Sei sulla pagina 1di 27

Tank venting diameter according API 2000

Operating conditions Auxiliary variables


Water flow entering the tank Evacuation flow (API 2000)
Q= 200 m3/h See sheet. "2 -Venting flow"
Local temperature and heigth above sea level In the case of water, select
tamb = 10 °C the case of boiling lower
H= 2638 m.a.s.l. than 149 ° C.
Allowable overpressure in tank For a movement of fluid into the
DP = 17.2 kPa (*) tank (air leaving the tank), the
venting requirement ratio is
Air properties Vn_unit = 2.02
Local atmospheric pressure (Nm3_air/h)/(m3_liq/h)

p= 101,325* (1 -2,25577E-5 * H)^5,25588 (from sheet 2.- Venting flow)


H= 2638 m.a.s.l.
p= 73.40 kPa For a water flow entering the tank
Ratio of specific weights Q= 200 m3/h
k= 1.4 The required venting is
(the value of "k" is practically constant Vn = Vn_unit * Q
in a wide range) Vn_unit = 2.02
Air molar mass Q= 200 m3/h
M= 28.97 kg/kmol Vn = 404 Nm3/h
Compression factor
Z= 0.99973 - Eq. 1
(this value is practically constant in Venting area is determined by equation of API 2000 [1]
the normaly used range) A= Q / (12503*Pin * ( (1/(M*T*Z)*(k/(k-1))
cjc. Rev. 10.08.2016

Air temperature Venting area. Eq. 1


t= 10 °C Q= 404.0 Nm3/h
Pin = Q
T= 283.15 K 0.906 bar Pamb
M= 28.97 kg/kmol d
Pin
Outside pressure T= 283.15 K
Pamb = t
73.4 kPa Z= 0.9997 -
Pout = Pamb Pa k= 1.4 -
Pout = 73.40 kPa Pout = 0.734 bar Fig. Venting in roof tank
Pout = 0.734 bar A= 8.30 cm²

Inside pressure
Pin = Pout + DP Calculated diameter
Pout = 73.40 kPa d= 2 * (A / (p) )^0.5
DP = 17.2 kPa A= 8.3 cm²
Pin = 90.6 kPa d= 3.25 cm Eq. 1
Pin = 0.906 bar (abs) d= 32.5 mm
Q
d= 1.28 in A=

√ [( ) ( ) ]
P 2 P k+1
1 k
12503⋅Pin⋅ ⋅ ⋅ out k − out k
M⋅T⋅Z k−1 Pin Pin
Selected diameter
Sea d = 4 in

by equation of API 2000 [1] (*) tank overpressure


(1/(M*T*Z)*(k/(k-1))) * ( (Pout/Pin )^(2/k) - (Pout/Pin )^((k+1)/k) ) )^0.5 ) 17.2 kPag = 2.5 psig
cjc. Rev. 10.08.2016

[( ) ( ) ]
P 2 P k+1
k
⋅ out k − out k
k−1 Pin Pin
API 2000

Venting flow
For the case of water, select the case of
a boiling point lower than 149 °C.
For a movement of fluid into the tank
(air leaving the tank), the venting
requirement is obtained from Table 1B
Vn/Q = 2.02 Nm3/h air / m3/h liquid

For a water flow entering the tank


Q= 200 m3/h
The venting requirement is
Vn = (Vn/Q) *Q
Vn/Q = 2.02
Q= 200 m3/h
Vn = 404 Nm3/h
cjc. Rev. 10.08.2016

Normal venting requirement


Vn/Q = 2.02 Nm3/h air / m3/h liquid
Nm3/h air / m3/h liquid
√ [( ) ( ) ]
P out 2k Pout k +1
1 k k
Q=12503⋅Pin⋅A⋅ ⋅ ⋅ −
M⋅T⋅Z k−1 Pin Pin A=

Q
A=

√ [( ) ( ) ]
Pout 2k P out k +1
1 k k
12503⋅Pin⋅ ⋅ ⋅ −
M⋅T⋅Z k−1 Pin Pin
cjc. Rev. 10.08.2016

Q= 404.0 Nm3/h
Pin = 0.906 bar
k= 1.4 -
M= 29.0 kg/kmol
T= 283.2 K
Z= 1.0 -
Pout = 0.734 bar

A= 8.30 cm²

Q / (12503*Pin * ( (1/(M*T*Z)*(k/(k-1))) * ( (Pout/Pin )^(2/k) - (Pout/Pin )^((k+1)/k) ) )^0.5 ) (4B)


√ [( )
2
1 k P out k
Q=278700⋅Pin⋅A⋅ ⋅ ⋅
M⋅T⋅Z k−1 Pin

Q
A=

278700⋅Pin⋅
1


k

Pout 2k
M⋅T⋅Z k−1 Pin

[( )
A = Q / (278700*Pin * ( (1/(M*T*Z)*(k/(k-1))

Q= 404.0
Pin = 0.906
k= 1.4
M= 29.0
T= 283.2
Z= 1.0
Pout = 0.7
cjc. Rev. 10.08.2016
Normal to real flow

√ [( ) ( ) ]
P out 2k Pout k+1
1 k k Flujo volumétrico normal
⋅Pin⋅A⋅ ⋅ ⋅ − Vn =
M⋅T⋅Z k−1 Pin Pin 1.000 Nm3

Normal conditions
Q Pn = 101,325 Pa

⋅Pin⋅
√ 1

k

M⋅T⋅Z k−1 Pin [( ) ( ) ]
Pout 2k

P out k +1
Pin
k
Tn = 273

Local atmospheric presure


Patm_loc = 101.33 kPa
K

Pin * ( (1/(M*T*Z)*(k/(k-1))) * ( (Pout/Pin )^(2/k) - (Pout/Pin )^((k+1)/k) ) )^0.5 ) Operation conditions


Pop = 17.2 kPa g
Nm /h 3
Q= 16,862 SCF top = 60 °F
bar (abs) Pin = 13.1405 psia top = 15.6 °C
- k= 1.4
kg/kmol M= 29.0 Operation absolute pressure
K T= 509.67 R Pop = Patm_loc + Pop
- Z= 1.0 Patm_loc = 101.33 kPa
bar Pout = 10.6458 Pop = 17 kPa g
A= 1.44 in² Pop = 118.53 kPa
A= 9.28 cm² Pop = 118,525 Pa

Operation temperature
Top = 289 K
Real volumetric flow rate

V= (Pn/Pop) * (Top/Tn) * Vn
Pn = 101,325 Pa
Tn = 273 K
Pop = 90,600 Pa (abs)
Top = 289 °C
Vn = 1.00 Nm3
V= 1.18 m3
V= 41.74 scf

1 m3 = 35.31 cf
1 Nm³ = 41.74 scf
1 bar = 14.50377 psi
1 in² = 6.4516 cm²
Compressibility factor for air (experimental values)
Pressure, bar (absolute)
Temp, K 1 5 10 20 40 60 80 100 150
75 0.0052 0.026 0.0519 0.1036 0.2063 0.3082 0.4094 0.5099 0.7581
80 0.025 0.0499 0.0995 0.1981 0.2958 0.3927 0.4887 0.7258
90 0.9764 0.0236 0.0453 0.094 0.1866 0.2781 0.3686 0.4681 0.6779
100 0.9797 0.8872 0.0453 0.09 0.1782 0.2635 0.3498 0.4337 0.6386
120 0.988 0.9373 0.886 0.673 0.1778 0.2557 0.3371 0.4132 0.5964
140 0.9927 0.9614 0.9205 0.8297 0.5856 0.3313 0.3737 0.434 0.5909
160 0.9951 0.9748 0.9489 0.8954 0.7803 0.6603 0.5696 0.5489 0.634
180 0.9967 0.9832 0.966 0.9314 0.8625 0.7977 0.7432 0.7084 0.718
200 0.9978 0.9886 0.9767 0.9539 0.91 0.8701 0.8374 0.8142 0.8061
250 0.9992 0.9957 0.9911 0.9822 0.9671 0.9549 0.9463 0.9411 0.945
283 0.999662 0.99768 0.995258 0.990648 0.983336 0.978132 0.97534 0.975354 0.986184
300 0.9999 0.9987 0.9974 0.995 0.9917 0.9901 0.9903 0.993 1.0074
350 1 1.0002 1.0004 1.0014 1.0038 1.0075 1.0121 1.0183 1.0377
400 1.0002 1.0012 1.0025 1.0046 1.01 1.0159 1.0229 1.0312 1.0533
450 1.0003 1.0016 1.0034 1.0063 1.0133 1.021 1.0287 1.0374 1.0614
500 1.0003 1.002 1.0034 1.0074 1.0151 1.0234 1.0323 1.041 1.065
600 1.0004 1.0022 1.0039 1.0081 1.0164 1.0253 1.034 1.0434 1.0678
800 1.0004 1.002 1.0038 1.0077 1.0157 1.024 1.0321 1.0408 1.0621
1000 1.0004 1.0018 1.0037 1.0068 1.0142 1.0215 1.029 1.0365 1.0556
al values)

200 250 300 400 500


1.0125
0.9588 1.1931 1.4139
0.8929 1.1098 1.311 1.7161 2.1105
0.8377 1.0395 1.2227 1.5937 1.9536
0.772 0.953 1.1076 1.5091 1.7366
0.7699 0.9114 1.0393 1.3202 1.5903
0.7564 0.884 1.0105 1.2585 1.497
0.7986 0.9 1.0068 1.2232 1.4361
0.8549 0.9311 1.0185 1.2054 1.3944
0.9713 1.0152 1.0702 1.199 1.3392
1.011758 1.049322 1.095742 1.204478 1.324086
1.0326 1.0669 1.1089 1.2073 1.3163
1.0635 1.0947 1.1303 1.2116 1.3015
1.0795 1.1087 1.1411 1.2117 1.289
1.0913 1.1183 1.1463 1.209 1.2778
1.0913 1.1183 1.1463 1.2051 1.2667
1.092 1.1172 1.1427 1.1947 1.2475
1.0844 1.1061 1.1283 1.172 1.215
1.0744 1.0948 1.1131 1.1515 1.1889
Bernoulli Equation http://www.engineeringtoolbox.com

Conservation of energy - non-viscous, incompressible fluid in


A statement of the conservation of energy in a form useful for solving problems involving fluids. For a non-viscous, incom

A special form of the Euler’s equation derived along a fluid flow streamline is often called the Bernoulli Equation

For steady state incompressible flow the Euler equation becomes (1). If we integrate (1) along the streamline it becomes

Head of Flow
Equation (3) is often referred to the head because all elements has the unit of length.

Dynamic Pressure

(2) and (3) are two forms of the Bernoulli Equation for steady state incompressible flow. If we assume that the gravitation
negligible, (3) can be written as (4). Both elements in the equation have the unit of pressure and it's common to refer the
component as the dynamic pressure of the fluid flow (5).

Since energy is conserved along the streamline, (4) can be expressed as (6). Using the equation we see that increasing
flow will reduce the pressure, decreasing the velocity will increase the pressure.

This phenomena can be observed in a venturi meter where the pressure is reduced in the constriction area and regaine
observed in a pitot tube where the stagnation pressure is measured. The stagnation pressure is where the velocity com

Example - Bernoulli Equation and Flow from a Tank through a small Orifice
Liquid flows from a tank through a orifice close to the bottom. The Bernoulli equation can be adapted to a streamline from
Since (1) and (2)'s heights from a common reference is related as (e2), and the equation of continuity can be expressed

Vented tank
A special case of interest for equation (e4) is when the orifice area is much lesser than the surface area and when the pre

"The velocity out from the tank is equal to speed of a freely body falling the distance h." - also known as

Example - outlet velocity from a vented tank

The outlet velocity of a tank with height 10 m can be calculated as

V2 = (2 (9.81 m/s2) (10 m))1/2

= 14 m/s

Pressurized Tank
If the tanks is pressurized so that product of gravity and height (g h) is much lesser than the pressure difference divided b

The velocity out from the tank depends mostly on the pressure difference.

Example - outlet velocity from a pressurized tank

The outlet velocity of a pressurized tank where

p1 = 0.2 MN/m2

p2 = 0.1 MN/m2

A2/A1 = 0.01

h = 10 m

can be calculated as

V2 = ( (2/(1-(0.01)2) ((0.2 106 N/m2) - (0.1 106 N/m2))/(1000 kg/m3) + (9.81 m/s2)(10 m)))1/2

= 19.9 m/s

Coefficient of Discharge - Friction Coefficient


Due to friction the real velocity will be somewhat lower than this theoretic examples. If we introduce a

The coefficient of discharge can be determined experimentally. For a sharp edged opening it may bee as low as
tp://www.engineeringtoolbox.com/bernouilli-equation-d_183.html

pressible fluid in steady flow


fluids. For a non-viscous, incompressible fluid in steady flow, the sum of pressure, potential and kinetic energies per unit volume is constan

the Bernoulli Equation

along the streamline it becomes (2). (2) can further be modified to (3) by dividing by gravity.
f we assume that the gravitational body force is
ure and it's common to refer the flow velocity

equation we see that increasing the velocity of the

he constriction area and regained after. It can also be


essure is where the velocity component is zero.

a small Orifice
n be adapted to a streamline from the surface (1) to the orifice (2) as (e1):
of continuity can be expressed as (e3), it's possible to transform (e1) to (e4).

he surface area and when the pressure inside and outside the tank is the same - when the tank has an open surface or "vented" to the atmo

- also known as Torricelli's Theorem.

the pressure difference divided by the density, (e4) can be transformed to (e6).

e introduce a friction coefficient c (coefficient of discharge), (e5) can be expressed as (e5b).

ng it may bee as low as 0.6. For smooth orifices it may bee between 0.95 and 1.
er unit volume is constant at any point
e or "vented" to the atmosphere. At this situation the (e4) can be transformed to (e5).
Flujo real a normal Normal volumetric flow rate Normal to real flow

Real flow rate data Vn = (Pop/Pn) * (Tn/Top) * V Flujo volumétrico normal


V= 262 m3/h Pop = 90,600 Pa Vn =
t= 10 °C Pn = 101,325 Pa
P= 17.2 kPa(g) Tn = 273 K Normal conditions
Top = 283 °C Pn =
Normal conditions V= 262.0 m3/h Tn =
Pn = 101,325 Pa Vn = 226.0 Nm3/h
Tn = 273 K Local atmospheric presure
Patm_loc =
Local atmospheric presure
Patm_loc = 73.40 kPa Operation conditions
Pop =
Operation absolute pressure top =
Pop = Patm_loc + Pop
Patm_loc = 73.40 kPa Operation absolute pressure
Pop = 17 kPa g Pop =
Pop = 90.60 kPa Patm_loc =
Pop = 90,600 Pa Pop =
Pop =
Operation temperature Pop =
Top = 283 K
Operation temperature
Top =
cjc. Rev. 10.08.2016

Normal to real flow Real volumetric flow rate

Flujo volumétrico normal V= (Pn/Pop) * (Top/Tn) * Vn


404.0 Nm3/h Pn = 101,325 Pa
Tn = 273 K
Normal conditions Pop = 90,600 Pa
101,325 Pa Top = 283 °C
273 K Vn = 404.000 Nm3/h
V= 468.37 m3/h
Local atmospheric presure
73.40 kPa

Operation conditions
17.2 kPa g
10 °C

Operation absolute pressure


Patm_loc + Pop
73.40 kPa
17 kPa g
90.60 kPa
90,600 Pa

Operation temperature
283 K
[1]

Potrebbero piacerti anche