Sample Calculations Sample Calculations

Sample Calculation 3. Given are the following :


General Information:
Project Identification: Shopping Mall
Width = 15 m
Average maintained Illuminance: 400 lux or 400 lux /1lux x 10.76fc
Length = 100 m
= 37.17 fc
Ceiling height = 3.5 m
Lamp data: 26W TC-D (compact fluorescent lamp)
Desired Illumination = 400 lux
Lamp flux: 1800 lumen (as per manufacturer’s data)
Type of Luminaire = 200mf Downlight w/ 26W TC-D Lamp
Luminaire data:
Manufacturer: Zumtobel Staff (Fumaco)
Model No: Panos HG 2/26W TC-D VVG 200
ñw = 50%

Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)

Sample Calculations Sample Calculations


Selection of Coefficient of Utilization:
Step 2: Determine Cavity Ratio

Step 1: Fill in all information in sketch If from manufacturer’s data, CU table are given based on
Room Cavity Ratio

L (Length) = 100 m

W (width) = 15 m

h (height) = 3.5 m

Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)

Sample Calculations Sample Calculations


If from manufacturer's data, CU table are given based on Step 3: Obtain effective cavity reflectance:
Room Index

Ceiling : cc = 70%
where:

Wall : w = 50%

Floor : fc = 20%

Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)

17