Sei sulla pagina 1di 147

CoverFireAritech.

qxd 18/02/2004 11:14 Page 1

GE Security

Aritech Fire Systems Product Catalogue


Aritech

FIRE SYSTEMS
Product catalogue

www.GE-Security.com
GE Security

GE Security reserves the right to change product specifications without notice.


For the latest product specifications, visit www.GE-Security.com or contact your Sales Representative. 03/2004
In this catalogue you will find a wide range of

Fire Protection equipment from GE Security.

GE Security is a global technology leader dedicated

to supporting the needs of the rapidly growing

electronic security industry and to expanding

current technologies, products and services that

GE Security, create revenue growth opportunities for its

customers. As part of the GE family, GE Security


unrivalled expertise in shares the spirit of innovation that has
Fire Protection distinguished GE for well over 100 years. GE

Security's commitment to the ongoing success of

its partners and affiliates means that we maintain

a sharp focus on product and service innovation,

world-class manufacturing practices and

operational excellence.

GE Security is a worldwide organisation with sales

and technical support operations in 27 countries,

and manufacturing and logistics operations in

Europe, the U.S. and China.

GE Security has expertise in all areas of electronic

security, including:
z Intrusion and Fire Protection

z Electronic Access and Facility Management

z Key Management and Remote Access Systems

and Services

z Fibre Optic Transmission and Reception

Equipment

z CCTV, Digital Video and Surveillance Equipment

z Video Multiplexing and Digital Storage

When you're looking for the finest in Fire

Protection products with leading-edge

technology and the backing of a world leader, you

need look no further than this catalogue.


CONVENTIONAL FIRE DETECTORS

300 SERIES
Conventional Fire Detectors
Page : 5

Ionisation detector, conventional DI322I

The 300 Series conventional fire detectors are the ideal solution for any conventional
installation. They are built specifically for use with the Aritech FP400, FP500, FP600
and FP700 series conventional fire panels, but can also be connected to most 3rd
party industry standard conventional control panels.

Specifications

Operating voltage 18 to 28 VDC


Current consumption
Quiescent at 24 VDC 30 µA
Alarm at 24 VDC < 100 mA
Radio-active source Americium 241
Average activity 0.33 +/-0.04µCi (12.1 +/- 1.5 kBq)
Remote alarm output < 100 mA
Heat specification
Operating temperature -10 to +60 °C
Storage temperature -10 to +70 °C
Humidity (non-condensing) 0 - 95%
IP rating IP205
Number of detectors per zone 20 l Full line consisting of Optical, Ionisation and Heat
Recommended protection resistor 300 ohm detectors
Dimensions (h x Ø)
l An ultra-fine grid prevents the ingress of dust and insects
Head 45 mm x 99 mm in smoke detectors
Base 24 mm x 103 mm
l Attractive, low-profile design
Approvals* VdS
LPCB l LPCB and VdS certification marks (*)
* Check current status with local office l Innovative base compensates for uneven surfaces

Ordering Information

DI322I Ionisation detector, conventional


Conventional Fire Detectors
Page : 6

Optical detector, conventional, with field exchangeable optical block DP331I

The 300 Series conventional fire detectors are the ideal solution for any conventional
installation. They are built specifically for use with the Aritech FP400, FP500, FP600
and FP700 series conventional fire panels, but can also be connected to most 3rd
party industry standard conventional control panels.

Specifications

Operating voltage 9 to 28 VDC


Current consumption
Quiescent at 24 VDC 85 µA
Alarm at 24 VDC < 100 mA
Radio-active source
Average activity
Remote alarm output < 100 mA
Heat specification
Operating temperature -10 to +70 °C
Storage temperature -10 to +70 °C
Humidity (non-condensing) 0 - 95%
IP rating IP42
l Full line consisting of Optical, Ionisation and Heat
Number of detectors per zone 20
detectors
Recommended protection resistor 300 ohm
Dimensions (h x Ø) l An ultra-fine grid prevents the ingress of dust and insects
Head 45 mm x 99 mm in smoke detectors
Base 24 mm x 103 mm l Attractive, low-profile design
Approvals* EN54
l LPCB and VdS certification marks (*)
*
* Check current status with local office l Innovative base compensates for uneven surfaces

Ordering Information

DP331I Optical detector, conventional, with field exchangeable optical block


Conventional Fire Detectors
Page : 7

Temperature detector (fixed and rate-of-rise), conventional DT313I

The 300 Series conventional fire detectors are the ideal solution for any conventional
installation. They are built specifically for use with the Aritech FP400, FP500, FP600
and FP700 series conventional fire panels, but can also be connected to most 3rd
party industry standard conventional control panels.

Specifications

Operating voltage 18 to 28 VDC


Current consumption
Quiescent at 24 VDC 70 µA
Alarm at 24 VDC < 100 mA
Radio-active source
Average activity
Remote alarm output < 100 mA
Heat specification Max. & ROR to EN54p5
Operating temperature -10 to +70 °C
Storage temperature -10 to +80 °C
Humidity (non-condensing) 0 - 95%
IP rating IP205
Number of detectors per zone 20 l Full line consisting of Optical, Ionisation and Heat
Recommended protection resistor 300 ohm detectors
Dimensions (h x Ø) l An ultra-fine grid prevents the ingress of dust and insects
Head 45 mm x 99 mm in smoke detectors
Base 24 mm x 103 mm l Attractive, low-profile design
Approvals* VdS
LPCB l LPCB and VdS certification marks (*)
* Check current status with local office l Innovative base compensates for uneven surfaces

Ordering Information

DT313I Temperature detector (fixed and rate-of-rise), conventional


Conventional Fire Detectors
Page : 8

KL731/DP331I Calibration Tool KCT731

The KCT731 is a calibration tool to recalibrate the KL731/DP331I conventional


detectors after replacement of the field exchangeable optical block.

Specifications

Supply 2 x 9 V batteries

Ordering Information

KCT731 KL731/DP331I Calibration Tool

l Easy to use
l Simple "go/no-go" function
l Battery operated
Conventional Fire Detectors
Page : 9

Universal fire detector base (Aritech 300 and 1500 series) DB304

The DB304 is a 4 contact universal detecor base for use with the Dx300 and Dx1500
series detectors from Aritech. It has the ability to compensate for uneven mounting
surfaces.

Specifications

Dimensions
Diameter 104 mm
Height 24 mm

Ordering Information

DB304 Universal fire detector base (Aritech 300 and 1500 series)

l Polarity sensitive
l Universal base fits conventional and analogue detectors
l Compensates for uneven surfaces
l Remote indicator contact available
l EN54 approved

Universal fire detector base with earth connection KZ705

The KZ705 is a 5 contact universal detector base for use with the KL700/Dx300 and
KL700A/Dx1500 series detectors from GE-Interlogix. In addition to the normal base
and remote indication connectors, the KZ705 also has an additional earth terminal
connector to allow for easy terminations of a possible cable screen.

Specifications

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage
Current Consumption
Isolation Current
Isolation Resistance
Sounder Frequency
Sound Output
@ 3 mA
@ 5 mA
Environmental Characteristics l Polarity sensitive
Operating Temperature -10 to 70 °C l Universal base fits conventional and analogue detectors
Storage Temperature -10 to 70 °C
l Additional earth terminal available
Relative Humidity (max) 95 % (non-cond.)
l Remote indicator contact available
Ordering Information

KZ705 Universal fire detector base with earth connection


Conventional Fire Detectors
Page : 10

Conventional fire detector base with diode KZ705D

The KZ705D is a 5 contact universal detector base for use with the KL700/Dx300
series detectors from GE-Interlogix. In addition to the normal base and remote
indication connectors, the KZ705D also has an additional earth terminal connector to
allow for easy terminations of a possible cable screen. The built in diode is
specifically targeted at systems using active end-of-line devices.

Specifications

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage
Current Consumption
Isolation Current
Isolation Resistance
Sounder Frequency
Sound Output
@ 3 mA
@ 5 mA
Environmental Characteristics
Operating Temperature -10 to 70 °C
l Polarity sensitive
Storage Temperature -10 to 70 °C l Universal base for conventional detectors
Relative Humidity (max) 95 % (non-cond.) l Additional earth terminal available
l Remote indicator contact available
Ordering Information
l Built in diode for active end-of-line systems
KZ705D Conventional fire detector base with diode
Conventional Fire Detectors
Page : 11

Active end-of-line device for use with FP400/KL700 fire panels EOL-ACT

The EOL-ACT is designed for use with the NK700/FP400 fire panels from GE-Interlogix.
It is an active end-of-line device to allow the monitoring of a conventional zone
through a diode base (such as the KZ705D).

Ordering Information

EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels

l Small
l Easy to install

Conventional fire detector base with relay KZ705R

The KZ705R is a 5 contact detector base for use with the KL731/DP331I detectors
from GE-Interlogix. In addition to the normal base and remote indication connectors,
the KZ705R also has an additional earth terminal connector to allow for easy
terminations of a possible cable screen. A built in 12 V relay makes it ideal for use on
low voltage intrusion systems.

Specifications

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage 12 V ± 10%
Current Consumption 12 µA
Isolation Current
Isolation Resistance
Sounder Frequency
Sound Output
@ 3 mA
@ 5 mA l Polarity sensitive
Environmental Characteristics
l 12 V relay for 4 wire systems
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C l Additional earth terminal available
Relative Humidity (max) 95 % (non-cond.) l Remote indicator contact available

Ordering Information

KZ705R Conventional fire detector base with relay


Conventional Fire Detectors
Page : 12

Surface mount supplement for KL300 detectors S300

The S300 is a base accessory designed for use with the KZ300 detector base. It
allows for a surface mount conduit and cable to enter the base from the side. The
KZ300 base fits on top of this accessory.

Specifications

Dimensions
Diameter 107 mm
Height 25 mm

Ordering Information

S300 Surface mount supplement for KL300 detectors

l Surface mount accessory for KZ300

Surface mount accessory for KZ700/DB304 and KZ700 series bases S700

The S700 is a base accessory designed for use with the KZ700 series detector bases.
It allows for a surface mount conduit and cable to enter the base from the side. The
KZ700 series base fits on top of this accessory.

Specifications

Dimensions
Diameter 95 mm
Height 30 mm

Ordering Information

S700 Surface mount accessory for KZ700/DB304 and KZ700 series bases

l Surface mount accessory for KZ700 series bases


CONVENTIONAL FIRE DETECTORS

700 SERIES
Conventional Fire Detectors
Page : 15

Photoelectric smoke detector with remote alarm LED output DP721I

700 series
The smoke detector continually monitors its own sensitivity and operational status.
Once a day, it performs a full diagnostic test which includes dynamically testing the
sensing chamber and internal electronics.

Specifications

Operating voltage 8.5 - 33 V dc FWR


Current consumption
Quiescent at 24 V dc 100 µA; Max. 70 µA average
In alarm at 24 V dc 60 mA
Alarm indication White LED (red alarm)
Fault indication Yellow LED
Remote alarm output 30 mA
RY contact rating 2 A @ 30 V dc;1 A @ 120 V ac
Humidity 0 - 95%; Non-condensing
IP rating IP 43
Sensitivity 10%/m (+1.6%, -3.3%)
Reset voltage 2,5 V max
Reset time 1 sec
Dimensions 10 cm Ø, H = 5 cm l EN 54 approved

Ordering Information l VDS certified

DP721I Photoelectric smoke detector with remote alarm LED output


DP721R Photoelectric smoke detector with C/O relay output
DB702 10 cm diameter base - 6 terminals

Photoelectric smoke and heat detector head with remote alarmLED output DP721T

700 series
Fitted with a field-exchangeable optical block. The smoke detector continually
monitors its own sensitivity and operational status. Once a day, it performs a full
diagnostic test which includes dynamically testing the sensing chamber and internal
electronics.

Specifications

Operating voltage 8.5 - 33 V dc FWR


Current consumption
Quiescent at 24 V dc 100 µA; Max. 70 µA average
In alarm at 24 V dc 60 mA
Alarm indication White LED (red alarm)
Fault indication Yellow LED
Remote alarm output 30 mA
RY contact rating 2 A @ 30 V dc;1 A @ 120 V ac
Humidity 0 - 95%; Non-condensing
IP rating IP 43
Sensitivity 10%/m (+1.6%, -3.3%) l EN 54 approved
Reset voltage 2,5 V max
Reset time 1 sec
l VDS certified
Dimensions 10 cm Ø, H = 5 cm

Ordering Information

DP721T Photoelectric smoke and heat detector head with remote alarmL
DP721RT Photoelectric smoke and heat detector with relay output
DP721RTA Photoelectric smoke and heat detector with relay output, autoreset
DB702 10 cm diameter base - 6 terminals
Conventional Fire Detectors
Page : 16

57º C fixed and rate-of-rise heat detector DT713-5

700 series
The smoke detector continually monitors its own sensitivity and operational status.
Once a day, it performs a full diagnostic test which includes dynamically testing the
sensing chamber and internal electronics.

Specifications

Operating voltage 8.5 - 33 V dc FWR


Current consumption
Quiescent at 24 V dc 100 µA; Max. 70 µA average
In alarm at 24 V dc 60 mA
Alarm indication Red LED
Fault indication Yellow LED
Remote alarm output 30 mA
RY contact rating 2 A @ 30 V dc;1 A @ 120 V ac
Humidity 0 - 95%; Non-condensing
IP rating IP 43
Heat specification
Max. 57º C ± 1.5º C
R.O.R. 8º C/min and > 40° C
Sensitivity l EN 54 approved
Reset voltage 2,5 V max l VDS certified
Reset time 1 sec
Dimensions 10 cm Ø, H = 5 cm

Ordering Information

DT713-5 57º C fixed and rate-of-rise heat detector


DT713-5R 57º C and R.O.R. heat detector, with relay output
DB702 10 cm diameter base - 6 terminals
Conventional Fire Detectors
Page : 17

70º C fixed and R.O.R. heat detector DT713-7

700 series
The smoke detector continually monitors its own sensitivity and operational status.
Once a day, it performs a full diagnostic test which includes dynamically testing the
sensing chamber and internal electronics.

Specifications

Operating voltage 8.5 - 33 V dc FWR


Current consumption
Quiescent at 24 V dc 100 µA; Max. 70 µA average
In alarm at 24 V dc 60 mA
Alarm indication Red LED
Fault indication Yellow LED
Remote alarm output 30 mA
RY contact rating 2 A @ 30 V dc;1 A @ 120 V ac
Humidity 0 - 95%; Non-condensing
IP rating IP 43
Heat specification
Max. 70º C ± 1.5º C
R.O.R. 8º C/min and > 40° C
Reset voltage 2,5 V max l EN 54 approved
Reset time 1 sec l VDS certified
Dimensions 10 cm Ø, H = 5 cm

Ordering Information

DT713-7 70º C fixed and R.O.R. heat detector


DB702 10 cm diameter base - 6 terminals
Conventional Fire Detectors
Page : 18

10 cm diameter base - 6 terminals DB702

700 series
Detector base for 700 series detectors

Ordering Information

DB702 10 cm diameter base - 6 terminals


DB702U 15 cm diameter base - 6 terminals

l EN 54 approved
l VDS certified
CONVENTIONAL FIRE DETECTORS

650 SERIES
Conventional Fire Detectors
Page : 21

Ionisation smoke detector DI650

650 series
This elegant slim-line ionisation detector offers high performance and wide operating
voltage

Specifications

Size of detector (mm)


Height 42
Diameter 100
Size of detector + base (mm)
Height 50
Diameter 100
Supply voltage 9 - 33 V dc
Quiescent Current at 24 V (typical) 28 µ A
Alarm indication LED
Normal operating temp. range (no icing) -20 to + 60°C
Humidity (no condensation) 0-95% RH
Max. wind 10m/s
Remote alarm output current 17 mA
IP Rating 43
l Polarity insensitive
Ordering Information l Common base
l Elegant slim-line design
DI650 Ionisation smoke detector
DI651 Integrating ionisation smoke dectector l EN 54 approved
DB860 Standard Base
l Wide operating voltage
Conventional Fire Detectors
Page : 22

Optical smoke detector DP652

650 series
This elegant slim-line optical sensor provides high performance and wide operating
range.

Specifications

Size of detector (mm)


Height 42
Diameter 100
Size of detector + base (mm)
Height 50
Diameter 100
Supply voltage 9 - 33 V dc
Quiescent Current at 24 V (typical) 40 µ A
Alarm indication LED
Normal operating temp. range (no icing) -20 to + 60°C
Humidity (no condensation) 0-95% RH
Max. wind Not affected
Remote alarm output current 17 mA
IP Rating 43

l Polarity insensitive
Ordering Information
l Common base
DP652 Optical smoke detector l Elegant slim-line design
DB860 Standard Base
l EN 54 approved
l Wide operating voltage
Conventional Fire Detectors
Page : 23

Heat detector, R.O.R., 57º C A1R DT654

650 series
This elegant slim-line heat sensor has a wide operating temperature and is available
in four ranges

Specifications

Size of detector (mm)


Height 42
Diameter 100
Size of detector + base (mm)
Height 50
Diameter 100
Supply voltage 9 - 33 V dc
Quiescent Current at 24 V (typical) 45 µ A
Alarm indication LED
Normal operating temp. range (no icing) -20 to + 60°C
Humidity (no condensation) 0-95% RH
Max. wind Not affected
Remote alarm output current 17 mA
IP Rating 54
l Polarity insensitive
Ordering Information l Common base
l Elegant slim-line design
DT654 Heat detector, R.O.R., 57º C A1R
DT655 Heat detector, 75º C BR l EN 54 approved
DT656 Heat detector, 95º C CR
DT657 Heat detector, 90º C CS
l Wide operating voltage
DB860 Standard Base
Conventional Fire Detectors
Page : 24

Standard Base DB860

650 series
The base has been designed to enable detectors to be plugged in without any need for
force - particularly useful when fitting to suspended ceilings.

Ordering Information

DB860 Standard Base

l Polarity insensitive
l Common base
l Elegant slim-line design
l EN 54 approved

Backplate for Ingress Protection 860-950 DB861

Ordering Information

DB861 Backplate for Ingress Protection 860-950

l Can prevent most ingress into the base and detector


Conventional Fire Detectors
Page : 25

Conduit box for 860 / 950 series bases DB806

An inexpensive and versatile accessory for surface mounting 860 and 950 series
bases

Ordering Information

DB806 Conduit box for 860 / 950 series bases

650 series relay base DB650

650 series
The relay base provides a volt-free contact for use in 4 wire control systems, and
other applications

Ordering Information

DB650 650 series relay base

l DB650
l For use with 4 wire control systems
l Automatic door closers
l Volt-free relay contacts
ANALOGUE ADDRESSABLE DETECTORS

1500 SERIES
Analogue Adressable Fire Detectors
Page : 29

Ionisation Sensor DI1552

The 1500 Series uses a microprocessor for measurement and communication. An


enhanced protocol ensures the overall
integrity and error free operation of the system, without compromising detection
speed. All sensors are compatible with a standard base that makes them easily
interchangeable and support the connection of a remote indicator.

Specifications

Operating voltage 22 to 38 VDC


Current consumption
Quiescent @ 38 VDC 200 µA
In Alarm < 11 mA
Alarm indication (Dual LED) White OFF - Red ON
Remote Alarm Output Available
Environment
Storage Temperature -10 to +70 °C
Operating Temperature -10 to +60 °C
Humidity (non-condensing) 0-95%
IP rating IP42 l Remote signalling capabilities
Radioactive Source 0.33 ± 0.04 µCi Am 241
Dimensions (h x Ø) 45 x 99 mm
l Optical sensor with field exchangeable optical chamber
l Easy soft addressing (1-125)
Ordering Information l SMD technology

DI1552
l Reliable communication protocol
Ionisation Sensor
l Full diagnostic self testing
l Full range: Ionisation, Optical and Heat and Dual sensors
(optical/heat)
l Full range of supporting I/O units and accessories
l EN54 Approved
Analogue Adressable Fire Detectors
Page : 30

Optical Sensor with field exchangeable optical block DP1561

The 1500 Series uses a microprocessor for measurement and communication. An


enhanced protocol ensures the overall integrity and error free operation of the system,
without compromising detection speed. All sensors are compatible with a standard
base that makes them easily interchangeable and support the connection of aremote
indicator.

Specifications

Operating voltage 22 to 38 VDC


Current consumption
Quiescent @ 38 VDC 350 µA
In Alarm < 11 mA
Alarm indication (Dual LED) Red
Remote Alarm Output Available
Environment
Storage Temperature -10 to +70 °C
Operating Temperature -10 to +60 °C
Humidity (non-condensing) 0-95%
IP rating IP42 l Remote signalling capabilities
Radioactive Source NA
Dimensions (h x Ø) 45 x 99 mm
l Optical sensor with field exchangeable optical chamber
l Easy soft addressing (1-125)
Ordering Information l SMD technology

DP1561
l Reliable communication protocol
Optical Sensor with field exchangeable optical block
l Full diagnostic self testing
l Full range: Ionisation, Optical and Heat and Dual sensors
(optical/heat)
l Full range of supporting I/O units and accessories
l EN54 Approved
Analogue Adressable Fire Detectors
Page : 31

Dual Sensor (Optical/Heat) DP1551T

The 1500 Series uses a microprocessor for measurement and communication. An


enhanced protocol ensures the overall integrity and error free operation of the system,
without compromising detection speed. All sensors are compatible with a standard
base that makes them easily interchangeable and support the connection of aremote
indicator.

Specifications

Operating voltage 22 to 38 VDC


Current consumption
Quiescent @ 38 VDC 350 µA
In Alarm < 5 mA
Alarm indication (Dual LED) Red
Remote Alarm Output Available
Environment
Storage Temperature -10 to +70 °C
Operating Temperature -10 to +70 °C
Humidity (non-condensing) 0-95%
IP rating IP42 l Remote signalling capabilities
Radioactive Source NA
Dimensions (h x Ø) 51 x 99 mm
l Optical sensor with field exchangeable optical chamber
l Easy soft addressing (1-125)
Ordering Information l SMD technology

DP1551T
l Reliable communication protocol
Dual Sensor (Optical/Heat)
l Full diagnostic self testing
l Full range: Ionisation, Optical and Heat and Dual sensors
(optical/heat)
l Full range of supporting I/O units and accessories
l EN54 Approved
Analogue Adressable Fire Detectors
Page : 32

Heat Sensor DT1553

The 1500 Series uses a microprocessor for measurement and communication. An


enhanced protocol ensures the overall integrity and error free operation of the system,
without compromising detection speed. All sensors are compatible with a standard
base that makes them easily interchangeable and support the connection of aremote
indicator.

Specifications

Operating voltage 22 to 38 VDC


Current consumption
Quiescent @ 38 VDC 250 µA
In Alarm < 11 mA
Alarm indication (Dual LED) White OFF - Red ON
Remote Alarm Output Available
Environment
Storage Temperature -10 to +80 °C
Operating Temperature -10 to +70 °C
Humidity (non-condensing) 0-95%
IP rating IP42 l Remote signalling capabilities
Radioactive Source NA
Dimensions (h x Ø) 45 x 99 mm
l Optical sensor with field exchangeable optical chamber
l Easy soft addressing (1-125)
Ordering Information l SMD technology

DT1553
l Reliable communication protocol
Heat Sensor
l Full diagnostic self testing
l Full range: Ionisation, Optical and Heat and Dual sensors
(optical/heat)
l Full range of supporting I/O units and accessories
l EN54 Approved
Analogue Adressable Fire Detectors
Page : 33

Fire sensor programmer PG700

The PG700 is a handheld device programmer and tester for the KL700A/Dx1500 series
detectors. It is battery operated and allows the installer to perform installation tasks
(such as device addressing) and maintenance tasks (such as device clibration) in the
field without external assistance.

Specifications

Supply 2 x 9 V batteries

Ordering Information

PG700 Fire sensor programmer

l Easy to use
l Battery operated
l 4 User selectable programs
l - Device analogue value
l - Change Device Address
l - Sequential device addressing
l - KL731A Calibration
Analogue Adressable Fire Detectors
Page : 34

Analogue fire detector base with isolator KZ705I

The KZ705I is a detector base with built in isolator for use with the KL700A/Dx1500
series detectors from GE-Interlogix. The isolator protects the loop from short circuit
conditions. A LED on the side of the base indicates the status of the isolator.

Specifications

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage 17 - 34 V
Current Consumption 50 µA
Isolation Current 6 mA
Isolation Resistance 140 MOhm
Sounder Frequency
Sound Output
@ 3 mA
@ 5 mA
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
Relative Humidity (max) 95 % (non-cond.)
l Polarity sensitive
Ordering Information l Universal base for analogue detectors
l Additional earth terminal available
KZ705I Analogue fire detector base with isolator l Remote indicator contact available
l Built in isolator
Analogue Adressable Fire Detectors
Page : 35

Analogue fire detector base with sounder KZ705AS

The KZ705AS is a detector base with built in analogue addressable sounder for use
with the KL700A/Dx1500 series detectors from GE-Interlogix. The sounder has its own
address on the fire panel loop and works independent of the detector. It is fully
controlled from the fire panel.

Specifications

Dimensions (Ø x h) 120 x 58 mm
Operating Voltage 22 - 38 V
Current Consumption 300 µA Quiescent
Isolation Current
Isolation Resistance
Sounder Frequency 1 KHz
Sound Output
@ 3 mA 85 dBA
@ 5 mA 95 dBA
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C l Polarity sensitive
Relative Humidity (max) 95 % (non-cond.)
IP Rating IP21c
l Universal base for analogue detectors
l Additional earth terminal available
Ordering Information l Remote indicator contact available
l Built in sounder
KZ705AS Analogue fire detector base with sounder
l Up to 90 dBA sound output
l Low current consumption
Analogue Adressable Fire Detectors
Page : 36

Analogue fire detector base with isolator and sounder KZ705IAS

The KZ705IAS is a detector base with built in analogue addressable sounder and
isolator for use with the KL700A/Dx1500 series detectors from GE-Interlogix. The
sounder has its own address on the fire panel loop and works independent of the
detector. It is fully controlled from the fire panel. The isolator protects the loop from
short circuit conditions.

Specifications

Dimensions (Ø x h) 120 x 58 mm
Operating Voltage 22 - 38 V
Current Consumption 350 µA Quiescent
Isolation Current 6 mA
Isolation Resistance 140 MOhm
Sounder Frequency 1 KHz
Sound Output
@ 3 mA 85 dBA
@ 5 mA 95 dBA
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
l Polarity sensitive
Relative Humidity (max) 95 % (non-cond.) l Universal base for analogue detectors
IP Rating IP21c l Additional earth terminal available
l Remote indicator contact available
Ordering Information
l Built in sounder
KZ705IAS Analogue fire detector base with isolator and sounder l Up to 90 dBA sound output
l Low current consumption
l Built in isolator
Analogue Adressable Fire Detectors
Page : 37

Conventional Zone Monitor Unit - 1 Zone KAL410

Allows the connection of one conventional zone to the analogue fire system loop. This
zone is constantly monitored. Up to 20 conventional devices may be connected to this
zone.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 90 µA
Quiescent @ 35 V 105 µA
Alarm < 3 mA
Aux. Supply (24V DC) Quiescent 200 µA + equip
Aux. Supply (24V DC) Alarm < 85 mA
End-of-line resistor 4.7 kOhm
Relay contact rating NA
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-condensing) 0-95 % l Easy numeric addressing
Dimensions (l x w x h) 117 x 80 x 44 mm
l Continuous supervision of the conventional zones
Ordering Information l Surface mount
l Local alarm indication
KAL410 Conventional Zone Monitor Unit - 1 Zone
l Externally powered
l Aesthetically pleasing
l Part of a family of I/O modules consisting of:
l - Conventional Zone Monitors
l - Digital Input Modules
l - Extinguishing Control Modules
l - Isolator Modules
l - Manual Call Points
l - Output Units
l - Retention Units
l - Supervised Output Units for sounder control
Analogue Adressable Fire Detectors
Page : 38

Conventional Zone Monitor Unit - 4 Zones KAL414/4

Allows the connection of four conventional zones to the analogue fire system loop.
These zones are constantly monitored. Up to 20 conventional devices may be
connected to any zone.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm < 5 mA
Aux. Supply (24V DC) Quiescent 200 µA + equip
Aux. Supply (24V DC) Alarm < 360 mA
End-of-line resistor 4.7 kOhm
Relay contact rating NA
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-condensing) 0-95 % l Easy numeric addressing
Dimensions (l x w x h) 163 x 107 x 36 mm
l Continuous supervision of the conventional zones
Ordering Information l Surface mount
l Local alarm indication
KAL414/4 Conventional Zone Monitor Unit - 4 Zones
l Externally powered
l Aesthetically pleasing
l Part of a family of I/O modules consisting of:
l - Conventional Zone Monitors
l - Digital Input Modules
l - Extinguishing Control Modules
l - Isolator Modules
l - Manual Call Points
l - Output Units
l - Retention Units
l - Supervised Output Units for sounder control
Analogue Adressable Fire Detectors
Page : 39

Extinguishing Control Module KAL426

The 400 Series modules consists of a complete range of interfaces developed for
input/output control in the KSA700/FP1500 analogue fire systems from GE Interlogix.
The KAL426 allows for the connection and control of one extinguishing area to the
addressable fire panel loop.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 210 µA
Alarm < 10 mA
Aux. Supply (24V DC) Quiescent 120 mA
Aux. Supply (24V DC) Alarm <1A
End-of-line resistor 4.7 kOhm
Relay contact rating 2½ A
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C l Aesthetically pleasing
Relative humidity (non-condensing) 0-95 %
l Easy numeric addressing
Dimensions (l x w x h) 163 x 107 x 36 mm
l Externally powered
Ordering Information l Supervised I/O
l Surface mount
KAL426 Extinguishing Control Module
PK10TD-ING Extinguishing RELEASE MCP with protective cover (English Version)
l Part of a range of I/O modules consiting of:
PK10TP-ING Extinguishing INHIBIT MCP with protective cover (English Version) l - Conventional Zone Monitors
KR24B Illuminated warning sign (No text) 24VDC l - Digital Input Modules
SK07 Low consumption multi-tone alarm siren
l - Isolator Modules
PK10CD Spare glass for extinguishing RELEASE call point
PK10CP Spare glass for extinguishing INHIBIT call point l - Manual Call Points
l - Output Units
l - Retention Units
l - Supervised Output Units for sounder control
Analogue Adressable Fire Detectors
Page : 40

Relay Module - 1 Relay KAL430

Provides for one potential free relay output for the fire system loop. Each relay allows
for COMMON, NORMALLY OPEN and NORMALLY CLOSED contacts. The output may be
used to activate ventilation controls, warning signs, activation of other alarm devices
etc. during fire situations.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 70 µA
Quiescent @ 35 V 100 µA
Alarm < 3.5 mA
Aux. Supply (24V DC) Quiescent 22 mA
Aux. Supply (24V DC) Alarm < 50 mA
End-of-line resistor NA
Relay contact rating 2½A @ 250 VAC
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C l Easy numeric addressing
Relative humidity (non-condensing) 0-95 %
l Externally powered
Dimensions (l x w x h) 117 x 80 x 44 mm
l Normally open / normally closed operation for I/O
Ordering Information l Surface mount
l Aesthetically pleasing
KAL430 Relay Module - 1 Relay
l Local status indication
l Part of a family of I/O modules consiting of:
l - Conventional Zone Monitors
l - Digital Input Modules
l - Extinguishing Control Modules
l - Isolator Modules
l - Manual Call Points
l - Output Units
l - Retention Units
l - Supervised Output Units for sounder control
Analogue Adressable Fire Detectors
Page : 41

Relay Module - 4 Relays KAL434/4

Provides for four potential free relay outputs for the fire system loop. Each relay
allows for COMMON, NORMALLY OPEN and NORMALLY CLOSED contacts. The outputs
may be used to activate ventilation controls, warning signs, activation of other alarm
devices etc. during fire situations.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm 10 mA
Aux. Supply (24V DC) Quiescent 100 µA
Aux. Supply (24V DC) Alarm 10 mA
End-of-line resistor NA
Relay contact rating 2½A @ 250 VAC
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C l Easy numeric addressing
Relative humidity (non-condensing) 0-95 %
l Externally powered
Dimensions (l x w x h) 163 x 107 x 36 mm
l Normally open / normally closed operation for I/O
Ordering Information l Surface mount
l Aesthetically pleasing
KAL434/4 Relay Module - 4 Relays
l Local status indication
l Part of a family of I/O modules consiting of:
l - Conventional Zone Monitors
l - Digital Input Modules
l - Extinguishing Control Modules
l - Isolator Modules
l - Manual Call Points
l - Output Units
l - Retention Units
l - Supervised Output Units for sounder control
Analogue Adressable Fire Detectors
Page : 42

Supervised Relay Module KAL440

Allows for the supervision of a single, 24 Volt powered output contact on the fire
system loop. This unit may be used to control for e.g. sounders in case of fire
conditions, but may also be used to switch any output considered crucial enough to
have the cable integrity between the unit and the switch point monitored.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm < 3.6 mA
Aux. Supply (24V DC) Quiescent 23 mA
Aux. Supply (24V DC) Alarm 23 mA + equip
End-of-line resistor 4.7 kOhm
Relay contact rating 1¼ A @ 250 VAC
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C l Easy numeric addressing
Relative humidity (non-condensing) 0-95 %
l Externally powered
Dimensions (l x w x h) 117 x 80 x 44 mm
l Normally open / normally closed operation for I/O
Ordering Information l Surface mount
l Aesthetically pleasing
KAL440 Supervised Relay Module
l Local status indication
l Part of a family of I/O modules consiting of:
l - Conventional Zone Monitors
l - Digital Input Modules
l - Extinguishing Control Modules
l - Isolator Modules
l - Manual Call Points
l - Output Units
l - Retention Units
l - Supervised Output Units for sounder control
Analogue Adressable Fire Detectors
Page : 43

Addressable Manual Call Point KAL450

The 400 Series modules consists of a complete range of interfaces developed for
input/output control in the KSA700/FP1500 analogue fire systems from GE Interlogix.
The KAL450 is an addressable manual call point for manual fire activation.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 90 µA
Quiescent @ 35 V 120 µA
Alarm < 3.5 mA
Aux. Supply (24V DC) Quiescent NA
Aux. Supply (24V DC) Alarm NA
End-of-line resistor NA
Relay contact rating NA
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-condensing) 0-95 % l Easy numeric addressing
Dimensions (l x w x h) 87 x 87 x 20
l Loop powered
Ordering Information l Local test facility
l Surface or flush mount
KAL450 Addressable Manual Call Point
l Aesthetically pleasing
DM715 Glass, EN54, Universal
DM790 Flush mount cradle with connectors l Local status indication
DM787 Surface mounting box with connectors
DM782
l Part of a family of I/O modules consiting of:
Hinged transparent MCP protection cover
DM800 Resettable element for MCP DM700/KAL450
l - Conventional Zone Monitors
l - Digital Input Modules
l - Extinguishing Control Modules
l - Isolator Modules
l - Manual Call Points
l - Output Units
l - Retention Units
l - Supervised Output Units for sounder control
Analogue Adressable Fire Detectors
Page : 44

Digital Input Module KAL460

Provides a remote input to the fire system loop. The input is constantly monitored and
its status communicated to the fire control panel. The input may be activated by
closing or opening a potential free contact, depending on the module configuration.

This module may be used to monitor any contact by showing its status through the
fire control panel e.g. the monitoring of pressure equipment and closure fire break
doors.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm < 10 mA
Aux. Supply (24V DC) Quiescent 200 µA
Aux. Supply (24V DC) Alarm < 50 mA
End-of-line resistor NA
Relay contact rating NA l Easy numeric addressing
Environmental
l Externally powered
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C l Normally open / normally closed operation for I/O
Relative humidity (non-condensing) 0-95 % l Surface mount
Dimensions (l x w x h) 117 x 80 x 44 mm l Aesthetically pleasing
Ordering Information l Local status indication
l Part of a family of I/O modules consiting of:
KAL460 Digital Input Module l - Conventional Zone Monitors
l - Digital Input Modules
l - Extinguishing Control Modules
l - Isolator Modules
l - Manual Call Points
l - Output Units
l - Retention Units
l - Supervised Output Units for sounder control
Analogue Adressable Fire Detectors
Page : 45

Isolator Module KAL470

The 400 series modules consist of a complete range of interfaces developed for
input/output control in the KSA700/FP1500 analogue fire systems from GE Interlogix.
The KAL470 is an isolator module in this series that isolates the faulty zone on a fire
panel loop during short circuit conditions. The KAL470 does not use an address on the
loop.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm 10 mA
Aux. Supply (24V DC) Quiescent NA
Aux. Supply (24V DC) Alarm NA
End-of-line resistor NA
Relay contact rating NA
Environmental
Storage temperature -10 to +50°C l Requires no device address
Operating temperature -10 to +50°C
l Automatic reset
Relative humidity (non-condensing) 0-95 %
Dimensions (l x w x h) 75 x 45 x 28 mm l Local status indication
l Surface mount
Ordering Information
l Part of a family of I/O modules consiting of:
KAL470 Isolator Module l - Conventional Zone Monitors
l - Digital Input Modules
l - Extinguishing Control Modules
l - Manual Call Points
l - Output Units
l - Retention Units
l - Supervised Output Units for sounder control
Analogue Adressable Fire Detectors
Page : 46

Retention Module - 1 Input / 1 Output KAL490

Provides a remote input and a potential free voltage relay output to the fire system
loop. The input signal is constantly monitored and its status displayed on the control
panel, whilst the output is fail-to-safe. Auxiliary supply monitoring is also included.

The module is used to for e.g. control and monitor doors such as fire break doors. The
relay provides the door activation and the input monitors the door status.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 µA
Quiescent @ 35 V 135 µA
Alarm 10 mA
Aux. Supply (24V DC) Quiescent 200 µA
Aux. Supply (24V DC) Alarm < 50 mA
End-of-line resistor NA
Relay contact rating 1A @ 30 VAC/VDC
Environmental l Easy numeric addressing
Storage temperature -10 to +50°C
l Externally powered
Operating temperature -10 to +70°C
Relative humidity (non-condensing) 0-95 % l Normally open / normally closed operation for I/O
Dimensions (l x w x h) 117 x 80 x 44 mm l Surface mount
l Aesthetically pleasing
Ordering Information
l Local status indication
KAL490 Retention Module - 1 Input / 1 Output l Part of a family of I/O modules consiting of:
l - Conventional Zone Monitors
l - Digital Input Modules
l - Extinguishing Control Modules
l - Isolator Modules
l - Manual Call Points
l - Output Units
l - Retention Units
l - Supervised Output Units for sounder control
ANALOGUE ADDRESSABLE DETECTORS

2000 SERIES
Analogue Adressable Fire Detectors
Page : 49

Optical Sensor DP2051

2000 Series
Equipped with a field-exchangeable optical block and has full certification, this
optical sensor provides good looks as well as top features

Specifications

Operating Voltage 17 - 28 V dc
Current consumption at 24 V dc
Quiescent < 150 µA
Alarm LED: 2 mA - 7-segment: 2 mA
Alarm indication White LED (red alarm)
Remote alarm output Not provided
Max. wind -
Humidity 0 - 95% non condensing
IP rating IP43
Source -
Dimensions
Height 5 cm
Diameter 10 cm

Ordering Information l Remote test capabilities


l Remote signalling capabilities
DP2051 Optical Sensor
DB2001
l Optical sensor with field exchangeable optical chamber
Standard Base 10 cm, 2 Terminals
DB2016 Isolating base l Easy numeric addressing (1-128)
l Enhanced communication protocol
l Full diagnostic self testing
l Polarity insensitive
l Full range: optical and heat
l Full range of I/0 units and accessories
l Isolator base
l EN54 approved
l VdS approved
Analogue Adressable Fire Detectors
Page : 50

Optical Sensor with remote LED output DP2061

2000 Series
Equipped with a field-exchangeable optical block and has full certification, this
optical sensor provides good looks as well as alarm and fault LEDs and remote output

Specifications

Operating voltage 17 - 28 V dc
Current consumption at 24 V dc
Quiescent < 150 µA
Alarm LED: 2 mA - 7-segment: 2mA
Remote alarm output 4 mA
Max. wind -
Humidity 0 - 95% non condensing
IP rating IP43
Source -
Dimensions
Height 5 cm
Diameter 10 cm

Ordering Information
l Remote test capabilities
DP2061 Optical Sensor with remote LED output l Remote signalling capabilities
DB2002 Standard Base 4 Terminals
DB2002U
l Optical sensor with field exchangeable optical chamber
Standard Base 15 cm, 4 Terminals
DB2016 Isolating base l Easy numeric addressing (1-128)
l Enhanced communication protocol
l Full diagnostic self testing
l Polarity insensitive
l Full range: optical and heat
l Full range of I/0 units and accessories
l Isolator base
l EN54 approved
l VdS approved
Analogue Adressable Fire Detectors
Page : 51

Optical Sensor with 7-segment display and remote LED output DP2071

2000 Series
Equipped with a field-exchangeable optical block and with full certification, this
optical sensor provides good looks as well as top features. Fitted with an exclusive
7-segment display, the sensor provides comprehensive information. In addition to
alarm signalling, information such as Fault, Pre-alarm, Maintenance Alarm (Clean
me), Disabled Sensor, Sensor in Test, Error (double address, wrong sensor type) and
Sensor Polled is provided.

Specifications

Operating voltage 17 - 28 V dc
Current consumption at 24 V dc
Quiescent < 150 µA
Alarm LED: 2 mA - 7-segment: 2 mA
Alarm indication White LED (red alarm)
Remote alarm output 4 mA
Max. wind -
Humidity 0 - 95% non condensing
IP rating IP43
Source -
Dimensions
l 7-segment display
Height 5 cm l Remote test capabilities
Diameter 10 cm l Remote signalling capabilities

Ordering Information
l Optical sensor with field exchangeable optical chamber
l Easy numeric addressing (1-128)
DP2071 Optical Sensor with 7-segment display l Enhanced communication protocol
DB2002 Standard Base 4 Terminals
DB2002U Standard Base 15 cm, 4 Terminals l Full diagnostic self testing
DB2016 Isolating base l Polarity insensitive
l Full range: optical and heat
l Full range of I/0 units and accessories
Analogue Adressable Fire Detectors
Page : 52

Heat Sensor DT2053

2000 series
Fully certified, this heat sensor provides good looks as well as top features.

Specifications

Operating voltage 17 - 28 V dc
Current consumption at 24 V dc
Quiescent < 150 µA
Alarm LED: 2 mA - 7-segment: 2 mA
Alarm indication Red LED
Remote alarm output Not provided
Max. wind -
Humidity 0 - 95% non condensing
IP rating IP43
Source -
Dimensions
Height 5 cm
Diameter 10 cm

Ordering Information
l VDS approved
DT2053 Heat Sensor
DB2001 Standard Base 10 cm, 2 Terminals
DB2016 Isolating base

Heat Sensor with Remote LED Output DT2063

2000 Series
Fully certified, this heat sensor provides good looks as well as top features. Dual
LED's indicate both alarm and fault. A remote output is also provided.

Specifications

Operating voltage 17 - 28 V dc
Current consumption at 24 V dc
Quiescent < 150 µA
Alarm LED: 2 mA - 7-segment: 2 mA
Alarm indication Red LED
Remote alarm output 4 mA
Max. wind -
Humidity 0 - 95% non condensing
IP rating IP43
Source -
Dimensions
Height 5 cm
Diameter 10 cm l VDS approved

Ordering Information

DT2063 Heat Sensor with Remote LED Output


DB2002 Standard Base 4 Terminals
DB2002U Standard Base 15 cm, 4 Terminals
DB2016 Isolating base
Analogue Adressable Fire Detectors
Page : 53

Heat Sensor with 7-segment Display and Remote LED Output DT2073

2000 Series
Fitted with an exclusive 7-segment display, this detector provides comprehensive, on
the spot information. In addition to alarm signalling, information such as Fault,
Pre-alarm, Maintenance Alarm (Clean me), Disabled Sensor, Sensor in Test, Error
(double address, wrong sensor type) and Sensor Polled is provided.

Specifications

Operating voltage 17 - 28 V dc
Current consumption at 24 V dc
Quiescent < 150 µA
Alarm LED: 2 mA - 7-segment: 2 mA
Alarm indication Red LED
Remote alarm output 4 mA
Max. wind -
Humidity 0 - 95% non condensing
IP rating IP43
Source -
Dimensions
Height 5 cm
Diameter 10 cm l VDS approved

Ordering Information

DT2073 Heat Sensor with 7-segment Display and Remote LED Output
DB2002 Standard Base 4 Terminals
DB2002U Standard Base 15 cm, 4 Terminals
DB2016 Isolating base
Analogue Adressable Fire Detectors
Page : 54

Standard Base 10 cm, 2 Terminals DB2001

2000 series
2 terminal base for DP2051 and DT2053

Ordering Information

DB2001 Standard Base 10 cm, 2 Terminals

l VDS approved

Standard Base 4 Terminals DB2002

2000 series
A four terminal base for all 2000 series detectors

Ordering Information

DB2002 Standard Base 4 Terminals


DB2002U Standard Base 15 cm, 4 Terminals

l VDS approved
Analogue Adressable Fire Detectors
Page : 55

Isolating base DB2016

2000 series
The DB2016 isolator base senses and isolates short circuit faults. A yellow LED
indicates a short circuit condition. The detector in the base will still receive power in
the event of a single short circuit. If every detector is fitted with an isolator base
then no device will be lost in the event of a single short circuit.

Ordering Information

DB2016 Isolating base

l VDS approved

Loop Isolator IU2016

2000 series
The Aritech Loop Isolator is designed to prevent an entire communication loop from
being disabled in the event of a short circuit. The IU 2016 isolates that part of the
loop containing the short from the remainder of the circuit.

Specifications

Operating voltage 17 - 28 V, comm. loop terminals


Total standby current < 250 µA
Isolated current
Average < 1.6 mA
Transition pulse < 36 mA (5 ms duration)
Operating temperature -10º C to 70º C
Operating humidity range 0 - 95%; Non-condensing
Line resistance
Normal 0.55 Ohms
Isolated > 33K Ohms
Switching voltage
Normal to isolated 13.8 V dc
l Complete isolation of loop short circuit
Isolated to normal 2.5 V dc l Automatic restore when fault is corrected
Switching time l Module LED indicates location of fault
Normal to isolated < 5 ms
Isolated to normal < 0.5 ms (after fault correction)

Ordering Information

IU2016 Loop Isolator


DB2003 Base for the IU2016 isolator
Analogue Adressable Fire Detectors
Page : 56

Base for the IU2016 isolator DB2003

Ordering Information

DB2003 Base for the IU2016 isolator


Analogue Adressable Fire Detectors
Page : 57

Manual call point, flying leads DM2000

2000 series
The DM 2000 is a break glass design call point with a high strength plastic housing.
The LED indicator provides visual confirmation of alarm initiation. The test key
(included with each unit) facilitates functional testing of the call point.

Specifications

Operating voltage 17 - 28 V, @ comm.loop terminals


Voltage modulation 4 - 9 V dc
Standby current < 250 µA
LED indicator current 2.5 mA maximum
Operating temperature -10º C to 70º C
Operating humidity 0 - 95%; Non-condensing
Dimensions (L x W x H)
Flush mount 87 x 87 x 24 mm
Surface mount 87 x 87 x 56 mm

Ordering Information

DM2000 Manual call point, flying leads


DM2000Y Manual call point flying leads - Yellow l Analogue addressable manual call point
DM2000B Manual call point flying leads - Blue l LED alarm indicator
DM711 Glass, EN54, Aritech
DM715 Glass, EN54, Universal l Tamper resistant break glass design
l Easy to test with self reset
l Fast response
l IP67 waterproof model available
Analogue Adressable Fire Detectors
Page : 58

Manual call point - Red IP67 waterproof, including backbox DM2000E

2000 series
The DM 2000E is a break glass design call point with a high strength plastic housing
and IP67 waterproof. The LED indicator provides visual confirmation of alarm
initiation. The test key (included with each unit) facilitates functional testing of the
call point.

Specifications

Operating voltage 17 - 28 V, @ comm.loop terminals


Voltage modulation 4 - 9 V dc
Standby current < 250 µA
LED indicator current 2.5 mA maximum
Operating temperature -10º C to 70º C
Operating humidity 0 - 95%; Non-condensing
Dimensions (L x W x H)
Flush mount 87 x 87 x 24 mm
Surface mount 87 x 87 x 56 mm

Ordering Information

DM2000E
l Analogue addressable manual call point
Manual call point - Red IP67 waterproof, including backbox
DM711 Glass, EN54, Aritech l LED alarm indicator
DM715 Glass, EN54, Universal
l Tamper resistant break glass design
l Easy to test with self reset
l Fast response
l IP67 waterproof model available
Analogue Adressable Fire Detectors
Page : 59

Input Output unit IO2014

2000 series IO
The Aritech range of loop powered Input/Output Modules are designed to provide
unlimited applications to input monitoring and output switching in 2000 Series
Analogue Addressable Fire Detection Systems.

The 2000 Series of I/O Modules combined with the powerful features of the FP 2000
Fire Panels gives the user total versatility.

Specifications

Operating voltage 17 - 28 V
Total standby current < 250 µA
Typical standby current < 200 µA
Operating temperature -10ºC to 70ºC
Operating humidity range 0 - 95%; Non-condensing
Outputs 2 A max. at 30 V dc
Inputs States
100 K resistor in series with switch Quiescent (switch open)
Switch closed
Open circuit
Short circuit l Wide range of I/O Modules : 2 input / 1 output, 2 input / 2
No resistor in series with switch Quiescent (switch open) output, 4 input, 4 input / 4 output
Not valid
Open circuit l Versatile input structure
Switch closed l Supervised inputs
EOL resistor 150 K, 1/4W, 5%
l Normally Open/Normally Closed operation
Ordering Information l Magnetic latched output relays
l Loop powered
IO2014 Input Output unit
IO2031 2 input/1 output
l No external power required
IO2032 2 input/2 output l Easy numeric addressing
IO2034 4 input/4 output
Analogue Adressable Fire Detectors
Page : 60

Single Input Module IU2050

2000 series
The Aritech Analogue Addressable Single Input Module is designed for use with the FP
2000 Fire Panel to monitor normally open or normally closed
contacts. It can typically be connected to conventional Manual Call Points, Pull
Stations or Door Monitors and will report actuation within 1 second
depending on the programming of the fire panel.

Specifications

Operating voltage 17 - 28 V, @ comm. loop terminals


Voltage modulation 4-9 V dc
Standby current < 250 µA
Operating temperature -20° C to 70° C
Operating humidity 0 - 95%; Non-condensing
EOL resistor 150 K, 1/4 W, 5%

Ordering Information

IU2050 Single Input Module

l Analogue Addressable Single Input Module


l Loop Powered
l Supervised Input
Analogue Adressable Fire Detectors
Page : 61

Conventional Zone Monitor IU2055

2000 series
The IU 2055 two-wire zone monitor is designed to provide an interface between
conventional smoke detectors and the analogue addressable FP 2000 fire panel. The
IU 2055 enables the FP 2000 panel to monitor the presence and operation of up to 30
detectors

Specifications

Operating voltage 17 - 39 V, @ comm. loop terminals


14 - 18.5 V, @ zone output terminals
Total standby current < 15 mA
Maximum alarm current <35 mA @ comm. loop
Maximum zone load current 3.5 mA, approx. 30 detectors
Maximum zone capacitance < 1µF
Maximum zone line length < 100 ohm
Operating temperature -10° C to 70° C
Operating humidity range 0 - 95%; Non-condensing
End of line resistor value 3.9 k ohm
Zone impedances @ 24 V
Short circuit <100 Ohms
Fire 240 - 620 Ohms l Monitors up to 30 conventional smoke detectors
Quiescent 2.7 K - 4.2 K Ohms
l Zone circuit supervised for open and short circuits
Open > 15 K
l Supports alarm verification/reset functions
Ordering Information l Loop powered
l Easy numeric addressing
IU2055 Conventional Zone Monitor

Galvanic barrier GBX2000

2000 series
A Galvanic barrier used with IU2055 zone monitor unit in intrinsic safe applications

Ordering Information

GBX2000 Galvanic barrier

l Approved with the IU2055 zone monitor unit


l Intrinsic safe operation when correctly installed
Analogue Adressable Fire Detectors
Page : 62

Indicating Circuit Controller IU2080

2000 series
The Aritech Indicating Circuit Controller is designed for efficient, addressable control
of sounders, bells and strobes in a fire detection system. The 3 A of output power
available from the IU 2080 assures meeting all requirements for signaling devices on
a fire alarm system.

Specifications

Operating voltage 17-28 V, at comm. loop terminals


Total standby current <350 µA, <200 µA typical
Maximum alarm current <3.5 mA at comm. loop
Operating temperature -10º C to 70º C
Operating humidity range 0 - 95%; Non-condensing
Circuit impedance at 24 V
Short circuit <3.3 K
Quiescent 3.3 K - 13 K
Open circuit <13 K
Power supply low voltage detection 24 V; <20.4 V
Standby current <11 mA @ 24 V dc
Alarm current <72 mA @ 24 V dc (plus output circuit load current from
ext. power supply) l Versatile, addressable control for sounders, bells and
Supervisory voltage 2.2 V dc, inverted strobes
Circuit voltage in alarm 24 V dc
Alarm current (fuse rating) 3A l Supervised output circuit
End of line resistor value 10 K, 1/4W, 5% l Programmable output

Ordering Information
l 24 V external power supply

IU2080 Indicating Circuit Controller


Analogue Adressable Fire Detectors
Page : 63

2000 series addressable reflective beam smoke detector; 5 - 50m FD2705R

2000 series
The FD 2705R and FD 2710R provides an integral, loop powered analogue
addressable reflective beam detector up to 100m distance. It operates with 2000
series protocol with the FP1200 / 2000 Fire panels

Specifications

Supply voltage 10.2 - 30 V dc


Range
FD 2705R: 5 - 50 meter
FD2710R: 50-100 meter
Lateral detection 7.5 meter
Current consumption:
quiescent less than 4 ma
alarm less than 25 ma
Optical wave length 880 nm
Operating temperature -30°C to 55 °C
Size 210 x 130 x 120 mm
IP rating IP50
Construction Flame retardent ABS
Colour Gray-black

Ordering Information

FD2705R 2000 series addressable reflective beam smoke detector; 5 - 50m


FD2710R 2000 series addressable reflective beam smoke detector; 50 - 100m
Analogue Adressable Fire Detectors
Page : 64

2000 series loop powered sounder AS2015

2000 series
The AS2015 is a 2000 series addressable loop powered sounder for the FP1200 and
FP2000 range of fire panels. The unit has a built in isolator and can be synchronized.

Specifications

Operating voltage 17-39 VDC


Supply current
not activated 240µA
activated 3mA
Sound output @ 1 meter 100 dB(A)
Continuous tone 990 Hz
Intermittent tone 990 Hz, On Off @ 1 Hz
Two tone 990 Hz / 650 Hz @ 1 Hz

Ordering Information

AS2015 2000 series loop powered sounder


AS2015W 2000 series loop powered sounder - white

l Loop powered
l Low current
l Built in isolators
l 3 tones
l FP1200 / 2000 fire panel operation
ANALOGUE ADDRESSABLE DETECTORS

950 SERIES
Analogue Adressable Fire Detectors
Page : 67

Analogue addressable ionisation sensor DI950

950 series
This elegant slim-line ionisation sensor provides high-performance smoke detection

Specifications

Supply voltage (V dc) 17-28


Quiescent current 280 µA
Alarm indication Red LED
Alarm LED current 2 mA
Normal operating temperature (no icing) -20º to +60º C
Rel. humidity (no condensation) 0-95 %
Max. wind (continuous) 10 m/s
Size of device in base (H x Ø mm) 50 x 100

Ordering Information

DI950 Analogue addressable ionisation sensor

l Passive base address


l Programmable slide-in address card
l Aesthetic design
l EN 54,BOSEC,VdS,CNBOP approved

Optical sensor DP951

950 series
This elegant slim-line optical sensor provides high performance analogue
addressable features

Specifications

Supply voltage (V dc) 17-28


Quiescent current 340 µA
Alarm indication Clear LED (red in alarm)
Alarm LED current 4 mA
Normal operating temperature (no icing) -20º to +60º C
Rel. humidity (no condensation) 0-95 %
Max. wind (continuous) Not affected
Size of device in base (H x Ø mm) 50 x 100

Ordering Information

DP951 Optical sensor


DB950 950 series standard base
l Passive base address
l Programmable slide-in address card
l Aesthetic design
l EN 54,BOSEC,VdS,CNBOP approved
Analogue Adressable Fire Detectors
Page : 68

Analogue addressable temperature sensor DT952

950 series
This elegant slim-line analogue addressable heat sensor provides exact temperature
information to the fire panel.

Specifications

Supply voltage (V dc) 17-28


Quiescent current 250 µA
Alarm indication Red LED
Alarm LED current 2 mA
Normal operating temperature (no icing) -20º to +60º C
Rel. humidity (no condensation) 0-95 %
Max. wind (continuous) Not affected in fixed temp. use
Size of device in base (H x Ø mm) 50 x 100

Ordering Information

DT952 Analogue addressable temperature sensor


DB950 950 series standard base

l Passive base address


l Programmable slide-in address card
l Aesthetic design
l EN 54,BOSEC,VdS,CNBOP approved

950 series analogue addressable manual callpoint DM960

950 series
A manual call point operating with 950 series protocol.

Ordering Information

DM960 950 series analogue addressable manual callpoint


Analogue Adressable Fire Detectors
Page : 69

Intrinsic safe analogue addressable ionisation detector DI970

970 series
An intrinsic safe ionisation detector, when used with the PT971/2 protocol simulator
and GBX70 barrier

Ordering Information

DI970 Intrinsic safe analogue addressable ionisation detector


PT971 Intrinsic safe protocol translator
PT972 Dual channel IS protocol translator
GBX70 Galvanic barrier (single channel)
DB970 Detector base for 970 series intrinsic safe sensors

l Passive base address


l Programmable slide-in address card
l Aesthetic design
l EN 54,BOSEC,VdS,CNBOP approved

Intrinsic safe optical detector DP971

970 series
An intrinsic safe optical detector, when used with the PT971/2 protocol translator and
GBX70 barrier

Ordering Information

DP971 Intrisic safe optical detector


PT971 Intrinsic safe protocol translator
PT972 Dual channel IS protocol translator
GBX70 Galvanic barrier (single channel)
DB970 Detector base for 970 series intrinsic safe sensors

l Passive base address


l Programmable slide-in address card
l Aesthetic design
l EN 54,BOSEC,VdS,CNBOP approved
Analogue Adressable Fire Detectors
Page : 70

Intrinsic safe heat detector DT972

970 series
An intrinsic safe heat detector, when used with the PT971/2 protocol translator and
GBX70 barrier

Ordering Information

DT972 Intrinsic safe heat detector


PT971 Intrinsic safe protocol translator
PT972 Dual channel IS protocol translator
GBX70 Galvanic barrier (single channel)
DB970 Detector base for 970 series intrinsic safe sensors

l Passive base address


l Programmable slide-in address card
l Aesthetic design
l EN 54,BOSEC,VdS,CNBOP approved

Intrinsic safe manual call point DM970

970 series
An intrinsic safe manual call point, when used with the PT971/2 protocol translator
and GBX70 barrier.

Ordering Information

DM970 Intrinsic safe manual call point


Analogue Adressable Fire Detectors
Page : 71

Intrinsic safe protocol translator PT971

970 series
A protocol translator for the 970 series analogue addressable intrinsic safe sensors.
This must be used with the GBX70 barrier

Ordering Information

PT971 Intrinsic safe protocol translator


PT972 Dual channel IS protocol translator

Galvanic barrier (single channel) GBX70

Ordering Information

GBX70 Galvanic barrier (single channel)


Analogue Adressable Fire Detectors
Page : 72

950 series mini switch monitor unit II950

950 series
This unit is designed to monitor the state of one or more single pole switches
connected on a single pair of cables.

Specifications

Supply voltage 14-28 Vdc


Current consumption
Quiescent (20kOhm) 1 mA
Alarm -
Led /relay on 3.5 mA
Switch on surge 3 mA
Switch monitoring 9-11 Vdc
Relay contact rating -
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54

Ordering Information

II950 950 series mini switch monitor unit


l Loop powered
II950I 950 series mini switch monitor unit with interrupt l Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
l LEDs for signalling of I/O and fault condition
l Aesthetically pleasing

950 series switch monitor unit - surface mount II952

950 series
This unit is designed to monitor the state of one or more single pole switches
connected on a single pair of cables. The circuit will report open and short-circuit
faults.

Specifications

Supply voltage 14-28 Vdc


Current consumption
Quiescent (20kOhm) 730µA
Alarm
Led /relay on 5.6 mA
Switch on surge 2.5 mA
Switch monitoring 9-11 Vdc
Relay contact rating -
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54
l Loop powered
Ordering Information l Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
II952 950 series switch monitor unit - surface mount l LEDs for signalling of I/O and fault condition
II953 Switch monitor unit plus - surface mount
l Aesthetically pleasing
Analogue Adressable Fire Detectors
Page : 73

950 series zone monitor unit - surface mount II955

950 series
The zone monitor powers and controls the operation of a zone of conventional
detectors.

Specifications

Supply voltage 14-28 Vdc


Current consumption
Quiescent (20kOhm) 4 mA
Alarm 11-19 mA
Led /relay on -
Switch on surge 2.8 mA
Switch monitoring -
Relay contact rating -
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54

Ordering Information

II955 950 series zone monitor unit - surface mount


l Loop powered
l Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
l LEDs for signalling of I/O and fault condition
l Aesthetically pleasing

950 series single channel IO - surface mount IO950

950 series
This unit provides a loop-powered relay output, a monitored input and an
un-monitored opto-coupled input. It can report fault, switch open and switch closed
condition. It uses the standard housing.

Specifications

Supply voltage 14-28 Vdc


Current consumption
Quiescent (20kOhm) 1.2 mA
Alarm -
Led /relay on 6 mA
Switch on surge 3.5 mA
Switch monitoring 9-11 Vdc
Relay contact rating 1A@30 Vac/dc
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54
l Loop powered
Ordering Information l Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
IO950 950 series single channel IO - surface mount l LEDs for signalling of I/O and fault condition
l Aesthetically pleasing
Analogue Adressable Fire Detectors
Page : 74

950 series output unit - surface mount IO955

950 series
This unit provides a loop-powered relay output

Specifications

Supply voltage 14-28 Vdc


Current consumption
Quiescent (20kOhm) 720µA
Alarm -
Led /relay on 3.3 mA
Switch on surge 3 mA
Switch monitoring -
Relay contact rating 1A@30 Vac/dc
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54

Ordering Information

IO955 950 series output unit - surface mount


l Loop powered
l Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
l LEDs for signalling of I/O and fault condition
l Aesthetically pleasing

950 series sounder circuit controller - surface mount IO956

950 series
This unit is designed to control a zone of sounders powered by an external DC supply.

Specifications

Supply voltage 14-28 Vdc


Current consumption
Quiescent (20kOhm) 1.9 mA
Alarm -
Led /relay on 1.7 mA
Switch on surge 2.6 mA
Switch monitoring 9-11 Vdc
Relay contact rating -
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54

Ordering Information
l Loop powered
IO956 950 series sounder circuit controller - surface mount l Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
l LEDs for signalling of I/O and fault condition
l Aesthetically pleasing
Analogue Adressable Fire Detectors
Page : 75

950 series loop isolator IU950

Ordering Information

IU950 950 series loop isolator


Analogue Adressable Fire Detectors
Page : 76

950 series loop powered sounder AS950

950 Series
Designed to operate with the 950 series analogue sensors and monitors, the AS950
loop sounders are addressed and utilise the same protocol using a very low current.

Specifications

Supply voltage 14 - 28 V dc
Current consumption
Quiescent 140 µA at 24 V dc
Switch on surge 1.24 mA for 3 sec.
Operated at 85 dBA 3 mA +/- 0.25 mA
Operated at 92 dBA 8 mA +/- 0.25 mA
Drive frequency 500 - 550 Hz (continuous mode)
Ingress protection IP43
Operating temperature -20 to 60 °C
Dimension (dia. x depth) 115 x 25 mm (sounder only)
115 x 33 mm (sounder with cap)
Weight 140 g (sounder only)
145 g (sounder with cap)

Ordering Information l Loop powered


l Low current consumption
AS950 950 series loop powered sounder
AS950I Loop powered sounder, for use with isolator base
l Aritech 950 and Apollo protocol compatible
AS950W Loop powered sounder, white cap l Continuous or pulsed tone
l Sound output 85 - 92 dBA at 1 metre
l Reduces wiring and installation cost
Analogue Adressable Fire Detectors
Page : 77

950 series high output loop powered sounder AS955

950 Series
Designed to operate with the 950 series analogue sensors and monitors, the AS955
high output loop sounders are addressed and utilise the same protocol using a very
low current.

Specifications

Supply voltage 14 - 28 V dc
Current consumption
Quiescent 140 µA at 24 V dc
Switch on surge 1.24 mA for 3 sec.
Operated 4.5 mA +/- 0.25 mA
Drive frequency 500 - 550 Hz (continuous mode)
Ingress protection IP43
Operating temperature -20 to 60 °C
Sound output 100 dB(A)

Ordering Information

AS955 950 series high output loop powered sounder


l Loop powered
l Low current consumption
l 950 series protocol
l Continuous or pulsed tone
l Sound output 100 dB(A) at 1 metre
l Reduces wiring and installation cost
Analogue Adressable Fire Detectors
Page : 78

950 series loop-powered beam detector FD950

950 Series
A 950 series loop-powered beam detector with a range of up to 100m long and 15m
wide.

Ordering Information

FD950 950 series loop-powered beam detector

l Loop-powered
l 950 series compatible with FP1200 and FP2000
l Four selectable alarm levels
l Drift compensation
l Remote interface
l Simple wiring
l Simple alignment
Analogue Adressable Fire Detectors
Page : 79

950 series standard base DB950

950 series
A unique, patented addressing method provides simple, user-friendly and accurate
identification of monitor location whereby a coded card, inserted in the base, is read
by any monitor as it is plugged in.

Ordering Information

DB950 950 series standard base

l Passive base address


l Programmable slide-in address card
l Aesthetic design
l EN 54,BOSEC,VdS,CNBOP approved

Base for IU 950 DB951

950 series
The isolating base senses and isolates short-circuit faults on 950 series loops and
spurs. Up to 20 devices may be placed between any two isolator bases.

Ordering Information

DB951 Base for IU 950

l Passive base address


l Programmable slide-in address card
l Aesthetic design
l EN 54,BOSEC,VdS,CNBOP approved
Analogue Adressable Fire Detectors
Page : 80

Isolating base (20 devices) DB961

The isolating base senses and isolates short circuit faults on 950 series loops and
spurs. Up to 20 devices may be placed between any two isolator bases.

Ordering Information

DB961 Isolating base (20 devices)

l Passive base address


l Programmable slide-in address card
l Aesthetic design
l EN 54,BOSEC,VdS,CNBOP approved

Detector base for 970 series intrinsic safe sensors DB970

Ordering Information

DB970 Detector base for 970 series intrinsic safe sensors

l Passive base address


l Programmable slide-in address card
l Aesthetic design
l EN 54,BOSEC,VdS,CNBOP approved
Analogue Adressable Fire Detectors
Page : 81

Coded cards, addresses 1 - 18 IU980

950 series
Precoded Xpert address cards for use in DB9xx bases

Ordering Information

IU980 Coded cards, addresses 1 - 18


IU981 Coded cards, addresses 19 - 36
IU982 Coded cards addresses 37 - 54
IU983 Coded cards, addresses 55 - 72
IU984 Coded cards, addresses 73 - 90
IU985 Coded cards, addresses 91- 108
IU986 Coded cards, addresses 109 - 126
FIRE PANELS & REPEATERS

CONVENTIONAL FIRE PANELS


FP200 SERIES
Conventional Fire Panels
Page : 85

Conventional fire alarm panel with 2 zones FP202

The FP200 Series microprocessor controlled, conventional fire panels incorporate


state of the art technology, reliability, ease of installation and maintenance in a
basic package. They are compatible with conventional detectors such as the Aritech
Series 300, Series 650 and Series 700 devices. The FP202 has 2 conventional zones.

Specifications

Supply Voltage 125/230 VAC @ 50/60 Hz


Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number of detectors 20
Ouput voltage 22 to 28 VDC l Modern, elegant design
End-of-line resitance 4k7 Ohm l Compact models for 2, 4 and 6 zones
Manual call point resistance 100 Ohm, 2 W
l Microprocessor controlled
Outputs
Fire alarm 24 VDC ± 15%, 300 mA l Multilingual keyboard
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA l 2 Access levels
Environmental
l Differentiation between alarms from manual call points and
Working temperature +5 to +40°C automatic detectors in the same zone
Storage temperature -10 to +70°C
Relative humidity 95 % (non-condencing)
l Acoustic indications for fire and fault
Physical Characteristics l Optical indications for fire and fault by zone
Size (w x h x d) 305 x 295 x 100 mm l Low maintenance
Weight without batteries 3 kg
l Compatible with all ranges of ARITECH conventional
detectors
Ordering Information

FP202 Conventional fire alarm panel with 2 zones


Conventional Fire Panels
Page : 86

Conventional fire alarm panel with 4 zones FP204

The FP200 Series microprocessor controlled, conventional fire panels incorporate


state of the art technology, reliability, ease of installation and maintenance in a
basic package. They are compatible with conventional detectors such as the Aritech
Series 300, Series 650 and Series 700 devices. The FP204 has 4 conventional zones.

Specifications

Supply Voltage 125/230 VAC @ 50/60 Hz


Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number of detectors 20
Ouput voltage 22 to 28 VDC l Modern, elegant design
End-of-line resitance 4k7 Ohm l Compact models for 2, 4 and 6 zones
Manual call point resistance 100 Ohm, 2 W
l Microprocessor controlled
Outputs
Fire alarm 24 VDC ± 15%, 300 mA l Multilingual keyboard
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA l 2 Access levels
Environmental
l Differentiation between alarms from manual call points and
Working temperature +5 to +40°C automatic detectors in the same zone
Storage temperature -10 to +70°C
Relative humidity 95 % (non-condencing)
l Acoustic indications for fire and fault
Physical Characteristics l Optical indications for fire and fault by zone
Size (w x h x d) 305 x 295 x 100 mm l Low maintenance
Weight without batteries 3 kg
l Compatible with all ranges of ARITECH conventional
detectors
Ordering Information

FP204 Conventional fire alarm panel with 4 zones


Conventional Fire Panels
Page : 87

Conventional fire alarm panel with 6 zones FP206

The FP200 Series microprocessor controlled, conventional fire panels incorporate


state of the art technology, reliability, ease of installation and maintenance in a
basic package. They are compatible with conventional detectors such as the Aritech
Series 300, Series 650 and Series 700 devices. The FP206 has 6 conventional zones.

Specifications

Supply Voltage 125/230 VAC @ 50/60 Hz


Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number of detectors 20
Ouput voltage 22 to 28 VDC l Modern, elegant design
End-of-line resitance 4k7 Ohm l Compact models for 2, 4 and 6 zones
Manual call point resistance 100 Ohm, 2 W
l Microprocessor controlled
Outputs
Fire alarm 24 VDC ± 15%, 300 mA l Multilingual keyboard
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA l 2 Access levels
Environmental
l Differentiation between alarms from manual call points and
Working temperature +5 to +40°C automatic detectors in the same zone
Storage temperature -10 to +70°C
Relative humidity 95 % (non-condencing)
l Acoustic indications for fire and fault
Physical Characteristics l Optical indications for fire and fault by zone
Size (w x h x d) 305 x 295 x 100 mm l Low maintenance
Weight without batteries 3 kg
l Compatible with all ranges of ARITECH conventional
detectors
Ordering Information

FP206 Conventional fire alarm panel with 6 zones


FIRE PANELS & REPEATERS

CONVENTIONAL FIRE PANELS


FP400 SERIES
Conventional Fire Panels
Page : 91

Conventional fire alarm panel with 2 zones FP402

The FP400 series of conventional fire alarm and extinguishing control panels is the
ideal solution for small to medium-sized installations. Very powerful and
cost-effective, they are extremely simple to install and use due to their ergonomic,
advanced design. The panels come in elegant, high-quality, conveniently sized,
heavy-duty metal enclosures with space for batteries and finished in high-gloss
paint. All panels have a high-quality keyboard with audible metallic click and good
travel

Specifications

Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz


Batteries
Capacity 2 x 2.3 Ah
Fuse rating 2A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders l Modern, attractive design
Maximum load 250 mA l Microprocessor controlled
Delay Selectable 0 - 9 min
l From 2 up to 16 zones
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs l EN54 compliant with approvals pending
Maximum load NA l 2 Access levels
Fuse rating NA
l 2 Monitored sounder outputs
Auxilliary Output 250 mA
24 VDC Resetable Output l One-man test capability
Maximum Load 100 mA l 24 Volt resetable output
Reset time 3s
l External 'class change' facility
Environment
Working temperature -5°C to +40°C
l Alarm output with potential free relay
Relative humidity (non condencing) 95 % l General fault output with potential free relay
IP rating IP30 l External watchdog
Physical Characteristics
Size (mm) 297 (w) x 307 (h) x 105 (d)
Weight (without batteries) 3.6 kg

Ordering Information

FP402 Conventional fire alarm panel with 2 zones


FP404 Conventional fire alarm panel with 4 zones
Conventional Fire Panels
Page : 92

Conventional fire alarm panel with 8 zones FP408

The FP400 series of conventional fire alarm and extinguishing control panels is the
ideal solution for small to medium-sized installations. Very powerful and
cost-effective, they are extremely simple to install and use due to their ergonomic,
advanced design. The panels come in elegant, high-quality, conveniently sized,
heavy-duty metal enclosures with space for batteries and finished in high-gloss
paint. All panels have a high-quality keyboard with audible metallic click and good
travel

Specifications

Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz


Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders l Modern, attractive design
Maximum load 250 mA l Microprocessor controlled
Delay Selectable 0 - 9 min
l From 2 up to 16 zones
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs l EN54 compliant with approvals pending
Maximum load NA l 2 Access levels
Fuse rating NA
l 2 Monitored sounder outputs
Auxilliary Output 250 mA
24 VDC Resetable Output l One-man test capability
Maximum load 100 mA l 24 Volt resetable output
Reset time 3s
l External 'class change' facility
Environment
Working temperature -5°C to +40°C
l Alarm output with potential free relay
Relative humidity (non condencing) 95 % l General fault output with potential free relay
IP rating IP30 l External watchdog
Physical Characteristics
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg

Ordering Information

FP408 Conventional fire alarm panel with 8 zones


Conventional Fire Panels
Page : 93

Conventional fire alarm panel with 12 zones FP412

The FP400 series of conventional fire alarm and extinguishing control panels is the
ideal solution for small to medium-sized installations. Very powerful and
cost-effective, they are extremely simple to install and use due to their ergonomic,
advanced design. The panels come in elegant, high-quality, conveniently sized,
heavy-duty metal enclosures with space for batteries and finished in high-gloss
paint. All panels have a high-quality keyboard with audible metallic click and good
travel

Specifications

Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz


Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders l Modern, attractive design
Maximum load 250 mA l Microprocessor controlled
Delay Selectable 0 - 9 min
l From 2 up to 16 zones
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs l EN54 compliant with approvals pending
Maximum load NA l 2 Access levels
Fuse rating NA
l 2 Monitored sounder outputs
Auxilliary Output 250 mA
24 VDC Resetable Output l One-man test capability
Maximum load 100 mA l 24 Volt resetable output
Reset time 3s
l External 'class change' facility
Environment
Working temperature -5°C to +40°C
l Alarm output with potential free relay
Relative humidity (non condencing) 95 % l General fault output with potential free relay
IP rating IP30 l External watchdog
Physical Characteristics
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg

Ordering Information

FP412 Conventional fire alarm panel with 12 zones


Conventional Fire Panels
Page : 94

Conventional fire alarm panel with 16 zones FP416

The FP400 series of conventional fire alarm and extinguishing control panels is the
ideal solution for small to medium-sized installations. Very powerful and
cost-effective, they are extremely simple to install and use due to their ergonomic,
advanced design. The panels come in elegant, high-quality, conveniently sized,
heavy-duty metal enclosures with space for batteries and finished in high-gloss
paint. All panels have a high-quality keyboard with audible metallic click and good
travel

Specifications

Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz


Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders l Modern, attractive design
Maximum load 250 mA l Microprocessor controlled
Delay Selectable 0 - 9 min
l From 2 up to 16 zones
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs l EN54 compliant with approvals pending
Maximum load NA l 2 Access levels
Fuse rating NA
l 2 Monitored sounder outputs
Auxilliary Output 250 mA
24 VDC Resetable Output l One-man test capability
Maximum load 100 mA l 24 Volt resetable output
Reset time 3s
l External 'class change' facility
Environment
Working temperature -5°C to +40°C
l Alarm output with potential free relay
Relative humidity (non condencing) 95 % l General fault output with potential free relay
IP rating IP30 l External watchdog
Physical Characteristics
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg

Ordering Information

FP416 Conventional fire alarm panel with 16 zones


Conventional Fire Panels
Page : 95

Relay module, 4 potential free relays for NK700/Fx400 fire panels RB404

The RB404 relay expander module has voltage-free 4 relays. The unit allows for a
relay for each detection zone or for programming the activation of different relays
depending on the status of one or more zones. It is used on the GE-Interlogix
NK700/FP400 conventional fire panel range.

Specifications

Relay Rating
Voltage 230 VDC
Current 2A
Delay setting 0 to 9 minutes

Ordering Information

RB404 Relay module, 4 potential free relays for NK700/Fx400 fire panels

l 4 Potential free relays


l Up to 4 modules may be housed inside the fire panel
cabinet
l Programable with basic boolen functions
l Power supplied from fire panel bus
l Output delay setting per relay
Conventional Fire Panels
Page : 96

Relay module, 4 supervised relays for NK700/Fx400 fire panels SB404

The SB404 module has 4 relays that provide 4 of 24 VDC supervised outputs. These
may be configured to power sounders or as standard 24 VDC supervised outputs for
other devices.

Specifications

Aux. Supply 24 VDC


Delay Setting 0 to 9 minutes

Ordering Information

SB404 Relay module, 4 supervised relays for NK700/Fx400 fire panels

l 4 Supervised relays
l Up to 4 modules may be housed inside the fire panel
cabinet
l Programable with basic boolen functions
l Output delay setting per relay
l Configurable for sounder control or as supervised outputs
Conventional Fire Panels
Page : 97

Conventional fire detection and extinguishing control panel with 3 zones including 1 extinguishing zone FEC403

The FP400 series of conventional fire alarm and extinguishing control panels is the
ideal solution for small to medium-sized installations. Very powerful and
cost-effective, they are extremely simple to install and use due to their ergonomic,
advanced design. The panels come in elegant, high-quality, conveniently sized,
heavy-duty metal enclosures with space for batteries and finished in high-gloss
paint. All panels have a high-quality keyboard with audible metallic click and good
travel

Specifications

Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz


Batteries
Capacity 2 x 7 Ah
Fuse rating 2A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders l Modern, attractive design
Maximum load 250 mA l Microprocessor controlled
Delay Selectable 0 - 9 min
l 3 zone (1 ext. area) and 6 zone (2 ext. areas) available
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs l Automatic extinguishing agent release control
Maximum load 350 mA l EN54 compliant
Fuse rating 1A
l 2 Access levels
Auxilliary Output 250 mA
24 VDC Resetable Output l Supervised general sounder output
Maximum Load 100 mA l Supervised extinguishing inputs and outputs
Reset time 3s
l One-man test capability
Environment
Working temperature -5°C to +40°C
l 24 Volt resetable output
Relative humidity (non condencing) 95 % l External 'class change' facility
IP rating IP30 l Alarm output with potential free relay
Physical Characteristics
l General fault output with potential free relay
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg l External watchdog

Ordering Information

FEC403 Conventional extinguishing control panel with 3 zones


Conventional Fire Panels
Page : 98

Conventional extinguishing control panel with 6 zones FEC406

The FP400 series of conventional fire alarm and extinguishing control panels is the
ideal solution for small to medium-sized installations. Very powerful and
cost-effective, they are extremely simple to install and use due to their ergonomic,
advanced design. The panels come in elegant, high-quality, conveniently sized,
heavy-duty metal enclosures with space for batteries and finished in high-gloss
paint. All panels have a high-quality keyboard with audible metallic click and good
travel

Specifications

Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz


Batteries
Capacity 2 x 7 Ah
Fuse rating 2A
Zone
Maximum load 94 mA
Max. number of detectors per zone 20
Maximum zone resistance 44 ohm
Sounders l Modern, attractive design
Maximum load 250 mA l Microprocessor controlled
Delay Selectable 0 - 9 min
l 3 zone (1 ext. area) and 6 zone (2 ext. areas) available
Relay Outputs (excluding sounders) 1 A @ 30 VDC
Extinguishing Relay Outputs l Automatic extinguishing agent release control
Maximum load 350 mA l EN54 compliant
Fuse rating 1A
l 2 Access levels
Auxilliary Output 250 mA
24 VDC Resetable Output l Supervised general sounder output
Maximum Load 100 mA l Supervised extinguishing inputs and outputs
Reset time 3s
l One-man test capability
Environment
Working temperature -5°C to +40°C
l 24 Volt resetable output
Relative humidity (non condencing) 95 % l External 'class change' facility
IP rating IP30 l Alarm output with potential free relay
Physical Characteristics
l General fault output with potential free relay
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg l External watchdog

Ordering Information

FEC406 Conventional extinguishing control panel with 6 zones


FIRE PANELS & REPEATERS

CONVENTIONAL FIRE PANELS


FP600 SERIES
Conventional Fire Panels
Page : 101

4-zone Conventional Fire Panel FP604

The FP 604 fire panel is designed using the latest technologies and is compatible
with most brands of conventional fire detectors. The FP 604 is a 4-zone panel which
is extendable up to 6 zones.

Specifications

Supply voltage 230 V (± 10% - 50 Hz ± 5%)


80 mA
Total current 12 V dc (no charge), quiescent
90 mA
Total current 24 V dc (no charge), quiescent
Auxiliary output 100 mA - 12 V dc
Battery back-up for 72 hrs 1 x 12 V - 7.2 Ah battery
Battery charger fuse 2A
Battery charger voltage 13.8 V
Bells - Fire Brigade fuse 315 mA
Dimensions 390 x 315 x 85 mm

Ordering Information

FP604 4-zone Conventional Fire Panel


ZI602 Two zone extension board, including 6 outputs l One man maintenance
RC606 Set of 6 bi-stable magnetic latch relays
l Alarm verification
l Individual zone alarm outputs
l One 12 V back-up battery
l 12 V dc auxiliary output
l 4 - 6 zones
l Mixed zone capability
l Head removal option
l Sirens output 12 or 24 V dc
l Microprocessor based
l EN 54 p2/4 approved
l LPCB certified
l Optional third source
l Optional digital dialler
Conventional Fire Panels
Page : 102

Two zone extension board, including 6 outputs ZI602

This board extends the FP604 from 4 zones to 6 zones. It also provides 6 outputs for
the 6 zones.

Ordering Information

ZI602 Two zone extension board, including 6 outputs

Set of 6 bi-stable magnetic latch relays RC606

A set of 6 relays for the ZI602 zone extension board

Ordering Information

RC606 Set of 6 bi-stable magnetic latch relays


FIRE PANELS & REPEATERS

CONVENTIONAL FIRE PANELS


FP700 SERIES
Conventional Fire Panels
Page : 105

Fire panel equipped with 8 zones FP708

FP700 series
A set of four conventional fire panels. The FP708 and FP708C are 8 zone
non-expandable fire panels. The FP740 and FP740C are 8 zone expandable to 40
zones. The FP708C and FP740C have an alarm counter. All panels can use the full
range of LON700 output boards.

Specifications

Dimensions (W x H x D) 444 x 340 x110 mm


Weight (no batteries) 5.5 kg
Supply voltage (see engineering guide) 230 V ac; 1,5 A; 50 Hz
Quiescent current @20 devices/zone 210 mA (8 zones)
Batteries for 24 hrs (in housing) 7.2 Ah
Batteries for 72 hrs 17 Ah
Battery charger rating 1.4 A max
Nominal battery charger voltage @ 25°C27,6 V
Auxiliary output 1 21 - 29,4 V dc; 1.2 A max.
Auxiliary output 2 11.5 - 12.5 V dc; 0.4 A max.
Total 24 V output (no charging) 3,5 A max
Sounder/warning 0,5 A, 19-31 V dc, polarity reversal
Evacuation/Fire brigade 0,5 A, 19-31 V dc, polarity reversal
Fault and Fire protection relay rating 2 A, @ 42 V
l Fully modular
RS 232 port 19200 baud, DB9, 1 start, 8 data, 1 stop, no parity l Echelon based network
l One Man maintenance
Ordering Information
l Alarm verification
FP708 Fire panel equipped with 8 zones l 700 series detectors Clean Me® detection
FP708C Fire panel equipped with 8 zones including alarm counter
FP740 Fire panel equipped with 8 zones expandable up to 40 zones
l Various output boards
FP740C Fire panel equipped with 8 zones exp. to 40 including alarm counter l Approved BOSEC
l Complies to EN 54 p2/p4
l Modular up to 40 zones
l Full line of repeaters
l Microprocessor based
l Local and remote control
Conventional Fire Panels
Page : 106

Repeater 8 zones, 24 VDC input FR708

FR700 series
The repeaters provide different solutions - 24 volt input and 230 volt input using the
PS700 power supply. The FR708 is 8 zones non expandable and the FR740 is 8 zones
expandable to 40 zones. The FR700 repeaters connect to the FP700 fire panel with
the LON 700 bus. The FR708V230 and FR740V230 include a card cage for LON board
expansion and have a PS700 power supply.

Ordering Information

FR708 Repeater 8 zones, 24 VDC input


FR708V230 Repeater 8 zones with card cage and PS700 PSU (230V input)
FR740 Repeater 8 zones, expandable up to 40 zones, 24 VDC input
FR740V230 Repeater 8 zones, exp to 40 zones with card cage and PS700 PSU (230V)

l Fully modular
l Echelon based network
l Various output boards
l Modular up to 40 zones
l Full line of repeaters
l Microprocessor based
l Local and remote control
Conventional Fire Panels
Page : 107

8 zone indicator LED extension board fire/fault ZE708

FP700 series
This zone indicator extension board is used to expand the FP740 and FR740 front
panel indications.

Ordering Information

ZE708 8 zone indicator LED extension board fire/fault

8 zone input extension board ZI708

FP700 series
An eight zone input expansion board for FP740 fire panels.

Ordering Information

ZI708 8 zone input extension board


Conventional Fire Panels
Page : 108

Synoptic driver for 80 LEDs and common signals FM740

LON 700 series


A LON700 output board to display LED's. It can be self-standing as well as plugging
into a card cage.

Specifications

Dimensions mm (L x W x D) 150x30x60
Weight 200 g
Operating temp °C -5°C - +40
Operating voltage Vdc 19 - 30
Current consumption
max quiesent mA 30
power consumption per LED (mW) 40
Bus Connection
FP1200/FP2000 (with LON2000) ***
FP700 (direct connection) ***
Bus Cable Cat 5
Total number of repeaters
FP1200/FP2000 15
FP700 8

Ordering Information

FM740 Synoptic driver for 80 LEDs and common signals

LON700 output board with 24 open collector outputs OCB724

LON700 series
A 24 way open collector board used in a LON700 system

Ordering Information

OCB724 LON700 output board with 24 open collector outputs


Conventional Fire Panels
Page : 109

LON700 output board with 8 relays RB708

LON700 series
An eight way relay board used in LON700 systems

Ordering Information

RB708 LON700 output board with 8 relays

LON700 output board with 8 supervised outputs SOB708

LON700 series
Eight supervised outputs that can be used in LON700 systems

Ordering Information

SOB708 LON700 output board with 8 supervised outputs


Conventional Fire Panels
Page : 110

FP700 black box with 7 slot card cage FB708

LON700 series
The FB708 and FB740 'black boxes' allow for the distribution of LON700 input /
output units. When used with the NC700 or FM740, the FB7xx is connected to the
FP700 / FP2000 firepanels with the LON700 bus.

Ordering Information

FB708 FP700 black box with 7 slot card cage


FB740 FP700 black box with 11 slot card cage and PS700
NC700 LON 700 interface board

l Fully modular
l Echelon based network
l Various output boards
l Microprocessor based
l Local and remote control
l For fire panel distributed systems
l 7 slot card cage or 11 slot card cage with power supply
Conventional Fire Panels
Page : 111

LON 700 interface board NC700

LON700 series
An interface board to connect a LON bus from a fire panel to a FB7xx 'black box'

Ordering Information

NC700 LON 700 interface board


FB708 FP700 black box with 7 slot card cage
FB740 FP700 black box with 11 slot card cage and PS700

Plug-in power supply 3.5 A PS700

LON700 series
This power supply can be used to extend the power output in LON700 systems. It is
standard in the FP700 and FR700V230 systems, as well the FB740 'black box'.

Ordering Information

PS700 Plug-in power supply 3.5 A


FIRE PANELS & REPEATERS

ANALOGUE ADDRESSABLE FIRE PANELS


FP1500 SERIES
Analogue Adressable Fire Panels
Page : 115

Analogue addressable fire detection panel - 1 loop FP1501

The FP1501 1 loop analogue addressable fire alarm control panel is the ideal solution
for small to medium-sized installations. Very powerful and cost-effective, it is
extremely simple to install and use due to is ergonomic, advanced design. The panel
is supplied in an elegant, high-quality, conveniently sized, heavy-duty enclosure. It
has a high-quality keyboard with audible metallic click and good travel.

Specifications

Supply Voltage 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)


Current Consumption 175 mA Quiescent / 241 mA in alarm with no devices
connected
Batteries
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse Rating 3A
Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperature
compensated -3 V / °C)
Loop characteristics per loop
Capacity 250 addresses per loop
Maximum Load 400 mA / 26 VDC to 32 VDC
Maximum Electrical Characteristics 44 Ohm / 500 nF approximately 2 km of 1.5 mm2 l Modern, attractive design
diameter cable
Sounders (reverse polarity supervision) l 4 x 40 characters LCD display
Maximum Load 250 mA each (2 Sounder outputs available) / 18 VDC to l 20 Display zones
24 VDC
Delays 10 seconds to 600 seconds, software adjustable in 10 l EN54 compliant with approvals pending
second intervals
Relay Outputs (potential free) 1 A @ 30 VDC l 3 User access levels
24 V Auxiliary Output l 2 Monitored sounder outputs
Maximum Load 250 mA @ 18 VDC to 28 VDC
l 2 Programmable voltage free relays
Environment
Working Temperature -5°C to +40 °C
l 24 Volt auxiliary output
Relative Humidity 0-95% non-condensing l I/O programming capabilities with Boolean functions
IP Rating IP30 l Day/night sensitivity settings
Physical Characteristics
l Coincidence within zones
Size 420 mm (w) x 335 (h) x 110 (d)
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah batteries l Upload/download and graphic PC software
l Panel networking
Ordering Information
l Installation test capability
FP1501 Analogue addressable fire detection panel - 1 loop
Analogue Adressable Fire Panels
Page : 116

Analogue addressable fire detection panel - 2 loops FP1502

The FP1500 series analogue addressable fire alarm control panels is the ideal
solution for small to medium-sized installations. Very powerful and cost-effective,
they are extremely simple to install and use due to their ergonomic, advanced design.

The panels are supplied in an elegant, high-quality, conveniently sized, heavy-duty


metal enclosure and are finished in a high-gloss paint. All panels have a high-quality
keyboard with audible metallic click and good travel.

The batteries for the system may be housed inside the cabinet.

Specifications

Supply Voltage 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)


Current Consumption 175 mA Quiescent / 241 mA in alarm with no devices
connected
Batteries
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse Rating 3A l Modern, attractive design
Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperature
compensated -3 V / °C) l 4 x 40 characters LCD display
Loop characteristics per loop
l 20 Display zones
Capacity 250 addresses per loop
Maximum Load 400 mA / 26 VDC to 32 VDC
l EN54 compliant with approvals pending
Maximum Electrical Characteristics 44 Ohm / 500 nF approximately 2 km of 1.5 mm2 l 3 User access levels
diameter cable
Sounders (reverse polarity supervision) l 2 Monitored sounder outputs
Maximum Load 250 mA each (2 Sounder outputs available) / 18 VDC to l 2 Programmable voltage free relays
24 VDC
Delays 10 seconds to 600 seconds, software adjustable in 10 l 24 Volt auxiliary output
second intervals
Relay Outputs (potential free) 1 A @ 30 VDC l I/O programming capabilities with Boolean functions
24 V Auxiliary Output l Day/night sensitivity settings
Maximum Load 250 mA @ 18 VDC to 28 VDC
l Coincidence within zones
Environment
Working Temperature -5°C to +40 °C
l Upload/download and graphic PC software
Relative Humidity 0-95% non-condensing l Panel networking
IP Rating IP30 l Installation test capability
Physical Characteristics
Size 420 mm (w) x 335 (h) x 110 (d)
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah batteries

Ordering Information

FP1502 Analogue addressable fire detection panel - 2 loops


Analogue Adressable Fire Panels
Page : 117

RS485 Expansion kit for KSA701/FP1500 fire panels NC785

The NC785 RS485 expander allows for an easy upgrade to the KSA701/FP1500 series
analalogue addressable fire panels. Each module adds an additional industry
standard RS485 communication port to the panel. This port could be used for
communications with other network nodes in the fire panel network.

Specifications

Number of ports 1
Communications medium RS485
Technical specifications
Maximum cable length 1200 m
Communication speed 9600 baud
Cable CAT5 - twisted with screen
Termination resistance 150 Ohm

Ordering Information

NC785 RS485 expansion kit for KSA701/FP1500 fire panels


l Industry standard RS485 communications
l No hardware configuration required
Analogue Adressable Fire Panels
Page : 118

Analogue addressable LCD Repeater/Emulator* FR1500

The FP1500 Series analogue addressable fire alarm panels are the ideal solution for
small to medium-sized installations. Very powerful and cost-effective, they are easy
to install and use due to their ergonomic, advanced design. The FR1500 LCD repeater
is supplied in the same enclosure as the FP1500.

Specifications

Supply Voltage
AC Version 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
DC Version 24 VDC
Current Consumption 175 mA Quiescent / 200 mA in alarm
Battery Charger (AC Version only)
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse Rating 3A
Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperature
compensated -3 V / °C)
Environment
Working Temperature -5°C to +40 °C
Relative Humidity 0-95% non-condensing
l Modern, attractive design
IP Rating IP30
Physical Characteristics l 4 x 40 characters LCD display
Size 420 mm (w) x 335 (h) x 110 (d) l 20 Display zones
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah batteries l EN54 compliant with approvals pending
Communication Ports RS232 and RS485 standard
l 3 User access levels
Ordering Information l 24 VDC or 230 VAC models available
l Panel networking
FR1500 Analogue addressable LCD Repeater/Emulator
l Full system control
Analogue Adressable Fire Panels
Page : 119

GSM Modem for Kilsen Fire Panels MODGSM

The MODGSM modem may be used in KSA701/FP1500, KSA702 and KSA705 fire panel
from GE-Interlogix. It is ideal for use as a standard modem for making and receiving
calls from and to the fire panel, but may also be used for GSM messaging.

Specifications

GSM Band 900/1800 MHz


Services Data, SMS, Voice and Fax
AT Commands GSM 07.07 and 07.05
Output Power (max)
GSM900 2W
GSM1800 1W
Input Voltage 5 to 32 V
Current @ 5V
Avarage 330 mA
Peak 1.8 A
SIM Interface 3V / 5V
Dimensions (h x w x d) 98 x 54 x 25 mm
Weight 130 g
Environmental Temperature l Dual-Band 90/1800 MHz
Storage - 25 °C to + 70 °C l Data and SMS services
Operating - 20 °C to + 55 °C
l Remote control by AT commands

Ordering Information l Wide input voltage range

MODGSM GSM Modem for Kilsen Fire Panels


Analogue Adressable Fire Panels
Page : 120

Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops) PCG-Graphic102

The PCG-Config series consists of 3 software applications. The individual software


formats allows the graphic package to grow with the installation. PCG-Config102
operates with a single panel and allows for the configuration of all devices up to a
maximum of two loops.

Specifications

Hardware Requirements
Communication RS232, Modem and/or TCP/IP
Display SVGA or higher resolution
Hard Disk 2 GB with 650 MB free space
Keyboard Required
Pointing Device Required
Printer System printer required for printing
Processor 1 GHz or higher Pentium III-compatible CPU
RAM 256 Mb or more
Removable Media 1.44 Mb stiffy and CD-ROM or DVD drive
Software Requirements
Operating System Windows '98 or Windows 2000 l Bi-directional communication with single panels and
networked fire systems
Ordering Information l Local or remote connection via modem or TCP/IP
l Large selection of user configurable icons
PCG-Graphic102 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops)
l Visualises device alarms and status of in- and outputs
l Event texts retrieval from the panel
l Configurator and operator contol levels
l Navigation buttons allowed
l Event logs with reporting facilities
l Basic drawing package included
l Imports bmp & drw format graphics
Analogue Adressable Fire Panels
Page : 121

Graphic Software for KSA700/FP1500 Fire Systems (1 panel-5 loops) PCG-Graphic105

The PCG-Config series consists of 3 software applications. The individual software


formats allows the graphic package to grow with the installation. PCG-Config105
supports a single panel up to 5 loops.

Specifications

Hardware Requirements
Communication RS232, Modem and/or TCP/IP
Display SVGA or higher resolution
Hard Disk 2 GB with 650 MB free space
Keyboard Required
Pointing Device Required
Printer System printer required for printing
Processor 1 GHz or higher Pentium III-compatible CPU
RAM 256 Mb or more
Removable Media 1.44 Mb stiffy and CD-ROM or DVD drive
Software Requirements
Operating System Windows '98 or Windows 2000
l Bi-directional communication with single panels and
Ordering Information networked fire systems
l Local or remote connection via modem or TCP/IP
PCG-Graphic105 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-5 loops) l Large selection of user configurable icons
l Visualises device alarms and status of in- and outputs
l Event texts retrieval from the panel
l Configurator and operator contol levels
l Navigation buttons allowed
l Event logs with reporting facilities
l Basic drawing package included
l Imports bmp & drw format graphics
Analogue Adressable Fire Panels
Page : 122

Graphic Software for KSA700/FP1500 Fire Systems (multi-panel) PCG-GraphicNW

The PCG-Config series consists of 3 software applications. The individual software


formats allows the graphic package to grow with the installation. PCG-ConfigNW
allows for monitoring on networked systems with multiple panels.

Specifications

Hardware Requirements
Communication RS232, Modem and/or TCP/IP
Display SVGA or higher resolution
Hard Disk 2 GB with 650 MB free space
Keyboard Required
Pointing Device Required
Printer System printer required for printing
Processor 1 GHz or higher Pentium III-compatible CPU
RAM 256 Mb or more
Removable Media 1.44 Mb stiffy and CD-ROM or DVD drive
Software Requirements
Operating System Windows '98 or Windows 2000
l Bi-directional communication with single panels and
Ordering Information networked fire systems
l Local or remote connection via modem or TCP/IP
PCG-GraphicNW Graphic Software for KSA700/FP1500 Fire Systems (multi-panel) l Large selection of user configurable icons
l Visualises device alarms and status of in- and outputs
l Event texts retrieval from the panel
l Configurator and operator contol levels
l Navigation buttons allowed
l Event logs with reporting facilities
l Basic drawing package included
l Imports bmp & drw format graphics
FIRE PANELS & REPEATERS

ANALOGUE ADDRESSABLE FIRE PANELS


FP1200/2000 SERIES
Analogue Adressable Fire Panels
Page : 125

Analogue panel, 2- 4 loop, 16 zones FP1216EN

FP1216 series
A versatile, cost effective analogue addressable fire panel, 2 to 4 loops, giving
powerfull features

Specifications

Supply voltage 230 V ac (+10/-15%)


50 Hz
220 VA
Min. supply current @ 24 V dc 0.2 A
Battery charger rating @ 27.6 V dc 1.6 A
Total supply rating @ 27.6 V dc 4A
Relay rating @ 24 V dc 2A
Weight (no batteries) 7.5 kg
Dimensions (mm H x W x D) 440 x 444 x 125

Ordering Information

FP1216EN Analogue panel, 2-4 loop, 16 zones

l One man maintenance


l Soak test
l On-line diagnostics and statistics
l Power supply for 72 hour autonomy
l Floating background for 2000 series sensors
l Coincidence within and in between zones
l Start-up default mode
l Upload/download
l I/O programming including Boolean functions
l EN 54 p2 & 4 approved
l 2 or 4 class A loops
Analogue Adressable Fire Panels
Page : 126

Analogue adressable fire panel - 2 to 4 loops. 16 zones FP2416

FP2000 Series

Specifications

Supply voltage 1 190 - 270 V ac


40- 60 Hz
160 VA max.
Supply voltage 2 21 - 27 V dc
Current consumption
Quiescent @ 24 V dc (Fully equipped500
loop)mA
Alarm current @ 24 V dc 600 mA
Available auxiliary current in alarm 3.4 A
Battery charger rating @ 27.5 V dc 3A
Total supply rating @ 27.5 V dc 4A
Relay rating @ 24 V dc 2A
Weight (no batteries) 11 kg
Dimensions (mm) (H x W x D) 609 x 441 x 109

Ordering Information

FP2416
l One man maintenance
Analogue adressable fire panel - 2 to 4 loops. 16 zones
l Graphic maintenance
l Maintenance warning
l Service reminder signal
l Soak test
l On-line diagnostics and statistics
l Floating background
l Day/night sensitivity setting
l Coincidence within and in between zones
l Automatic timed and manual on/off zones
l Start-up default mode
l Service switch
l Upload/download, remote maintenance and graphic PC
software
l I/O programming including Boolean functions
l ARCNET panel networking
l EN 54 approved; certified Bosec, VdS, NFA2P
l Networkable "black box" and "global zone" system
l Full range of repeater panels
Analogue Adressable Fire Panels
Page : 127

Analogue addressable panel - 2 to 4 loops, 16 to 32 zones FP2432

FP2000 Series

Specifications

Supply voltage 1 190 - 270 V ac


40- 60 Hz
160 VA max.
Supply voltage 2 21 - 27 V dc
Current consumption
Quiescent @ 24 V dc (Fully equipped500
loop)mA
Alarm current @ 24 V dc 600 mA
Available auxiliary current in alarm 3.4 A
Battery charger rating @ 27.5 V dc 3A
Total supply rating @ 27.5 V dc 4A
Relay rating @ 24 V dc 2A
Weight (no batteries) 11 kg
Dimensions (mm H x W x D) 609 x 441 x 109

Ordering Information

FP2432
l One man maintenance
Analogue addressable panel - 2 to 4 loops, 16 to 32 zones
l Graphic maintenance
l Maintenance warning
l Service reminder signal
l Soak test
l On-line diagnostics and statistics
l Floating background
l Day/night sensitivity setting
l Coincidence within and in between zones
l Automatic timed and manual on/off zones
l Start-up default mode
l Service switch
l Upload/download, remote maintenance and graphic PC
software
l I/O programming including Boolean functions
l ARCNET panel networking
l EN 54 approved; certified Bosec, VdS, NFA2P
l Networkable "black box" and "global zone" system
l Full range of repeater panels
Analogue Adressable Fire Panels
Page : 128

Analogue addressable fire panel - 2 to 8 loops. 16 - 64 zones FP2864

FP2000 series

Specifications

Supply voltage 1 190 - 270 V ac


40 - 60 Hz
160 VA max.
Supply voltage 2 21 - 27 V dc
Current consumption
Quiescent @ 24 V dc (Fully equipped800
loop)mA
Alarm current @ 24 V dc 1A
Available auxiliary current in alarm 3A
Battery charger rating @ 27.5 V dc 3A
Total supply rating @ 27.5 V dc 4A
Relay rating @ 24 V dc 2A
Weight (no batteries) 15 kg
Dimensions (mm) (H x W x D) 804 x 441 x 109

Ordering Information

FP2864
l One man maintenance
Analogue addressable fire panel - 2 to 8 loops. 16 - 64 zones
l Graphic maintenance
l Maintenance warning
l Service reminder signal
l Soak test
l On-line diagnostics and statistics
l Floating background
l Day/night sensitivity setting
l Coincidence within and in between zones
l Automatic timed and manual on/off zones
l Start-up default mode
l Service switch
l Upload/download, remote maintenance and graphic PC
software
l I/O programming including Boolean functions
l ARCNET panel networking
l EN 54 approved; certified Bosec, VdS, NFA2P
l Networkable "black box" and "global zone" system
l Full range of repeater panels
Analogue Adressable Fire Panels
Page : 129

Analogue addressable fire panel - 2 to 4 loops, 'black box' FB2400

FP2000 series
The FB2400 / FB2800 'black box' system allows a cost-effective network of fire panels
to be interconnected to a global repeater

Specifications

Supply voltage 1 190 - 270 V ac


40- 60 Hz
160 VA max.
Supply voltage 2 21 - 27 V dc
Current consumption
500 mA
Quiescent @ 24 V dc (Fully equipped loop)
Alarm current @ 24 V dc 600 mA
Available auxiliary current in alarm 3.4 A
Battery charger rating @ 27.5 V dc 3A
Total supply rating @ 27.5 V dc 4A
Relay rating @ 24 V dc 2A
Weight (no batteries) 11 kg
Dimensions (mm H x W x D) 609 x 441 x 109

Ordering Information
l One man maintenance
FB2400 Analogue addressable fire panel - 2 to 4 loops, 'black box' l Graphic maintenance
FB2800 Analogue addressable fire panel - 2 to 8 loops, 'black box' l Maintenance warning
l Service reminder signal
l Soak test
l On-line diagnostics and statistics
l Floating background
l Day/night sensitivity setting
l Coincidence within and in between zones
l Automatic timed and manual on/off zones
l Start-up default mode
l Service switch
l Upload/download, remote maintenance and graphic PC
software
l I/O programming including Boolean functions
l ARCNET panel networking
l EN 54 approved; certified Bosec, VdS, NFA2P
l Networkable "black box" and "global zone" system
l Full range of repeater panels
Analogue Adressable Fire Panels
Page : 130

2-loop extension board for FP1200 / FP2000 fire panels LC2002

FP1200 / FP2000 series

Specifications

Current consumption
Quiescent @ 24 V dc (Fully equipped+loop)
150 mA (252 detectors)

Ordering Information

LC2002 2-loop extension board for FP1200 / FP2000 fire panels

16-zone LED extension fire and fault LED ZE2016

FP1200 / FP2000 series


Extends the zones of the FP 2x32 and 2x64

Ordering Information

ZE2016 16-zone LED extension fire and fault LED


Analogue Adressable Fire Panels
Page : 131

LON700 driver for FP1200 / FP2000 LON2000

FP1200 / FP2000 series


A LON700 driver that connects FP1200 / FP2000 fire panels to LON700 devices

Ordering Information

LON2000 LON700 driver for FP1200 / FP2000

ARCNET RS 485 network card with single, RS 485 interface NC2011

FP1200 / FP2000 series

Ordering Information

NC2011 ARCNET RS 485 network card with single, RS 485 interface


NE2011 RS 485 network extension board
Analogue Adressable Fire Panels
Page : 132

ARCNET network card with single optical, interface board NE 2051 NC2051

FP1200 / FP2000 series

Ordering Information

NC2051 ARCNET network card with single optical, interface board NE 2051
NE2051 Fibre optic network extension board

RS 485 network extension board NE2011

FP1200 / FP2000 series


A RS485 network extension board for the NC2011 to allow dual bus and closed ring
networks

Ordering Information

NE2011 RS 485 network extension board


Analogue Adressable Fire Panels
Page : 133

Fibre optic network extension board NE2051

FP1200 / FP2000 series


An extension board for the NC2051 to allow a fibre optic ring bus

Ordering Information

NE2051 Fibre optic network extension board


Analogue Adressable Fire Panels
Page : 134

LCD repeater FRL700

FP1200 / FP2000 series


A LON 700 LCD repeater for the FP1200 / FP2000 fire panels. Up to 15 repeater
panels may be connected to the fire panel using the LON2000 interface board. The
repeater is also available as a fire brigade panel for Dutch and Scandinavian norms.

Specifications

Dimensions mm (L x W x D) 240x320x60
Weight 1.5 kg
Operating temp °C -5°C - +40
Operating voltage Vdc 15 - 30
Current consumption
max quiesent mA 100
Bus Connection
FP1200/FP2000 (with LON2000) ***
Bus Cable Cat 5
Total number of repeaters
FP1200/FP2000 15
FP700 ***

l 2 wire connection between fire panel and repeaters


Ordering Information
l Up to 1500 metre bus length
FRL700 LCD repeater l 24 Volt power supply
FBP70006 Fire brigade panel Swedish (SS3654)
FBP70005 Fire brigade panel Norwegian (SS3654)
l Cost effective repeater solutions
FBP70007 Fire brigade panel Danish (SS3654) l Easily installed, simple operation
FBP70001 Fire brigade panel (NEN2535)
LON2000 LON700 driver for FP1200 / FP2000 l 4 x 20 charater LCD display, common LED's, push button
control
l LON700
Analogue Adressable Fire Panels
Page : 135

LCD repeater FR1200

FP1200 / FP2000 series


A powerful LCD repeater that can be used as a local or global repeater on a FP1200 /
FP2000 network.

Specifications

Supply voltage 230 V ac (+10/-15%)


50 Hz
50 VA
Min. supply current @ 24 V dc 0.15 A
Battery charger rating @ 27.6 V dc 0.3 A
Total supply rating @ 27.6 V dc 1A
Relay rating @ 24 V dc 2A
Weight (no batteries) 7.5 kg
Dimensions (mm H x W x D) 365 x 444 x 111

Ordering Information

FR1200 LCD repeater

l 8 x 40 character graphic display


l Arcnet network connection to FP1200/FP2000 series
firepanels
l Global repeater function
l Comprehensive control and display functions
Analogue Adressable Fire Panels
Page : 136

LCD repeater with emulator functions FR2000

FR1200 / FP2000 series


A powerful LCD repeater that can be used as a local or global repeater on a FP1200 /
FP2000 fire panel network. Fire panels can be emulated from the FR2000

Specifications

Supply voltage 230 V ac (+10/-15%)


50 Hz
50 VA
Min. supply current @ 24 V dc 0.15 A
Battery charger rating @ 27.6 V dc 0.3 A
Total supply rating @ 27.6 V dc 1A
Relay rating @ 24 V dc 2A
Weight (no batteries) 7.5 kg
Dimensions (mm H x W x D) 365 x 444 x 111

Ordering Information

FR2000 LCD repeater with emulator functions

l 8 x 40 character graphic display


l Arcnet network connection to FP1200/FP2000 series
firepanels
l Global repeater function
l Comprehensive control and display functions
l Fire panel emulation function
l Dual RS232 ports
Analogue Adressable Fire Panels
Page : 137

Repeater/emulator 32 zones/panels FR2032

FP1200 / FP2000 series


A powerful repeater / emulator with 16 to 32 displayed fire and fault zones. The
repeater is connected on the arcnet network and can operate in a local or global
repeater mode.

Ordering Information

FR2032 Repeater/emulator 32 zones/panels

l 8 x 40 character graphic display


l Arcnet network connection to FP1200/FP2000 series
firepanels
l Global repeater function
l Comprehensive control and display functions
l 16 zones fire and fault expandable to 32 zones
l 24 Volt operation
l Emulation functions
Analogue Adressable Fire Panels
Page : 138

Repeater/emulator 64 zones FR2064

FP1200 / FP2000 series


A powerful repeater / emulator with 16 to 64 displayed fire and fault zones. The
repeater is connected on the arcnet network, and can operate in local or global
repeater mode.

Ordering Information

FR2064 Repeater/emulator 64 zones

l 8 x 40 character graphic display


l Arcnet network connection to FP1200/FP2000 series
firepanels
l Global repeater function
l Comprehensive control and display functions
l Emulation function
l 16 to 64 zones fire and fault displayed
l 24 volt operation
Analogue Adressable Fire Panels
Page : 139

ARCNET universal node UN2011

FP1200 / FP2000 series


The unversal node allows the fire panel arcnet network to extend to computer
software applications either locally, or remotely using the MOD2000.

Ordering Information

UN2011 ARCNET universal node

l FP1200 / FP2000 arcnet to RS232 interface


l Allows computer applications to operate on the network
l 230V operation
l Can be extended with MOD2000 for remote operation
l 'Black box' operation

Modem kit MOD2000

FP1200 / FP2000 series


An internal modem for the FP1200 / FP2000 fire panels or a UN2011 universal node.
The modem has the autonomy of the fire panel power supply, and has extended
telephone line protectection. The MOD2000 can also be used with a computer.

Ordering Information

MOD2000 Modem kit

l MOD2000
l For fire panel and universal node operation
l Internal installation
l Autonomous power supply
Analogue Adressable Fire Panels
Page : 140

Programming and configuration software PCC2000

FP1200 / FP2000 series

Specifications

Processor 486 66 MHz


RAM 12 Mb
Display adapter VGA
Hard disk space 20 MB
Pointing device MS Mouse, etc.
Graphical environment Windows 95
Communications ports 1 x RS-232
1 parallel

Ordering Information

PCC2000 Programming and configuration software

l Provide communication with single fire panels and


networked fire systems, both locally or remote via modem
l Windows 95 and NT compatible
l For use with FP2000, FP1200
l Menu driven
l Full or partial up- and download
l Dynamic Link Library (DLL) for third party integration
Analogue Adressable Fire Panels
Page : 141

Maintenance and support software with copy protection key PCM2000

FP1200 / FP2000 series

Specifications

Processor Pentium 133Mhz (or better)


RAM 32 Mb (or more)
Display Adapter VGA
Hard Disk Space 20 MB
Pointing Device Bus or P/S2 Mouse
Graphical Environment Windows 98, NT or 2000
Communications ports Depending on Drivers Printer port (for key)
1 Parallel

Ordering Information

PCM2000 Maintenance and support software with copy protection key

l Provide communication with single fire panels and


networked fire systems, both locally or remote via modem
l Windows 95, 98 and NT compatible
l For use with FP2000, FP1200
l Full panel emulation
l Data retrieval
l Central station
l History log
l Address book
l Dynamic Link Library (DLL) for third party integration
Analogue Adressable Fire Panels
Page : 142

Graphics package with copy protection key PCG-S

PCG Series
A total of 4 packages allow the graphic package to grow with the installation. The
basic version PCG-S operates with a single panel, while the PCG-N supports a
network. The PCG-CS allows for TCP/IP client server applications. Upgrades do not
require rework on the existing database, drawings, etc.

Specifications

Item Recommended
Processor Pentium II 266 MHz (or better)
RAM 64 Mb (or more)
Display adapter SVGA or better
Hard disk space 200 MB
Pointing device MS Mouse, Bus or P/S2
Graphical environment Windows NT
Communication ports 1 x RS-232 - Depending on drivers
1 x Parallel - Printer port (for key)

Ordering Information

PCG-S Graphics package with copy protection key l Provide bi-directional communication with single fire
PCG-N Graphics package network application with copy protection key panels and networked fire systems, both locally and
PCG-CS Graphics package for client-server application with copy protection ke remote via modem
PCG-C Extra client for PCG-CS
l Windows 2000 and NT compatible
l For use with FP2000, FP1200, FP1100 and FP700
l Constructed around Sybase SQL Anywhere
l Large selection of icons
l Visualises inputs & outputs
l Information page per point
l Get texts from panel
l Several operator levels and passwords
l Operator configurable
l Multiple navigation buttons
l Event logs
l Basic drawing package included
l Imports .bmp & .wmf drawings from virtually any package
l Hardware key protected
Content

Conventional Fire Detectors


DI322I Ionisation detector, conventional Page : 5
DP331I Optical detector, conventional, with field exchangeable optical block Page : 6
DT313I Temperature detector (fixed and rate-of-rise), conventional Page : 7
KCT731 KL731/DP331I Calibration Tool Page : 8
DB304 Universal fire detector base (Aritech 300 and 1500 series) Page : 9
KZ705 Universal fire detector base with earth connection Page : 9
KZ705D Conventional fire detector base with diode Page : 10
EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels Page : 11
KZ705R Conventional fire detector base with relay Page : 11
S300 Surface mount supplement for KL300 detectors Page : 12
S700 Surface mount accessory for KZ700/DB304 and KZ700 series bases Page : 12
DP721I Photoelectric smoke detector with remote alarm LED output Page : 15
DP721T Photoelectric smoke and heat detector head with remote alarmLED output Page : 15
DT713-5 57º C fixed and rate-of-rise heat detector Page : 16
DT713-7 70º C fixed and R.O.R. heat detector Page : 17
DB702 10 cm diameter base - 6 terminals Page : 18
DI650 Ionisation smoke detector Page : 21
DP652 Optical smoke detector Page : 22
DT654 Heat detector, R.O.R., 57º C A1R Page : 23
DB860 Standard Base Page : 24
DB861 Backplate for Ingress Protection 860-950 Page : 24
DB806 Conduit box for 860 / 950 series bases Page : 25
DB650 650 series relay base Page : 25

Analogue Adressable Fire Detectors


DI1552 Ionisation Sensor Page : 29
DP1561 Optical Sensor with field exchangeable optical block Page : 30
DP1551T Dual Sensor (Optical/Heat) Page : 31
DT1553 Heat Sensor Page : 32
PG700 Fire sensor programmer Page : 33
KZ705I Analogue fire detector base with isolator Page : 34
KZ705AS Analogue fire detector base with sounder Page : 35
KZ705IAS Analogue fire detector base with isolator and sounder Page : 36
KAL410 Conventional Zone Monitor Unit - 1 Zone Page : 37
KAL414/4 Conventional Zone Monitor Unit - 4 Zones Page : 38
KAL426 Extinguishing Control Module Page : 39
KAL430 Relay Module - 1 Relay Page : 40
KAL434/4 Relay Module - 4 Relays Page : 41
KAL440 Supervised Relay Module Page : 42
KAL450 Addressable Manual Call Point Page : 43
KAL460 Digital Input Module Page : 44
KAL470 Isolator Module Page : 45
KAL490 Retention Module - 1 Input / 1 Output Page : 46
DP2051 Optical Sensor Page : 49
DP2061 Optical Sensor with remote LED output Page : 50
DP2071 Optical Sensor with 7-segment display and remote LED output Page : 51
DT2053 Heat Sensor Page : 52
DT2063 Heat Sensor with Remote LED Output Page : 52
DT2073 Heat Sensor with 7-segment Display and Remote LED Output Page : 53
DB2001 Standard Base 10 cm, 2 Terminals Page : 54
DB2002 Standard Base 4 Terminals Page : 54
DB2016 Isolating base Page : 55
IU2016 Loop Isolator Page : 55
DB2003 Base for the IU2016 isolator Page : 56
DM2000 Manual call point, flying leads Page : 57
DM2000E Manual call point - Red IP67 waterproof, including backbox Page : 58
IO2014 Input Output unit Page : 59
IU2050 Single Input Module Page : 60
IU2055 Conventional Zone Monitor Page : 61
GBX2000 Galvanic barrier Page : 61
IU2080 Indicating Circuit Controller Page : 62
FD2705R 2000 series addressable reflective beam smoke detector; 5 - 50m Page : 63
AS2015 2000 series loop powered sounder Page : 64
DI950 Analogue addressable ionisation sensor Page : 67
DP951 Optical sensor Page : 67
DT952 Analogue addressable temperature sensor Page : 68
DM960 950 series analogue addressable manual callpoint Page : 68
DI970 Intrinsic safe analogue addressable ionisation detector Page : 69
DP971 Intrinsic safe optical detector Page : 69
DT972 Intrinsic safe heat detector Page : 70
DM970 Intrinsic safe manual call point Page : 70
PT971 Intrinsic safe protocol translator Page : 71
GBX70 Galvanic barrier (single channel) Page : 71
II950 950 series mini switch monitor unit Page : 72
II952 950 series switch monitor unit - surface mount Page : 72
II955 950 series zone monitor unit - surface mount Page : 73
IO950 950 series single channel IO - surface mount Page : 73
IO955 950 series output unit - surface mount Page : 74
IO956 950 series sounder circuit controller - surface mount Page : 74
IU950 950 series loop isolator Page : 75
AS950 950 series loop powered sounder Page : 76
AS955 950 series high output loop powered sounder Page : 77
FD950 950 series loop-powered beam detector Page : 78
DB950 950 series standard base Page : 79
DB951 Base for IU 950 Page : 79
DB961 Isolating base (20 devices) Page : 80
DB970 Detector base for 970 series intrinsic safe sensors Page : 80
IU980 Coded cards, addresses 1 - 18 Page : 81

Conventional Fire Panels


FP202 Conventional fire alarm panel with 2 zones Page : 85
FP204 Conventional fire alarm panel with 4 zones Page : 86
FP206 Conventional fire alarm panel with 6 zones Page : 87
FP402 Conventional fire alarm panel with 2 zones Page : 91
FP408 Conventional fire alarm panel with 8 zones Page : 92
FP412 Conventional fire alarm panel with 12 zones Page : 93
FP416 Conventional fire alarm panel with 16 zones Page : 94
RB404 Relay module, 4 potential free relays for NK700/Fx400 fire panels Page : 95
SB404 Relay module, 4 supervised relays for NK700/Fx400 fire panels Page : 96
FEC403 Conventional fire detection and extinguishing control panel with 3 zones including 1 extinguishing zone Page : 97
FEC406 Conventional extinguishing control panel with 6 zones Page : 98
FP604 4-zone Conventional Fire Panel Page : 101
ZI602 Two zone extension board, including 6 outputs Page : 102
RC606 Set of 6 bi-stable magnetic latch relays Page : 102
FP708 Fire panel equipped with 8 zones Page : 105
FR708 Repeater 8 zones, 24 VDC input Page : 106
ZE708 8 zone indicator LED extension board fire/fault Page : 107
ZI708 8 zone input extension board Page : 107
FM740 Synoptic driver for 80 LEDs and common signals Page : 108
OCB724 LON700 output board with 24 open collector outputs Page : 108
RB708 LON700 output board with 8 relays Page : 109
SOB708 LON700 output board with 8 supervised outputs Page : 109
FB708 FP700 black box with 7 slot card cage Page : 110
NC700 LON 700 interface board Page : 111
PS700 Plug-in power supply 3.5 A Page : 111

Analogue Adressable Fire Panels


FP1501 Analogue addressable fire detection panel - 1 loop Page : 115
FP1502 Analogue addressable fire detection panel - 2 loops Page : 116
NC785 RS485 Expansion kit for KSA701/FP1500 fire panels Page : 117
FR1500 Analogue addressable LCD Repeater/Emulator* Page : 118
MODGSM GSM Modem for Kilsen Fire Panels Page : 119
PCG-Graphic102 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops) Page : 120
PCG-Graphic105 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-5 loops) Page : 121
PCG-GraphicNW Graphic Software for KSA700/FP1500 Fire Systems (multi-panel) Page : 122
FP1216EN Analogue panel, 2- 4 loop, 16 zones Page : 125
FP2416 Analogue adressable fire panel - 2 to 4 loops. 16 zones Page : 126
FP2432 Analogue addressable panel - 2 to 4 loops, 16 to 32 zones Page : 127
FP2864 Analogue addressable fire panel - 2 to 8 loops. 16 - 64 zones Page : 128
FB2400 Analogue addressable fire panel - 2 to 4 loops, 'black box' Page : 129
LC2002 2-loop extension board for FP1200 / FP2000 fire panels Page : 130
ZE2016 16-zone LED extension fire and fault LED Page : 130
LON2000 LON700 driver for FP1200 / FP2000 Page : 131
NC2011 ARCNET RS 485 network card with single, RS 485 interface Page : 131
NC2051 ARCNET network card with single optical, interface board NE 2051 Page : 132
NE2011 RS 485 network extension board Page : 132
NE2051 Fibre optic network extension board Page : 133
FRL700 LCD repeater Page : 134
FR1200 LCD repeater Page : 135
FR2000 LCD repeater with emulator functions Page : 136
FR2032 Repeater/emulator 32 zones/panels Page : 137
FR2064 Repeater/emulator 64 zones Page : 138
UN2011 ARCNET universal node Page : 139
MOD2000 Modem kit Page : 139
PCC2000 Programming and configuration software Page : 140
PCM2000 Maintenance and support software with copy protection key Page : 141
PCG-S Graphics package with copy protection key Page : 142