Sei sulla pagina 1di 1

NEWLY ADDED FANS

S.NO LOCATION FAN REF AIR FLOW(L/S) ESP (PA) TYPE SPECIAL REQUIREMENTS MOUN TING DETAILS QTY REMARKS

AXIAL INLINE -TRULY


SMOKE EXHAUST-MAKE UP REVERSIBLE EI
1 ATRIUM FANS SEF-P-01 TO SEF-P-08 12156 450 /BELT DRIVEN / 2 FLOOR MOUNTED 8
AIR QACC-WH-DT-8661
HR FIRE RATED (250 DEG C)

VANE AXIAL /BELT DRIVEN / 2 EI


2 GENERATOR ROOM EAF-G-1 5952 / 3571 464 EXHAUST AIR SPEED / 2 HR FIRE RATED (250 FLOOR MOUNTED 2 QACC-WH-DT-8661
DEG C)
CENTRIFUGAL INLINE / BELT QACC-WH-RFI-02-H-138
3 FRSH-MED-01 170 200 FRESH AIR 2(1D+1S)
MED LAB ROOM DRIVEN REV 00
CEILING MOUNTED
(CAR PARK AREA) CENTRIFUGAL INLINE / BELT QACC-WH-RFI-02-H-138
4 EXF-MED-01 170 150 EXHAUST AIR 2(1D+1S)
DRIVEN REV 00

STERILIZATION ROOM CENTRIFUGAL INLINE / BELT QACC-WH-RFI-02-H-139


5 FRSH-STR-01 131 150 FRESH AIR 2(1D+1S)
(COMPRESSED AIR DRIVEN REV 00
CEILING MOUNTED
PLANT - NEW CENTRIFUGAL INLINE / BELT QACC-WH-RFI-02-H-139
6 SUBSTATION) EXF-STR-01 131 150 EXHAUST AIR 2(1D+1S)
DRIVEN REV 00

7 EXF-BSC-01 406 300 EXHAUST AIR 1


AXIAL INLINE (1-PHASE)
8 BIO HAZARD SAFETY EXF-BSC-02 1350 420 EXHAUST AIR CORROSIVE RESISTANCE(WITH 1 QACC-WH-RFI-02-G-051
CEILING MOUNTED
CABINET VFD) REV 00
9 EXF-BSC-03 2704 600 EXHAUST AIR 1
10 EXF-BSC-04 1815 500 EXHAUST AIR 1
11 EXF-BSC-05 373 362 EXHAUST AIR 1
23

new fan requirement

fan selection need to be revised

fan mounting details need to be verified and ensured as


mentioned