / 23,5 / 23,5 3RT1035 125 63 50 63
10-100A 3RT1034 32,0 / 32,0 / 20,0 25,5 / 25,5 / 20,0 22,3 / 22,3 / 20,0 20,3 / 20,3 / 20,0 10-100A 3RT1034 19,1 / 19,1 / 19,1 17,6 / 17,6 / 17,6 16,1 / 16,1 / 16,1 10-100A 3RT1034 125 63 50 63
3RT1035 40,0 / 40,0 / 24,0 33,0 / 33,0 / 24,0 29,4 / 29,4 / 24,0 28,0 / 28,0 / 24,0 3RT1035 26,5 / 26,5 / 24,0 25,0 / 25,0 / 24,0 23,5 / 23,5 / 23,5 3RT1035 125 63 50 80
3RT1036 50,0 / 50,0 / 24,0 38,5 / 38,5 / 24,0 32,7 / 32,7 / 24,0 29,4 / 29,4 / 24,0 3RT1036 26,5 / 26,5 / 24,0 25,0 / 25,0 / 24,0 23,5 / 23,5 / 23,5 3RT1036 160 80 50 80
3RT1044 65,0 / 65,0 / 47,0 56,0 / 56,0 / 47,0 49,0 / 49,0 / 47,0 45,0 / 45,0 / 45,0 3RT1044 41,7 / 41,7 / 41,7 38,2 / 38,2 / 38,2 34,5 / 34,5 / 34,5 3RT1044 200 125 63 125
3RT1045 80,0 / 80,0 / 58,0 61,0 / 61,0 / 58,0 53,0 / 53,0 / 53,0 47,0 / 47,0 / 47,0 3RT1045 45,0 / 45,0 / 45,0 43,0 / 43,0 / 43,0 40,0 / 40,0 / 40,0 3RT1045 200 160 80 160
3RT1046 95,0 / 95,0 / 58,0 69,0 / 69,0 / 58,0 59,0 / 59,0 / 58,0 53,0 / 53,0 / 53,0 3RT1046 50,0 / 50,0 / 50,0 47,0 / 47,0 / 47,0 44,0 / 44,0 / 44,0 3RT1046 200 160 100 160
3RT1054 100,0 / 100,0 / 100,0 93,2 / 93,2 / 93,2 81,7 / 81,7 / 81,7 74,8 / 74,8 / 74,8 3RT1054 69,0 / 69,0 / 69,0 63,0 / 63,0 / 63,0 57,0 / 57,0 / 57,0 3RT1054 355 315 160 250
3RT1055 100,0 / 100,0 / 100,0 100,0 / 100,0 / 100,0 97,5 / 97,5 / 97,5 3RT1055 90,0 / 90,0 / 90,0 82,0 / 82,0 / 82,0 74,0 / 74,0 / 74,0 3RT1055 355 315 200 315
20-200A 3RT1054 115,0 / 115,0 / 115,0 93,2 / 93,2 / 93,2 81,7 / 81,7 / 81,7 74,8 / 74,8 / 74,8 20-200A 3RT1054 69,0 / 69,0 / 69,0 64,0 / 64,0 / 64,0 20-200A 3RT1054 355 315 160 250
3RT1055 150 / 150 / 150 122 / 122 / 122 107 / 107 / 107 98 / 98 / 98 3RT1055 90 / 90 / 90 82 / 82 / 82 74 / 74 / 74 3RT1055 355 315 200 315
3RT1056 185 / 185 / 170 150 / 150 / 150 131 / 131 / 131 120 / 120 / 120 3RT1056 111 / 111 / 111 102 / 102 / 102 93 / 93 / 93 3RT1056 355 315 200 315
63-630A 3RT1064 225 / 225 / 225 182 / 182 / 182 160 / 160 / 160 146 / 146 / 146 63-630A 3RT1064 135 / 135 / 135 126 / 126 / 126 63-630A 3RT1064 500 400 250 400
3RT1065 265 / 265 / 265 215 / 215 / 215 188 / 188 / 188 172 / 172 / 172 3RT1065 159 / 159 / 159 146 / 146 / 146 133 / 133 / 133 3RT1065 500 400 315 400
3RT1066 300 / 300 / 280 243 / 243 / 243 213 / 213 / 213 195 / 195 / 195 3RT1066 180 / 180 / 180 165 / 165 / 165 150 / 150 / 150 3RT1066 500 400 315 400
3RT1075 400 / 400 / 400 324 / 324 / 324 284 / 284 / 284 260 / 260 / 260 3RT1075 240 / 240 / 240 220 / 220 / 220 200 / 200 / 200 3RT1075 630 500 400 450
3RT1076 500 / 500 / 450 405 / 405 / 405 355 / 355 / 355 325 / 325 / 325 3RT1076 300 / 300 / 300 275 / 275 / 275 250 / 250 / 250 3RT1076 630 500 500 500
3RT1264 225 / 225 / 225 225 / 225 / 225 225 / 225 / 225 194 / 194 / 194 3RT1264 173 / 173 / 173 152 / 152 / 152 131 / 131 / 131 3RT1264 500 500 400 450
3RT1265 265 / 265 / 265 265 / 265 / 265 265 / 265 / 265 228 / 228 / 228 3RT1265 204 / 204 / 204 180 / 180 / 180 156 / 156 / 156 3RT1265 500 500 400 450
3RT1266 300 / 300 / 300 300 / 300 / 300 300 / 300 / 300 258 / 258 / 258 3RT1266 231 / 231 / 231 204 / 204 / 204 177 / 177 / 177 3RT1266 500 500 400 450
3RT1275 400 / 400 / 400 400 / 400 / 400 400 / 400 / 400 344 / 344 / 344 3RT1275 316 / 316 / 316 3RT1275 800 800 630 800
3RT1276 500 / 500 / 500 500 / 500 / 500 500 / 500 / 500 430 / 430 / 430 3RT1276 385 / 385 / 385 340 / 340 / 340 316 / 316 / 316 3RT1276 800 800 630 800
2)
3TF68 630 / 630 / 630 502 / 502 / 502 440 / 440 / 440 408 / 408 / 408 3TF68 2) 376 / 376 / 376 344 / 344 / 344 317 / 317 / 317 3TF68 2) 800 5004) 630 500
2) 2)
3TF69 630 / 630 / 630 630 / 630 / 630 572 / 572 / 572 531 / 531 / 531 3TF69 500 / 500 / 500 469 / 469 / 469 438 / 438 / 438 3TF69 2) 800 6304) 630 630
1) Can be mounted on contactors (after demounting the box terminal block). 1) Can be mounted on contactors (after demounting the box terminal block). 1) Can be mounted on contactors (after demounting the box terminal block).
2) Cannot be mounted on contactors. 2) Cannot be mounted on contactors. 2) Cannot be mounted on contactors.
3) Observe operating voltage. 3) Observe operating voltage. 3) Observe operating voltage.
4) Ensure that the safety margin between the maximum AC-3 operating current and the fuse rating is sufficient 4) Ensure that the safety margin between the maximum AC-3 operating current and the fuse rating is sufficient. 4) Ensure that the safety margin between the maximum AC-3 operating current and the fuse rating is sufficient.
5) Assignment and short-circuit devices according IEC60947-4-1. 5) Assignment and short-circuit devices according IEC60947-4-1. 5) Assignment and short-circuit devices according IEC60947-4-1.
Type of coordination "1": Contactors and starters may not endanger either persons or systems in the event of a short circuit. Type of coordination "1": Contactors and starters may not endanger either persons or systems in the event of a short circuit. Type of coordination "1": Contactors and starters may not endanger either persons or systems in the event of a short circuit.
They are not suitable for further operation until they have been repaired or the respective parts have been replaced. They are not suitable for further operation until they have been repaired or the respective parts have been replaced. They are not suitable for further operation until they have been repaired or the respective parts have been replaced.
Type of coordination "2": Contactors and starters may not endanger either persons or systems in the event of a short circuit and must be suitable Type of coordination "2": Contactors and starters may not endanger either persons or systems in the event of a short circuit and must be suitable Type of coordination "2": Contactors and starters may not endanger either persons or systems in the event of a short circuit and must be suitable
for further operation. There is danger of contact welding. for further operation. There is danger of contact welding. for further operation. There is danger of contact welding.
for Short-Circuit Currents up to 50 kA and 690 V
Short-Circuit Protection with Fuses for Motor Feeders
1) Based upon a typical hardware set-up: Basic Unit + Current Measuring Module + 2 expansion modules
Example:
You wish to switch a relay output of the Basic Unit via PROFIBUS when the
"remote" bit is set:
• SIMOCODE pro C:
Reaction time = 30 ms + 30 ms + 10 ms = 70 ms
• SIMOCODE pro V:
Reaction time = 5 ms + 5 ms + 10 ms = 20 ms
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 D-15
Technical Data
SIMOCODE pro
D-16 GWA 4NEB 631 6050-22 DS 02
Example Circuits E
In this chapter
In this chapter you will find example circuits
• for the following parameterizable control functions:
– Overload Relay
– Direct Starter
– Reversing Starter
– Molded Case Circuit Breaker (MCCB)
– Star-Delta Starter
– Star-Delta Reversing Starter
– Dahlander
– Dahlander Reversing Starter
– Pole-Changing Starter
– Pole-Changing Reversing Starter
– Solenoid Valve
– Positioner
– Soft Starter
– Soft Starter with Reversing Contactor.
• for safety-oriented tripping with Emergency-STOP for:
– Direct Starters (category 2 and 4)
– Reversing Starters (category 2 and 4)
– Star-Delta Starters (category 4)
– Pole-Changing Starters (category 2 and 4)
– Dahlanders (category 4).
Target groups
This manual is addressed to the following target groups:
• Planners
• Configurators
• Technicians
• Electricians
• Commissioners.
Necessary knowledge
You will require the following knowledge:
• Basic SIMOCODE pro knowledge (see Chapter 1)
• Basic knowledge of SIMOCODE ES parameterization software.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-1
Example Circuits
E.1 General
Objectiveof the example circuits
The examples should
• Show how to implement a circuit for a specific Control Function
using SIMOCODE pro
• Help you modify these examples for your respective application
• Help you implement other applications easily.
Fundamental steps
• Implementation of external wiring (for control and feedback of main circuit
devices and control and signaling devices) (see circuit diagrams)
• Implementation/activation of internal SIMOCODE pro functions, with control
and evaluation of the SIMOCODE pro Inputs/Outputs (internal
SIMOCODE pro wiring) (see function circuit diagrams with the functions
blocks of the graphical editor of the "SIMOCODE ES" configuration software).
• Setting up the Cyclic Receive and Send Data for the communication of
SIMOCODE pro with a PLC (See function circuit diagrams and the
"Assignment of Cyclic Receive and Send Data" tables)
Prerequisites
• Load feeder/motor is present
• PLC/PCS Control with PROFIBUS DP interface is present
• The main circuit is already connected
• PC/programming device is present
• SIMOCODE ES software is installed
• The Basic Unit has the factory settings. More information about how to apply
the factory settings can be found in the "Resetting the factory settings"
section of the SIMOCODE pro manual.
SIMOCODE pro
E-2 GWA 4NEB 631 6050-22 DS 02
Example Circuits
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-3
13($&+]9
1$&+]9 1$&+]9
E-4
/ / /
E.2.1
/ 1 1
/
1
3( 352),%86
$
%
$
%
3(
Example Circuits
; ;
) )
4
,! ,!
&$ &$
,! ,! ,!
$
$
;
$
%
63(3(
7
/
/
/
3URILEXV'3 9$&
'HYLFH
6<6
%86
&7
6,02&2'(SUR&9
*HQIDXOW
%DVLF8QLW 7HVWUHVHW
%8
&XUUHQWPHDVXUHPHQW
37& 287 287 287
9
,1 ,1 ,1 ,1
7
7
7
7
7
"Overload Relay" Circuit Diagram
!
+
!
.
; ;
;
0DLQVFRQWDFWRU
3(
8
9
:
0
0 3(
$&
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-5
13($&+]9
E-6
1$&+]9 1$&+]9 E.3
/ / /
E.3.1
/ 1 1
/
1
3( 352),%86
$
%
$
%
3(
Example Circuits
; ;
) ) ) ) )
&$ &$
$
%
;
63(3(
$
$
7 $
/
/
/
3URILEXV'3 9$&
'HYLFH
%86 21 2)) 7(67
6<6
6,02&2'(SUR&9
&7
6<6
5(6(7
*HQIDXOW
%DVLF8QLW '(9,&( %86 *(1)$8/7
7HVWUHVHW
%8
&XUUHQWPHDVXUHPHQW
37& 287 287 287 2SHUDWRUSDQHO
9
"Direct Starter" Circuit Diagram
7
7
7
7
7
$
.
"Direct Starter" Example Circuit
$
.
'2/
; ;
; 0DLQVFRQWDFWRU
/RFDO
2Q
6 6
/RFDO
2II
3(
8
9
:
0
0 3(
$&
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-7
13($&+]9
1$&+]9 1$&+]9
E-8
/ / /
E.4
E.4.1
/ 1 1
/
1
3(
352),%86
$
%
$
%
3(
Example Circuits
; ;
,! ,! ,! ,! ,!
&$ &$
$
%
$
$
;
63(3(
7 $
/
/
/
3URILEXV'3 9$&
'HYLFH
%86 21 21! 2)) 7(67
&7
6<6
6<6
6,02&2'(SUR&9 5(6(7
*HQIDXOW
%DVLF8QLW '(9,&( %86 *(1)$8/7
7HVWUHVHW
%8
2SHUDWRUSDQHO
&XUUHQWPHDVXUHPHQW
37& 287 287 287
9
,1 ,1 ,1 ,1
7
7
7
7
7
"Reversing Starter" Circuit Diagram
$
$
. .
$
$
. .
"Reversing Starter" Example Circuit
; ;
0DLQVFRQWDFWRU
; 5XQVLJQDOULJKW
0DLQVFRQWDFWRU
5XQVLQJDOOHIW
6 6 6
/RFDO
2II
3(
8
9
:
/RFDO
0 5XQVLJQDOULJKW
0 3(
$& /RFDO
5XQVLJQDOOHIW
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-9
4
;
;
13($&+]9
E-10
E.5
1$&+]9 1$&+]9
E.5.1
/ / / 0
;
;
/ 1 1
/ ,! ,! ,!
1
;
;
;
;
;
3( 352),%86
$
%
$
%
;
;
Example Circuits
$
$
'
'
$
$
$
; ;
Circuit
0
) ) ) ) )
&$ &$
$
;
63(3(
$
%
$
$
7 $
/
/
/
3URILEXV'3 9$&
'HYLFH
%86 21 2)) 7(67
6,02&2'(SUR9
&7
6<6
5(6(7
6<6
*HQIDXOW
%DVLF8QLW '(9,&( %86 *(1)$8/7
7HVWUHVHW
%8
2SHUDWRUSDQHO
&XUUHQWPHDVXUHPHQW
37& 287 287 287
9
,1 ,1 ,1 ,1
7
7
7
7
7
Fig. E-7: "Molded Case Circuit Breaker (MCCB) 3VL" circuit diagram
;
;
4 4
;
;
;
4
;
;
0 ;
;
&
&
&
; ;
)HHGEDFN
&%5RQ
6 6
)HHGEDFN
&%5UHOHDVHG
"Molded Case Circuit Breaker (MCCB) 3VL" Example
/RFDO
2Q
/RFDO
E.5.2 "Molded Case Circuit Breaker (MCCB) 3VL" Function Circuit Diagram
Fig. E-8: "Molded Case Circuit Breaker (MCCB) 3VL" function circuit diagram
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-11
13($&+]9
1$&+]9 1$&+]9
E-12
/ / /
E.6
E.6.1
/ 1 1
/
1
3( 352),%86
$
%
$
%
3(
'
'
'
'
Example Circuits
$
$
$
; ;
,! ,! ,!
,! ,!
&$ &$
$
$
%
$
$
;
63(3(
7 $
/
/
/
3URILEXV'3 9$&
'HYLFH
%86 21 2)) 7(67
6<6
6<6
&7
6,02&2'(SUR9 5(6(7
*HQIDXOW
%DVLF8QLW '(9,&( %86 *(1)$8/7
7HVWUHVHW
%8
2SHUDWRUSDQHO
&XUUHQWPHDVXUHPHQW
37& 287 287 287
9
,1 ,1 ,1 ,1
7
7
7
7
7
$
$
$
"Star-Delta Starter" Example Circuit
&
&
&
&
&
; ; ;
0DLQVFRQWDFWRU
'HOWDFRQWDFWRU
6WDUFRQWDFWRU
6 6
/RFDO
"Star-Delta Starter" Circuit Diagram (Current Measuring in Delta)
2Q
0
/RFDO
: :
2II
9 0 9
8 $& 8
3(
3(
Fig. E-10: "Star-Delta Starter" function circuit diagram (Current Measuring in Delta)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-13
13($&+]9
1$&+]9 1$&+]9
/ / /
E-14
E.6.3
/ 1 1
/
1
3( 352),%86
$
%
$
%
3(
'
'
'
'
Example Circuits
$
$
$
; ;
Cable)
,! ,! ,!
,! ,!
&$ &$
$
$
%
$
$
;
63(3(
7 $
/
/
/
3URILEXV'3 9$&
'HYLFH
%86 21 2)) 7(67
6<6
6<6
&7
6,02&2'(SUR9 5(6(7
*HQIDXOW
%DVLF8QLW '(9,&( %86 *(1)$8/7
7HVWUHVHW
%8
2SHUDWRUSDQHO
&XUUHQWPHDVXUHPHQW
37& 287 287 287
9
,1 ,1 ,1 ,1
7
7
7
7
7
$
$
$
. . . . . .
$
$
$
Fig. E-11: "Star-Delta Starter" circuit diagram (Current Measuring in Incoming Cable)
&
&
&
&
&
; ; ;
0DLQVFRQWDFWRU
'HOWDFRQWDFWRU
6WDUFRQWDFWRU
6 6
/RFDO
2Q
0
"Star-Delta Starter" Circuit Diagram (Current Measuring in Incoming
/RFDO
: :
2II
9 0 9
8 $& 8
3(
3(
Fig. E-12: "Star-Delta Starter" function circuit diagram (Current Measuring in Incoming Cable)
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-15
13($&+]9
1$&+]9 1$&+]9
/ / /
E-16
E.7
E.7.1
/ 1 1
/
1
3( 352),%86
$
%
$
%
3(
'
'
'
'
$
$
$
$
$
; ;
Example Circuits
$
4 ) ) 21 21! 2)) 7(67
6<6
5(6(7
'(9,&( %86 *(1)$8/7
2SHUDWRUSDQHO
,! ,! ,!
,! ,!
&$ &$
$
$
;
63(3(
$
$
$
%
3(
3URILEXV'3 9$& 10
.5 ./ 'HYLFH 287 287
%86
6<6
6<6
&7
6<6
6,02&2'(SUR9
*HQIDXOW 6,02&2'(SUR9
%DVLF8QLW 7HVWUHVHW
5HDG\
9$& 'LJLWDOPRGXOH
37& 287 287 287
7
7
/
/
/
7
$
$
$
$
$
$
$
$
&XUUHQWPHDVXUHPHQW
7
7
7
"Star-Delta Reversing Starter" Circuit Diagram
&
&
&
&
&
; ; ;
0DLQVFRQWDFWRU
5LJKW
0DLQVFRQWDFWRU
/HIW
6 6 6
'HOWDFRQWDFWRU
"Star-Delta Reversing Starter" Example Circuit
6WDUFRQWDFWRU
0
: : /RFDO
9 0 9 5LJKW
8 $& 8
/RFDO
3(
3(
/HIW
/RFDO
2II
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-17
13($&+]9 1$&+]9 1$&+]9
/ / /
E.8
E-18
E.8.1
/ 1 1
/
1
3( 352),%86
$
%
$
%
0%
'
'
'
'
$
$
$
$
$
Example Circuits
; ;
) )
4
) ) )
) )
;
63(3(
$
$
%
$
$
$
/
/
/
7 3URILEXV'3 9$&
'HYLFH
%86 21!! 21! 2)) 7(67
6,02&2'(SUR9
&7
6<6
5(6(7
6<6
*HQIDXOW
%DVLF8QLW '(9,&( %86 *(1)$8/7
"Dahlander" Circuit Diagram
7HVWUHVHW
%8
37& 2SHUDWRUSDQHO
287 287 287
&XUUHQWPHDVXUHPHQW
9
,1 ,1 ,1 ,1
7
7
7
7
7
"Dahlander" Circuit Diagram
$
$
$
. . . . . .
$
$
$
0DLQVFRQWDFWRU
&
&
&
&
&
; ; ; )DVW
0DLQVFRQWDFWRU
6ORZ
6WDUFRQWDFWRU
)DVW
6 6 6
/RFDO
)DVW
0 /RFDO
:
6ORZ
:
9 0 9
$& /RFDO
8 8 2II
3(
3(
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-19
13($&+]9
E.9
E-20
1$&+]9 1$&+]9
E.9.1
/ / /
/ 1 1
/
1
3( 352),%86
$
%
$
%
3(
Example Circuits
'
'
'
'
$
$
$
$
$
; ;
$
!!! 21 21! 2)) 7(67 0DLQVFRQWDFWRU
6<6
5(6(7
4 ) ) '(9,&( %86 *(1)$8/7
)DVW
5LJKW
2SHUDWRUSDQHO
0DLQVFRQWDFWRU
) ) ) 6ORZ
) )
5LJKW
&$ &$
6WDUFRQWDFWRU
$
$
./ ./ )DVW
$
$
0DLQVFRQWDFWRU
6ORZ
/HIW
$ 0DLQVFRQWDFWRU
;
$
63(3(
$
%
$
$
3(
7 )DVW
/
/
/
3URILEXV'3 9$& 10
$EVICE 287 287 /HIW
"53
6<6
3)-/#/$%PRO 6
#4
'ENFAULT 6,02&2'(SUR9 /RFDO
"ASIC 5NIT
5HDG\
4ESTRESET 9$& 'LJLWDOPRGXOH
%8 2II
37& 287 287 287
&XUUHQWPHDVXUHPHQW
,1 ,1 ,1 ,1
9
,1 ,1 ,1 ,1
7
7
7
/RFDO
7
7
6ORZ
5LJKW
/RFDO
)DVW
5LJKW
$
$
$
$
$
$
6ORZ
/HIW
"Dahlander Reversing Starter" Circuit Diagram
/RFDO
)DVW
/HIW
&
&
&
&
&
%
%
%
%
%
0
: :
9 0 9
$&
8 8
3(
3(
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-21
Example Circuits
SIMOCODE pro
E-22 GWA 4NEB 631 6050-22 DS 02
Example Circuits
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-23
13($&+]9
1$&+]9 1$&+]9
/ / /
E-24
/ 1 1
E.10.1
/
1
3( 352),%86
$
%
$
%
3(
'
'
'
'
$
$
$
; ;
Example Circuits
,! ,! ,!
,! ,!
&$ &$
$
;
63(3(
$
%
$
$
7 $
/
/
/
3URILEXV'3 9$&
&7
6<6
6,02&2'(SUR9 5(6(7
6<6
*HQIDXOW
%DVLFXQLW 'HYLFH %86 *(1)$8/7
7HVWUHVHW
%8
2SHUDWRUSDQHO
&XUUHQWVHQVLQJ
37& 287 287 287
9
,1 ,1 ,1 ,1
7
7
7
7
7
"Pole-Changing Starter" Circuit Diagram
$
$
. .
. .
$
$
&
&
&
&
&
; ; ;
0DLQVFRQWDFWRU
)DVW
0DLQVFRQWDFWRU
6ORZ
6 6 6
0 /RFDO
)DVW
: :
9 0 9 /RFDO
8 $& 8 6ORZ
3(
3(
/RFDO
2II
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-25
13($&+]9
1$&+]9 1$&+]9
E-26
/ / /
E.11
E.11.1
/ 1 1
/
1
3( 352),%86
$
%
$
%
3(
Example Circuits
'
'
'
'
$
$
$
; ; $
0DLQVFRQWDFWRU
!!! 21 21! 2)) 7(67
6<6
5(6(7 )DVW
4 ) ) '(9,&( %86 *(1)$8/7
5LJKW
2SHUDWRUSDQHO
0DLQVFRQWDFWRU
) ) ) 6ORZ
,! ,! 5LJKW
&$ &$
$
$
0DLQVFRQWDFWRU
./ ./ 6ORZ
/HIW
$
$
0DLQVFRQWDFWRU
)DVW
$ /HIW
$
63(3(
$
%
$
$
;
0%
7
/
/
/
3URILEXV'3 9$& 10 /RFDO
'HYLFH 287 287
%86 2II
6<6
6<6
6<6
6,02&2'(SUR9
&7
*HQIDXOW 6,02&2'(SUR9
%DVLF8QLW
5HDG\
7HVWUHVHW 9$& 'LJLWDOPRGXOH /RFDO
%8
6ORZ
9
&XUUHQWPHDVXUHPHQW
,1 ,1 ,1 ,1 ,1 ,1 ,1 ,1 5LJKW
7
7
7
7
7
/RFDO
)DVW
5LJKW
/RFDO
$
$
6ORZ
.5 ./ .5 ./ .5 .5 /HIW
$
$
/RFDO
)DVW
/HIW
"Pole-Changing Reversing Starter" Circuit Diagram
&
&
&
&
&
%
%
%
%
%
0
: :
"Pole-Changing Reversing Starter" Example Circuit
9 0 9
8 $& 8
3(
3(
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-27
Example Circuits
SIMOCODE pro
E-28 GWA 4NEB 631 6050-22 DS 02
Example Circuits
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-29
13($&+]9
1$&+]9 1$&+]9
/ / /
E-30
/ 1 1
E.12.1
/
1
3( 352),%86
$
%
$
%
3(
Example Circuits
; ;
,! ,! ,! ,! ,!
&$ &$
$
%
$
$
;
63(3(
$
3URILEXV'3 9$&
'HYLFH
%86 23(1 &/26( 7(67
6<6
&7
6<6
6,02&2'(SUR9 5(6(7
*HQIDXOW
%DVLF8QLW '(9,&( %86 *(1)$8/7
7HVWUHVHW
37& 2SHUDWRUSDQHO
287 287 287
9
,1 ,1 ,1 ,1
"Solenoid Valve" Circuit Diagram
7
7
$
.
$
.
; ;
0DLQVFRQWDFWRU )HHGEDFN
1
; /LPLWVZLWFK
/RFDO &ORVH
2Q
)HHGEDFN
6 6 50= 50$ /RFDO OLPLWVZLWFK
3(
2II 2SHQ
3(
<
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-31
13($&+]9 1$&+]9 1$&+]9
/ / /
E-32
/ 1 1
E.13
E.13.1
/
1
3( 352),%86
$
%
$
%
3(
Example Circuits
; ;
$ 0DLQVFRQWDFWRU
2SHQ
4 ) ) &/26( 23(1 6723 7(67
6<6
5(6(7
'(9,&( %86 *(1)$8/7 0DLQVFRQWDFWRU
&ORVHG
2SHUDWRUSDQHO
,! ,! ,! ,! ,! /RFDO
&$ &$
6WRS
/RFDO
$ 2SHQ
$
;
63(3(
$
%
$
$
3(
7
/
/
/
3URILEXV'3 9$& 10
'HYLFH 287 287
%86 )HHGEDFN
6<6
6<6
6,02&2'(SUR9
&7
6<6
*HQIDXOW 6,02&2'(SUR9 /LPLWVZLWFK
%DVLF8QLW
5HDG\
7HVWUHVHW 9$& 'LJLWDOPRGXOH &ORVHG
%8
"Positioner 1" Circuit Diagram
9
&XUUHQWPHDVXUHPHQW
,1 ,1 ,1 ,1 ,1 ,1 ,1 ,1
7
7
7
)HHGEDFN
/LPLWVZLWFK
7
7
2SHQ
"Positioner" Example Circuit
$
$
. .
$
$
. .
;
3(
8
9
:
0
0 3(
$&
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-33
13($&+]9
1$&+]9 1$&+]9
/ / /
E-34
/ 1 1
E.13.3
/
1
3( 352),%86
$
%
$
%
3(
;
Example Circuits
;
$
0DLQVFRQWDFWRU
4 ) ) &/26( 23(1 6723 7(67
2SHQ
6<6
5(6(7
'(9,&( %86 *(1)$8/7
0DLQVFRQWDFWRU
2SHUDWRUSDQHO &ORVH
,! ,! ,! ,! ,! /RFDO
&$ &$
6WRS
$ /RFDO
$ 2SHQ
63(3(
$
%
$
$
;
3(
7
/
/
/
3URILEXV'3 9$& 10
'HYLFH 287 287 )HHGEDFN
%86 7RUTXHVZLWFK
6<6
6<6
6<6
6,02&2'(SUR9
&7
*HQIDXOW 6,02&2'(SUR9 &ORVHG
%DVLF8QLW
5HDG\
7HVWUHVHW 9$& 'LJLWDOPRGXOH
%8
"Positioner 2" Circuit Diagram
9
&XUUHQWPHDVXUHPHQW
,1 ,1 ,1 ,1 ,1 ,1 ,1 ,1
7
7
7
/LPLWVZLWFK
7
7
&ORVHG
)HHGEDFN
/LPLWVZLWFK
2SHQ
$
$
. . )HHGEDFN
7RUTXHVZLWFK
$
$
2SHQ
. .
;
'0= 50= 50$ '0$
6 6 6
3(
8
9
:
0
0 3(
$&
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-35
13($&+]9 1$&+]9 1$&+]9
/ / /
E-36
/ 1 1
E.13.5
/
1
3( 352),%86
$
%
$
%
3(
; ;
Example Circuits
$
0DLQVFRQWDFWRU
4 ) ) &/26( 23(1 6723 7(67 2SHQ
6<6
5(6(7
'(9,&( %86 *(1)$8/7
0DLQVFRQWDFWRU
2SHUDWRUSDQHO &ORVHG
,! ,! ,! ,! ,!
&$ &$ /RFDO
6WRS
$ /RFDO
$
$
%
$
$
2SHQ
;
63(3(
3(
7
/
/
/
3URILEXV'3 9$& 10
'HYLFH 287 287 )HHGEDFN
%86
6<6
6<6
&7
6<6
6,02&2'(SUR9 7RUTXHVZLWFK
*HQIDXOW 6,02&2'(SUR9
%DVLF8QLW &ORVHG
5HDG\
7HVWUHVHW 9$& 'LJLWDOPRGXOH
%8
"Positioner 3" Circuit Diagram
&XUUHQWPHDVXUHPHQW
9
,1 ,1 ,1 ,1 ,1 ,1 ,1 ,1
7
7
7
/LPLWVZLWFK
7
7
&ORVHG
)HHGEDFN
/LPLWVZLWFK
2SHQ
$
$
. .
$
$
. .
;
'0= 50= 50$ 6 6 6
3(
8
9
:
0
0 3(
$&
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-37
13($&+]9
1$&+]9 1$&+]9
/ / /
E-38
/ 1 1
E.13.7
/
1
3( 352),%86
$
%
$
%
3(
Example Circuits
; ;
$ 0DLQVFRQWDFWRU
2SHQ
4 ) ) &/26( 23(1 6723 7(67
6<6
5(6(7
'(9,&( %86 *(1)$8/7 0DLQVFRQWDFWRU
&ORVHG
2SHUDWRUSDQHO
,! ,! ,! ,! ,! /RFDO
&$ &$
6WRS
/RFDO
$ 2SHQ
$
$
%
$
$
;
63(3(
3(
7
/
/
/
3URILEXV'3 9$& 10
'HYLFH 287 287
%86 )HHGEDFN
6<6
6<6
6<6
6,02&2'(SUR9
&7
*HQIDXOW 6,02&2'(SUR9 /LPLWVZLWFK
%DVLF8QLW
5HDG\
7HVWUHVHW 9$& 'LJLWDOPRGXOH &ORVHG
%8
"Positioner 4" Circuit Diagram
9
&XUUHQWPHDVXUHPHQW
,1 ,1 ,1 ,1 ,1 ,1 ,1 ,1 )HHGEDFN
7
7
7
/LPLWVZLWFK
7
7
2SHQ
)HHGEDFN
7RUTXHVZLWFK
2SHQ
$
$
. .
$
$
. .
;
50= 50$ '0$ 6 6 6
3(
8
9
:
0
0 3(
$&
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-39
13($&+]9
1$&+]9 1$&+]9
/ / /
E-40
/ 1 1
E.13.9
/
1
3( 352),%86
$
%
$
%
3(
Example Circuits
; ;
$
0DLQVFRQWDFWRU
2SHQ
4 ) ) &/26( 23(1 6723 7(67
6<6
5(6(7
'(9,&( %86 *(1)$8/7 0DLQVFRQWDFWRU
2SHUDWRUSDQHO &ORVHG
,! ,! ,! ,! ,! /RFDO
&$ &$
6WRS
/RFDO
$
$ 2SHQ
63(3(
$
%
$
$
;
3(
7
/
/
/
3URILEXV'3 9$& 10
'HYLFH 287 287 )HHGEDFN
%86 7RUTXHVZLWFK
6<6
6<6
6<6
6,02&2'(SUR9
&7
*HQIDXOW 6,02&2'(SUR9 /LPLWVZLWFK
%DVLFXQLW
5HDG\
7HVWUHVHW 9$& 'LJLWDOPRGXOH &ORVHG
%8
"Positioner 5" Circuit Diagram
9
&XUUHQWPHDVXUHPHQW
,1 ,1 ,1 ,1 ,1 ,1 ,1 ,1
7
7
7
)HHGEDFN
7
7
7RUTXHVZLWFK
/LPLWVZLWFK
2SHQ
$
$
. .
$
$
. .
;
'0=50= '0$50$
6 6 6
3(
8
9
:
0
0 3(
$&
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-41
13($&+]9 1$&+]9 1$&+]9
/ / /
E-42
/ 1 1
E.14
E.14.1
/
1
3( 352),%86
$
%
$
%
3(
Example Circuits
;
;
4 ) )
$
%
RII
,! ,! ,!
$
%
,! ,!
&$ &$
;
63(3(
$
%
$
$
7 $
/
/
/
3URILEXV'3 9$&
'HYLFH
%86 21! 2)) 7(67
6<6
6,02&2'(SUR9
&7
6<6
5(6(7
*HQIDXOW
"Soft Starter" Circuit Diagram
&XUUHQWPHDVXUHPHQW
9
,1 ,1 ,1 ,1
7
7
7
7
7
0DLQVFRQWDFWRU
6RIWVWDUWHU
$(55
$21
!2%3
!
"Soft Starter" Example Circuit
6WDUW
.
6RIWVWDUWHU
5HVHW
$/
$/
$/
!
+ 6RIWVWDUWHU
)DXOW
!
/RFDO
2Q
/RFDO
2II
;
6 6
$
0
5:
6,.267$57
8 7 / $/
7
$&
9 / $/
0
: 7 / $/
3(
3( 3( 3(
%UDNH
FRQWDFWRU
$FFHOHUDWLRQ
ILQLVKHG
$(55
)DXOW
$5(6
5HVHW
2II
$21
2Q
$
'&/9
1/
&$
)
$&9
$&9
,!
$&9
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-43
Example Circuits
SIMOCODE pro
E-44 GWA 4NEB 631 6050-22 DS 02
Example Circuits
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-45
13($&+]9
E-46
1$&+]9 1$&+]9
/ / /
E.15.1
/ 1 1
/
1
3( 352),%86
$
%
$
%
3(
Example Circuits
;
$ 0DLQVFRQWDFWRU
; 5LJKW
4 ) ) 21!! 21! 2)) 7(67
$
%
6<6
5(6(7
'(9,&( %86 *(1)$8/7
0DLQVFRQWDFWRU
RII /HIW
2SHUDWRUSDQHO
,! ,! ,! 6RIWVWDUWHU
,! ,!
$
%
6WDUW
&$ &$
6RIWVWDUWHU
5HVHW
$
$21
$5(6
%XVFRQWDFWRURQ6XE'
6RIWVWDUWHU
$ )DXOW
$
$
%
$
$
;
63(3(
3(
7
/
/
/
3URILEXV'3 9$& 10 /RFDO
'HYLFH 287 287 5LJKW
%86
6<6
6<6
&7
6<6
6,02&2'(SUR9
*HQIDXOW 6,02&2'(SUR9
%DVLFXQLW /RFDO
5HDG\
7HVWUHVHW 9$& 2SHUDWRUSDQHO
%8 2II
37& 287 287 287
9
,1 ,1 ,1 ,1 ,1 ,1 ,1 ,1
&XUUHQWPHDVXUHPHQW
7
7
7
/RFDO
7
7
/HIW
$(55
$
$
Fig. E-40: "Soft Starter with Reversing Contactor" circuit diagram (1/2)
. . . .
$
$
$/
$/
$/
;
"Soft Starter with Reversing Contactor" Circuit Diagram
6 6 6
0
8 7 / $/
9 7 / $/
5:
$&
: 7 / $/
6,.267$57
0 3(
3( 3(
3(
%UDNH
FRQWDFWRU
$FFHOHUDWLRQ
ILQLVKHG
$(55
)DXOW
$5(6
5HVHW
2II
$21
2Q
$
'&/9
1/
)
&$
$&9
$&9
,!
$&9
Example Circuits
Example Circuits
Fig. E-42: "Soft Starter with Reversing Contactor" function circuit diagram
SIMOCODE pro
E-48 GWA 4NEB 631 6050-22 DS 02
Example Circuits
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-49
/9'&
E-50
E.16.1
/ 13($&+]9 0
/
/ 352),%86
$
%
$
%
1
3(
3(
Example Circuits
$
) 21 2)) 7(67
5(6(7
6<6
'(9,&( %86 *(1)$8/7
4
,! /9'&
,!,!,!
$
$
%
;
63(3(
$
$
.
Direct Starter, Category 2
3URILEXV'3 'HYLFH
%XV
&7
6<6
6,02&2'(SUR&9
*HQIDXOW
7HVWUHVHW
/
/
/
37& ,1 1 1 ,1 287 287 287
9
7
7
%8
7
7
7
&XUUHQWPHDVXUHPHQW
.
$FNQRZOHGJH(0(5*(1&<6723
8
9
:
3(
$ < <
0
0 3(
$&
$
$
7.%%
.
$
Fig. E-43: "Safety-Oriented Tripping with Emergency STOP" circuit diagram, Direct Starter, category 2
$FWXDWRUIDLOXUH
(0(5*(1&<6723SXVKEXWWRQ
%DVLFXQLW
2SHUDWRUSDQHO 0
Fig. E-44: "Safety-Oriented Tripping with Emergency STOP" function circuit diagram,
Direct Starter, category 2
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-51
/9'&
13($&+]9
E-52
0
/
E.16.2
/
/ 352),%86
$
%
$
%
1
3(
3(
;
Example Circuits
5(6(7
6<6
) '(9,&( %86 *(1)$8/7
4
/9&'
)
,!,!,!
$
$
%
.
;
63(3(
$
$
3URILEXV'3 'HYLFH 9'&
Direct Starter, Category 4
%86
&7
6<6
6,02&2'(SUR&9
*HQIDXOW
7HVWUHVHW
/
/
/
.
287 287 287
9
37& ,1 ,1 ,1 ,1
.
7
7
%8
7
7
7
&XUUHQWPHDVXUHPHQW
. (0(5*(1&<6723DFNQRZOHGJHG
3(
$ << <
9
8
:
0 0 3(
$&
$
<< $ <
$FNQRZOHGJHPHQW(0(5*(1&<6723
7.&%
.
$
$
Fig. E-45: "Safety-Oriented Tripping with Emergency STOP" circuit diagram, Direct Starter, category 4
.
$
(0(5*(1&<6723SXVKEXWWRQ
%DVLFXQLW
2SHUDWRUSDQHO
0
Fig. E-46: "Safety-Oriented Tripping with Emergency STOP" function circuit diagram,
Direct Starter, category 4
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-53
/9'&
0
E-54
13($&+]9
/
E.16.3
/ 352),%86
$
%
$
%
/
1
3(
3(
;
Example Circuits
5(6(7
6<6
;
)
'(9,&( %86 *(1)$8/7
4
,!
/9'&
,!,!,!
$
$
%
;
63(3(
$
$
.
3URILEXV'3 'HYLFH 9'& .
6<6
%XV
&7
6,02&2'(SUR&9
/
/
/
*HQIDXOW
7HVWUHVHW
287 287 287
9
37& ,1 ,1 ,1 ,1
Reversing Starter, Category 2
%8
7
7
7
7
7
&XUUHQWPHDVXUHPHQW
(0(5*(1&<6723DFNQRZOHGJHG
$FNQRZOHGJH(0(5*(1&<6723
$ < <
. .
7.&%
$
$
$
. .
3(
$
$
9
8
:
$FWXDWRUIDLOXUH
0 0 3(
$&
(0(5*(1&<6723SXVKEXWWRQ
0DLQVFRQWDFWRUURWDWLRQOHIW
Fig. E-47: "Safety-Oriented Tripping with Emergency STOP" circuit diagram, Reversing Starter, category 2
0DLQVFRQWDFWRUURWDWLRQULJKW
%DVLFXQLW
0
2SHUDWRUSDQHO
Fig. E-48: "Safety-Oriented Tripping with Emergency STOP" function circuit diagram,
Reversing Starter, category 2
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-55
13($&+]9
/
E-56
/ /9'&
E.16.4
/ 0
1
3( 352),%86
$
%
$
%
3(
;
Example Circuits
; 21! 21!! 2)) 7(67
5(6(7
6<6
4 '(9,&( %86 *(1)$8/7
)
,!,!,!
,! /9'&
.
$
$
%
;
63(3(
$
$
3URILEXV'3 'HYLFH 9'&
6<6
%XV
&7
6,02&2'(SUR&9
/
/
/
*HQIDXOW
7HVWUHVHW
Reversing Starter, Category 4
.
287 287 287
9
37& ,1 ,1 ,1 ,1
%8
7
7
.
7
7
7
.
&XUUHQWPHDVXUHPHQW
(0(5*(1&<6723DFNQRZOHGJHG
$FNQRZOHGJH(0(5*(1&<6723
. .
7.&%
. .
$
$
3(
9
$
8
:
0 0 3( .
$&
0DLQV&RQWDFWRUOHIW
0DLQV&RQWDFWRUULJKW
$
Fig. E-49: "Safety-Oriented Tripping with Emergency STOP" circuit diagram, Reversing Starter, category 4
(0(5*(1&<6723SXVKEXWWRQ
%DVLF8QLW
2SHUDWRU3DQHO
Fig. E-50: "Safety-Oriented Tripping with Emergency STOP" function circuit diagram,
Reversing Starter, category 4
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-57
13($&+]9
E-58
/ /9'&
352),%86
E.16.5
/
/ $ % $% 0
1
3(
$
;
3(
21! 21!! 2)) 7(67
; 5(6(7
6<6
Example Circuits
category 4
'(9,&( %86 *(1)$8/7
4
)
! ! !
/9'&
!
. $
$
$
%
$
63(3(
;
3URILEXV'3 'HYLFH 9'&
6,02&2'(SUR9 %XV
6<6
&7
*HQIDXOW
7HVWUHVHW
/
/
/
37& ,1 1 1 ,1 287 287 287
9
.
7
Star-Delta Starter, Category 4
7
.
7
7
7
&XUUHQWPHDVXUHPHQW
.
(0(5*(1&<6723DFNQRZOHGJHG
. . .
7.&% $FNQRZOHGJH(0(5*(1&<6723
$
$
$
. . .
$
$
$
Fig. E-51: "Safety-Oriented Tripping with Emergency STOP" circuit diagram, Star-Delta Starter,
6WDUFRQWDFWRU
'HOWDFRQWDFWRU
0
0DLQVFRQWDFWRU
$
: :
.
9 0 9
$
8 $& 8
3(
3(
(0(5*(1&<6723SXVKEXWWRQ
0
%DVLF8QLW
2SHUDWRU3DQHO
Fig. E-52: "Safety-Oriented Tripping with Emergency STOP" function circuit diagram, Star-Delta Starter,
category 4
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-59
/9'&
E-60
13($&+]9 0
/
E.16.6
/ 352),%86
$
%
$
%
/
1
3(
21!! 21 2)) 7(67
5(6(7
3(
6<6
; '(9,&( %86 *(1)$8/7
category 2
Example Circuits
;
)
4
,! /9'&
,!,!,!
$
$
%
;
63(3(
.
$
$
3URILEXV'3 'HYLFH 9'& .
6<6
%86
&7
6,02&2'(SUR&9
*HQIDXOW
/
/
/
7HVWUHVHW
287 287 287
9
37& ,1 1 1 ,1
%8
7
7
7
7
7
Pole-Changing Starter, Category 2
(0(5*(1&<6723DFNQRZOHGJHG
$FNQRZOHGJH(0(5*(1&<6723
$ < <
. .
$
$
$
7.%%
. .
$
$
$FWXDWRUIDLOXUH
0
0DLQVFRQWDFWRUIDVW
0DLQVFRQWDFWRUVORZ
::
Fig. E-53: "Safety-Oriented Tripping with Emergency STOP" circuit diagram, Pole-Changing Starter,
9 0 9
(0(5*(1&<6723SXVKEXWWRQ
8 $& 8
3(
3(
0
%DVLF8QLW
2SHUDWRU3DQHO
Fig. E-54: "Safety-Oriented Tripping with Emergency STOP" function circuit diagram,
Pole-Changing Starter, category 2
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-61
/9'&
E-62
13($&+]9 0 E.16.7
/
/ 352),%86
$
%
$
%
/
1
3(
3(
;
Example Circuits
category 4
21! 21!! 2)) 7(67
5(6(7
6<6
;
)
'(9,&( %86 *(1)$8/7
4
,!
/9'&
,!,!,!
$
$
%
;
63(3(
$
$
.
3URILEXV'3 'HYLFH 9'&
6<6
%86
&7
6,02&2'(SUR&9
/
/
/
*HQIDXOW
7HVWUHVHW
287 287 287
9
37& ,1 1 1 ,1 .
%8
7
7
7
7
7
.
Pole-Changing Starter, Category 4
&XUUHQWPHDVXUHPHQW
.
$FNQRZOHGJH(0(5*(1&<6723
. .
7.&%
. .
(0(5*(1&<6723DFNQRZOHGJHG
0
$
$
Fig. E-55: "Safety-Oriented Tripping with Emergency STOP" circuit diagram, Pole-Changing Starter,
: :
$
9 0 9
0DLQVFRQWDFWRUIDVW
0DLQVFRQWDFWRUVORZ
8 $& 8 .
3(
3(
$
%DVLFXQLW
(0(5*(1&<6723SXVKEXWWRQ
0
2SHUDWRUSDQHO
Fig. E-56: "Safety-Oriented Tripping with Emergency STOP" function circuit diagram,
Pole-Changing Starter, category 4
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-63
13($&+]9
E-64
/ /9'&
352),%86
E.16.8
/
/ $ % $% 0
1
3(
;
3(
21! 21!! 2)) 7(67
; 5(6(7
6<6
Example Circuits
category 4
'(9,&( %86 *(1)$8/7
4
)
! ! !
/9'&
!
. $
$
$
%
$
63(3(
;
3URILEXV'3 'HYLFH
Dahlander, Category 4
%XV
6<6
6,02&2'(SUR9
&7
*HQIDXOW
7HVWUHVHW
/
/
/
37& ,1 1 1 ,1 287 287 287
9
.
7
7
.
7
7
7
&XUUHQWPHDVXUHPHQW
.
(0(5*(1&<6723DFNQRZOHGJHG
$FNQRZOHGJH(0(5*(1&<6723
. . .
7.&%
Fig. E-57: "Safety-Oriented Tripping with Emergency STOP" circuit diagram, Dahlander,
$
$
$
. . .
$
$
$
0
$
6WDUFRQWDFWRUIDVW
0DLQVFRQWDFWRUVORZ
0DLQVFRQWDFWRUIDVW
: :
.
9 0 9
$
8 $& 8
3(
3(
(0(5*(1&<6723SXVKEXWWRQ
0
%DVLFXQLW
2SHUDWRUSDQHO
Fig. E-58: "Safety-Oriented Tripping with Emergency STOP" function circuit diagram,
Dahlander, category 4
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 E-65
Example Circuits
SIMOCODE pro
E-66 GWA 4NEB 631 6050-22 DS 02
Safety and Commissioning Information
for EEx Areas F
In this chapter
In this chapter you will find safety and commissioning information for
explosive areas. It is imperative that you observe this information for the
protection of any motors in potentially explosive areas.
Target groups
This chapter is addressed to the following target groups:
• Planners and configurators
• Commissioners
• Maintenance and service personnel.
Necessary knowledge
You will require the following knowledge:
• Explosion protection
• IEC 60079-14/EN 60079-14/DIN VDE 0165 - 1 Electrical apparatus for
explosive gas atmospheres - Electrical installations in hazardous areas (other
than mines)
• IEC 60079-17/EN 60079-17/DIN VDE 0165 - 10 - 1 Electrical apparatus for
explosive gas atmospheres - Inspection and maintenance of electrical
installations in hazardous areas (other than mines)
• IEC 61241-14/DIN VDE 0165 - 2 Electrical apparatus for use in the presence
of combustible dust - Selection and installation
• IEC 61241-17/DIN VDE 0165 - 10 - 2 Electrical apparatus for use in the
presence of combustible dust - Inspection and maintenance of electrical
installations in hazardous areas (other than mines)
• VDE 0118 Erection of electrical installations in mines
• Betriebssicherheitsverordnung - BetrSichV (Ordinance on Industrial
Safety and Health).
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 F-1
Safety and Commissioning Information for EEx Areas
F.1 General
Information and standards
Increased danger in potentially explosive areas means it is necessary to
carefully observe the following notes and standards:
• IEC 60079-14/EN 60079-14/DIN VDE 0165 - 1 Electrical apparatus for
explosive gas atmospheres - Electrical installations in hazardous areas (other
than mines)
• IEC 60079-17/EN 60079-17/DIN VDE 0165 - 10 - 1 Electrical apparatus for
explosive gas atmospheres - Inspection and maintenance of electrical
installations in hazardous areas (other than mines)
• IEC 61241-14/DIN VDE 0165 - 2 Electrical apparatus for use in the presence
of combustible dust - Selection and installation
• IEC 61241-17/DIN VDE 0165 - 10 - 2 Electrical apparatus for use in the
presence of combustible dust - Inspection and maintenance of electrical
installations in hazardous areas (other than mines)
• VDE 0118Erection of electrical installations in mines
• Betriebssicherheitsverordnung - BetrSichV (Ordinance on Industrial
Safety and Health).
All 3UF7 devices are approved under Device Group I, Category "M2" (mining)
and Device Group II, Category 2 in the area "GD" (areas in which explosive
gas, steam, fog and air mixtures as well as inflammable dust are present):
*) Note:
This safety and commissioning information is also valid for devices with the
certificate number BVS 04 ATEX F 003.
These devices are suitable for the protection of motors in explosive areas
and comply with the standards listed above.
Tests other than those legally stipulated (Ordinance on Industrial
Safety and Health) are not required.
Warning
All installation, commissioning and maintenance work is to be carried out by
responsible, qualified personnel only. Unprofessional behavior can cause
serious damage to persons and goods.
SIMOCODE pro
F-2 GWA 4NEB 631 6050-22 DS 02
Safety and Commissioning Information for EEx Areas
Notice
Please observe the operating instructions (enclosed with the devices)
SIMOCODE pro
Basic Unit Order number: 3ZX1012-0UF70-1AA1
Current Measuring Module Order number: 3ZX1012-0UF71-1AA1
Current/Voltage Measuring Module Order number: 3ZX1012-0UF77-1BA1
Digital Module Order number: 3ZX1012-0UF73-1AA1
Set the 3UF7 to the Rated Motor Current (according to the type plate or
design test certificate of the motor).
Notice
Note the trip class /tripping characteristic of the 3UF7.
Select the trip class so that the motor is thermally protected, even when the
rotor is stalled.
Motors, cables and contactors must be suitable for the selected trip class.
Notice
Set the response of the overload protection to "Tripping"!
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 F-3
Safety and Commissioning Information for EEx Areas
Example
Motor 500 V, 50/60 Hz, 110 kW, 156 A, temperature class T3, time TE = 11 s,
IA/Is = 5.5:
TE = 11 s
IA/Is = 5.5
SIMOCODE pro
F-4 GWA 4NEB 631 6050-22 DS 02
Safety and Commissioning Information for EEx Areas
For the 3UF70, you can use a type A temperature sensor with a
characteristic curve according to IEC 60947-8 (DIN VDE 0660, Part 303),
DIN 44081 and DIN 44082.
Depending on the number of sensors, this will result in the following trip
and restart temperatures:
Notice
Set the response for the activated thermistor to "Tripping"!
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 F-5
Safety and Commissioning Information for EEx Areas
Caution
Lay the measuring circuit cables as separate control cables.
The use of motor feeder wires or other main current cables is not permitted.
Shielded control cables must be used if extremely inductive or capacitive
interferences are to be expected because of parallel high-voltage cables.
Caution
When combining with other contactors, observe the respective maximum
fuse protection of the contactor for Type of Coordination 2.
SIMOCODE pro
F-6 GWA 4NEB 631 6050-22 DS 02
Safety and Commissioning Information for EEx Areas
Caution
Avoid impermissibly high cable surface temperatures by correctly
dimensioning the cross sections!
Select ample cable cross sections, particularly for heavy starting CLASS 20
to CLASS 40 (see the "Short-Circuit Protection with Fuses for Motor
Feeders" table in the "Technical Data" chapter of the SIMOCODE pro system
manual!
F.2.6 Test
Test phases
• Phase 1: Hardware Test/Lamp Test (0 to 2 s):
The hardware (e.g. the thermistor electronics) is tested, all LEDs and displays
are activated, including Lamp Controls. Contactor Controls remain
unchanged.
• Phase 2: Hardware test results (2 to 5 s):
If there is a fault, the "Hardware Fault Basic Unit" fault is triggered.
If there is no fault,
– the "GEN. FAULT" LED flashes when no main current is flowing
– the "GEN. FAULT" LED flickers if main current is flowing in all three
phases (special case: for "1-phase load" in one phase).
• Phase 3: Relay test (> 5 s):
If testing is carried out with tripping, the contactor controls are deactivated.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 F-7
Safety and Commissioning Information for EEx Areas
The following table shows the test phases carried out when the "TEST/
RESET" button is pressed for the required length of time:
Relay Test
SIMOCODE pro
F-8 GWA 4NEB 631 6050-22 DS 02
Safety and Commissioning Information for EEx Areas
Caution
Only the Relay Outputs of the 3UF70 Basic Unit or the 3UF730 Monostable
Digital Module may be used for the Protection Function!
Warning
The 3UF7 is not suitable for installation in potentially explosive areas.
The device may only be used in a switchgear cabinet with at least 4 times
the IP degree of protection.
When setting up the equipment in potentially explosive areas, ensure the
3UF7 is does not present a fire hazard. Appropriate measures must be taken
(e.g. encapsulation).
Notice
The 3UF7 is not suitable for load-side operation on frequency converters.
Warning
Repairs may only be carried out by the manufacturer.
F.4 Warranty
For this warranty to be considered valid, the safety and commissioning
information of the following operating instructions must be observed:
SIMOCODE pro
Basic Unit Order number 3ZX1012-0UF70-1AA1
Current Measuring Module Order number 3ZX1012-0UF71-1AA1
Current/Voltage Measuring Module Order number: 3ZX1012-0UF77-1BA1
Digital Module Order number: 3ZX1012-0UF73-1AA1
And the entire manual Order number: 3UF7970-0AA01-0
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 F-9
Safety and Commissioning Information for EEx Areas
SIMOCODE pro
F-10 GWA 4NEB 631 6050-22 DS 02
Index
Binary inputs for 110... 240 V AC/DC 1-9 Circuit breaker (MCCB) control 1-23
Binary inputs on the basic units and digital Circuit diagram with 3RW 40/44 E-47
modules 7-1 Class 3-8, Glossary-2
Bistable outputs 1-54 Class 1 master 12-2, 12-15, Glossary-2
Bistable relay output 1-9 Class 2 master 12-2, Glossary-2
BU input settings 7-5 Class time 3-14
BU inputs 1-91 Clear 1-60
BU outputs 1-91, 6-5 Clockwise rotation 4-30
BU outputs function block 6-4 Closing the system interface using the
Bus Glossary-2 system interface cover on the door
Bus connection D-6 adapter 13-30
Bus connection system 1-18, 13-23, Closing the system interface using the sy-
13-24 stem interface cover on the Operator
Bus connection system from Panel 13-30
20 A to 630 A 13-23, 13-24 Closing the system interface using the sy-
Bus monitoring 1-50, 10-17, 10-18 stem interface cover on the Operator Pa-
Bus ok 1-50 nel with display 13-30
Bus ok, PLC/PCS in run 1-43 Cold starting 10-8
Bus parameters 12-1 Cold starting function test 10-8
Bus segment Glossary-2 Color coding for the connection cable
Bus termination module 13-40 13-34, 13-36
Bus/PLC-fault - reset 1-50, 10-18 Commands 1-33
Buttons D-12, D-13 Comment 1-63
Buttons on the operator panel with Commissioning 2-9, 14-1, 14-2, 14-3, F-3
display 7-7 Commissioning options 14-2
Communication 1-33, 12-1
C Communication principle 12-4
Cable cross sections 13-10 Compatibility mode 1-51
Cable length of the sensor circuit Conductor cross section 13-23, 13-24
cables F-6 Configuration fault 15-2
Cable lengths D-4 Configuration information for using an
Cable protection F-7 Operator Panel with display and/or
Cables 13-10, D-4, D-7 a decoupling module 1-76
Calculation modules 1-15, 11-2, 11-27 Configuration of the slave diagnosis 12-7
Calculator 1-15, 11-2, 1-88 Configure diagnosis response 12-6
Calculator (calculation module) 1 1-39, Configuring a reversing starter 2-1
1-88 Connecting cable 1-20, 1-78, Glossary-3
Calculator (calculation module) 2 1-39, Connecting cables to the system interface
1-88 of the Operator Panel 13-37
Calculator examples 11-30 Connecting cables to the system interface
Calculator formulae 11-29 of the Operator Panel with display
Calculator logic modules 11-27, 11-28 13-38
Calculator settings 11-29 Connecting plugs with sockets 1-84
Calculators (calculation modules) 1-15, Connecting system components to the
11-2, 11-27 system interface 13-32, 13-36
Catalogs LV1/LV1T F-10 Connecting the PROFIBUS DP to the
Change-over pause 4-16, 4-17, 4-28, 4-29, 9-pole SUB-D socket 13-39
4-31, 4-33, 4-34, 4-36, 4-38, 4-40, 4-41, Connecting the system components
4-43, 4-45, 4-47 13-29
Change-over pause active 1-44 Connection D-4, D-8, D-9, D-11
Channel-related diagnosis 12-6, 12-12 Connection cross sections D-4, D-6, D-7,
Characteristic curve of a type A sensor D-8, D-9, D-10, D-11
F-5 Connection for voltage measurement
Check list for selecting a device series D-6
1-8 Consumed energy 1-47
Circuit breaker (MCCB) 1-13, 4-14, 4-26 Contactor controls 4-12, 4-30, 4-60, A-2
SIMOCODE pro
Index-2 GWA 4NEB 631 6060-22 DS 02
Index
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Index-3
Index
Data record 92 - device diagnosis B-10 Direct starter control function 4-20
Data record 94 - measured values B-16 Direct starter function circuit diagram E-7
Data record 95 - service data / statistical Direct starter, category 2 E-50
data B-17 Direct Starter, category 4 E-52
Data records 12-22, B-1, B-3 Direction of rotation 4-22
Data records - overview B-2 Display 1-66, D-3, D-7, D-8, D-9, D-10,
Data transfer 12-4 D-12, D-13
Date 1-63 Display of all pending faults 1-62
Decoupling module 1-19, 1-70, C-14, D-7, Display of all pending status
Glossary-4 information 1-61
Decoupling module connection Display of all pending warnings 1-61
example 13-22 Display of measured values in the measu-
Decoupling module pin assignment red value indicator 1-40
13-22 Display of statistical and maintenance-rele-
Degree of pollution D-5 vant information on the
Degree of protection (according to statistics/maintenance display 1-46
IEC 60529) D-2 Display of the current status of all
Delay x, 1-72 device I/Os 1-53
Delay time 7-10 Display settings 1-33
Device class 1-65 Displays (lamp control) 4-12
Device data 12-2 Displays of the operator panel with
Device data (GSD file) Glossary-4 display 1-30
Device family 1-64 DM inputs 7-10
Device I/Os 1-33 DM inputs function blocks 7-9
Device parameters 12-1 DM outputs 6-9
Device replacement 1-78 DM1(2) inputs 1-89
Device series 1-2 DM1(2) outputs 1-88, 6-10
Device subfamily 1-64 Door adapter 1-20, 1-79, C-15, Glossary-4
Device test active 1-45 Double 0 15-2
Diagnosis alarm - configuration 12-13 Double 1 15-2
Diagnosis alarms 12-6 PLC/PCS 4-9
Diagnosis data 12-6 DP master 9-2, 12-2, Glossary-5
Diagnosis device fault 1-52 DP master connections for
Diagnosis fault 1-52 SIMATIC S7-400 10-19
Diagnosis for device errors 12-6 DP master with DPV1 alarm support
Diagnosis status info 1-52 (DPV1 alarm mode) 12-19
Diagnosis triggered by event 12-6 DP master without DPV1 alarm support
Diagnosis triggered by trips 12-6 (DPV1 alarm mode) 12-19
Diagnosis triggered by warning 12-6 DP masters which are operated
Diagnosis via LED display 14-5 in "DPV1" DP mode 12-20
Diagnosis warning 1-52 DP masters which are operated
Diagnostic data 1-17 in "S7 compatible" DP mode 12-20
Diagram of the diagnosis data 9-4 DP slave Glossary-5
Digital Module 1-19, 1-54, 1-71, 1-72, D-8, DP standard SIMOCODE-DP 9-4
Glossary-4 DP standard slave Glossary-5
Digital Module 1 inputs 7-3 DPV0 1-51
Digital Module 2 inputs 7-3 DPV1 1-51, 9-2
Digital Module connection example DPV1 SIMOCODE-DP 9-4
13-15 DPV1 slave 12-2
Digital Module inputs 7-9 DPV1 slave via GSD 12-15
Digital Module outputs 6-9
Digital Module pin assignment 13-14 E
Dimension drawings C-1 Early warning and fault signals 1-17
Direct starter 1-4, 1-5, 1-8, 1-13, 1-22, Earth fault 5-2
4-14, 4-21, B-42 Earth-fault detection 1-2
Direct starter circuit diagram E-6
SIMOCODE pro
Index-4 GWA 4NEB 631 6060-22 DS 02
Index
Earth-fault module 1-19, 1-71, 1-74, D-10, External fault 1-14, 10-2, 10-9, 10-10, 15-2
Glossary-5 External fault 1 (and 2, 3, 4, 5, 6) 1-90
Earth-fault module connection External fault 1 to 6 B-36
example 13-17 External fault function blocks 10-9
Earth-fault module pin assignment 13-16 External fault response 10-10
Earth-fault monitoring 1-10, 1-19, 1-97, 5- External fault settings 10-10
1, 5-2, Glossary-5
Earth-fault monitoring via the current F
measuring module (internal) 1-8 Factory settings 1-59, 1-60, 14-2,
Earth-fault monitoring with external sum- E- 2, Glossary-6
mation current transformer via the earth- Fault current 5-2
fault module 1-9 Fault memory 1-34
EEx e applications 3-10, 3-15, 5-22 Faults 1-34, 1-58
Electronic overload protection 1-10 FB 62 TIMESTMP function block 10-19
EMC emitted interference according to FB ON 4-16, 4-17
IEC 60947-1 D-2 FC, FO, TC, TO 1-44
EMC stability according to Feedback fault 1-17
IEC 60947-1 D-2 Feedback OFF 15-3
Emergency start 1-14, 1-91, 10-2, 10-16, Feedback ON 4-16, 4-41, 4-44, 15-3
Glossary-5 Feedback time 4-17, 4-18, 4-21, 4-24,
Emergency start executed 1-45 4-26, 4-29, 4-33, 4-36, 4-40, 4-43, 4-47,
Emergency start function block 10-16 4-54, 4-56, 4-59
Enabled control command 4-7 Feeder power consumption 1-16
Enabled control command - OFF 4-49 Flashing 1-15, 11-2, 11-21
4-54, 4-59 Flashing 1 (2, 3) 1-87
Enabled control command - ON 4-49, Flashing logic modules 11-21
4-54 Flashing settings 11-21
Enabled control command - ON > 4-54 Flickering 1-15, 11-2, 11-22
End position 4-49, 15-2 Flickering 1 (2, 3) 1-90
Error buffer / Error protocol read-out Flickering logic modules 11-22
14-13 Flickering settings 11-22
Error message 1-x Frequencies D-2
Error protocolling with timestamp 1-17 Function blocks (alphabetical) 1-85
Error types 12-12 FW version 1-65, 1-66
Evaluating diagnosis data 12-19
Events of the slave diagnostics A-14 G
Example circuits E-1 General fault, general warning 1-43
Exchanging a 3UF52 Operator Panel for a General information about commissioning
3UF720 Operator Panel 13-8 and service 14-2
Execution ON-command 15-2 General representation of the input
Execution STOP-command 15-2 types 7-2
Execution time 4-17, 4-18, 4-21, 4-24 General settings and definitions 4-15
4-26, 4-29, 4-33, 4-36, 4-40, 4-43, 4-47, GSD 12-2
4-49, 4-54, 4-56, 4-59 GSD file 1-81, 12-16
Expansion modules C-14, D-8,
Glossary-5 H
Expansion modules for the Hardware faults 15-3
SIMOCODE pro V device series 1-71 Hardware test 10-5, F-7, F-8
Explosion protection F-1 Heating motor model 1-16, 1-41
Extended control 1-90 HW version 1-65, 1-66
Extended protection 1-89 Hysteresis for 0/4-20 mA 5-16
External current transformer 13-26 Hysteresis for monitoring functions 5-23
External earth fault 15-2 Hysteresis for voltage, cos phi, power
External earth-fault monitoring 1-10, 5-2 5-6, 5-7, 5-9
External earth-fault monitoring (with sum-
mation current transformer) 5-4
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Index-5
Index
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Index-7
Index
SIMOCODE pro
Index-8 GWA 4NEB 631 6060-22 DS 02
Index
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Index-9
Index
SIMOCODE pro
Index-10 GWA 4NEB 631 6060-22 DS 02
Index
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Index-11
Index
SIMOCODE pro
Index-12 GWA 4NEB 631 6060-22 DS 02
Index
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Index-13
Index
V
Voltage in phases 1, 2 and 3 1-16
Voltage measurement 1-8, 1-54
Voltage monitoring 1-11, 1-97, 5-1, 5-8,
Glossary-13
Voltage monitoring for undervoltage 1-8
W
Warning level 0/4 - 20 mA < undershot
15-8
Warning level 0/4 - 20 mA > overshot
15-8
Warning level cos phi 15-7
Warning level I 15-7
Warning level I> overshot 15-7
Warning level P 15-7
Warning level P> overshot 15-7
Warning level U 15-8
Warning/tripping 0/4 - 20 mA B-36
Warnings 1-34, 1-58
Warranty F-9
Watchdog 1-14, 1-100, 10-2, 10-17
Watchdog function block 10-17
Watchdog settings 10-18
Win-SIMOCODE-DP 9-2
Win SIMOCODE DP converter 1-81, 9-2,
Glossary-13
Win SIMOCODE DP parameter files 1-81
Wiring 13-1, 13-10
Wiring the basic units, expansion modules
and decoupling module 13-10
Wiring the removable terminals for
Basic Units 13-12
Wiring the removable terminals of the
Digital Module 13-39
Wiring the removable terminals of the ex-
pansion modules and the decoupling
module 13-22
Writing data 12-3
Writing/reading data records with
STEP7 B-3
Wrong password 15-8
SIMOCODE pro
Index-14 GWA 4NEB 631 6060-22 DS 02
List of Abbreviations
Abbreviation Meaning
AM Analog Module
AS Alarm Switch
AWG American Wire Gauge
Acycl. Acyclic
OP Operator Panel
OPD Operator Panel with Display
OPO Operational Protection OFF
DCM Decoupling Module
DM Digital Module
TO Torque OPEN
TC Torque CLOSED
DP Decentralized Periphery
EM Earth-Fault Module
EMF Electromotive Force
EMC Electromagnetic Compatibility
FMS Fieldbus Message Specification
BU Basic Unit
GSD Device Data
AS Auxiliary Switch
IM Current Measuring Module
MM Memory Module
NTC Negative Temperature Coefficient (resistance dependent on temperature)
OM Object Manager
PCS Process Control System
PDM Process Device Manager
PD Programming Device
PCS Process Control System
PTC Positive Temperature Coefficient (resistance dependent on temperature)
FB Feedback
FO Feedback OPEN
TPF Test Position Feedback
FC Feedback CLOSE
CF Control Function
PLC Programmable Logical Controller
Th Thermistor
TM Temperature Module
UM Current/Voltage Measuring Module
LC Local control
Cycl. Cyclic
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Abbreviations-1
List of Abbreviations
SIMOCODE pro
Abbreviations-2 GWA 4NEB 631 6050-22 DS 02
Glossary
Addressing Plug
The Addressing Plug is necessary to enable the "hardware-
related" allocation of the PROFIBUS DP address to a Basic
Unit without a PC/programming device.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Glossary-1
Glossary
Baud Rate
The Baud Rate is the speed with which data is transferred
and indicates the number of transmitted bits per second
(Baud Rate = Bit Rate).
With PROFIBUS DP, Baud Rates from 9.6 kBaud to 12 MBaud
are possible.
Bus
A common transmission path with which all stations are
connected. It has two defined ends.
With PROFIBUS, the bus is a two-wire line (copper
conductor) or a fiber optic cable.
Bus Segment
The PROFIBUS DP consists of at least one bus segment. A
bus segment has at least two stations, one of which must be
a DP master. A maximum of 32 stations can be connected to
a bus segment.
Class
The Class (Tripping Class) indicates the maximum tripping
time in which SIMOCODE must trip a current that is 7.2 times
the value of the Set Current (Is) in a cold state (Motor
Protection according to IEC 60947). If Class 10 is set for
SIMOCODE pro (for example), it is guaranteed that if a
current that is 7.2 times the Set Current occurs, the (cold)
motor will switch off after 10 seconds. The Tripping Class can
be set to 8 different settings ranging from Class 5 to Class
40.
Class 1 Master
Active stations on PROFIBUS DP. The Cyclic Data exchange
with other stations is characteristic for this type of master.
Typical Class 1 Masters are, for example, PLCs with a
PROFIBUS DP connection.
Class 2 Master
Optional stations on PROFIBUS DP.
Typical Class 2 Masters are, for example,
• PC/programming devices with the
"SIMOCODE ES professional" software
• PDM (PCS7)
• PC with "SIMARIS manager" software (power
management).
SIMOCODE pro
Glossary-2 GWA 4NEB 631 6050-22 DS 02
Glossary
5 minutes.
Supply voltage failures of SIMOCODE pro during this time
extend the specified time correspondingly.
Connecting cable
Connecting cables are necessary for connecting the
individual Basic Units with their Current Measuring Modules
and, if required, with their Expansion Modules or Operator
Panels. They are available in various versions and lengths
(ribbon cable 0.025 m, 0.1 m, 0.5 m; round cable 2.0 m). The
total length of all connecting cables must not exceed 3 m per
system!
Control Functions
Control functions (e.g. Direct Starters, Reversing Starters)
are used for controlling load feeders. They have the following
important features:
• Monitoring the switch-on/switch-off process (no current
flows in the main circuit without the ON command)
• Monitoring the OFF state (no current flows in the main
circuit without the ON command)
• Monitoring the ON status
• Tripping if a fault occurs.
Control Stations
Control Stations are places from which Control Commands
are issued to the motor. The "Control Stations" function block
is used for administration, switching and prioritization of
these different Control Stations. With this, SIMOCODE pro
allows the parallel administration of up to four different
Control Stations. Dependent on the Control Function, up to 5
different Control Commands can be transmitted from every
Control Station to SIMOCODE pro.
• Local control, in the direct vicinity of the motor. Control
commands via pushbuttons.
• PLC/PCS, switching commands are issued by the
automation system (remote).
• PC, Control Commands are issued via an operator control
station or via PROFIBUS DPV1 with the SIMOCODE ES
software.
• Operator Panel / Operator Panel with Display, Control
Commands are issued via the buttons of the Operator
Panel / Operator Panel with Display in the switchgear
cabinet door.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Glossary-3
Glossary
Decoupling Module
A module for the upstream (series) connection of a Current/
Voltage Measuring Module to the system interface when
voltage and power measurements are implemented in non-
earthed networks.
Door Adapter
The door adaptor is necessary for making the system
interface of a Basic Unit available at an easily accessible
location (e.g. front panel), thus enabling fast
parameterization.
SIMOCODE pro
Glossary-4 GWA 4NEB 631 6050-22 DS 02
Glossary
DP Master
A master which works with the DP protocol according to the
EN 50 170 standard, Volume 2, PROFIBUS.
Cyclic Send Data is exchanged between the DP master and
the DP slave once in every DP cycle. The DP master sends
the Cyclic Receive Data to SIMOCODE pro. In response,
SIMOCODE pro sends the Cyclic Send Data to the DP
master.
Earth-Fault Monitoring
See Monitoring Earth Faults.
Emergency Start
The Emergency Start deletes the Thermal Memory from
SIMOCODE pro each time it is activated. This enables
immediate Restarting of the motor after an Overload Trip.
This function can be used to:
• Enable an immediate Restart/Reset after an Overload Trip
• Influence the operation of the Thermal Memory (Motor
Model), if required.
Since the Emergency Start is edge-triggered, this function
cannot permanently affect the Thermal Motor Model.
Expansion Modules
Expansion Modules are intended as optional additions for the
SIMOCODE pro V device series. The following Expansion
Modules are available:
• Digital Module (DM)
• Analog Module (AM)
• Earth-fault Module (EM)
• Temperature Module (TM).
All Expansion Modules have the same design with an
enclosure width of 22.5 mm. They are equipped with
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Glossary-5
Glossary
Factory Settings
The Factory Settings are used to reset all parameters of a
device to the default settings to which they were set at the
factory.
The Factory Settings can be configured using the "TEST/
RESET" button on the Basic Unit or via the SIMOCODE ES
software.
Function Block
Defined group of functions that can be freely-parameterized
by the user and connected to other Function Blocks in order
to create a complete branched logic system. This means
conventional wired control circuits containing Auxiliary Relays
and Time Relays can be completely replaced.
Independent Operation
SIMOCODE pro C and pro V protect and control the motor
feeder independent of the automation system. Even if the
automation system (PLC) fails, or if communication is
disrupted, the motor feeder remains fully protected and
controllable. SIMOCODE pro can be used without being
connected to PROFIBUS DP. This can easily be connected
later as applicable.
Logic Module
Logical Functions, Time Relay Functions and Counter
Functions are implemented using Logic Modules.
Master
PROFIBUS DP is based on a Master-Slave architecture.
Telegrams are sent from the Master to the actuated station
(Slave) and are answered by it in return.
Memory Module
The Memory Module is plugged into the system interface
and is used for fast reading in or out of the entire
SIMOCODE pro parameterization, e.g. if a unit is exchanged.
Monitoring 0/4-20 mA
SIMOCODE pro supports two-phase monitoring of the
Analog Signals of a transducer (standard 0/4 - 20 mA Output
Signal). The Analog Signals are fed to the "0/4 - 20 mA"
Function Block via the Analog Module.
SIMOCODE pro
Glossary-6 GWA 4NEB 631 6050-22 DS 02
Glossary
Monitoring Functions
The following Monitoring Functions
• Earth-Fault Monitoring
• Current Limit Monitoring
• Voltage Monitoring
• Power Factor (cos phi) Monitoring
• Active Power Monitoring
• 0/4 A - 20 mA Signal Monitoring
• Operation Monitoring
• Analog Temperature Monitoring
operate "in the background" in the same way as Motor
Protection and Motor Control. They can be active or not,
according to the control function selected.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Glossary-7
Glossary
Motor Protection
The Basic Unit has several protection mechanisms for
current-dependent Motor Protection:
• Overload Protection
• Unbalance Protection
• Stalled Rotor Protection
• Thermistor Protection.
SIMOCODE pro
Glossary-8 GWA 4NEB 631 6050-22 DS 02
Glossary
protocol. It contains all the status LEDs that are also present
on the Basic Unit and provides a system interface outside the
switchgear cabinet. Its keys can be used to control the motor
and to navigate the display menu.
The Operator Panel with Display can only be used in
combination with Basic Unit 2 (SIMOCODE pro V) from
product version *E03* onwards.
Operation Monitoring
SIMOCODE pro can monitor the Operating Hours and Stop
Times of a motor and restrict the Number of Start-Ups in a
defined time frame in order to avoid plant downtimes due to
failed motors caused by running or being stopped for too
long.
Overload Protection
SIMOCODE pro protects three-phase and AC motors
according to IEC 60947-4-1. The tripping class can be set to 8
different settings, ranging from Class 5 to Class 40.
Pause Time
The Pause Time is the specified time for the Cooling
Response of the Motor when tripped under normal operating
conditions (not in the case of an Overload Trip!). After this
interval, the Thermal Memory in SIMOCODE pro is deleted
and a new cold start is possible. This makes frequent start-
ups possible within a short period of time.
PC Cable
A PC can be connected to the system interface of a Basic
Unit for device parameterization using the PC cable and the
serial interface.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Glossary-9
Glossary
PROFIBUS
Process Fieldbus, European process and fieldbus standard as
defined in the PROFIBUS standard (EN 50 170, Volume 2,
PROFIBUS).
It lays down the functional, electrical and mechanical
properties for a serial bit fieldbus system.
PROFIBUS is a bus system that networks PROFIBUS-
compatible automation systems and field devices at the
cabinet and field level. PROFIBUS is available with the DP
protocols (decentralized periphery), FMS (fieldbus message
specification), PA (process automation) or TF (technological
functions).
PROFIBUS DP
PROFIBUS bus system with the DP protocol (decentralized
periphery).
The main task of PROFIBUS DP is fast Cyclic Data exchange
between the central DP devices and the periphery devices.
PROFIBUS DP Interface
SIMOCODE pro has an integrated PROFIBUS DP interface
(SUB-D socket or terminal connection on the Basic Units).
PROFIBUS DPV1
Expansion of the DP protocol.
This enables Acyclic Data exchange of Parameter, Diagnosis,
Receive and Test Data.
SIMATIC
Term for industrial automation products and systems from
Siemens AG.
SIMATIC PDM
You can also configure SIMOCODE pro via the SIMATIC PDM
(Process Device Manager).
The following options are available:
• SIMATIC PDM as a stand-alone program
• PDM, integrated into STEP7.
SIMOCODE pro
Glossary-10 GWA 4NEB 631 6050-22 DS 02
Glossary
SIMOCODE ES
Standard parameterization software for SIMOCODE pro,
which can be run on a PC/programming device under
Windows 2000 or Windows XP.
Slave
PROFIBUS DP is based on a Master-Slave architecture.
Telegrams are sent from the Master to the actuated station
(Slave) and are answered by it in return.
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Glossary-11
Glossary
Standard Function
Standard functions are typical motor functions that can be
activated according to need and, as applicable, individually
set for each motor feeder.
They are already available, work independently of the
selected control function and can be used/activated as
optional additions.
Station
Device which can send, receive or amplify data via the bus,
e.g. Master, Slave.
Statistical Data
SIMOCODE pro makes Statistical Data available which can be
read out with SIMOCODE ES under Target System >
Service Data/Statistical Data (for example).
STEP7
Engineering system. Contains programming languages for
creating user programs for SIMATIC-S7 controls.
Tripping Class
See "Class".
SIMOCODE pro
Glossary-12 GWA 4NEB 631 6050-22 DS 02
Glossary
Temperature Monitoring
See Temperature Module (TM).
Thermistor Protection
The Basic Units (BU1 and BU2) also make it possible to
connect thermistor sensors (binary PTC) for monitoring the
motor temperature.
Unbalance Protection
The extent of the Phase Unbalance can be monitored and
transmitted to the Control System. A definable and delayable
response can be tripped when an adjustable limit has been
overshot. If Phase Unbalance is greater than 50 %, a
reduction in the Tripping Time according to the overload
characteristic curve takes place automatically since the heat
development in motors increases under asymmetrical
conditions.
Voltage Monitoring
See Monitoring the Voltage
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02 Glossary-13
Glossary
SIMOCODE pro
Glossary-14 GWA 4NEB 631 6050-22 DS 02
From (please complete)
Name
Company/Department
To
SIEMENS AG Address
A&D CD MM3
Telephone
92220 Amberg, Germany
Fax
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 02
Siemens Aktiengesellschaft