Power Factor (PF) is the ratio of real power to the apparent power flowing to the
load from the source. It is measured between 0 and 1.0 (unity) and is usually
deemed as either leading or lagging, depending on the position of the current
waveform with respect to the voltage.
In an electric power system, a load with a low power factor (tending towards zero)
draws more current than a load with a high power factor (tending towards one) for
the same amount of useful power transferred. The higher currents increase the
energy lost in the distribution system and require larger wires and other equipment.
Because of the costs of larger equipment and wasted energy, electrical utilities will
usually charge a higher cost to industrial or commercial customers where there is a
low power factor. Linear loads with low power factor (such as induction motors)
can be corrected with a passive network of capacitors or inductors. On-linear loads,
such as rectifiers, distort the current drawn from the system. In such cases, active
or passive power factor correction may be used to counteract the distortion and
raise the power factor. The devices for correction of the power factor maybe at a
1
central substation, spread out over a distribution system, or built into power-
consuming equipment. A high power factor is generally desirable in a transmission
system to reduce transmission losses and improve voltage regulation at the load. It
is often desirable to adjust the power factor of a system to near 1.0. When reactive
elements supply or absorb reactive power near the load, the apparent power is
reduced. Power factor correction may be applied by an electrical power
transmission utility to improve the stability and efficiency of the transmission
network. Individual electrical customers who are charged by their utility for low
power factor may install correction equipment to reduce those costs. Motors driven
by Variable Speed Drives will use the same powers before, but may draw more
current, it should be noted that with reduced stored energy in the DC Bus
capacitors, they may be more vulnerable to power dips
2
HOW TO IMPROVE POWER FACTOR?
Power factor correction is achieved by the addition of capacitors in parallel with
the connected motor or lighting circuits and can be applied at the equipment,
distribution board or at the origin of the installation. Static power factor correction
can be applied at each individual motor by connecting the correction capacitors to
the motor starter. A disadvantage can occur when the load on the motor changes
and can result in under or over correction. Static power factor correction must not
be applied at the output of a variable speed drive, solid state soft starter or inverter
as the capacitors can cause serious damage to the electronic components. Over-
correction should not occur if the power factor correction incorrectly sized.
Typically the power factor correction for an individual motor is based on the non-
load (magnetizing) power since the reactive load of a motor is comparatively
constant compared to actual kW load over compensation should be avoided. Care
should be taken when applying power factor correction star/delta type controls that
the capacitors are not subjected torpid on-off-on conditions. Typically the
correction would be placed on either the Main or Delta contactor circuits. Power
factor correction applied at the origin of the installation consists of a controller
monitoring the VA’s and this controller switches capacitors in or out to maintain
the correction is installed, other loads can in theory be connected anywhere on the
network. Power factor better than a preset limit (typically 0.95).Where ‘bulk’
power factor
POWER FACTOR IMPROVEMENT USING SHUNT CAPACITORS
Shunt capacitors are used in rating from 15KVAR to 10000 KVAR . Small
bank of capacitors, up to a few hundred KVAR rating are used to an individual
distribution capacitor circuit of costumers. Capacitor bank of 500-3000 KVAR are
used in small distribution substations and those with still larger rating n larger
substation.
3
Capacitors are installed either in groups at once central location , at the primary or
the secondary of transformer or individually on each motor or brunch circuit
feeding group of motors ,They are arranged in 3-phase banks connected n star or
delta.
It is not economical to raise the power factor to unity for the following reasons:
1-If the power factor is improved to unity for full load conditions, the PF would
become leading the load is less than full load (unless some capacitors are switched
off which is generally difficult).
2-As the PF approaches unity, the capacity of power improvement device increases
more rapidly e.g. the PF of an installation can be improved from 0.8 to 0.9 by
much smaller capacitive KVAR than which will be needed to raise PF from 0.9 to
unity.
3-Improvement in PF means a reduction in KVA charge. However installation of
PF improvement devices needs capital investment. The PF should be improved to
such an extent that the saving is maximum.
4
DISADVANTAGES OF LOW POWER FACTOR
Many engineers are oblivious to the effects of low power factor. They view it only
as a direct charge on their electrical bill, and only when stated as such. Low power
factor is a direct cost to the utility company and must be paid for. Direct costs of
low power factor Power factor may be billed as one of or combination of, the
following:
1) A penalty for power factor below and a credit for power factor above a
predetermined value,
2) An increasing penalty for decreasing power factor,
3) A charge on monthly KVAR Hours,
4) KVA demand: A straight charge is made for the maximum value of KVA used
during the month. Included in this charge is a charge for KVAR since KVAR
increase the amount of KVA. Indirect costs of low power factor Loss in efficiency
of the equipment: When an installation operates with a low power factor, the
amount of useful power available inside the installation at the distribution
transformers is considerably reduced due to the amount of reactive energy that the
transformers have to carry. The figure below indicates the available actual power
of distribution equipment designed to supply 1000 KW.
Lighting
Incandescent Lamps: The power factor is equal to unity. Fluorescent Lamps:
Usually have a low power factor, for example, 50% power factor would not be
unusual. They are sometimes supplied with a compensation device to correct low
power factor. Mercury Vapor Lamps: The power factor of the lamp is low; it can
vary between 40% to 60%, but the lamps are often supplied with correction
devices.
Distribution Transformer
The power factor varies considerably as a function of the load and the design of the
transformer. A completely unloaded transformer would be very inductive and have
a very low power factor.
Electrical Motors
Induction Motors: The power factor varies in accordance with the load. Unloaded
or lightly loaded motors exhibit a low power factor. The variation can be 30% to
90%.Synchronous Motors: Very good power factor when the excitation is properly
adjusted. Synchronous motors can be over excited to exhibit a leading power factor
and can be used to compensate a low power system.
7
Industrial Heating
With resistance, as in ovens or dryers, the power factor is often closed to 100%.
Welding
Electric arc welders generally have a low power factor, around 60%.Other types of
machinery or equipment those are likely to have a low power factor.
8
passive power factor correction and active power factor correction. Passive PFC is
the simpler route of the two. It is generally done by introducing an inductance to a
system to counteract the reactive current due to capacitance. Recall that inductors
introduce positive reactive power while capacitors introduce negative reactive
power. So if there is a large capacitive value associate with a system, there will be
large amount of negative reactive power. Introducing an inductance to the system
will counteract this effect by bringing the negative reactive power back towards
zero.
Active PFC involves using complex circuitry to counteract the effects of the
reactive components. Such a discussion is beyond the scope of this paper but the
concept is similar to the tug of war reference. Most power sources and systems
manufactured presently utilize active power factor correction. The reason is
because once a source or system reaches a certain size (over about 200-250VA),
the inductor necessary for passive PFC becomes too large for a feasible design.
9
POWER FACTOR CORRECTION: ADVANTAGES
There are several advantages in utilizing power factor correction capacitors.
These include:
REDUCED DEMAND CHARGES
Most Utility companies charge for maximum metered demand based on either the
highest registered demand in kilowatts (KW meter), or a percentage of the highest
registered demand in KVA (KVA meter),Whichever is greater? If the power factor
is low, the percentage of the measured KVA will be significantly Greater than the
KW demand. Increasing the power factor will, therefore, lower the demand charge.
INCREASED LOAD CARRYING CAPABILITIES IN EXISTING
CIRCUITS
Loads drawing reactive power also demand reactive current. Installing capacitors
at the end of existing circuits near the inductive loads reduces the current carried
by each circuit. The reduction in current flow resulting from improved power
factor may allow the circuit to carry new loads, saving the cost of upgrading the
distribution network when extra capacity is required for additional machinery. In
addition, the reduced current flow reduces resistive losses in the circuit.
IMPROVED VOLTAGE
A lower power factor causes a higher current flow for a given load. As the line
current increases, the voltage drop in the conductor increases, which may result in
a lower voltage at the equipment. With an improved power factor, the voltage drop
in the conductor is reduced, improving the voltage at the equipment.
REDUCED POWER SYSTEM LOSSES
Although the financial return from conductor loss reduction alone is seldom
sufficient to justify the installation of capacitors, it is sometimes an attractive
additional benefit; especially in older plants with long feeders or in field pumping
10
operations. System conductor losses are proportional to the current squared and,
since the current is reduced in direct proportion to the power factor improvement,
the losses are inversely proportional to the square of the power factor.
FIXED VERSUS AUTOMATIC CAPACITORS
What is the difference between fixed and automatic Power Factor Correction
Capacitors? Fixed capacitor banks are “on” at all times, regardless of the load in
the facility, while an automatic capacitor bank varies the amount of correction
(KVAR) supplied to an electrical system. An automatic capacitor is much more
expensive per kVAR (3 to 5 times) than a fixed system.100 kVAr of fixed
capacitors will save as much power factor penalties as a 100 kVAr automatic
capacitor. Generally, when a capacitor is connected to a system there is a reduction
in amperage on the system (the lower the power factor the greater the KVA
reduction). This reduction in amperage reduces the voltage drop across a
transformer, which results in a higher voltage in the system. If 100 kVAr is
connected to a1000 KVA transformer, there is approximately a ¾% voltage rise on
the system (if there are no other loads on the system). The more kVAr connected,
the higher the voltage rise. This voltage rise is counter acted by the increase of load
in the facility. Typically, in the night and on weekends, utility voltage is higher
than normal, and facilities that are not normally loaded during these times, could
experience a higher than normal voltage rise if too much capacitance is connected
to their system. Based on this, we generally limit fixed capacitors to 10% to 15%
fixed kVAR to KVA of transformer size. We would recommend an automatic
capacitor bank if the amount of kVAR exceeds 20% of the KVA size of the
transformer.
TYPES OF POWER FACTOR CORRECTION
There are no general rules applicable to every type of installation and, in theory,
capacitors can be installed at any point, but it is necessary to evaluate the relevant
11
practical and economic feasibility. According to the location modalities of the
capacitors, the main methods of power factor correction are:
1-Distributed power factor correction
Distributed power factor correction is achieved by connecting capacitor bank
properly sized directly to the terminals of the load which demands reactive power.
The installation is simple and inexpensive; capacitor and load can use the same
protective devices again Stover currents and are connected
12
method reaching a compromise between the inexpensive solution and the proper
management of the installation since the benefits deriving from power factor
correction shall be felt only by the line upstream the point where the capacitor
bank is located.
13
such way, the distributed compensation is used for high-power electrical
equipment and the centralized modality for the remaining part. Combined power
factor correction is prevailingly used in installations where large equipment only
are frequently used; in such circumstances their power factor is corrected
individually, whereas the power factor of small equipment is corrected by the
centralized modality.
5- Automatic power factor correction
In most installations there is not a constant absorption of reactive power for
example due to working cycles for which machines with different electrical
characteristics are used. In such installations there are systems for automatic power
factor correction which, thanks to a monitoring varmetric device and a power
factor regulator, allow the automatic switching of different capacitor banks, thus
following the variations of the absorbed reactive power and keeping constant the
power factor of the installation constant. An automatic compensation system is
formed by:• some sensors detecting current and voltage signals; an intelligent unit
which compares the measured power factor with the desired one and operates the
connection and disconnection of the capacitor banks with the necessary reactive
power (power factor regulator); an electric power board comprising switching and
protection devices some capacitor banks. To supply a power as near as possible to
the demanded one, the connection of the capacitors is implemented step by step
with a control accuracy which will be the greater the more steps are foreseen and
the smaller the difference is between them.
• Shorter return on investment. Even though the initial cost of the At Load
system will be higher than the cost of the Service Entrance system, the savings are
greater. The service entrance system will only save the customer on VAR charges,
while the “At Load” system will reduce both demand and usage charges by
approximately two percent every month. In addition, the decreased usage after the
meter, obtained with the “At Load” system, also decreases the generation
requirements of the utility. In the longer term, if widely adopted, these reduced
costs will eventually be reflected in customer bills. The reduced operating costs
also lead to a shorter return on investment. The additional installation and
equipment costs of larger “At Load” systems (>150 Kvar) will be recovered within
the first six to eight months. With smaller services, where service entrance systems
would not be cost effective because of the high cost, “At Load” systems will still
generate savings to offset the investment within a relatively short time period.
15
costs, both by generating fewer harmonics that might damage equipment, and by
lessening or eliminating the need for expensive harmonic mitigation systems.
RESONANCE
To improve the load-power factor of the electrical power system, the common
practice is to add shunt-connected capacitors at the main substation to correct for
the inductive loads (transformers, motors, etc.). Although shunt-connected
capacitors may improve the power factor, they may also create serious problems,
particularly when harmonics are present. Any capacitance and inductance forms a
circuit tuned (capacitance and inductive reactance are equal) to what is called the
"resonant" frequency. If enough harmonic energy is present and its frequency
matches that of the resonant circuit, then a very large current (many times the
original harmonic current) will flow. This current will produce extreme voltage
drops across all circuit elements, blowing fuses, damaging components, and
deflecting an excessively high harmonic level back into the power system.
Resonance often occurs when shunt capacitors are located near a harmonic current
source and, thus, create a parallel resonant circuit with the equivalent
system????????Tana
16
component) and the “true power factor”, which is a measure of the power factor of
both the fundamental and harmonic components in the power system.
FIG .Power
Factor
Components in
System with
Harmonics
Conclusion
PFC is rapidly becoming a mandatory feature in AC power sources because IEC
6100-3-2 requires the use of PFC circuits. Active and passive PFC circuits are
designed to bring the PF of a system closer to unity (PF = 1.0). While no system is
17
100% efficient, most PFC technology makes the power factor of a system greater
than 0.95. Highly efficient electrical systems have the advantage of supplying less
current to drive a load. This is beneficial to customers that have low power factor
problems because utilities sometimes charge penalties for low power factor. While
cost savings from PFC on small AC sources isn’t nearly as noticeable as money
saved from PFC on large systems, in the long run PFC will provide reduced costs
for high energy consumers.