Sei sulla pagina 1di 8

Journal of Electrical Engineering

www.jee.ro

Single-Phase SOGI-PLL Based Reference Current


Extraction for Three-Phase Four-Wire
DSTATCOM
Hareesh Kumar Yada
Research Scholar, Department of Electrical Engineering, JNTU, Hyderabad, Telangana, INDIA.
hari_yada60@yahoo.co.in

Dr.M.S.R Murthy
Professor, Department of Electrical Engineering, ATRI, Hyderabad, Telangana, INDIA.
drmsrmurthy@gmail.com

Abstract— This paper describes a novel control algorithm compensation. The PLL should respond effectively in
based on single-phase SOGI (Second Order Generalized distorted load conditions by detecting the phase angle and
Integrator) PLL (Phase Locked Loop) for a three-phase four- amplitude at a faster rate. In recent days, Non-linear loads
wire DSTATCOM (Distribution Static Compensator). The are increased extensively at the utility end and causing
proposed DSTATCOM performs various functions such as load
power quality problems at the PCC in the supply system
balancing, harmonic mitigation, reactive power compensation
[1].
and neutral current compensation under distorted load
conditions. This control algorithm extracts the fundamental These nonlinear loads include diode bridge rectifiers,
component of the load currents for estimating the reference variable speed drives, thyristor converters and variable
currents based on three single-phase SOGI-PLLs. The main power supplies [3]. Harmonics play a major role in the
objective of the controller is to reduce the overall complexity power quality problems at the consumer end and shunt
and computational burden. SOGI-PLL is enhancing the active power filter is the crucial tool in mitigating
capability of reference current tracking for compensation harmonics and also other PQ issues [2] [4]. Various
under the step changes in load currents. During the design researchers have discussed numerous control techniques
procedure, the effects of load unbalancing and sudden
for estimation of reference components to mitigate PQ
increase/decrease in loads are also taken into account and
problems using a three-phase four-wire DSTATCOM. The
performance is found satisfactory. The effectiveness of the
design is simulated and shown using MATLAB/Simulink. neutral current should not be more than 20% of the full
load current [5]-[6]. Several PLL techniques have been
Index Terms— Second Order Generalized Integrator, Phase introduced for detecting the amplitude and phase angle for
-Locked Loop, DSTATCOM, Load balancing, Power Quality grid-connected systems. A three phase Synchronous
(PQ). Reference Frame PLL gives satisfactory performance
under ideal conditions but poor performance under
I. INTRODUCTION distortion [7]. The DFT (Digital Fourier Transform) and
FFICIENT phase tracking capability for utility grid RDFT (Recursive Digital Fourier Transform) are
E voltage is the important factor in converters for
custom power applications. The reference component
frequency domain approaches that suffer from high
computational burden but widely used owing to accuracy
generated from the phase-locked loop decides the [8]-[10]. Josep M. Guerrero and Saeed Golestan have been
performance of the converters for compensating power deeply analyzed the structures of two different PLLs
quality problems such as load unbalance, harmonic namely SOGI and Park PLL [11]. The LPN-PLL and Pre-
mitigation, high neutral current and reactive power filtered SRF PLL was excellent under steady-state and

1
Journal of Electrical Engineering
www.jee.ro

VSI based DSTATCOM is capable of suppressing the


harmonics in the source currents, power factor correction
and load balancing. A small capacity rated R-C filter is
connected in parallel with the source to eliminate the high
switching ripple content of the VSC. DSTATCOM is
connected to the a.c mains through source impedance (Rs,
Ls) and Loads. The load under consideration is a
combination of linear and non-linear type. A ripple filter
(Rf, Cf) is also connected in parallel to the load and source
to reduce the high frequency noise at the PCC. The
controller currents (Ica, Icb, Icc) are injected into PCC to
compensate harmonics and reactive power in the load. The
load current is sensed and made as input to the SOGI PLL
to extract the accurate phase and amplitude. The SOGI
PLL is chosen because of its low computational burden
Fig. 1 Line Diagram of the Proposed System. and desired performance under distorted conditions.

transient conditions in comparison with SRF-PLL [12]- III. CONTROL ALGORITHM


[13]. Several control algorithms has been developed for
The control algorithm consists of four modules: SOGI
the satisfactory operation of DSTATCOM [14]-[16].
PLL, Active & Reactive Component Extraction, Reference
In this paper, a novel control algorithm using SOGI-
Current Generation and Current Controller.
PLL has been introduced for extracting the reference
components under distorted load conditions. The proposed A. SOGI-PLL
algorithm maintains balanced sinusoidal currents with stiff The basic block diagram of the PLL is shown in
DC bus voltage at DSTATCOM. This control algorithm is Fig.2. The basic PLL consists of three building blocks as
used to reduce harmonics and reactive power shown in Fig.2. 1) Phase Detector that generates a signal
compensation under unbalanced non linear loads. The which is the difference in phase between the input and
control structure has advantages, a) Amplitude and Phase feedback signal and then it is passed through the loop filter
detection according to the change in requirements. b) (LF). 2) LF is used to control the Voltage Controlled
Speed and Accuracy c) fundamental component extraction Oscillator (VCO). 3) VCO generates the frequency signal
under adverse load conditions. Finally, an effective from its nominal frequency.
implementation of the algorithm to reduce the overall The proposed method of designing a SOGI PLL is
computational burden, low bulkiness and low complexity shown in Fig. 3. In fig (3b), the outputs I Lα and I Lβ
in design and variable compensation for three-phase four-
generates two sine waves with a phase shift of 900. The
wire DSTATCOM is presented. This approach is based on
component I Lα and IL has the same magnitude and phase.
single-phase SOGI-PLL to extract three phase reference
components. In this technique, Power quality The SOGI structure is defined as [11].
improvement with neutral current compensation is also w
GI = 2 (1)
done using a four leg VSC and the effectiveness of the s + w2
system is shown through simulation results. Simulations Where w- Resonance Frequency of the SOGI
are carried out using MATLAB/Simulink, simpower I Lα (2)
Hd =
systems block set. IL
I Lβ (3)
Hq =
II. PROPOSED SYSTEM CONFIGURATION IL
Fig. 1 shows a line diagram of the proposed system with The k shown in figure.3 affects the bandwidth of the
control diagram for a four leg VSC (Voltage Source closed-loop system. When the grid frequency has
Converter) feeding nonlinear loads. The DSTATCOM is fluctuations, problems may occur as the structure is
connected in parallel to the source and load at the Point of frequency dependent. Hence, the w value of the SOGI is
Common Coupling (PCC) through interfacing inductor Lc tuned according to the frequency provided by the PLL
to reduce the ripple currents in the controller current. The structure.

2
Journal of Electrical Engineering
www.jee.ro

 v 2 sa  (5)
V ' ta = 2( ) ,
 2 

 v 2 sb  (6)
V ' tb = 2( )
 2 
 v 2 sc  (7)
Fig. 2 Block Diagram of PLL. V ' tc = 2( )
 2 
Using the proposed method, the input IL if filtered leading Where, (vsa, vsb, and vsc) are the phase voltages and
to two waveforms ( I Lα and I Lβ ) because of the resonant Vta’, Vtb’, Vtc’ are the constant value amplitudes.
frequency. The gain k decides the level of filtering and the The In-phase unit templates of PCC voltages are estimated
filter band pass becomes narrower and dynamic response as:
will become slower with the decrease in k. Park vsa v v
ua = ; ub = sb ; uc = sc ` (8)
transformation is used to convert αβ to dq. Vta Vtb Vtc
 cos θˆ sin θˆ  (4) Quadrature unit templates of PCC voltages are estimated
T =
ˆ ˆ
− sin θ cos θ  as:
To attenuate the high igh frequency noises, the
wa =
(− ub + uc ) , w =
(3ua + ub − uc ) ,
transformation output ILq is passed through a Proportional b
3 2 3 (9)
– Integral (PI) controller. The fundamental frequency (W ( ff)
is added to the PI control signal and then it is integrated to wc =
(− 3ua + ub − uc )
generate the estimated phase angle θˆ . In order
o to get a 2 3
balanced set of in-quadrature
quadrature outputs with exact The amplitude of the PCC voltage is estimated as:
amplitudes, the SOGI frequency must be equal to the input
fundamental frequency. 2(v 2 sa + v 2 sb + v 2 sc )
v' t = (10)
B. Estimation of Unit Voltage Templates 3
The basic equations for estimation of the different control This amplitude ( v't ) is supplied to the low pass filter to
signals are shown below. The three phase source voltages reduce the ripples and to attain the amplitude of the
may be unbalanced or consists of harmonics and those are fundamental positive-sequence
sequence voltages for controlling the
processed through filters to eliminate the noise and PCC voltages. These unit vector templates are now used to
harmonics. The individual phases are estimated through extract the active and reactive components of currents.
squaring them and then processed through filters as
follows [16].

(a)

Fig.4 Block Diagram of Active and Reactive Component Extraction

C. Active and Reactive Component Extraction


Fig.4 shows the block diagram of the active and reactive
(b)
Fig. 3 a) Basic Design of SOGI PLL b) SOGI Block .
component nt extraction based on SOGI PLL scheme. In this
algorithm, load currents (ILa, ILb, ILc), unit vector (ua,ub,uc)

3
Journal of Electrical Engineering
www.jee.ro

and quadrature vector templates (wa,wb,wc) are required Icd(n)=Icd(n-1)+kpt{vdcer(n)-vdcer(n-1)}+k


(n itvdcer(n) (20)
for extraction of in-phase (Iph) and quadrature currents Where, Kpt and Kit are the proportional
propor and integral gain
(Iqh). constants of the PI controller. Vde(n) and Vde(n-1) are the
phase component and quadrature component for
The in-phase voltage errors of the DC bus in nth and n-1th instant and
each phases a,b,c are calculated as follows: Icd(n) and Icd(n-1)
1) are the amplitude of active power
ipa = iαawa + iβaua (11) component of the fundamental reference current at nth and
iqa = -iαaua + iβawa (12) (n-1)th instant.
ipb = iαbwb + iβbub (13) i = u (I + I )
sap a ph cd
(21)
iqb = -iαbub + iβbwb (14)
i sbp = u b (I ph + I cd ) (22)
ipc = iαcwc + iβcuc (15)
iqc = -iαcuc + iβcwc (16) i scp = u c (I ph + I cd ) (23)
The average amplitude of active and reactive The output of the PI controller (Icd) is summed to the
components of the three phase load currents are estimated amplitude of active component (Iph) and the resultant is
for load balancing and to be used in the extraction of three multiplied with the unit vector of the three phases (ua, ub,
phase source currents as: uc) to generate the amplitude of fundamental active
i pa + i pb + i pc component of current Isap, Isbp and Iscp respectively as
i ph = (17) shown in fig.5.
3
The voltage across the load is used to generate the
iqa + iqb + iqc amplitude of the load voltage (Vtm) as in (10) and
iqh = (18)
3 compared with the reference load voltage V*tm and this
error at the nth sampling instant is expressed as:
D. Reference Current Generation
V ter ( r ) = V t (r ) − V t (r )
*
(24)
Fig.5 shows the block diagram of the reference current
This voltage error is fed to PI controller to regulate the AC
generation. This block requires DC link voltage (Vdc),
voltage to its reference value. At nth sampling instant, the
Load Voltages (VabcL), active, reactive component of
output of the PI controller is as:
currents (Iph, Iqh) and unit vector templates to generate the
I cq (r) = I cq (r − 1) + k pt {Vter (r ) − Vter (r −1)} + kitVter (r ) (25)
reference source currents.
The voltage across the DC capacitor Vdc is sensed and Where, Kpt and Kit are the proportional and integral gain
compared with the reference DC bus voltage V*dc and this constants of the PI controller. Vter(r) and Vter (r-1) are the
error at the nth sampling instant is expressed as: voltage errors of the AC bus in rth and r-1th instant and
Vde(n)= V*dc(n) - Vdc(n) (19) Icq(r) and Icq(r-1)
1) are the amplitude of reactive power
This voltage error is fed to PI controller to maintain the component of the fundamental reference current at rth and
DC voltage of the DSTATCOM. At nth sampling instant, (r-1)th instant. The output of the PI controller (Icq) is
the output of the PI controller is as: summed to the amplitude of reactive component (Iqh) and
the resultant is multiplied with the unit quadrature vector
of the three phases (wa, wb, wc) to generate the amplitude
of fundamental
undamental reactive component of current Isaq, Isbq and
Iscq respectively as shown in fig.5.
i = w (I + I )
saq a qh cq
(26)

i sbq = w b (I qh + I cq ) (27)

i scq = w c (I qh + I cq ) (28)

Finally, the active and reactive component of currents


are summed to generate reference supply currents Isa*,
Isb*, Isc* respectively.
i*sa = isap + isaq (29)
i*sb = isbp + iscq (30)
i*sc = iscp + iscq (31)
Fig.5 Block Diagram of Reference Currents Generation

4
Journal of Electrical Engineering
www.jee.ro

PCC Voltage Vsa Vsb Vsc


350
0
-350
Source Current Isa Isb Isc
40
0
-40
Load Current ILa
40
0
-40
Load Current ILb
40
0
-40
Load Current ILc
40
0
-40
Injected Current Ica Icb Icc
40
0
-40
Nuetral Current Isn ILn
40
0
-40
Dc Link Voltage Vdc
800
700
600
1.8 1.9 2 2.1 2.2 2.3 2.4 2.5 2.6
Time (sec)

Fig. 6 Performance of DSTATCOM for the considered

These estimated three phase reference source currents


A. Harmonic Compensation
(i*sa, i*sb, i*sc) and i*sn are compared with sensed source
currents (isa, isb, isc) and isn (isa+isb+isc) to estimate the Fig. 7 and Fig.8 shows the results for the case harmonic
current errors. These errors are regulated using PI compensation. A single phase-current source type of
controllers and are compared with carrier signals to nonlinear load is applied on all the three phases for which
generate PWM pulses for DSTATCOM. the source currents are obtained sinusoidal. The harmonic
spectrum for the nonlinear load currents and the obtained
IV. SIMULATION RESULTS AND DISCUSSION source currents are shown in the fig. 8. Load current (ILa)
have a THD of 25.17% with a fundamental component of
The proposed control algorithm for three-phase four- 35.44A and the source current has a THD of 1.73% with a
wire DSTATCOM is modeled in MATLAB / Simulink fundamental component of 40.19A. Thus, the magnitude
using Simpower systems toolbox. The performance of the and THD of the Load currents and the source currents
control algorithm is studied for harmonic compensation, shows the effectiveness of the proposed control algorithm.
load compensation/neutral current Compensation and
Power Factor correction/Reactive Power Compensation B. Load / Neutral Current Compensation
which are discussed individually in this section. Fig. 6. The performance of the DSTATCOM with the proposed
Shows the PCC-Voltage (Vpcc), Source Current (Is_abc), control algorithm for the unbalanced and varying loads for
Load Currents – (ILa,ILb,ILc), Compensation Currents the case of load compensation/neutral current
(Ic_abc), Neutral Currents (IN_S,IN_L) and the DC-Bus compensation is shown in fig.7 and fig.10. The unbalance
voltage (Vdc). The parameters for the system are given in in the load is created by opening the phase ‘a’, phase ‘b’
appendix. during 1.9sec to 2.25sec and 2sec to 2.15sec respectively.
Table-I
Source Source
Load Currents Load Currents Source Currents Load Currents
Quantity Currents Currents
THD % THD % THD % THD % THD % THD %
Normal Condition Un-Balanced Condition Increase in Load Condition
Ph-a 25.17 1.73 64.28 4.73 20.12 1.65
Ph-b 25.15 1.77 66.12 4.98 20.18 1.69
Ph-c 16.58 1.77 17.29 3.56 18.23 1.71

5
Journal of Electrical Engineering
www.jee.ro

PCC Voltage Vsa Vsb Vsc


350 FFT window: 3 of 140 cycles of selected signal
50
0
-350

ILabc
0

S ource Current Isa Isb Isc -50


40 2.4 2.42
Time (s)
2.44 2.46

0
-40 100
Fundamental (50Hz) = 35.83 , THD= 25.22%

Load Current ILa

Mag (% of Fundamental)
80
40
60
0
-40 40

Load Current ILb 20

40 0
0 5 10 15 20
Harmonic Order
0
-40 40
20

Isabc
Load Current ILc 0
40 -20
0 -40
-40 2.4 2.42 2.44
Injected Current Ica Icb Icc Time (s)
40

Mag (% of Fundamental)
Fundamental (50Hz) = 40.19 , THD= 1.73%
0 100
-40
Nuetral Current Isn ILn
40 50
0
-40
Dc Link Voltage Vdc 0
800 0 5 10 15 20
700 Harmonic order
600
1.9 1.95 2 2.05 2.1 2.15 2.2 2.25 2.3 Fig. 8. Harmonic Spectrum of ‘a’-ph of Load
Time (sec) Current and Source Current
Fig. 7 Performance of DSTATCOM under unbalanced and varying nonlinear loads

The increase in load neutral current can be observed with


the increase in the unbalanced load currents shown in C. Reactive Power Compensation / Power Factor
fig.10. The source neutral current is observed to be almost Correction
zero, which presents the effectiveness of the control Power factor correction at various load conditions are
algorithm. The source currents are observed to be balance shown in Fig. 9. The source voltage is scaled to (1/20)V
under all these conditions. The DC bus voltage of for effective visualization of zero crossing of source
DSTATCOM is regulated to the reference value under all current (Isa) and Source Voltage (Vsa). From the figure, it
load conditions. The values of each phase currents are can be observed that the source current is in phase with the
tabulated with all the conditions in Table-I. source voltage at various load conditions.

S ource Voltage S ource Current

50

-50
1.7 1.8 1.9 2 2.1 2.2 2.3 2.4 2.5 2.6

20 20 60

40

20
0 0
0

-20

-20 -20 -40


1.7 1.72 1.74 2.1 2.12 2.14 2.4 2.42 2.44

Fig. 9 Results presenting the zero crossing of source voltage and source current at various load levels

6
Journal of Electrical Engineering
www.jee.ro

PCC Voltage Vsa Vsb Vsc V. CONCLUSION


350
0 A control algorithm based on SOGI-PLL for
-350 DSTATCOM has been implemented for compensation of
Source Current Isa Isb Isc three-phase four-wire non-linear - Unbalanced and
40
0 Varying loads. The four-leg, eight switches VSC is used as
-40 the DSTATCOM. The simulation results have proved the
Load Current ILa
40 fast and effective response for the extraction of
0 fundamental component of load currents for harmonic
-40
Load Current ILb compensation, load balancing, neutral current
40 compensation and power factor / reactive power
0
-40 compensation with a limit of IEEE - 519 -1992 standard
Load Current ILc guidelines. The proposed SOGI controller is taking less
50
0 computational burden and has proved its effectiveness in
-50
Injected Current Ica Icb Icc
mitigating source-neutral current and the DC bus voltage
40 is regulated compared with the reference and power factor
0 is also improved as expected. The dynamics and
-40
Nuetral Current Isn ILn efficiency confirms the potential for implementing in real-
40 time applications.
0
-40
Dc Link Voltage Vdc
800 APPENDIX
700 AC supply source 3-Phase, 415 V (L-L)
600
2.3 2.4 2.5 Frequency 50Hz
Time (sec) Source Impedance Rs=0.05 Ω, Ls =2mH
Non-linear: Three phase R=24 Ω, L= 80mH
Fig.10 Performance of DSTATCOM under Varying Nonlinear load full bridge uncontrolled
conditions rectifier
Non-linear: Single phase R=50 Ω
A three-leg single-phase voltage source converter (VSC) full bridge uncontrolled
based DSTATCOM [15] requires 12 switches and hence rectifier
Rating of VSC 12 KVA
the cost and complexity is high. The split capacitor based
Ripple filter Rf = 5Ω, Cf =7μF
VSC has a disadvantage of maintaining same DC voltage Switching frequency 8kHz
at the series capacitors [15]. Zig-Zag transformer with Reference dc bus voltage 720V
three-leg VSC has better performance in neutral current Interfacing inductor Ls=5mH
compensation but costly and effective design should be Gains of PI controller for kpt =2, kit=0.3
dc bus
done [16]. A T-connected transformer also requires two
Cut off frequency of low 45Hz
single-phase transformers and compensation has no much pass filter used in dc bus
change compared with the zig-zag transformer [17]. A voltage
star/delta transformer is also reported in the literature for Cut off frequency of low 16Hz
pass filter used in ac bus
neutral current compensation [18]-[20]. The disadvantages
voltage
of the above mentioned topologies require an additional Gains of PI controller for kpt =0.2, kit=0.3
transformer specially designed for proper compensation. AC bus
Because, the level of compensation is affected by the
transformer impedance. The four-leg VSC based REFERENCES
DSTATCOM is superior and requires 8 switches but the [1] F. F. Ewald and A. S.M.Mohammad, Power Quality in Power
controller is to be tuned accordingly. The proposed Systems and Electrical Machines. London, U.K.: Elsevier
controller has proved its effectiveness in voltage Academic Press, 2008.
[2] G. Arindam and L. Gerard, Power Quality Enhancement using
regulation, harmonic elimination, power factor correction,
Custom Power Devices, Springer International Edition ed. Delhi,
neutral current compensation and load balancing. India: Springer, 2009.
[3] C. Sankaran, Power Quality. Boca Raton, FL: CRC, 2001.
[4] IEEE Recommended Practices and requirement for Harmonic
Control on electric power System, IEEE Standard 519, 1992.

7
Journal of Electrical Engineering
www.jee.ro

[5] Nagesh Geddada, Srinivas Bhaskar Karanki , Mahesh K. Mishra, [19] Bhim Singh, and Sabha Raj Arya and Chinmay Jain “Simple peak
and B. Kalyan Kumar “modified four leg dstatcom topology for detection control algorithm of distribution static compensator for
compensation of unbalanced and nonlinear loads in three phase power quality improvement” IET Power Electronics, December
four wire system” in power electronics and applications (epe 2013.
2011). [20] Ashraf A. hagras, Sherif Zaid, Ahmed Alaa Elkousy, and Shokry
[6] Ashish Negi, S.Ranjith Kumar, P.Raja “Assessment and M. Saad “Adaptive control of DSP based Shunt Active Power
Comparison of Different Neutral Current Compensation Filter” Journal of Electrical Engineering, Volume 16, December,
Techniques in Three-Phase four-wire Distribution System” 3rd 2016.
IEEE International Symposium on Power Electronics for
Distributed Generation Systems (PEDG) 2012.
[7] Zhan C., Fitzer C., Ramachandaramurthy K., Arulampalam A.,
Barnes M., Jenkins N. “Software phase-locked loop applied to
dynamic voltage restorer” // Proc IEEE-PES Winter Meeting –
2001. – P. 1033–1038. B. P. McGrath, D. G. Holmes, and J. J. H.
Galloway, "Power converter line synchronization using a discrete
Fourier transform (DFT) based on 517 variable sampling rate,"
IEEE Trans. Power Electron., vol. 20, no. 4, pp. 877-884, Jul.
2005. L. Asiminoaei, F. Blaabjerg, and S. Hansen, "Detection is
key-Harmonic detection methods for active power filter
applications," IEEE Ind. Appl. Mag., vol. 13, no. 4, pp. 22-33,
Jul.lAug. 2007.
[8] E. Jacobsen, and R. Lyons, "The sliding DFT," IEEE Signal
Process. Mag., vol. 20, no. 2, pp. 74-80, Mar. 2003.
[9] Saeed Golestan, Mohammad Monfared, Francisco D. Freijedo,
Josep M. Guerrero “Dynamics Assessment of Advanced Single-
Phase PLL Structures” IEEE transactions on industrial electronics,
vol. 60, no. 6, june 2013.
[10] Kyoung-Jun Lee, Jong-Pil Lee, Dongsul Shin, Dong-Wook Yoo,
Hee-Je Kim “A Novel Grid Synchronization PLL Method Based on
Adaptive Low-Pass Notch Filter for Grid-Connected PCS” IEEE
transactions on industrial electronics, vol. 61, no. 1, january 2014.
[11] Saeed Golestan, Mohammad Monfared, Francisco D. Freijedo
Josep M. Guerrero “Performance Improvement of a Pre-filtered
Synchronous-Reference-Frame PLL By Using a PID-Type Loop
Filter” IEEE transactions on industrial electronics, january 2014.
[12] Bhim Singh, and Sabha Raj Arya “Adaptive Theory-Based
Improved Linear Sinusoidal Tracer Control Algorithm for
DSTATCOM” IEEE transactions on power electronics, vol. 28, no.
8, august 2013.
[13] Bhim Singh, and Sabha Raj Arya “Back-Propagation Control
Algorithm for Power Quality Improvement using DSTATCOM”
IEEE transactions on industrial electronics, january 2014.
[14] Bhim Singh, and Sabha Raj Arya “Implementation of Single-
Phase Enhanced Phase-Locked Loop-Based Control Algorithm for
Three-Phase DSTATCOM” IEEE transactions on power delivery,
vol. 28, no. 3, july 2013.
[15] H. Akagi, E. H. Watanabe, and M. Aredes, Instantaneous Power
Theory and Applications to Power Conditioning. Hoboken, NJ:
Wiley, 2007.
[16] H.-L. Jou, K.-D. Wu, J.-C. Wu, and W.-J. Chiang, “A three-phase
four-wire power filter comprising a three-phase three-wire active
filter and a zig-zag transformer” IEEE Trans. Power Electron.,
vol.23, no.1, pp. 252–259, Jan. 2008.
[17] Bhim Singh, P. Jaya Prakash and D.P Kothari “A T-connected
transformer and three-leg VSC based DSTATCOM for Power
Quality Improvement” IEEE transactions on power electronics,
vol. 23, no. 6, November 2008.
[18] P. Enjeti, W. Shireen, P. Packebush, and I. Pitel, “Analysis and
design of a new active power filter to cancel neutral current
harmonics in three-phase four-wire electric distribution systems,”
IEEE Trans. Ind. Appl., vol.30, no. 6, pp. 1565–1572, Nov./Dec.
1994.

Potrebbero piacerti anche