SE-107 MANUAL

GROUND-FAULT GROUND-CHECK MONITOR


REVISION 5-C-050715

F1

CT1 CT2 A B L1 L2

GROUND RESET GROUND


FAULT CHECK
1.0

0.1 2.0 GF POWER


GF TRIP 4.0 A
TIME (s) 2.0 A ENHANCED
0.5 A F I LT E R I N G

SW CI GI GC G

F2

Copyright  2015 by Littelfuse Startco

All rights reserved.

Document Number: PM-1305-EN


Printed in Canada.
Page i
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

This page intentionally left blank.


Page ii
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

TABLE OF CONTENTS LIST OF TABLES


SECTION PAGE TABLE PAGE
1 General ................................................................. 1 1 Terminal Designations ...........................................4
2 Operation ............................................................. 1 2 Ground-Fault-Test Record ...................................14
2.1 Settings.................................................................. 1
2.1.1 GF Trip Time ............................................. 1
2.1.2 GF .............................................................. 1
2.2 Output Relay ......................................................... 1 DISCLAIMER
2.3 Indication and Reset .............................................. 1
2.4 Fusing.................................................................... 1 Specifications are subject to change without notice.
3 Installation ........................................................... 1 Littelfuse Startco is not liable for contingent or
3.1 SE-107 .................................................................. 1 consequential damages, or for expenses sustained as a
3.2 Ground-Fault CT................................................... 3 result of incorrect application, incorrect adjustment, or a
3.3 Ground-Check Termination .................................. 4 malfunction.
3.4 Remote Operation ................................................. 4
3.5 Parallel-Path Isolation ........................................... 4
3.6 Ground-Fault Testing ............................................ 4
4 Compatibility ....................................................... 4
5 Technical Specifications ................................... 11
5.1 SE-107 ................................................................ 11
5.2 Current Sensors ................................................... 12
5.3 Termination Assemblies ..................................... 12
6 Ordering Information ....................................... 13
7 Warranty ........................................................... 13
8 Ground-Fault Performance Test ..................... 14
Appendix A SE-107 Revision History......................... 15

LIST OF FIGURES
FIGURE PAGE

1 Typical Application .............................................. 2


2 SE-107 Outline and Mounting Details .................. 3
3 Current Transformers ............................................ 5
4 Zener-Diode Termination Devices........................ 5
5 SE-TA6 Termination Assembly ............................ 6
6 SE-TA6SF-WL Small-Format Termination
Assembly with Wire Leads ................................... 6
7 RK-102 Remote Indication and Reset Kit ............ 7
8 RK-105 Remote Indication-and-Reset Assembly . 7
9 RK-105I Remote Indication Assembly ................. 8
10 RK-13 Relay Interface Module ............................. 8
11 PPI-600V Parallel-Path Isolator ............................ 9
12 PPI-600V Typical Installation ............................ 10
13 Ground-Fault-Test Circuits ................................. 14
Page iii
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

This page intentionally left blank.


Page 1
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

1. GENERAL 2.2 OUTPUT RELAY


The output relay operates in the undervoltage mode. It
The SE-107 is a combination ground-fault and ground- is energized and its contact is closed when the ground-
check monitor for resistance-grounded systems in non- check loop is valid and the ground-fault circuit is not
hazardous applications. The ground-fault circuit is tripped. The undervoltage mode is referred to as fail-safe
latching and the ground-check circuit is typically non- because:
latching. One output contact is provided for contactor  Undervoltage devices release if supply voltage fails.
control or for undervoltage operation in a breaker trip  Undervoltage ground-check circuits do not allow
circuit. cable couplers to be energized until the ground-check
Ground-fault current is sensed by a CT200-series loop is verified.
current transformer. A trip level of 0.5, 2.0, or 4.0 A is
switch selectable for use with a 5-, 15-, or 25-A 2.3 INDICATION AND RESET
grounding resistor. Enhanced filtering eliminates false The blue POWER LED indicates that the internal
ground-fault trips from adjustable-speed-drive harmonic power supply is on. The red GROUND FAULT LED
distortion. Trip time is adjustable from 0.1 to 2.0 indicates a ground-fault trip and the green GROUND
seconds. CHECK LED indicates a valid ground-check loop. When
The fail-safe ground-check circuit is validated by an a ground-fault trip occurs, the SE-107 remains latched
end-of-line termination with a 5.6-volt Zener until the reset switch is pressed or the supply voltage is
characteristic. The Zener characteristic clamps induced cycled. The ground-check circuit is non-latching and
voltage and allows induced current to flow in the ground- does not require a reset. Terminals are provided for
check loop. Consequently, induced-ac-withstand remote indication and reset as shown in Fig. 1.
capability, noise immunity, and open/short detection are For the latching ground-check (Option L), the
independent of current in the phase conductors. GROUND CHECK LED is red and it indicates a latched
Enhanced filtering prevents false ground-check validation ground-check trip.
due to an active chopper condition. See
www.littelfuse.com/relayscontrols for Technical Note 2.4 FUSING
GC-1. The output contact is protected by fuse F1 (4.0 A, time
delay). The ground-check circuit is protected by fuse F2
CAUTION: The SE-107 is not a lock-out device. Follow (0.5 A, time delay).
lock-out procedures for maintenance.
3. INSTALLATION
2. OPERATION 3.1 SE-107
2.1 SETTINGS SE-107 outline and mounting details are shown in
2.1.1 GF TRIP TIME Fig. 2. Typical connections are shown in Fig. 1. Connect
Ground-fault trip time is adjustable from 0.1 to supply voltage to L1 and L2. For a 120-Vac supply,
2.0 seconds. Time-coordinated ground-fault protection connect supply neutral to L2. For a direct-current supply
requires this setting to be longer than the trip time of (Option D), connect supply negative to L2. Connect
downstream ground-fault devices. chassis-bonding terminal to ground.
Connect contact terminals A and B as required.
2.1.2 GF Faceplate LED’s are driven in series with remote-
The ground-fault-circuit trip level is 0.5, 2.0, or 4.0 A indication LED’s. When a remote kit is not used,
when current is sensed with a CT200-series current terminals CI, +, and GI must be connected for the
transformer. Since the ground-fault-circuit trip level faceplate LED’s to operate. These jumpers are installed
should not be greater than 20% of the grounding resistor at the factory.
let-through current, these levels are appropriate for use Connect terminal GC to the outgoing ground-check
with 5-, 15-, or 25-A grounding resistors. For other conductor and connect terminal G to ground. To meet
applications, the trip level of the ground-fault circuit is electrical code requirements, do not jumper chassis-
0.25, 1.0, or 2.0% of the primary rating of the bonding terminal to terminal G.
5-A-secondary current transformer. Install the upper terminal-block cover to prevent
inadvertent contact with line terminals.
Page 2
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

CT200
LOAD

GROUND
UV START
STOP
120 VAC GROUND CHECK
GC
L N GC NOTE 1
USE LOW- HOLD-IN
NOTE 1 CONTACT
G
LEVEL
F1 G CONTACTS

GROUND-CHECK ALTERNATE TERMINATION CIRCUIT


FOR REMOTE CONTACTOR CONTROL
CT1 CT2 A B L1 L2 TERMINATION

GROUND RESET GROUND


FAULT CHECK
SW CI GI GC G
1.0

0.1 2.0 POWER F2


GF TRIP
TIME (s)
ENHANCED
F I LT E R I N G

GI GROUND-FAULT
SW CI GI GC G INDICATOR
RED
+

F2 CI GROUND-CHECK
GREEN INDICATOR
SW
RESET SWITCH

REMOTE INDICATION AND RESET

SW CI GI GC G

SW CI GI GC G
F2
SW CI/GI + GI/RI

F2
SW CI/GI + GI/RI

TB1 S
W
R
S
R
S K1
C
G +
G
R K2
NOTE 2
1 2 I I

K1 K2 GI GROUND-FAULT
TB1 S
W
R
S
1
R
S
2
K1
C
G
I
+
G
R
I
K2
RED INDICATOR
K1 K2 NOTE 2 +

RK-13 CONNECTION WITHOUT REMOTE INDICATION OR RESET CI GROUND-CHECK


GREEN INDICATOR
NOTES:
SW
RESET SWITCH
1. SEE ORDERING INFORMATION FOR
24-120 Vac/Vdc
TERMINATION DEVICES. 5-W AXIAL
LEAD DEVICE INCLUDED. ALTERNATE
RESET CIRCUIT
2. K1 CLOSES ON GROUND-CHECK VALID.
FOR OPTION L K1 CLOSES ON RK-13 CONNECTION WITH REMOTE INDICATION AND RESET
GROUND-CHECK TRIP.
K2 CLOSES ON GROUND-FAULT TRIP.

FIGURE 1. Typical Application.


Page 3
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

NOTE 5

109.0 100.0

(1.71)
43.5
(4.29) (3.93)
88.9 77.8
(3.50) (3.06)

F1

CT1 CT2 A B L1 L2
NOTE 4

GROUND RESET GROUND


FAULT CHECK

(5.50)

(5.90)
150.0
139.7
1.0

0.1 2.0 POWER


GF TRIP
TIME (s)
ENHANCED
F I LT E R I N G

SW CI GI GC G

F2

4.8 (0.19) DIA


NOTES:
(1.71)
43.5

1. DIMENSIONS IN MILLIMETRES (INCHES).


2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25.
NOTE 5 3. MOUNTING SCREWS: M4 OR 8-32.
4. SHOWN WITH TERMINAL-BLOCK COVER REMOVED.
5. MINIMUM CLEARANCE FOR FUSE REMOVAL.

FIGURE 2. SE-107 Outline and Mounting Details.

3.2 GROUND-FAULT CT
Outline and mounting details for CT200 and CT200L NOTE: The CT200 and CT200L are 600-V-rated current
current transformers are shown in Fig. 3. Pass the phase transformers. When system voltage is above 600 V,
conductors through the CT window as shown in Fig. 1. ensure conductors passed through the sensor window are
Do not pass the ground or ground-check conductors insulated to system voltage.
through the CT. In applications that require shields or
drain wires to pass through the CT, return them through
the CT before connecting them to ground.
Connect the secondary of the ground-fault CT to
SE-107 terminals CT1 and CT2. The CT connection to
the SE-107 is not polarity sensitive. Ground one side of
the CT secondary.
Page 4
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

3.3 GROUND-CHECK TERMINATION 3.6 GROUND-FAULT TESTING


Install the ground-check termination at the load to Use CT-primary current injection to test the ground-
complete the ground-check loop as shown in Fig. 1. fault circuit. Fig. 13 shows test circuits using the SE-400
Termination outlines and mounting details are shown in Ground-Fault-Relay Test Unit and the SE-100T Ground-
Figs. 4, 5, and 6. Use only a Littelfuse Startco termination Fault-Relay Tester. The SE-400 has a programmable
device; others may not meet performance requirements. output of 0.5 to 9.9 A for a duration of 0.1 to 9.9 seconds.
Connect terminal G of the termination to the equipment The SE-100T has LO and HI outputs for 5- and 15-A
frame so that the ground-conductor-to-equipment-frame resistance-grounded systems.
connection is included in the monitored ground-check A test-record form is provided in Section 8 of this
loop. Connect terminal GC of the termination to the manual. Record the test results and test dates on this form
incoming ground-check conductor. to meet the requirements of the National Electrical Code
If ground-check interlocks are used, low-level (NEC). Retain the form so that the test data can be made
(bifurcated, precious-metal, or sealed-reed) contacts are available to the authority having jurisdiction.
recommended.
If used as a ground-fault monitor only, install the
termination at the SE-107. 4. COMPATIBILITY
The SE-107 is a direct replacement for the SEL-100,
3.4 REMOTE OPERATION SEL-100TD, SE-101, SE-102, SE-103, and SE-105 in
Terminals SW, CI, , and GI are provided for remote fail-safe applications. Terminal designations are shown
LED indication and remote reset as shown in Fig. 1. in Table 1.
Remote LED’s are driven in series with the front-panel Terminals CT1 and CT2 are transformer isolated so
LED’s. that the CT secondary can be grounded. Units with old
Remove factory-installed jumpers from terminals CI, +, designations do not allow the secondary of the ground-
and GI, and connect a remote kit as shown in Fig. 1. fault CT to be grounded when the ground-check circuit is
Optional remote kits are shown in Figs. 7, 8, and 9. used.
Standard LED indicator lamps are not compatible with
the SE-107. TABLE 1. TERMINAL DESIGNATIONS
For general-purpose applications, use the RK-105
OLD SE-105/SE-107
Remote Indication-and-Reset Assembly or the RK-105I
DESIGNATION DESIGNATIONS
Remote Indication Assembly. Connect terminals SW, CI,
CT CT1
+, and GI to remote-kit terminals SW, CI/RI, +, and GI.
CT CT2
For 22-mm-component applications, use the RK-102 (RELAY) A
Remote Indication and Reset Kit. Connect terminal X2 of (RELAY) B
the green ground-check indicator to CI, terminal X2 of L L1
the red ground-fault indicator to GI, and connect indicator N L2
X1 terminals to +. For remote reset, connect the normally SW SW
open push-button switch across terminals + and SW. PL CI
If indication is required from a separate voltage source, + +
or if separate ground-fault and ground-check contacts are GL GI
P GC
required, use an RK-13 Relay Interface Module. The
G G
RK-13 mounts on the SE-107 lower terminal block and is
compatible with the RK-102, RK-105 and RK-105I. See
Figs. 1 and 10. Contact K1 closes when the GC LED is
on and contact K2 closes when the GF LED is on.

3.5 PARALLEL-PATH ISOLATION


A PPI-600V can be used for parallel-path rejection. A
PPI-600V will also eliminate intermachine arcing and
prevent stray ac and dc currents from flowing in the
monitored ground wire. See Figs. 11 and 12. See
Technical Note GC-10 “Parallel Path Isolator” at
www.littelfuse.com/relayscontrols, or contact Littelfuse
Startco for application details.
Page 5
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

D 44.5 MAX
(1.75)

NOTES:

1. DIMENSIONS IN MILLIMETRES
(INCHES).

2. MOUNTING SCREWS: M4 OR
8-32.
A X1 X2
E

BLACK

WHITE

FRONT SIDE
B
9.4
(0.37) C

(0.87)
22.2
F

(1.75)
44.5
TAP M4 OR 8-32

BOTTOM MOUNTING DETAIL

PART DIMENSIONS
NUMBER A B C D E F

CT200 55.9 (2.20) 120.7 (4.75) 101.6 (4.00) 98.3 (3.87) 108.0 (4.25) 5.6 (0.22)

CT200L 88.9 (3.50) 154.0 (6.06) 133.4 (5.25) 139.7 (5.50) 144.5 (5.69) 7.1 (0.28)

FIGURE 3. Current Transformers.

69.9
(2.75)
G GC
250 (9.84) LENGTH OF # 14 AWG
GC
G

YELLOW STRANDED WIRE


(1.38)
35.0
LOAD.
BE INSTALLED AT
TERMINATION MUST

NOTES:
(0.40)
10.0

0.25” - 28 UNF
1. DIMENSIONS IN MILLIMETRES (INCHES).

1N5339B SE-TA6-SM 2. CAN BE IMMERSED IN GLYCOL.

FIGURE 4. Zener-Diode Termination Devices.


Page 6
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

41.5 40.0
(1.63) (1.57)

(0.31)
8.0
40.0 22.2 10.5 19.0
(1.57) (0.87) (0.41) (0.75)

SE-TA6
TERMINATION
ASSEMBLY
TAP M4
GC OR 8-32

(2.64)
(2.01)

67.0
51.0
(2.64)

G
67.0

4.5 (0.18) Ø, C’BORE 10.0 (0.39) Ø


3.2 (0.13) DEEP
FRONT SIDE MOUNTING DETAIL

NOTES:

1. DIMENSIONS IN MILLIMETRES (INCHES).

2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25.

3. MOUNTING SCREWS: M4 OR 8-32.

4. ENCLOSURE IS ELECTRICALLY CONNECTED


TO TERMINAL G.

5. CAN BE IMMERSED IN GLYCOL.

FIGURE 5. SE-TA6 Termination Assembly.

NOTE 2
(0.50)
12.7

4.0 50.8
(0.13)
3.2

(0.16) (2.00)
MOUNTING DETAIL
SE-TA6ASF-WL TERMINATION ASSY
(0.50)

R
12.7

Rev: 01 Serial No: DE130600619


Rating: 5.6 Vdc @ 105 mA 12 W Max C US
Use with: SE-134, SE-134C, SB6100LR 53428
SIDE
NOTES:
58.8
(2.32)
GC 1. DIMENSIONS IN MILLIMETRES (INCHES).
300 (12) OF
YELLOW WIRE 2. MOUNTING SCREWS M3.5 OR 6-32.
(0.75)
19.0

3. CAN BE IMMERSED IN GLYCOL.


G
300 (12) OF
GREEN/YELLOW WIRE
TOP
FIGURE 6. SE-TA6ASF-WL Small-Format Termination Assembly with Wire Leads.
Page 7
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

30.0
(1.18)
RESET GROUND CHECK GROUND FAULT

(0.98)
25.0
LEGEND
PLATE

(1.71)
NOTE 2

43.5

(0.59)
15.0
(0.89)
22.5
22.2 (0.87) DIA

17.3 36.6 29.9


(0.68) (1.44) (1.17)
LEGEND PLATES NOTES:
LED PILOT LIGHTS
1. DIMENSIONS IN MILLIMETRES
(INCHES).

40.0 MINIMUM
(1.71) 2. ----- INDICATES CLEARANCE
43.5

30.0 MINIMUM

(1.57)
REQUIRED.
(1.18)
3. PANEL THICKNESS 1.0 TO 6.0
(0.04 TO 0.24).
14.9 36.6 29.9
4. NEMA 4X.
(0.59) (1.44) (1.17)
5. CERTIFICATIONS NOT SHOWN.
PUSH BUTTON MOUNTING DETAIL

FIGURE 7. RK-102 Remote Indication and Reset Kit.

30.0
(1.18) 60.0
(2.36)
25.0 7.7 44.5
(0.98) (0.30) (1.75)
(0.40)

OUTLINE
10.0

GROUND CHECK

(1.125)
28.58

CI/RI GROUND FAULT


1.25”
+ CONDUIT
GI KNOCKOUT
1.70” DIA
SW RESET
(3.78)

(3.00)
96.0

76.0

RK-105

3.8 (0.15)
22.25 DIA
(0.875)
SIDE VIEW FRONT VIEW MOUNTING DETAIL
NOTES:

1. DIMENSIONS IN MILLIMETRES (INCHES).

2. NEMA 1.

FIGURE 8. RK-105 Remote Indication-and-Reset Assembly.


Page 8
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

30.0
60.0
(1.18) (2.36)
7.7 44.5
25.0
(0.30) (1.75)
(0.98)

(0.40)
OUTLINE

10.0
GROUND CHECK

(1.125)
28.58
CI/RI GROUND FAULT 1.25”
CONDUIT
+
KNOCKOUT
GI 1.70” DIA
SW

(3.78)

(3.00)
96.0

76.0
RK-105I

3.8 (0.15)
22.25 DIA
(0.875)

SIDE VIEW FRONT VIEW MOUNTING DETAIL


NOTES:

1. DIMENSIONS IN MILLIMETRES (INCHES).

2. NEMA 1.

FIGURE 9. RK-105I Remote Indication Assembly.

SW CI/GI + GI/RI
(1.87)
47.5
(1.22)
31.0

TB1 S R R C G
S S G + R
W 1 2 K1 I I K2

SIDE VIEW
60.2 RK-13 SHOWN MOUNTED ON SE-105/SE-107/SE-325
(2.37)

INSTALLATION INSTRUCTIONS:
S R R C G
S S G + R
W 1 2 K1 I I K2
1. REMOVE FOUR LEFTMOST LOWER TERMINAL BLOCK SCREWS.
(0.83)
21.0

2. PLACE RK-13 ON TERMINAL BLOCK AND REPLACE SCREWS.


3. MAKE REQUIRED CONNECTIONS TO TERMINAL BLOCK TB1.

NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).

FIGURE 10. RK-13 Relay Interface Module.


Page 9
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

9.5 DIA.
(0.38 DIA.)

(0.75) (0.50)
12.7
19.1

(2.50)
63.5
(0.75)
19.1
8-32 TAP

260.4
(10.25)
34.9 190.5 34.9
(1.38) (7.50) (1.38)
152.4
(6.00)

(1.50)
38.1

(4.03)
(1.03)
102.4
26.2
(1.50)
38.1

235.0
(9.25)

NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).

FIGURE 11. PPI-600V Parallel-Path Isolator.


Page 10
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

GROUND CHECK MONITOR


SE-105, SE-107, SE-134C, OR SE-135

CABLE GROUND
GROUND CHECK
G GC

GC OUTGOING
GROUND CHECK

G OUTGOING
GROUND

INCOMING
GROUND

CHASSIS GROUND BUS PPI-600V

NOTES:

1. THE PARALLEL-PATH ISOLATOR IS NOT POLARIZED. EITHER FLANGE CAN BE


CONNECTED TO CHASSIS.

2. THE OUTGOING GROUND MUST BE ISOLATED FROM THE CHASSIS GROUND BUS.
IF A FLANGE-MOUNTED RECEPTACLE IS USED, VERIFY THAT THE FLANGE IS ISOLATED
FROM THE GROUND PIN, AND

- USE A MATING PLUG WITH A NON-METALLIC HOUSING, OR

- ISOLATE THE FLANGE FROM THE CHASSIS IF THE MATING PLUG HAS A
METALLIC HOUSING.

3. CABLE PLUGS AND RECEPTACLES WITH GROUNDED METAL HOUSING MUST BE


ISOLATED FROM GROUND TO PREVENT PARALLEL GROUND PATHS.

4. FOR SYSTEMS ABOVE 600 VAC, CONNECT A V131DA40 MOV ACROSS THE PPI-600V.

FIGURE 12. PPI-600V Typical Installation.


Page 11
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

5. TECHNICAL SPECIFICATIONS Trip-Time Accuracy ........... +10, -30%


GC-Loop
5.1 SE-107 Trip Resistance(3) ................ 40 ± 10 
Operating Mode.................. Non-Latching,
Supply:
Latching with Option L
ac ............................................10 VA, 120 or 240 Vac
(+10, -45%), 50/60 Hz,
ac/dc .......................................5 W, 120 Vdc (+40, -8%); Output Relay:
10 VA, 120 Vac CSA/UL Contact Ratings ... 1 mA to 4 A Resistive,
(+10, -45%), 50/60 Hz, 240 Vac or 28 Vdc
Supplemental Contact Ratings:
Make/carry 0.2 s .............. 10 A
NOTE: Voltage between supply terminals (L1, L2) and
ground terminal (G) must not exceed 300 Vac continuous Carry continuous ............. 4 A
or 1,250 Vac under transient conditions. Break:
dc .................................. 20 W Resistive,
Dimensions: 10 W Inductive
Height ................................. 150 mm (5.9”) (L/R = 0.04 s)
Width .................................. 109 mm (4.3”) ac................................... 960 VA Resistive,
Depth .................................. 100 mm (4.0”) 700 VA Inductive
(PF = 0.4)
Shipping Weight....................... 1 kg (2.2 lb) Subject to maximums of 4 A and 240 V (ac or dc).
Contact Configuration ........ N.O. (Form A)
Environment: Fuse Rating (F1) ................. 4.0 A, 250 Vac,
Operating Temperature ....... -40 to 60°C (-40 to 140°F) Time Delay
Storage Temperature........... -55 to 80°C (-67 to 176°F) Fuse Part Number ............... Littelfuse 313004. or
Humidity ............................. 85% Non-Condensing Bussman MSL-4
Operating Mode.................. Undervoltage (Fail-Safe)
Ground-Fault Circuit:
CT Ratio ............................. 200:5
Remote Indication:
CT Input Burden ................. 0.02 
Trip Level (1) ....................... 0.5, 2.0, or 4.0 A .......................................... 12 Vdc
Frequency Response ........... 25 to 110 Hz GI/CI .................................. Current Sink,
Trip Time ............................ 0.1 to 2.0 s Adjustable 560  Internal
Thermal Withstand (1) ......... 200 A Continuous,
2,500 A for 2 s Optional RK-13 Module:
Trip-Level Accuracy........... +10, -20% Contact Ratings ..................... 0.08 A, 120 V (ac or dc)
CT Lead Resistance Limit (2) 0.50 A, 24 Vdc
0.5 A Trip Level......... 2  Contact Configuration........... N.O. (Form A)
2 A Trip Level............ 5  Reset Input ............................. 24 to 120 V (ac or dc),
4 A Trip Level............ 5  Isolated
Trip-Time Accuracy ........... 10%
Trip Mode ........................... Latching PWB Conformal Coating............ MIL-1-46058 qualified,
UL QMJU2 recognized
Ground-Check Circuit:
Open-Circuit Voltage ......... 12 Vdc
Output Impedance............... 240 
Nominal Loop Current........ 25 mA
Induced-ac Withstand ......... 25 Vac Continuous,
120 Vac for 3 s
Fuse Rating (F2) ................. 0.5 A, 250 Vac,
Time Delay
Fuse Part Number ............... Littelfuse 313.500 or
Bussman MDA-1/2,
MDL-1/2
Pull-in Filter........................ Chopper Rejection
Pull-in Time ........................ 1.5 s
Trip Time ............................ 0.2 s (GC open),
0.5 s (GC to G short)
Page 12
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

Certification.............................. CSA, Canada and USA SE-TA6ASF-WL:


R LR 53428 Characteristic ...................... 6-V Zener, Temperature
C US Compensated
Circuit Type........................ High-Current Shunt
UL Listed
Regulator
Reverse Voltage ................. 5.6 ±0.03 Vdc @ 100 mA
Forward Voltage................. 0.5 ±0.1 Vdc @ 100 mA
Australia(4) Operating Temperature....... -40 to 60°C (-40 to 140°F)
Current Range .................... 2 mA to 15 A
N11659 Maximum Clamping
Voltage ............................... 55 V @ 250 A,
FCC 5x20 µs Pulse
Power Rating ...................... 12 W
Wire Leads ......................... 18 AWG (0.82 mm2),
NOTES: 300 mm (11.8”)
(1)
Currents referred to primary of CT200 for prospective Dimensions ......................... 58.8 x 19 x 12.7 mm
ground-fault currents less than 4,000 A. (2.32 x 0.75 x 0.5”)
(2)
Typical maximum CT lead resistance to meet Shipping Weight................. 45 g (0.1 lb)
specified trip level accuracy.
(3)
The GROUND CHECK LED may flash when the SE-TA6-SM:
GC-loop trip resistance is near the trip level. Characteristic ...................... Zener Diode,
(4)
Applicable only on 240 Vac Supply (Option E in the Unidirectional
ordering information). Circuit Type........................... High Current Shunt
Regulator
5.2 CURRENT SENSORS Reverse Voltage .................... 5.6 ± 0.3 Vdc @ 25 mA
Environment: Forward Voltage ................... 0.65 ± 0.1 Vdc @ 25 mA
Operating Temperature ....... -40 to 60°C (-40 to 140°F) Operating Temperature ......... -40 to 60°C (-40 to 140°F)
Storage Temperature........... -55 to 80°C (-67 to 176°F) Power Rating ......................... 50 W
Humidity ............................. 85% Non-Condensing Screw Terminal ..................... 0.25” – 28 UNF
Dimensions:
CT200: Body ................................ 45 mm
Current Ratio ...................... 200:5 A Wire Lead ........................ 250 mm (9.84”),
Insulation ...............................600-V Class 14 AWG (2.08 mm2)
Window Diameter .................56 mm (2.2”) Shipping Weight ................... 45 g (0.1 lb)
Shipping Weight ....................1 kg (2.2 lb)

CT200L:
Current Ratio ...................... 200:5 A
Insulation ...............................600-V Class
Window Diameter .................89 mm (3.5”)
Shipping Weight ....................1 kg (2.2 lb)

5.3 TERMINATION ASSEMBLIES


SE-TA6:
Characteristic ...................... Zener Diode,
Unidirectional
Circuit Type ...........................High Current Shunt
Regulator
Reverse Voltage.....................5.6 ± 0.3 Vdc @ 25 mA
Forward Voltage ....................0.65 ± 0.1 Vdc @ 25 mA
Operating Temperature .........-40 to 60°C (-40 to 140°F)
Power Rating .........................50 W
Screw Terminal .....................6-32 x 0.25”
Dimensions ............................67 x 40 x 41.5 mm
(2.6 x 1.6 x 1.6”)
Shipping Weight ....................200 g (0.45 lb)
Page 13
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

6. ORDERING INFORMATION 7. WARRANTY


Option List (1) The SE-107 Ground-Fault Ground-Check Monitor is
SE-107- warranted to be free from defects in material and
workmanship for a period of five years from the date of
120-Vac Supply (2) L Latching Ground-Check Trip purchase.
E 240-Vac Supply (3) Littelfuse Startco will (at Littelfuse Startco’s option)
D 120-Vac/dc Supply repair, replace, or refund the original purchase price of an
Each SE-107 is supplied with a 1N5339B termination device.
(1)
SE-107 that is determined by Littelfuse Startco to be
List options required in order shown above.
(2)
Standard, leave blank.
defective if it is returned to the factory, freight prepaid,
(3)
Only Supply option available with C-Tick within the warranty period. This warranty does not apply
certification. to repairs required as a result of misuse, negligence, an
accident, improper installation, tampering, or insufficient
Ground-Fault CT’s: care. Littelfuse Startco does not warrant products
CT200 ................................. 56 mm (2.2”) window repaired or modified by non-Littelfuse Startco personnel.
CT200L............................... 89 mm (3.5”) window

Ground-Check Termination:
1N5339B ............................ 5-W Axial Lead
SE-TA6 ............................... 50-W Assembly
SE-TA6-SM ........................ 50-W Stud-Mount
Termination Assembly
SE-TA6ASF-WL ................ 12-W Small-Format
Termination Assembly
with Wire Leads

Remote Indication and Reset:


RK-102 ............................... Includes two LED pilot
lights, a reset push button,
and legend plates
RK-105 ............................... Indication-and-Reset
Assembly
RK-105I .............................. Indication Assembly
RK-13 ................................. Relay Interface Module

Parallel-Path Isolator:
PPI-600V ............................ For system voltages up to
600 Vac
Page 14
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

8. GROUND-FAULT PERFORMANCE TEST


a) USING SE-400 CT200

To meet the requirements of the National Electrical FROM


POWER
Code (NEC), as applicable, the overall ground-fault SOURCE
LOAD

protection system requires a performance test when first


installed. A written record of the performance test is to
be retained by those in charge of the electrical installation CT1 CT2
L L1
in order to make it available to the authority having SE-107
N L2
jurisdiction. A test record form is provided for recording
11 12
the date and the final results of the performance tests. OP1 OP2
3
L1
The following ground-fault system tests are to be L
5
N L2
conducted by qualified personnel: 1 SE-400

a) Evaluate the interconnected system in accordance with REMOTE


8
RMT1

the overall equipment manufacturer’s detailed TEST 9


RMT2

instructions. b) USING SE-100T


CT200

b) Verify proper location of the ground-fault current FROM


POWER LOAD
transformer. Ensure that the cable or bus passes SOURCE
through the ground-fault current transformer window,
and that the grounding conductors or shields are not
encompassed by the ground-fault current transformer CT1 CT2
L L1
in such a way as to cause ground-fault current to be N
SE-107
L2
missed. These checks can be done visually with
0.65 A
knowledge of the circuit involved. The connection of C LO
2.75 A
L L1 HI
the current-transformer secondary to the SE-107 is not REMOTE
N L2
polarity sensitive. TEST
SE-100T

c) Verify that the system is correctly grounded and that RMT

alternate ground paths do not exist that bypass the


current transformer. High-voltage testers and FIGURE 13. Ground-Fault-Test Circuits.
resistance bridges can be used to determine the
existence of alternate ground paths. TABLE 2. GROUND-FAULT-TEST RECORD
d) Verify proper reaction of the circuit-interrupting DATE TEST RESULTS
device in response to a simulated or controlled
ground-fault current. To simulate ground-fault
current, use CT-primary current injection. Fig. 13a
shows a test circuit using an SE-400 Ground-Fault-
Relay Test Unit. The SE-400 has a programmable
output of 0.5 to 9.9 A for a duration of 0.1 to 9.9
seconds. Set the test current to 0.6, 2.3, or 4.6 A for
SE-107 units set at 0.5, 2.0, or 4.0 A respectively.
Fig. 13b shows a test circuit using an SE-100T
Ground-Fault Relay Tester. The SE-100T provides a
test current of 0.65 or 2.75 A for testing 0.5- and 2.0-
A trip levels. Inject the test current through the
current-transformer window for at least 2.5 seconds.
Verify that the circuit under test has reacted properly.
Correct any problems and re-test until the proper
reaction is verified. Retain this record for the authority having jurisdiction.
e) Record the date and the results of the test on the
attached test-record form.
Page 15
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715

APPENDIX A
SE-107 REVISION HISTORY
MANUAL MANUAL PRODUCT REVISION
RELEASE DATE REVISION (REVISION NUMBER ON PRODUCT LABEL)
May 7, 2015 5-C-050715
04
April 29, 2015 5-B-042915
September 11, 2014 5-A-091114 03

MANUAL REVISION HISTORY


REVISION 5-C-050715
SECTION 5
FCC certification added.
Updated Fuse F1 part number.
Sections 5.2 and 5.3 added.
APPENDIX A
Revision history updated.
REVISION 5-B-042915
SECTION 5
Updated Fuse F1 part number.
APPENDIX A
Revision history updated.
REVISION 5-A-091114
SECTION 3
Updated Fig. 1.
SECTION 4
Updated Figs. 5, 6, 8, and 9.
SECTION 5
Updated RK-13 contact ratings.
Updated notes.
APPENDIX A
Revision history added.

PRODUCT REVISION HISTORY


REVISION 04
Minor hardware change.
REVISION 03
No change.
Page 16
SE-107 Ground-Fault Ground-Check Monitor Rev. 5-C-050715