Sei sulla pagina 1di 3

BASE DE DATOS DE AJUSTE DE PROTECCIONES

Tipo: PROTECCION GENERADOR Tipo Central: HIDROELECTRICA Región: ZONA SUR


Fabricante: ABB C.H.: CHARCANI VI Dpto:
Modelo: REG670 Tensión Nom.: 5,25 kV Empresa:
Versión: Grupo Gen.: G1 Diag.Unif.N°:
N° Serie: Uprim[kV]: 5,25kV Man.Serv.N°:
Tecnología: NUMÉRICA Fases: RSTN Fecha: 13-Feb-14
Año instal.: Ucc [V]: Respons.: K.V.H.
Código: Uca [V]: 100 Revisión: 0
Ubic.Tabl: Ica [A]: 5
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 (AS BUILT) GRUPO 1 (AECP 2014) OBSERVACIONES
ACTUAL PROPUESTO
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

DATOS GENERALES
DATOS DEL GENERADOR TRANSFORMADORES DE CORRIENTE (TERMINAL)
TRANSFORMADORES DE CORRIENTE (NEUTRO) TRANSFORMADOR DE TENSION
RELACIONES DE IMPEDANCIA

VALORES DE AJUSTE
@ AJUSTES GENERALES 87N Restricted earth fault protection (PDIF)
87G Generator differential protection (PDIF) 21 Full-scheme distance measuring, Mho characteristic, PDIS (Impedance Protection)
RDIR Directional impedance Mho 78 Pole slip protection (PPAM).(PERDIDA DE SINCRONISMO)
40 Loss of excitation (PDIS). (PERDIDA DE EXCITACIÓN) 50 INSTANTANEOUS PHASE OVERCURRENT PROTECTION (PIOC)
51_67 Four step phase overcurrent protection (PTOC) 50N INSTANTANEOUS RESIDUAL OVERCURRENT PROTECTION (PIOC)
51N/67NFour step residual overcurrent protection (PTOC) 67N Sensitive directional residual overcurrent and power protection (PSDE)

49 Thermal overload protection, two time constants (PTTR) 50BF Breaker failure protection (RBRF)

52PD Pole discrepancy protection (RPLD) 37 Directional underpower protection (PDUP)


32 Directional overpower protection (PDOP) 27 Two step undervoltage protection (PTUV)
59 Two step overvoltage protection (PTOV) 59N Two step residual overvoltage protection (PTOV)
24 Overexcitation protection (PVPH) 60 Voltage differential protection (PTOV)
59THD 95% and 100% Stator earthground fault protection based on 3rd
81harmonic
Underfrequency protection (PTUF)
81 Overfrequency protection (PTOF) 81 Rate-of-change frequency protection (PFRC).

DATOS GENERALES
Características nominales
Tipo (CH=Hidráulica, D=Diesel, TV=Turb.Vapor, TG=Turb.Gas, etc.) - CH
Potencia activa nominal MW 9.18
Potencia aparente nominal MVA 10.8
Factor de potencia nominal - 0.85
Potencia activa máxima MW
Potencia activa mínima MW
Potencia reactiva máxima MVAr
Potencia reactiva mínima MVAr
Tensión nominal primaria entre fases kV 5.25
Rango de tensión entre fases %
Velocidad de rotación rpm
Frecuencia Hz 0
Características operativas
Reactancia de secuencia positiva, subtransitoria, no saturada. pu 0.180
Reactancia de secuencia negativa, no saturada. pu 0.201
Reactancia de secuencia cero. pu 0.120
Resistencia estatórica. ohm/fase
Resistencia estatórica. ohm/fase

TRANSFORMADORES DE CORRIENTE (TERMINAL)


Marca - -
Tipo - -
Modelo - -
Cantidad de núcleos - -
Corriente nominal A - 5 100 5 100
Relación de transformación - - 20.00 20.00
Clase - -
Prestación VA - 40 40
TRANSFORMADORES DE CORRIENTE (NEUTRO)
Marca - -
Tipo - -
Modelo - -
Cantidad de núcleos - -
Corriente nominal A - 5 1250 5 1250
Relación de transformación - - 250.00 250.00
Clase - -
Prestación VA - 40 40
TRANSFORMADOR DE TENSION
Marca - -
Tipo - -
Modelo - -
Cantidad de arrollamientos - -
Tensión nominal entre fases V - 100 5250 100 5250
Relación de transformación - - 52.50 52.50
Clase - - 3 3
Prestación VA - 50 50
RELACIONES DE IMPEDANCIA
Relación secundario/primario (Zs/Zp = Us/Is:Up/Ip) - - 0.38 0.38
Relación primario/secundario (Zp/Zs = Up/Ip:Us/Is) - - 2.63 2.63
VALORES DE AJUSTE
AJUSTES GENERALES Disp.s/interr.:
Configuración del Alcance de las Funciones Disponibles
87N 87N Restricted earth fault protection (PDIF) - Enabled - Disabled Disabled - Disabled -
87G 87G Generator differential protection (PDIF) - Enabled - Disabled Enabled - Enabled -
21 21 Impedance Protection, PDIS - Enabled - Disabled Disabled - Disabled -
RDIR RDIR Directional impedance Mho - Enabled - Disabled Disabled - Disabled -
78 78 Pole slip protection (PPAM). - Enabled - Disabled Disabled - Disabled -
40 40 Loss of excitation (PDIS). - Enabled - Disabled Enabled - Enabled -
50 50 Instantaneous phase overcurrent protection (PIOC) - Enabled - Disabled Disabled - Disabled -
51_67 51_67 Four step phase overcurrent protection (PTOC) - Enabled - Disabled Enabled - Enabled -
50N 50N Instantaneous residual overcurrent protection (PIOC) - Enabled - Disabled Disabled - Disabled -
51N/67N 51N/67N Four step residual overcurrent protection (PTOC) - Enabled - Disabled Disabled - Disabled -
67N 67N Sensitive directional residual overcurrent and power - Enabled - Disabled Disabled - Disabled -
protection (PSDE)
49 49 Thermal overload protection, two time constants (PTTR) - Enabled - Disabled Disabled - Disabled -
50BF 50BF Breaker failure protection (RBRF) - Enabled - Disabled Disabled - Disabled -
52PD 52PD Pole discrepancy protection (RPLD) - Enabled - Disabled Disabled - Disabled -
37 37 Directional underpower protection (PDUP) - Enabled - Disabled Enabled - Enabled -
32 32 Directional overpower protection (PDOP) - Enabled - Disabled Enabled - Enabled -
27 27 Two step undervoltage protection (PTUV) - Enabled - Disabled Enabled - Enabled -
59 59 Two step overvoltage protection (PTOV) - Enabled - Disabled Enabled - Enabled -
59N 59N Two step residual overvoltage protection (PTOV) - Enabled - Disabled Disabled - Disabled -
24 24 Overexcitation protection (PVPH) - Enabled - Disabled Disabled - Disabled -
60 60 Voltage differential protection (PTOV) - Enabled - Disabled Disabled - Disabled -
59TH 59TH 95% and 100% Stator earthground fault protection based - Enabled - Disabled Disabled - Disabled -
81 on
81 3rd harmonic
Underfrequency protection (PTUF) - Enabled - Disabled Enabled - Enabled -
81 81 Overfrequency protection (PTOF) - Enabled - Disabled Enabled - Enabled -
81 81 Rate-of-change frequency protection (PFRC) - Enabled - Disabled Disabled - Disabled -
25 Synchronizing (RSYN,25) - Enabled - Disabled Enabled - Enabled -
87N Restricted earth fault protection (PDIF)
Operation Operación Off / On - ON - OFF OFF - OFF -

IBase Corriente base A 1.0 999999 1.0 - 866.0 - 866.0


IdMi Maximum sensitivity in % of Ibase %IB 4.00 100.00 0.10 30.00 - 30.00 -
CTFactorPri1 CT factor for HV side CT1 - 1.0 10.0 0.1 1.0 - 1.0 -
CTFactorPri2 CT factor for HV side CT2 - 1.0 10.0 0.1 1.0 - 1.0 -
CTFactorPri1 CT factor for MV side CT1 - 1.0 10.0 0.1 1.0 - 1.0 -
CTFactorPri2 CT factor for MV side CT2 - 1.0 10.0 0.1 1.0 - 1.0 -
ROA Relay operate angle for zero sequence directional feature deg 60.0 90.0 1.0 1.0 - 1.0 -
87G Generator differential protection (PDIF)
IBase Corriente nominal del generador protegido A 100.00 100000 0.1 750.0 750.0
InvertCT2Curr Inversor CT 2 de corriente - NO - YES NO - NO -

Operation Operación - ON - OFF OFF - OFF -


IdMi Sección sensitiva1, multiple of generator rated current (IdMin) IB 0.05 1.00 0.01 0.3 - 0.3 -
EndSection1 End of section 1, multiple of generator rated current IB 0.20 1.50 0.01 - -
EndSection2 End of section 2, multiple of generator rated current IB 1.00 10.00 0.01 - -
SlopeSection2 Slope in section 2 of operate-restrain characteristic, in % % 10.0 50.0 0.1 - -
SlopeSection3 Slope in section 3 of operate-restrain characteristic, in % % 30.0 100.0 0.1 - -
IdUnre Unrestr. prot. limit, multiple of generator rated current IB 1.00 50.00 0.01 10.00 - 10.00 -
OpCrossBlock Operation Enable/ Disable for cross-block logic between phases - NO - YES - -
OpNegSeqDiff Habilita diferencial de Secuencia negativa Off/On - NO - YES YES - YES -
IMinNegSeq Limite de Corriente en Secuencia Negativa IB 0.02 0.20 0.01 0.1000 - 0.1000 -
NegSeqROA Operate Angle of int/ext neg. seq. fault discriminator, deg deg 30.00 120.00 0.10 - -
HarmDistLimit (Total) relative harmonic % 5.0 100.0 0.1 - -
TempIdMin Transitorio.Id Arranque cuando la entrada raisePickUp=1 IdMin 1.0 5.0 0.1 - -
AddTripDelay Retardo adicional de disparo s 0.00 60.00 0.00 - -
OperDCBiasing Operación DC Predispuesta On/Off - ON - OFF - -
87T Differential protection
TransformerDiff3Wind(PDIF,87T)
RatedVoltageW1 Rated voltage of transformer winding 1 (HV winding) in kV kV 0.05 2000.00 0.05 - 34 - 34
RatedVoltageW2 Rated voltage of transformer winding 2 in kV kV 0.05 2000.00 0.05 - 5.25 - 5.25
RatedVoltageW3 Rated voltage of transformer winding 3 in kV kV 0.05 2000.00 0.05 - 5.25 - 5.25
RatedCurrentW1 Rated current of transformer winding 1 (HV winding) in A A 1 99999 1 181.0 181.0
RatedCurrentW2 Rated current of transformer winding 2 in A A 1 99999 1 1233 1233
RatedCurrentW3 Rated current of transformer winding 3 in A A 1 99999 1 1233 1233
ConnectTypeW1 Connection type of winding 1: Y-wye (1) or D-delta (2) - WYE (Y) - WYE(Y) - WYE(Y) MAX: sobrecorriente
ConnectTypeW2 Connection type of winding 2: Y-wye (1) or D-delta (2) - Delta (D)
WYE (Y) - Delta (D) - Delta (D) MIN: subcorriente
MAX: sobrecorriente
ConnectTypeW3 Connection type of winding 3: Y-wye (1) or D-delta (2) - Delta (D)
WYE (Y) - Delta (D) - Delta (D) MAX-Inrrush:
MIN:
MAX: sobrecorriente con bloqueo por Inrush
subcorriente
sobrecorriente
ClockNumberW2 Phase displacement between W2 & W1=HV winding - 0 [0 deg ] Delta (D)deg lead]
a 11 [30 - 11 [30 deg - 11 [30 deg MAX-Inrrush:
MIN:
MAX: sobrecorriente con bloqueo por Inrush
subcorriente
sobrecorriente
ClockNumberW3 Phase displacement between W3 & W1=HV winding - 0 [0 deg ] a 11 [30 deg lead] - 11 lead]
[30 deg - lead]deg
11 [30 MAX-Inrrush:
MIN:
MAX: sobrecorriente con bloqueo por Inrush
subcorriente
sobrecorriente
ZSCurrSubtrW1 Enable zer. seq. current subtraction for W1 side - ON - OFF - lead]
ON - lead]
ON MAX-Inrrush:
MIN:
MAX: sobrecorriente con bloqueo por Inrush
subcorriente
sobrecorriente
ZSCurrSubtrW2 Enable zer. seq. current subtraction for W2 side - ON - OFF - OFF - OFF MAX-Inrrush:
MIN:
MAX: sobrecorriente con bloqueo por Inrush
subcorriente
sobrecorriente
ZSCurrSubtrW3 Enable zer. seq. current subtraction for W3 side - ON - OFF - OFF - OFF MAX-Inrrush:
MIN:
MAX: sobrecorriente con bloqueo por Inrush
subcorriente
sobrecorriente
TconfigForW1 Two CT inputs (T-config.) for winding 1 - YES - NO - NO - NO MAX-Inrrush:
MIN:
MAX: sobrecorriente con bloqueo por Inrush
subcorriente
sobrecorriente
CT1RatingW1 CT primary rating in A, T-branch 1, on transf. W1 side A 1 99999 1 3000 3000 MAX-Inrrush:
MIN: sobrecorriente con bloqueo por Inrush
subcorriente
CT2RatingW1 CT primary rating in A, T-branch 2, on transf. W1 side A 1 99999 1 3000 3000 MAX-Inrrush: sobrecorriente con bloqueo por Inrush
TconfigForW2 Two CT inputs (T-config.) for winding 2 - YES - NO NO NO MAX: sobrecorriente
CT1RatingW2 CT primary rating in A, T-branch 1, on transf. W2 side A 1 99999 1 3000 3000 MIN: subcorriente
CT2RatingW2 CT primary rating in A, T-branch 2, on transf. W2 side A 1 99999 1 3000 3000 MAX-Inrrush: sobrecorriente con bloqueo por Inrush
TconfigForW3 Two CT inputs (T-config.) for winding 3 - YES - NO NO NO MAX: sobrecorriente
CT1RatingW3 CT primary rating in A, T-branch 1, on transf. W3 side A 1 99999 1 3000 3000 MIN: subcorriente
CT2RatingW3 CT primary rating in A, T-branch 2, on transf. W3 side A 1 99999 1 3000 3000 MAX-Inrrush: sobrecorriente con bloqueo por Inrush
Location OLTC1 Location OLTC1 Not Used Not Used
LowTapPosOLTC1 LowTapPosOLTC1 0 10 1 1
RatedTapOLTC1 RatedTapOLTC1 1.00 100.00 6 6
HighTapPsPLTC1 HighTapPsPLTC1 1.00 100.00 11 11
TapHighVolTC1 TapHighVolTC1 1.00 100.00 1 1
StepSizeOLTC1 StepSizeOLTC1 % 0.01 30.00 1 1
Location OLTC2 Location OLTC2 Not Used Not Used
LowTapPosOLTC2 LowTapPosOLTC2 0.00 10.00 1 1
RatedTapOLTC2 RatedTapOLTC2 1.00 100.00 6 6
HighTapPsPLTC2 HighTapPsPLTC2 1.00 100.00 11 11
TapHighVolTC2 TapHighVolTC2 1.00 100.00 1 1
StepSizeOLTC2 StepSizeOLTC2 % 0.01 30.00 1 1
Setting Group 1 Setting Group 1 Not Used Not Used
Operation Operation - ON - OFF ON ON
SOTFMode SOTFMode - ON - OFF ON ON
IDiffAlarm IDiffAlarm IB 0.05 1 0.30 0.30
eAlarmDelay eAlarmDelay s 0.00 60 10 10
IdMin IdMin IB 0.05 0.60 0.30 0.30
IdUnre IdUnre IB 1 50 10 10
NegSeqdiffEn NegSeqdiffEn - ON - OFF ON ON
CrossBlockEn CrossBlockEn - ON - OFF ON ON
IMinNegSeq IMinNegSeq IB 0.02 0.20 0.10 0.10
NegSeqROA NegSeqROA Deg 30 120 60 60
PROTECCIÓN IMPEDANCIA
21 Full-scheme distance measuring, Mho characteristic, PDIS (Impedance Protection)
Ajustes Zona 1 (ZMH1)
Off
Operation Operación On/Off - OFF - OFF -
On
Ibase Corriente Base A 1 99999 1 - 3930.0 - 3930.0
Ubase Voltaje Base KV 0.01 2000.00 0.05 - 12.5 - 12.5
Off
Offset
DirMode Direction mode - - -
Forward
Reverse
LoadEnchMode Load enchroachment mode Off/On - OFF - ON - -
OverReach
ReachMode Reach mode Over/ Underreach - - -
Underreach
Non-directional - -
Direction mode for offset
OffsetMhoDir - Forward
mho Reverse
OpModePE Operation mode Disable/ Enable of Phase-Phase loops - OFF - ON - -
ZPE Impedance setting reach for phase to phase elements ohm/p 0.005 3000.00 0.001 - 0.156 - 0.156
ZAngPE Angle for positive sequence line impedance for Phase-Phase deg 10 90 1 - -
KN elements
Magnitud of ground return compensation factor KN - 0.000 3.00 0.010 - -
KNAng Angle for earth return compensation factor KN deg -180 180 1 - -
ZRevPE Reverse reach of the phase to phase loop(magnitude) ohm/p 0.005 3000.00 0.001 0.156 0.156
OpModetPE Operation mode Disable/ Enable of Zone timer, Ph-G - OFF - ON - -
tPE Delay time for operation of phase to phase s 0.00 60.00 0.001 - -
IMinOpPE Minimum operation phase to phase current %IB 10 30 1 - -
OpModePP Operation mode Disable/ Enable of Phase-Phase loops - OFF - ON - -
ZPP Impedance setting reach for phase to phase elements ohm/p 0.005 3000.00 0.001 0.156 0.156
ZAngPP Angle for positive sequence line impedance for Phase-Phase deg 10 90 1 - -
ZRevPP elements
Reverse reach of the phase to phase loop(magnitude) ohm/p 0.005 3000.00 0.001 - 0.156 - 0.156
OpModetPP Operation mode Off / On of Zone timer, Ph-ph - OFF - ON - -
tPP Delay time for operation of phase to phase s 0.00 60.00 0.001 - -
IMinOpPP Minimum operation phase to phase current %UB 10 30 1 - -
Ajustes Zona 2 (ZMH2)
Off
Operation Operación On/Off - OFF - OFF -
On
Ibase Corriente Base A 1.00 99999.00 1.00 - 3930.0 - 3930.0
Ubase Voltaje Base KV 0.01 2000.00 0.05 - 12.5 - 12.5
Off
Offset
DirMode Direction mode - - -
Forward
Reverse

DirMode Direction mode - - -

LoadEnchMode Load enchroachment mode Off/On - OFF - ON - -


ReachMode Reach mode Over/ Underreach - OverReach - -
Underreach
OpModePE Operation mode Disable/ Enable of Phase-Phase loops - OFF - ON - -
ZPE Impedance setting reach for phase to phase elements ohm/p 0.005 3000.00 0.001 0.235 0.235
ZAngPE Angle for positive sequence line impedance for Phase-Phase deg 10 90 1 - -
KN elements
Magnitud of ground return compensation factor KN - 0.000 3.00 0.010 - -
KNAng Angle for earth return compensation factor KN deg -180 180 1 - -
ZRevPE Reverse reach of the phase to phase loop(magnitude) ohm/p 0.005 3000.00 0.001 0.235 0.235
tPE Delay time for operation of phase to phase s 0.00 60.00 0.001 - -
IMinOpPE Minimum operation phase to phase current %IB 10 30 1 - -
OpModePP Operation mode Disable/ Enable of Phase-Phase loops - OFF - ON - -
ZPP Impedance setting reach for phase to phase elements ohm/p 0.005 3000.00 0.001 0.235 0.235
ZAngPP Angle for positive sequence line impedance for Phase-Phase deg 10 90 1 - -
ArgDir elements
Angle of blinder in fourth quadrant for forward direction (AngDir) deg 5 45 1 - -
IMinOpPE Minimum pickup phase current for Phase-toground loops %IB 5 30 1 - -
IMinOpPP Minimum pickup delta current (2 x current of lagging phase) for %IB 5 30 1 - -
78 Phaseto-
Pole slip protection phase loops
(PPAM).(PERDIDA DE SINCRONISMO)
Ajustes
Off
Operation Operación On/Off - - -
On
IBase Cirriente Base (primary phase current in Amperes) A 0.1 99999.9 0.1 - 3930.0 - 3930.0
UBase Voltaje Base (primary phase-tophase voltage in kV) KV 0.1 9999.9 0.1 - 12.5 - 12.5
PosSeq
L1L2
MeasureMode Modo Medición (PosSeq, L1L2, L2L3, L3L1) Ohm - -
L2L3
L3L1
InvertCTcurr Invert current direction - NO - YES - -
OperationZ1 Operación Zona 1 On / Off - ON - OFF - -
OperationZ2 Operación Zona 2 On / Off - ON - OFF - -
ImpedanceZA Forward impedance in % of Zbase % 0.00 1000.00 0.01 - -
ImpedanceZB Forward impedance in % of Zbase % 0.00 1000.00 0.01 - -
ImpedanceZC Forward impedance in % of Zbase % 0.00 1000.00 0.01 - -
AnglePhi Angle of the slip impedance line deg 72.0 90.0 0.01 - -
StartAngle Rotor angle for the start signal deg 0.00 180.00 0.10 - -
TripAngle Rotor angle for the trip1 and trip2 signals deg 0.00 180.00 0.10 - -
N1Limit Count limit for the trip1 signal - 1 20 1 - -
N2Limit Count limit for the trip2 signal - 1 20 1 - -
ResetTime Time without slip to reset all signals s 0.00 60.00 0.001 - -
40 Loss of excitation (PDIS). (PERDIDA DE EXCITACIÓN)
Off
Operation Operación On/Off - ON - ON -
On
IBase Corriente Base (primary phase current in Amperes) A 0.1 99999.9 0.1 1250.0 1250.0
UBase Voltaje Base (primary phase-tophase voltage in kV) KV 0.1 9999.9 0.1 5.3 5.3
invertCTcurren Corriente Inversa CT - NO - YES - - - -
PosSeq
MeasureMode Modo Medición (PosSeq, L1L2, L2L3, L3L1) Ohm L1L2 PosSeq - PosSeq -
L2L3
L3L1
DirSuperv Operation Off/On for additional directional criterion - ON - OFF - - - -
XoffsetDirLine Offset of directional line along X axis in % of Zbase % -1000 3000 0.0 - - - -
DirAngle Angle between directiona line and R-axis in degrees deg -180 180 0.1 - - - -
Alcance Zona 1
OperationZ1 Operation Disable/Enable zone Z1 - ON - OFF ON - ON -
XoffsetZ1 Offset of Z1 circle top point along X axis in % of Zbase % -1000 1000.00 0.01 -19.00 - -19.00 -
Z1diameter Diameter of imedance circle for Z1 in % of Zbase % 0.01 3000.00 0.01 100.00 - 100.00 -
tZ1 Trip time delay for Z1 s 0.00 6000.00 0.01 0.20 - 0.20 -
Alcance Zona 2
OperationZ2 Operation Disable/Enable zone Z2 - ON - OFF ON - ON -
XoffsetZ2 Offset of Z2 circle top point along X axis in % of Zbase % -1000 1000.00 0.01 -19.00 - -19.00 -
Z2diameter Diameter of imedance circle for Z2 in % of Zbase % 0.01 3000.00 0.01 128.00 - 128.00 -
tZ2 Trip time delay for Z2 s 0.00 6000.00 0.01 1.00 - 1.00 -
PROTECCIÓN DE SOBRESORRIENTE
50 INSTANTANEOUS PHASE OVERCURRENT PROTECTION (PIOC)
I>
Off
Operation Operación On/Off - - -
On
IBase Cirriente Base (IBase) A 1.0 99999 1 - 3000 - 3000
2 out of 3
OpMode Select operation mode 2-out of 3 / 1- out of 3 - 1 out of 3 - 1 out of 3 -
1 out of 3
Pickup Operate phase current level in % of Ibase %IB 1 2500 1 200 - 200 -
MultPU Multiplier for operate current level %IB 1 5 0 1.0 - 1.0 -
51_67 Four step phase overcurrent protection (PTOC)
DFT
MeasType Selection between DFT and RMS measurement - DFT - DFT -
RMS
Disabled
Operation Disable/Enable Operation - ON - ON -
Enabled
IBase Base current A 1 99999 1 - 1250 - 1250
UBase Base voltage KV 0.05 2000.00 0.05 - 5.25 - 5.25
AngleRCA Relay characteristic angle deg 40 65 1 55 - 55 -
AngleROA Relay operation angle deg 40 89 1 80 - 80 -
StartPhSel - Not Used - -
Number of phasesrequired for phase 1 out of 3
1 out of 3 1 out of 3
selection (1 of 3, 2 of 3, 3 of 3) 2 out of 3
3 out of 3
IMinOpPhSel Minimum current for phase selection in % of Ibase %IB 1 100 1 - - - -
2ndHarmStab Pickup of second harm restraint in % of Fundamental %IB 5 100 1 - - - -
Step 1
DirModeSel1 - Disabled - -
Directional mode of step 1 Non-directional Non-
Forward Non-directional
(Disabled, Nondir, Forward, Reverse) directional
Reverse
Characterist1 - ANSI E. inv., V. inv., N. inv., - -
ANSI Mod. inv., Def. Time,
L.T.E. inv, V. inv., inv.,
Selection of time delay ANSI Ext.
IEC N. inv., V. inv., inv., E. inv., ANSI Ext. Inv.
curve type for step 1 Inv.
IEC S.T. inv., L.T. inv., Def. Time,
Reserved, Programmable,
RI type, RD type.

380201555.xls 02/28/2018 1 de 3
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: PROTECCION GENERADOR Tipo Central: HIDROELECTRICA Región: ZONA SUR
Fabricante: ABB C.H.: CHARCANI VI Dpto:
Modelo: REG670 Tensión Nom.: 5,25 kV Empresa:
Versión: Grupo Gen.: G1 Diag.Unif.N°:
N° Serie: Uprim[kV]: 5,25kV Man.Serv.N°:
Tecnología: NUMÉRICA Fases: RSTN Fecha: 13-Feb-14
Año instal.: Ucc [V]: Respons.: K.V.H.
Código: Uca [V]: 100 Revisión: 0
Ubic.Tabl: Ica [A]: 5
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 (AS BUILT) GRUPO 1 (AECP 2014) OBSERVACIONES
ACTUAL PROPUESTO
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

I1> Phase current operate level for step1 in % of IBase %IB 1 2500 1 98 103 1287.50
t1 Definitive time delay of step 1 s 0.00 60.00 0.001 0.050 - 0.050 -
TD1 Time multiplier for the inverse time delay for step 1 - 0.05 999.00 0.01 1.10 - 1.10 -
t1Min Minimum operate time for inverse curves for step 1 s 0.00 60.00 0.001 0 - 0 -
MultPU1 Multiplier for current operate level for step 1 - 1.00 10.00 0.1 2.0 - 2.0 -
Selection of reset curve - Instantaneous - - - -
ResetTypeCrv1 type for step 1 IEC Reset
ANSI reset
tReset1 Reset time delay used in IEC Definite Time curve step 1 S 0.0 60.0 0.001 - - - -
tPCrv1 Parameter P for customer programmable curve for step 1 - 0.005 3.0 0.001 - - - -
tACrv1 Parameter A for customer programmable curve for step 1 - 0.005 200.0 0.001 - - - -
tBCrv1 Parameter B for customer programmable curve for step 1 - 0.10 10.0 0.01 - - - -
tCCrv1 Parameter C for customer programmable curve for step 1 - 0.005 3.0 0.10 - - - -
tPRCrv1 Parameter PR for customer programmable curve for step 1 - 0.005 100.0 0.001 - - - -
tTRCrv1 Parameter TR for customer programmable curve for step 1 - 0.10 10.0 0.001 - - - -
tCRCrv1 Parameter CR for customer programmable curve for step 1 - 0.10 10.0 0.10 - - - -
- Disabled - - - -
HarmRestrain1 Enable block of step 1 from harmonic restrain
Enabled
Step 2
DirModeSel2 - Disabled - -
Directional mode of step 2 Non-directional Non-
Forward Non-directional
(Disabled, Nondir, Forward, Reverse) directional
Reverse
Characterist2 - ANSI E. inv., V. inv., N. inv., - -
ANSI Mod. inv., Def. Time,
L.T.E. inv, V. inv., inv.,
Selection of time delay IEC Def
IEC N. inv., V. inv., inv., E. inv., IEC Def Time
curve type for step 2 Time
IEC S.T. inv., L.T. inv., Def. Time,
Reserved, Programmable,
RI type, RD type.
I2> Phase current operate level for step2 in % of IBase %IB 1 2500 1 392 - 392 -
t2 Definitive time delay of step 2 s 0.00 60.00 0.001 0.10 - 0.10 -
TD2 Time multiplier for the inverse time delay for step 2 - 0.05 999.00 0.01 0.05 - 0.05 -
t2Min Multiplier for current operate level for step 2 s 1.00 10.00 0.1 2.0 - 2.0 -
MultPU2 Minimum operate time for inverse curves for step 2 - 0.00 60.00 0.001 0.000 - 0.000 -
Selection of reset curve - Instantaneous - -
ResetTypeCrv2 type for step 2 IEC Reset
ANSI reset
tReset2 Reset time delay used in IEC Definite Time curve step 2 S 0.0 60.0 0.001 - -
tPCrv2 (tReset2)
Parameter P for customer programmable curve for step 2 - 0.005 3.0 0.001 - -
tACrv2 Parameter A for customer programmable curve for step 2 - 0.005 200.0 0.001 - -
tBCrv2 Parameter B for customer programmable curve for step 2 - 0.10 10.0 0.01 - -
tCCrv2 Parameter C for customer programmable curve for step 2 - 0.005 3.0 0.10 - -
tPRCrv2 Parameter PR for customer programmable curve for step 2 - 0.005 100.0 0.001 - -
tTRCrv2 Parameter TR for customer programmable curve for step 2 - 0.10 10.0 0.001 - -
tCRCrv2 Parameter CR for customer programmable curve for step 2 - 0.10 10.0 0.10 - -
- Disabled - -
HarmRestrain2 Enable block of step 2 from harmonic restrain
Enabled
Step 3
DirModeSel3 - Disabled - -
Directional mode of step 3 Non-directional
OFF OFF
(Disabled, Nondir, Forward, Reverse) Forward
Reverse
Characterist3 - ANSI E. inv., V. inv., N. inv., - -
ANSI Mod. inv., Def. Time,
Selection of time delay
curve type for step 3 L.T.E. inv, V. inv., inv.,
IEC N. inv., V. inv., inv., E. inv.,
IEC S.T. inv., L.T. inv., Def. Time,
Characterist4 - ANSI: E. inv., V. inv., N. inv., - -
Selection of time delay ANSI: Mod. inv., Def. Time,
curve type for step 4 L.T.: E. inv, V. inv., inv.,
IEC: N. inv., V. inv., inv., E. inv.,
I4> Phase current operate level for step4 in % of IBase %IB 1 2500 1 - -
t4 Definitive time delay of step 4 s 0.00 60.00 0.001 - -
TD4 Time multiplier for the inverse time delay for step 4 - 0.05 999.00 0.01 - -
t4Min Minimum operate time for inverse curves for step 4 s 0.00 60.00 0.001 - -
tPRCrv2 Parameter PR for customer programmable curve for step 2 - 0.005 100.0 0.001 - -
tTRCrv2 Parameter TR for customer programmable curve for step 2 - 0.10 10.0 0.001 - -
tCRCrv2 Parameter CR for customer programmable curve for step 2 - 0.10 10.0 0.10 - -
TimeChar - L.T.: E. inv, V. inv., inv., - -
IEC: N. inv., V. inv., inv., E. inv.,
IEC: S.T. inv., L.T. inv., Def. Time,
Reserved, Programmable,
RI type, RD type.
t_MinTripDelay Minimum operate time for IEC IDMT curves, in sec s 0.000 60.000 0.001 - -
TDIN IDMT time mult for non-dir res over current protection - 0.00 2.00 0.01 - -
OpVN Operation of non- directional residual overvoltage protection - Disabled
- -
Enabled
VN_PU Set level for non- directional residual over voltage, in %Vb %VB 1.00 200.00 0.01 - -
tVNNonDir Time delay for non-directional residual over voltage, in sec s 0.000 60.000 0.001 - -
INRelPU Residual release current for all directional modes, in %Ib %IB 0.25 200.00 0.01 - -
VNRelPU Residual release voltage for all direction modes, in %Vb %VB 0.01 200.00 0.01 - -
RotResV Setting for rotating polarizing quantity if deg 0 180 1 - -
tReset Time delay used for reset necessary
of definite timers, in sec s 0.000 60.000 0.001 - -
tPCrv Setting P for customer programmable curve - 0.005 3.000 0.001 - -
tACrv Setting A for customer programmable curve - 0.005 200.000 0.001 - -
tBCrv Setting B for customer programmable curve - 0.00 20.00 0.01 - -
tCCrv Setting C for customer programmable curve - 0.1 10.0 0.1 - -
ResetTypeCrv Reset mode when current drops off. (ResetTypeCrv) - Immediate
IEC Reset - -
ANSI reset
tPRCrv Setting PR for customer programmable curve - 0.005 3.000 0.001 - -
tTRCrv Setting TR for customer programmable curve - 0.005 100.000 0.001 - -
tCRCrv Setting CR for customer programmable curve - 0.1 10.0 0.01 - -
49 Thermal overload protection, two time constants (PTTR)
Disabled
Operation Disable/Enable Operation - OFF - OFF -
Enabled
ThetaInit Initial Heat content, in % of heat content trip value % 0.0 95.0 1.0 - -
Warning Time setting, below which warning would be set Min 1.0 500.0 0.1 - -
tPulse Length of the pulse for trip signal (in msec). s 0.01 0.30 0.01 - -
RetripMode
Operation mode of re-trip logic - -

Pickup_PH Phase current pickup in % of IBase (Pickup_PH) (IP>) %IB 5 200 1 - -


Pickup_N Operate residual current level in % of IBase (Pickup_N) (IN>) %IB 2 200 1 - -
t1 Time delay of re-trip s 0.000 60.000 0.001 - -
t2 Time delay of back-up trip s 0.000 60.000 0.001 - -
t2MPh Time delay of back-up trip at multi-phase pickup s 0.000 60.000 0.001 - -
tPulse Trip pulse duration s 0.000 60.000 0.001 - -
I>BlkCont Current for blocking of CB contact operation in % of IBase %IB 5 200 1 - -
t3 Additional time delay to 27P2TDLY for a second back-up trip s 0.000 60.000 0.001 - -
tCBAlarm Time delay for CB faulty signal s 0.000 60.000 0.001 - -
52PD Pole discrepancy protection (RPLD)
Disabled
Operation Disable/Enable Operation - - -
Enabled
Ibase Base current (IBase) A 1 99999 1 - 3000 - 3000
tTrip Time delay between trip condition and trip signal (tTrip) s 0.000 60.000 0.001 - -
ContactSel - Disabled
Contact function selection (ContactSel) PD signal from CB - -
Pole pos aux cont.
CurrentSel - Disabled
CB oper monitor
Current function selection (CurrentSel) - -
Continuous
monitor
CurrUnsymPU Unsym magn of lowest phase current compared to the highest. % 0 100 1 - -
CurrRelPU Current magnitude for release of the function in % of IBase %IB 0 100 1 - -
37 Directional underpower protection (PDUP)
IBase Current-Reference (primary current A) (IBase) A 1 99999 1 660.00 660.00
VBase Voltage-Reference (primary voltage kV) (VBase) KV 0.05 2000.00 0.05 5.25 5.25
Mode A, B, C BC
Arone CA
Selection of measured current and voltage (Mode) - Pos Seq A Pos Seq - Pos Seq -
AB B
C

Operation Disable/Enable Operation - Disabled OFF - OFF -


Enabled
K Low pass filter coefficient for power measuremt, P and Q (K) - 0.00 0.99 0.01 - -
IMagComp5 Magnitude factor to calibrate current at 5% of In % -10.000 10.000 0.001 - -
IMagComp30 Magnitude factor to calibrate current at 30% of In % -10.000 10.000 0.001 - -
IMagComp100 Magnitude factor to calibrate current at 100% of In % -10.000 10.000 0.001 - -
VMagComp5 Magnitude factor to calibrate voltage at 5% of Vn % -10.000 10.000 0.001 - -
VMagComp30 Magnitude factor to calibrate voltage at 30% of Vn % -10.000 10.000 0.001 - -
VMagComp100 Magnitude factor to calibrate voltage at 100% of Vn % -10.000 10.000 0.001 - -
IAngComp5 Angle calibration for current at 5% of In Deg -10.000 10.000 0.001 - -
IAngComp30 Angle calibration for current at 30% of In Deg -10.000 10.000 0.001 - -
IAngComp100 Angle calibration for current at 100% of In Deg -10.000 10.000 0.001 - -
Step 1
OpMode1 - Disabled OFF OFF
Operation mode 1 - -
UnderPower
Power1 Power setting for stage 1 in % of Sbase %SB 0.0 500.0 0.1 5.00 - 5.00 -
Angle1 Angle for stage 1 Deg -180.0 180.0 0.1 0.00 - 0.00 -
TripDelay1 Trip delay for stage 1 s 0.010 6000.000 0.001 30.00 - 30.00 -
DropDelay1 Drop delay for stage 1 s 0.010 6000.000 0.001 1.00 - 1.00 -
Hysteresis1 Absolute hysteresis of stage 1 pu 0.2 5.0 0.1 - -
Step 2
OpMode2 Disabled
Operation mode 2 - OFF - OFF -
OverPower
Power2 Power setting for stage 2 in % of Sbase %SB 0.0 500.0 0.1 5.00 - 5.00 -
Angle2 Angle for stage 2 Deg -180 180.0 0.1 0.00 - 0.00 -
TripDelay2 Trip delay for stage 2 s 0.010 6000.000 0.001 5.00 - 5.00 -
DropDelay2 Drop delay for stage 2 s 0.010 6000.000 0.001 1.00 - 1.00 -
Hysteresis2 Absolute hysteresis of stage 2 pu 0.2 5.0 0.1 - -
32 Directional overpower protection (PDOP)
IBase Current-Reference (primary current A) A 1 99999 1 1233.00 1233.00
VBase Voltage-Reference (primary voltage kV) KV 0.05 2000.00 0.05 5.25 5.25
Mode A, B, C BC
Arone CA
Selection of measured current and voltage - Pos Seq A Pos Seq - Pos Seq -
AB B
C
Disabled
Operation Disable/Enable Operation - ON - ON -
Enabled
K Low pass filter coefficient for power measurement, P and Q - 0.00 0.99 0.01 - - - -
IMagComp5 Magnitude factor to calibrate current at 5% of In % -10.000 10.000 0.001 - - - -
IMagComp30 Magnitude factor to calibrate current at 30% of In % -10.000 10.000 0.001 - - - -
IMagComp100 Magnitude factor to calibrate current at 100% of In % -10.000 10.000 0.001 - - - -
VMagComp5 Magnitude factor to calibrate voltage at 5% of Vn % -10.000 10.000 0.001 - - - -
VMagComp30 Magnitude factor to calibrate voltage at 30% of Vn % -10.000 10.000 0.001 - - - -
VMagComp100 Magnitude factor to calibrate voltage at 100% of Vn % -10.000 10.000 0.001 - - - -
IAngComp5 Angle calibration for current at 5% of In Deg -10.000 10.000 0.001 - - - -
IAngComp30 Angle calibration for current at 30% of In Deg -10.000 10.000 0.001 - - - -
IAngComp100 Angle calibration for current at 100% of In Deg -10.000 10.000 0.001 - - - -
Step 1
OpMode1 - Disabled Over Power Over Power
Operation mode 1 - -
OverPower
Power1 Power setting for stage 1 in % of Sbase %SB 0.0 500.0 0.1 14.00 - 14.00 -
Angle1 Angle for stage 1 Deg -180.0 180.0 0.1 180.00 - 180.00 -
TripDelay1 Trip delay for stage 1 s 0.010 6000.000 0.001 5.00 - 5.00 -
DropDelay1 Drop delay for stage 1 s 0.010 6000.000 0.001 1.00 - 1.00 -
Hysteresis1 Absolute hysteresis of stage 1 in % of Sbase pu 0.2 5.0 0.1 - - - -
Step 2
OpMode2 Disabled
Operation mode 2 - OFF - OFF -
OverPower
Power2 Power setting for stage 2 in % of Sbase %SB 0.0 500.0 0.1 - -
Angle2 Angle for stage 2 Deg -180 180.0 0.1 - -
TripDelay2 Trip delay for stage 2 s 0.010 6000.000 0.001 - -
DropDelay2 Drop delay for stage 2 s 0.010 6000.000 0.001 - -
Hysteresis2 Absolute hysteresis of stage 2 in % of Sbase pu 0.2 5.0 0.1 - -
VOLTAGE PROTECTION
27 Two step undervoltage protection (PTUV)
ConnType PhN DFT
PhPh RMS
Group selector for connection type - PhN RMS PhPhDFT - PhPhDFT -
PhPh DFT

Operation Disable/Enable Operation - Off / On ON - ON -

VBase Voltage-Reference (primary voltage kV) KV 0.05 2000.00 0.05 - 5.25 - 5.25
Step 1
OperationStep1 Enable execution of step 1 - Off / On ON - ON -
Characterist1 Definite time
Inverse curve A
Definite
Selection of time delay curve type for step 1 - Inverse curve B Definite time - -
time
Prog. inv. curve

OpMode1 1 out of 3
Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step
- 2 out of 3 3 out of 3 - 3 out of 3 -
1 3 out of 3
Pickup1 (U1<) Voltage pickup value (Definite-Time & Inverse-Time curve) in % %UB 1 100 1 70.00 - 70.00 -
of VBase, step 1
t1 Definitive time delay of step 1 s 0.00 6000.00 0.01 3.00 - 3.00 -
tReset1 Reset time delay used in IEC Definite Time curve step 1 s 0.000 60.000 0.001 - -
t1Min Minimum operate time for inverse curves for step 1 s 0.000 60.000 0.001 5.00 - 5.00 -
Instantaneous
Frozen timer
ResetTypeCrv1 Selection of reset curve type for step 1 - - -
Linearly
decreased
tIReset1 Time delay in Inverse- Time reset (s), step 1 s 0.000 60.000 0.001 - -
TD1 (K1) Time multiplier for the inverse time delay for step 1 - 0.05 1.10 0.01 0.05 - 0.05 -
ACrv1 Parameter A for customer programmable curve for step 1 - 1.000 200.000 0.001 - -
BCrv1 Parameter B for customer programmable curve for step 1 - 1.00 100.00 0.01 - -
CCrv1 Parameter C for customer programmable curve for step 1 - 0.0 1.0 0.1 - -
DCrv1 Parameter D for customer programmable curve for step 1 - 0.000 60.000 0.001 - -
PCrv1 Parameter P for customer programmable curve for step 1 - 1.000 3.000 0.001 - -
CrvSat1 Tuning param for prog. under voltage Inverse- Time curve, step % 0 100 1 - -
1 Off
IntBlkSel1 Internal (low level) blocking mode, step 1 - Block of trip off - off -
Block all
IntBlkStVal1 Voltage setting for internal blocking in % of VBase, step 1 %UB 1 100 1 20.00 - 20.00 -
tBlkUV1 Time delay of internal (low level) blocking for step 1 s 0.000 60.000 0.001 0.00 - 0.00 -
HystAbs1 Absolute hysteresis in % of VBase, step 1 %UB 0.00 100.00 0.01 0.50 - 0.50 -
Step 2
OperationStep2 Enable execution of step 2 - Off / On OFF - OFF -

Characterist2 Definite time


Selection of time delay curve type for step 2 - Inverse curve A - -
Inverse curve B
Prog. inv. Curve
OpMode2 1 out of 3
Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step
- 2 out of 3 - -
2
3 out of 3
Pickup2 (U2<) Voltage pickup value (Definite-Time & Inverse-Time curve) in % %UB 1 100 1 - -
of VBase, step 2
t2 Definitive time delay of step 2 s 0.000 60.000 0.001 - -
t2Min Minimum operate time for inverse curves for step 2 s 0.000 60.000 0.001 - -
TD2 (K2) Time multiplier for the inverse time delay for step 2 - 0.05 1.10 0.01 - -
tReset2 Reset time delay used in IEC Definite Time curve step 2 s 0.000 60.000 0.001 - -
Instantaneous
Frozen timer
ResetTypeCrv2 Selection of reset curve type for step 2 - - -
Linearly
decreased
tIReset2 Time delay in Inverse-Time reset (s), step 2 s 0.000 60.000 0.001 - -
ACrv2 Parameter A for customer programmable curve for step 2 - 1.000 200.000 0.001 - -
BCrv2 Parameter B for customer programmable curve for step 2 - 1.00 100.00 0.01 - -
CCrv2 Parameter C for customer programmable curve for step 2 - 0.0 1.0 0.1 - -
DCrv2 Parameter D for customer programmable curve for step 2 - 0.000 60.000 0.001 - -
PCrv2 Parameter P for customer programmable curve for step 2 - 1.000 3.000 0.001 - -
CrvSat2 Tuning param for prog. under voltage Inverse- Time curve, step % 0 100 1 - -
2 Off
IntBlkSel2 Internal (low level) blocking mode, step 2 - Block of trip - -
Block all
IntBlkStVal2 Voltage setting for internal blocking in % of VBase, step 2 %UB 1 100 1 - -
tBlkUV2 Time delay of internal (low level) blocking for step 2 s 0.000 60.000 0.001 - -
HystAbs2 Absolute hysteresis in % of VBase, step 2 %UB 0.0 100.0 0.1 - -
59 Two step overvoltage protection (PTOV)
ConnType PhN DFT
PhPh RMS
Group selector for connection type - PhN RMS PhPhDFT - PhPhDFT -
PhPh DFT

Operation Disable/Enable Operation - Off / On ON - ON -

VBase Voltage-Reference (primary voltage kV) (VBase) KV 0.05 2000.00 0.05 5.25 5.25
Step 1
Disabled
OperationStep1 Enable execution of step 1 - ON - ON -
Enabled
Characterist1 Definite time
Inverse curve A
Selection of time delay curve type for step 1 - Inverse curve B Definite time - Definite -
time
Inverse curve C
Prog. inv. Curve
OpMode1 1 out of 3
Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step
- 2 out of 3 3 out of 3 - 3 out of 3 -
1
3 out of 3
Pickup1 (U1>) Voltage pickup value (Definite-Time & Inverse-Time curve) in % %VB 1 200 1 130.00 130.00
of VBase, step 1
t1 Definitive time delay of step 1 s 0.00 6000.00 0.01 0.10 - 0.10 -
tReset1 Reset time delay used in IEC Definite Time curve step s 0.000 60.000 0.001 - -
t1Min Minimum operate time for inverse curves for step 1 s 0.000 60.000 0.001 5.00 - 5.00 -
Instantaneous
Frozen timer
ResetTypeCrv1 Selection of reset curve type for step 1 - - -
Linearly
decreased
tIReset1 Time delay in Inverse- Time reset (s), step 1 s 0.000 60.000 0.001 - -
TD1 (K1) Time multiplier for the inverse time delay for step 1 - 0.05 1.10 0.01 0.05 - 0.05 -
ACrv1 Parameter A for customer programmable curve for step 1 - 1.000 200.000 0.001 - -
BCrv1 Parameter B for customer programmable curve for step 1 - 1.00 100.00 0.01 - -
CCrv1 Parameter C for customer programmable curve for step 1 - 0.0 1.0 0.1 - -
DCrv1 Parameter D for customer programmable curve for step 1 - 0.000 60.000 0.001 - -
PCrv1 Parameter P for customer programmable curve for step 1 - 1.000 3.000 0.001 - -
CrvSat1 Tuning param for prog. under voltage Inverse- Time curve, step % 0 100 1 - -
HystAbs1 1
Absolute hysteresis in % of VBase, step 1 %VB 0.00 100.00 0.01 0.5 - 0.5 -
Step 2
Disabled
OperationStep2 Enable execution of step 2 - Disabled - Disabled -
Enabled
Characterist2 Definite time
Inverse curve A
Selection of time delay curve type for step 2 - Inverse curve B - -
Inverse curve C
Prog. inv. Curve
OpMode2 1 out of 3
Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step
- 2 out of 3 - -
2
3 out of 3
Pickup2 (U2>) Voltage pickup value (Definite-Time & Inverse-Time curve) in % %VB 1 200 1 - -
of VBase, step 2
t2 Definitive time delay of step 2 s 0.000 60.000 0.001 - -
tReset2 Reset time delay used in IEC Definite Time curve step 2 s 0.000 60.000 0.001 - -
t2Min Minimum operate time for inverse curves for step 2 s 0.000 60.000 0.001 - -

380201555.xls 02/28/2018 2 de 3
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: PROTECCION GENERADOR Tipo Central: HIDROELECTRICA Región: ZONA SUR
Fabricante: ABB C.H.: CHARCANI VI Dpto:
Modelo: REG670 Tensión Nom.: 5,25 kV Empresa:
Versión: Grupo Gen.: G1 Diag.Unif.N°:
N° Serie: Uprim[kV]: 5,25kV Man.Serv.N°:
Tecnología: NUMÉRICA Fases: RSTN Fecha: 13-Feb-14
Año instal.: Ucc [V]: Respons.: K.V.H.
Código: Uca [V]: 100 Revisión: 0
Ubic.Tabl: Ica [A]: 5
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 (AS BUILT) GRUPO 1 (AECP 2014) OBSERVACIONES
ACTUAL PROPUESTO
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

Instantaneous
Frozen timer
ResetTypeCrv2 Selection of reset curve type for step 2 - - -
Linearly
decreased
tIReset2 Time delay in Inverse-Time reset (s), step 2 s 0.000 60.000 0.001 - -
TD2 (K2) Time multiplier for the inverse time delay for step 2 - 0.05 1.10 0.01 - -
ACrv2 Parameter A for customer programmable curve for step 2 - 1.000 200.000 0.001 - -
BCrv2 Parameter B for customer programmable curve for step 2 - 1.00 100.00 0.01 - -
CCrv2 Parameter C for customer programmable curve for step 2 - 0.0 1.0 0.1 - -
DCrv2 Parameter D for customer programmable curve for step 2 - 0.000 60.000 0.001 - -
PCrv2 Parameter P for customer programmable curve for step 2 - 1.000 3.000 0.001 - -
CrvSat2 Tuning param for prog. under voltage Inverse- Time curve, step % 0 100 1 - -
HystAbs2 2Absolute hysteresis in % of VBase, step 2 %VB 0.0 100.0 0.1 - -
59N Two step residual overvoltage protection (PTOV)
Disabled
Operation Disable/Enable Operation - ON - ON -
Enabled
Vbase Voltage-Reference (primary voltage kV) KV 0.05 2000.00 0.05 - 5.25 - 5.25
Step 1
Disabled
OperationStep1 Enable execution of step 1 - ON - ON -
Enabled
Characterist1 Definite time
Inverse curve A
Selection of time delay curve type for step 1 - Inverse curve B Definite time - Definite -
time
Inverse curve C
Prog. inv. Curve
OpMode1 1 out of 3
Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step
- 2 out of 3 - -
1
3 out of 3
Pickup1 (U1>) Voltage pickup value (Definite-Time & Inverse-Time curve) in % %VB 1 200 1 9.00 9.00
- -
of VBase, step 1
t1 Definitive time delay of step 1 s 0.00 6000.00 0.01 1.00 - 1.00 -
tReset1 Reset time delay used in IEC Definite Time curve step 1 s 0.000 60.000 0.001 - -
t1Min Minimum operate time for inverse curves for step 1 s 0.000 60.000 0.001 5.00 - 5.00 -
Instantaneous
Frozen timer
ResetTypeCrv1 Selection of reset curve type for step 1 - - -
Linearly
decreased
tIReset1 Time delay in Inverse- Time reset (s), step 1 s 0.000 60.000 0.001 - -
TD1 (K1) Time multiplier for the inverse time delay for step 1 - 0.05 1.10 0.01 0.05 - 0.05 -
ACrv1 Parameter A for customer programmable curve for step 1 - 1.000 200.000 0.001 - -
BCrv1 Parameter B for customer programmable curve for step 1 - 1.00 100.00 0.01 - -
CCrv1 Parameter C for customer programmable curve for step 1 - 0.0 1.0 0.1 - -
DCrv1 Parameter D for customer programmable curve for step 1 - 0.000 60.000 0.001 - -
PCrv1 Parameter P for customer programmable curve for step 1 - 1.000 3.000 0.001 - -
CrvSat1 Tuning param for prog. under voltage Inverse- Time curve, step % 0 100 1 - -
HystAbs1 1
Absolute hysteresis in % of VBase, step 1 %VB 0.00 100.00 0.01 0.50 - 0.50 -
Step 2
Disabled
OperationStep2 Enable execution of step 2 - OFF - OFF -
Enabled
Characterist2 Definite time
Inverse curve A
Selection of time delay curve type for step 2 - Inverse curve B - -
Inverse curve C
Prog. inv. Curve
OpMode2 1 out of 3
Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step
- 2 out of 3 - -
2
3 out of 3
Pickup2 (U2<) Voltage pickup value (Definite-Time & Inverse-Time curve) in % %VB 1 100 1
- -
of VBase, step 2
t2 Definitive time delay of step 2 s 0.000 60.000 0.001 - -
t2Min Minimum operate time for inverse curves for step 2 s 0.000 60.000 0.001 - -
TD2 (K2) Time multiplier for the inverse time delay for step 2 - 0.05 1.10 0.01 - -
tReset2 Reset time delay used in IEC Definite Time curve step 2 s 0.000 60.000 0.001 - -
Instantaneous
Frozen timer
ResetTypeCrv2 Selection of reset curve type for step 2 - - -
Linearly
decreased
tIReset2 Time delay in Inverse-Time reset (s), step 2 s 0.000 60.000 0.001 - -
ACrv2 Parameter A for customer programmable curve for step 2 - 1.000 200.000 0.001 - -
BCrv2 Parameter B for customer programmable curve for step 2 - 1.00 100.00 0.01 - -
CCrv2 Parameter C for customer programmable curve for step 2 - 0.0 1.0 0.1 - -
DCrv2 Parameter D for customer programmable curve for step 2 - 0.000 60.000 0.001 - -
PCrv2 Parameter P for customer programmable curve for step 2 - 1.000 3.000 0.001 - -
CrvSat2 Tuning param for prog. under voltage Inverse- Time curve, step % 0 100 1 - -
HystAbs2 2Absolute hysteresis in % of VBase, step 2 %VB 0.0 100.0 0.1 - -
24 Overexcitation protection (PVPH)
PosSeq
MeasuredV
AB
Selection of measured voltage (MeasuredV) - BC PosSeq - PosSeq -
CA

MeasuredI AB
BC
Selection of measured current (MeasuredI) - CA PosSeq - PosSeq -
PosSeq

Disabled
Operation Disable/Enable Operation - OFF - OFF -
Enabled
IBase Base current (rated phase current) in A A 1 99999 1 6890.00 6890.00
VBase Base voltage (main voltage) in kV kV 0.05 2000.00 0.05 15.75 15.75
Pickup1 (V/Hz>) Operate level of V/Hz at no load and rated freq in % of %VB/f 100.0 180.0 0.1 140.00 - 140.00 -
Pickup2 (V/Hz>>) (Vbase/frated)
High level of V/Hz above which tMin is used, in % of (Vbase/fn) %VB/f 100.0 200.0 0.1 110.0 - 110.0 -
Xleakage Winding leakage reactance in primary ohms ohm 0.000 200.000 0.001 0.00 - 0.00 -
t_TripPulse Length of the pulse for trip signal (in sec) s 0.000 60.000 0.001 0.10 - 0.10 -
t_MinTripDelay Minimum trip delay for V/ Hz inverse curve, in sec s 0.000 60.000 0.001 7.00 - 7.00 -
t_MaxTripDelay Maximum trip delay for V/ Hz inverse curve, in sec s 0.00 9000.00 0.01 1800.00 - 1800.00 -
t_CoolingK Transformer magnetic core cooling time constant, in sec s 0.10 9000.00 0.01 1200.00 - 1200.00 -
IEEE
CurveType Inverse time curve selection, IEEE/Tailor made - IEEE - IEEE -
Tailor made
TDForIEEECurve Time multiplier for IEEE inverse type curve - 1 60 1 1.00 - 1.00 -
t1_UserCurve Time delay t1 (longest) for tailor made curve, in sec (t1Tailor) s 0.00 9000.00 0.01 - -
t2_UserCurve Time delay t2 for tailor made curve, in sec (t2Tailor) s 0.00 9000.00 0.01 - -
t3_UserCurve Time delay t3 for tailor made curve, in sec (t3Tailor) s 0.00 9000.00 0.01 - -
t4_UserCurve Time delay t4 for tailor made curve, in sec (t4Tailor) s 0.00 9000.00 0.01 - -
t5_UserCurve Time delay t5 for tailor made curve, in sec (t5Tailor) s 0.00 9000.00 0.01 - -
t6_UserCurve Time delay t6 (shortest) for tailor made curve, in sec (t6Tailor) s 0.00 9000.00 0.01 - -
AlarmPickup Alarm pickup level as % of Step1 trip pickup level % 50.00 120.00 0.1 - -
tAlarm Alarm time delay, in sec s 0.00 9000.00 0.01 5.00 - 5.00 -
60 Voltage differential protection (PTOV)
Disabled
Operation Disable/Enable Operation - - -
Enabled
VBase Base Voltage (VBase) kV 0.05 2000.00 0.05 - 400.00 - 400.00
No
BlkDiffAtULow Block operation at low voltage (BlkDiffAtULow) - - -
Yes
VDTrip Operate level, in % of VBase %UB 1.0 100.0 0.1 - -
tTrip Time delay for voltage differential operate, in milliseconds s 0.000 60.000 0.001 - -
tReset Time delay for voltage differential reset, in seconds s 0.000 60.000 0.001 - -
V1Low Input 1 undervoltage level, in % of VBase %UB 0.0 100.0 0.1 - -
V2Low Input 2 undervoltage level, in % of VBase %UB 0.0 100.0 0.1 - -
tBlock Reset time for undervoltage block s 0.000 60.000 0.001 - -
VDAlarm Alarm level, in % of VBase %UB 0.0 100.0 0.1 - -
tAlarm Time delay for voltage differential alarm, in seconds s 0.000 60.000 0.001 - -
RF_A Ratio compensation factor phase A VCap*RF_A=VBus_A - 0.000 3.000 0.001 - -
RF_B Ratio compensation factor phase B VCap*RF_B=VBus_B - 0.000 3.000 0.001 - -
RF_C Ratio compensation factor phase C VCap*RF_C=VBus_C - 0.000 3.000 0.001 - -
59THD 95% and 100% Stator earthground fault protection based on 3rd harmonic
GenRatedVolt Generator rated (nominal) phase-to-phase voltage in kV kV 1.0 100.0 0.1 - 5.3 - 5.3
NoVoltage
ResidualVoltage
All
Used connection type for gen. terminal voltage transformer AllThreePhases All
TVoltType - - ThreePhas -
(TVoltType) PhaseA ThreePhases
es
PhaseB
PhaseC

Operation Disable/Enable Operation - Disabled OFF - OFF -


Enabled
Beta Portion of voltN3rdHarmonic used as bias kV 1.00 10.00 0.01 1.00 - 1.00 -
No
Cbexists Defines if generator CBexists (between Gen & Transformer) - YES - YES -
Yes
FactorCBopen Beta is multiplied by this factor when CB is open - 1.00 10.00 0.01 1.00 - 1.00 -
VN3rdHPU Pickup 3rd Harm V< protection (when activated) % of VB/1,732 % 0.5 10.0 0.1 2.00 - 2.00 -
VT3BlkLevel If VT3 is below limit 3rdH Diff is blocked, in % of VB/ 1,732 % 0.1 10.0 0.1 1.00 - 1.00 -
VNFundPU Pickup fundamental VN> protection (95% SEF), % of VB/1,732 % 1.0 50.0 0.1 5.00 - 5.00 -
t3rdH Operation delay of 3rd harm-based protection (100% SEF) s 0.020 60.000 0.001 1.00 - 1.00 -
tVNFund Operation delay of fundamental VN> protection (95% SEF) s 0.000 60.000 0.001 0.500 - 0.500 -
FREQUENCY PROTECTION
81 Underfrequency protection (PTUF)
TUF1
Operation Disable/Enable Operation - Off / On ON - ON -

Vbase Base voltage kV 0.05 2000.00 0.05 5.25 5.25


Startrequency Frequency setting pickup value. Hz 35.00 75.00 0.01 57.00 - 57.00 -
IntBlockLevel Internal blocking level in % of VBase. %UB 0 100 1 50.00 - 50.00 -
TimeDlyOperate Operate time delay in over/ under-frequency mode. s 0.000 60.000 0.001 2.00 - 2.00 -
TimeDlyReset Time delay for reset. s 0.000 60.000 0.001 0.00 - 0.00 -
TimeDlyRestore Restore time delay. s 0.000 60.000 0.001 0.00 - 0.00 -
RestoreFreq Restore frequency if frequency is above frequency value. Hz 45.00 65.00 0.01 50.10 - 50.10 -
Definite timer Definite
TimerOperation Setting for choosing timer mode. - Definite timer - -
Volt based timer timer
Vnom Nominal voltage in % of VBase for voltage based timer. %UB 50 150 1 100.00 - 100.00 -
Vmin Lower operation limit in % of VBase for voltage based timer. %UB 50 150 1 90.00 - 90.00 -
Exponent For calculation of the curve form for voltage based timer. - 0.0 5.0 0.1 1.0 - 1.0 -
t_MaxTripDelay Maximum time operation limit for voltage based timer. (tMax) s 0.010 60.000 0.001 1.00 - 1.00 -
t_MinTripDelay Minimum time operation limit for voltage based timer. (tMin) s 0.010 60.000 0.001 1.00 - 1.00 -
TUF2
Operation Disable/Enable Operation - Off / On ON - ON -

Vbase Base voltage kV 0.05 2000.00 0.05 - 5.25 - 5.25


PUFrequency Frequency setting pickup value. Hz 35.00 75.00 0.01 55.00 - 55.00 -
IntBlockLevel Internal blocking level in % of VBase. %UB 0 100 1 50.00 - 50.00 -
TimeDlyOperate Operate time delay in over/ under-frequency mode. s 0.000 60.000 0.001 1.00 - 1.00 -
TimeDlyReset Time delay for reset. s 0.000 60.000 0.001 0.000 - 0.000 -
TimeDlyRestore Restore time delay. s 0.000 60.000 0.001 0.000 - 0.000 -
RestoreFreq Restore frequency if frequency is above frequency value. Hz 45.00 65.00 0.01 50.10 - 50.10 -
Definite timer Definite
TimerOperation Setting for choosing timer mode. - Definite timer - -
Volt based timer timer
Vnom Nominal voltage in % of VBase for voltage based timer. %UB 50 150 1 100 - 100 -
Vmin Lower operation limit in % of VBase for voltage based timer. %UB 50 150 1 90 - 90 -
Exponent For calculation of the curve form for voltage based timer. - 0.0 5.0 0.1 1.0 - 1.0 -
t_MaxTripDelay Maximum time operation limit for voltage based timer. (tMax) s 0.010 60.000 0.001 1.000 - 1.000 -
t_MinTripDelay Minimum time operation limit for voltage based timer. (tMin) s 0.010 60.000 0.001 1.000 - 1.000 -
TUF3 OFF OFF
Operation Disable/Enable Operation - Off / On - -
Vbase Base voltage kV 0.05 2000.00 0.05 - 12.50 - 12.50
PUFrequency Frequency setting pickup value. Hz 35.00 75.00 0.01 - -
IntBlockLevel Internal blocking level in % of VBase. %UB 0 100 1 - -
TimeDlyOperate Operate time delay in over/ under-frequency mode. s 0.000 60.000 0.001 - -
TimeDlyReset Time delay for reset. s 0.000 60.000 0.001 - -
TimeDlyRestore Restore time delay. s 0.000 60.000 0.001 - -
RestoreFreq Restore frequency if frequency is above frequency value. Hz 45.00 65.00 0.01 - -
Definite timer
TimerOperation Setting for choosing timer mode. - - -
Volt based timer
Vnom Nominal voltage in % of VBase for voltage based timer. %UB 50 150 1 - -
Vmin Lower operation limit in % of VBase for voltage based timer. %UB 50 150 1 - -
Exponent For calculation of the curve form for voltage based timer. - 0.0 5.0 0.1 - -
t_MaxTripDelay Maximum time operation limit for voltage based timer. (tMax) s 0.010 60.000 0.001 - -
t_MinTripDelay Minimum time operation limit for voltage based timer. (tMin) s 0.010 60.000 0.001 - -
81 Overfrequency protection (PTOF)
TOF1
Disabled
Operation Disable/Enable Operation - Enabled Enable - Enable -
Vbase Base voltage kV 0.05 2000.00 0.05 5.25 5.25
startFrequency Frequency gradient start value. Sign defines direct. Hz/s 35.00 75.00 0.01 64.00 - 64.00 -
IntBlockLevel (StartFrequency)
Internal blocking level in % of VBase. %UB 0 100 1 50.00 - 50.00 -
TimeDlyOperate Operate time delay in over/ under-frequency Mode. s 0.000 60.000 0.001 3.000 - 3.000 -
TimeDlyReset Time delay for reset. s 0.000 60.000 0.001 0.00 - 0.00 -
TOF2
Disabled
Operation Disable/Enable Operation - Enable - Enable -
Enabled
Vbase Base voltage kV 0.05 2000.00 0.05 5.25 5.25
PUFrequency Frequency gradient start value. Sign defines direct. Hz/s 35.00 75.00 0.01 65.00 - 65.00 -
(StartFrequency)
IntBlockLevel Internal blocking level in % of VBase. %UB 0 100 1 50.00 - 50.00 -

TimeDlyOperate Operate time delay in over/ under-frequency Mode. s 0.000 60.000 0.001 1.000 - 1.000 -
TimeDlyReset Time delay for reset. s 0.000 60.000 0.001 0.00 - 0.00 -
TOF3
Disabled
Operation Disable/Enable Operation - Disabled - Disabled -
Enabled
Vbase Base voltage kV 0.05 2000.00 0.05 - 12.50 - 12.50
PUFrequency Frequency gradient start value. Sign defines direct. Hz/s 35.00 75.00 0.01 - -
IntBlockLevel (StartFrequency)
Internal blocking level in % of VBase. %UB 0 100 1 - -
TimeDlyOperate Operate time delay in over/ under-frequency Mode. s 0.000 60.000 0.001 - -
TimeDlyReset Time delay for reset. s 0.000 60.000 0.001 - -
81 Rate-of-change frequency protection (PFRC).
Disabled
Operation Disable/Enable Operation - - -
Enabled
Vbase Base voltage kV 0.05 2000.00 0.05
PUFrequency Frequency setting pickup value. Hz 35.00 75.00 0.01 - -
IntBlockLevel Internal blocking level in % of VBase. %UB 0 100 1 - -
tTrip Operate time delay in pos./ neg. frequency gradient mode. s 0.000 60.000 0.001 - -
RestoreFreq Restore frequency if frequency is above frequency value (Hz) Hz 45.00 65.00 0.01 - -
tRestore Restore time delay. s 0.000 60.000 0.001 - -
tReset Time delay for reset s 0.000 60.000 0.001 - -
@ SECONDARY SYSTEM SUPERVISION
25 Synchrocheck and energizing check (RSYN, 25)
Operation Operation - phase1, phase2,
On - Off phase3 OFF - OFF -
phase1-phase2
phase1, phase2, phase3
SelPhaseBus1 Select phase for bus1 - - -
phase2-phase3
phase1-phase2
phase1, phase2, phase3
SelPhaseBus2 Select phase for bus2 - phase3-phase1 - -
phase2-phase3
phase1-phase2
phase1, phase2, phase3
SelPhaseLine1 Select phase for line1 - phase3-phase1 - -
phase2-phase3
phase1-phase2
SelPhaseLine2 Select phase for line2 - phase3-phase1
phase2-phase3 - -
UBase Base voltage in kV kV 0.001 phase3-phase1
9999.999 0.001 5.70 5.70
PhaseShift Phase Shift Deg -180 180 5 - -
URatio Voltage Ratio - 0.20 5.00 0.01 - -
OperationSync Operation for synchronism check function Off/On - On - Off - -
UHighBusSync Voltage high limit bus for synchrocheck in % of UBase %UB 50.0 120.0 1.0 - -
UHighLineSync Voltage high limit line for synchrocheck in % of UBase %UB 50.0 120.0 1.0 - -
UDiff U difference limit between bus and line in % of UBase %UB 2.0 50.0 1.0 - -
FreqDiffMin Freq. difference Min. Hz 0.003 1.000 0.001 - -
FreqDiffMax Freq. Difference Max. Hz 0.003 1.000 0.001 - -
FreqRateChange gradienteFreq. Difference Max. Hz 0.000 0.500 0.001 - -
tBreaker s 0.000 60.000 0.001 - -
tClose Pulse s 0.000 60.000 0.001 - -
tMaxSynch s 0.000 60.000 0.001 - -
tMinSynch s 0.000 60.000 0.001 - -
OperationSc - On - Off - -
UHighBusSc Voltage high limit bus for synchrocheck in % of UBase %UB 50.0 120.0 1.0 - -
UHighLineSc Voltage high limit line for synchrocheck in % of UBase %UB 50.0 120.0 1.0 - -
UDiffSc U difference limit between bus and line in % of UBase %UB 2.0 50.0 1.0 - -
FreqDiffA Freq. Difference limit between bus and line Auto Hz 0.003 1.000 0.001 - -
FreqDiffM Freq. difference limit between bus and line Manual Hz 0.003 1.000 0.001 - -
PhaseDiffA F angle difference limit between bus and line Auto Deg 5 90 1 - -
PhaseDiffM F angle difference limit between bus and line Manual Deg 5 90 1 - -
tSCA s 0.000 60.000 0.001 - -
tSCM s 0.000 60.000 0.001 - -
AutoEnerg Automatic energizing check mode - Off, DLLB, DBLL, Both - -
ManEnerg Manual energizing check mode - Off, DLLB, DBLL, Both - -
ManEnerDBDL Manual dead bus, dead line energizing - On - Off - -
UHighBusEnerg Voltage high limit bus for energ. check in % of UBase %UB 50.0 120.0 1.0 - -
UHighLineEnerg Voltage high limit line for energ. check in % of UBase %UB 50.0 120.0 1.0 - -
ULowBusEnerg Voltage low limit bus for energ check in % of UBase %UB 50.0 120.0 1.0 - -
ULowLineEnerg Voltage low limit line for energ check in % of UBase %UB 50.0 120.0 1.0 - -
UMaxEnerg Maximum voltage for energizing in % of UBase %UB 80.0 140.0 1.0 - -
tAutoEnerg Time delay for automatic energizing check s 0.000 60.000 0.001 - -
tManEnerg Time delay for manual energizing check s 0.000 60.000 0.001 - -
Hz 0.003 1.000 0.001 - -
RFUF Fuse failure supervision (RFUF)
FSD1
Operation Operation - On - Off OFF OFF
IBase Base value for current settigns in A A 1 99999 1 - 600.00 - 600.00
UBase Base value for voltage settings in kV kV Off, UNsINs,
0.05 2000.00 UZsIZs,
0.01 - -
5.25 5.25
UZsIZs OR UNsINs,
OpMode Operating mode selection - -
UZsIZs AND UNsINs,
3U0> Operate level of 3U0 overvoltage in % of UBase %UB 1 100
OptimZsNs 1 -
3I0< Operate level of 3I0 undercurrent in % of IBase %IB 1 100 1 -
3U2> Operate level of neg.seq overvoltage in % of UBase %UB 1 100 1 -
3I2< Operate level of neg.seq undercurrent in % of IBase %IB 1 100 1 -
OperationDUDI Operation of change based function Off/On - On - Off -
DU> Op level of change in phase voltage in % of UBase %UB 1 100 1 -
DI< Op level of change in phase current in % of IBase %IB 1 100 1 -
UPh> Operate level of phase voltage in % of UBase %UB 1 100 1 -
IPh> Operate level of phase current in % of IBase %IB 1 100 1 -
SealIn Seal in functionality - On - Off -
USealIn< Op level of seal-in phase voltage in % of UBase %UB 1 100 1 -
IDLD< Op level for open phase curr. detection in % of IBase %IB 1 100 1 -
UDLD< Op level for open phase voltage detec in % of UBase %UB 1 100 1 -

380201555.xls 02/28/2018 3 de 3