GENERAL NOTES: LEGEND & SYMBOLS A B C

A B C

1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE


PROVISION OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC).
THE RULES AND REGULATIONS OF LOCAL AND NATIONAL AUTHORITIES CONCERNED 50W PIN LIGHT 1
PL
WITH ENFORCEMENT OF RULES AND REGULATIONS OF LOCAL UTILITY COMPANY. 1 uv
ONE GANG SWITCH Z5 Z4
S
2. THE SERVICE VOLTAGE SHALL BE THREE PHASE, FOUR WIRES,
230 VOLTS, 60 HERTZ SYSTEM. V
Sab TWO GANG SWITCH k L
L U
3. THE INSTALLATION SHALL BE DONE AS FOLLOWS:
a) RIGID STEEL CONDUIT ( RSC ) ----- POWER SERVICE ENTRANCE FEEDERS Sabc THREE GANG SWITCH
b) POLYVINYL CHLORIDE (RSC,EMT) ----- LIGHTING, POWER BRANCH CIRCUITS, k
AND AUXILIARY LAYOUT. ij R
S3W 3 WAY SWITCH
4. ALL WIRES TO BE USED SHALL BE COPPER AND THERMOPLASTIC HEAT W U T
INSULATED TYPE "THHN" UNLESS NOTED OTHERWISE SPECIFIED. LP j S
CIRCUIT HOMERUN
0 Q
5. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED LP R
w R
TYPE FOR THE LOCATION AND PURPOSED INTENDED. i xy 2
POWER SERVICE ENTRANCE S
z z2
6. THE MINIMUM SIZE OF WIRE AND CONDUIT TO BE USED SHALL BE 2.0 sqmm THHN f X T
AND 20 mm dia. RESPECTIVELY. PANELBOARD
e R
7. WHENEVER NECESSARY PULLBOX SHALL BE PROVIDED EVEN NOT INDICATED h g 2
IN THE PLAN. TELEPHONE SERVICE ENTRANCE 2 N Z4

h Z5 N
efg Y Y N
8. BRANCH CIRCUIT HOMERUNS SHALL NOT BE COMBINED IN THE SAME RACEWAY
TELEPHONE OUTLET ab
AND RACEWAY FOR AUXILIARY LINES SHALL NOT CONTAINS POWER LINES.
cd
mn O
9. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: CONVENIENCE OUTLET op Z LP Z2
qr P
a) 0.30m ABOVE FLOOR FINISH ----- C.O. OUTLET & AUX. OUTLET c st 4
M
b) 1.40m ABOVE FLOOR FINISH ----- LIGHT CONTROL SWITCH WFCO WHEATHER PROOF CO.
c) 1.70m ABOVE FLOOR FINISH@ CENTER ----- PANELBOARDS
d) ALL OTHER HEIGHTS ----- VERIFY TO THE ARCHITECT RANGE OUTLET
RANGE
d
10. ALL SERVICE ENTRANCE EQUIPMENTS SUCH AS PANELBOARD SHALL BE PROPERLY RANGE HOOD OUTLET
RH
Z Z2
GROUNDED IN ACCORDANCE WITH THE PROVISION OF THE PHILIPPINE ELECTRICAL P O
CODE. REF
REFRIGERATOR OUTLET
Y Y LP N
11. ALL ELECTRICAL WORKS AND INSTALLATIONS HEREIN SHALL BE DONE UNDER THE AIRCON OUTLET c 3

PP/LP
ACU N
DIRECT SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINNER OR MASTER
ELECTRICIAN. Z5 N
z4, z5 z3
LP z6, z7 3 Z4
12. ALL CIRCUIT BREAKERS MUST BE G.E. BRAND & CONDUITS MUST BE NELTEX & 3 1
Z3 Z3
WIRES SHOULD BE PHILFLEX BRAND

Z6 Z7 Z6 Z7

LIGHTING & POWER PANEL


3 4

A B C A B C

1 1

2 2

PP
AC
5
6

PP
5

3 3
2

5 6

1
E-1