GE

Digital Energy

Multilin™ 8 Series
845 Transformer Protection System
8 Series Overview
Platform Highlights

Quality / Reliability Performance Communications Diagnostics


• No Electrolytic Capacitors • 1/8 cycle protection pass • IEC61850 Environment Diagnostics
• Extruded Aluminum Chassis • 1/16 cycle digital input pass • IEC62439 / PRP • Temperature Monitoring
• Field Swappable PSU • 128 samples / cycle oscillography • DNP 3.0 • Humidity Monitoring
• IPC Class 3 Manufacturing • 64 samples / cycle protection • MODBUS RTU, TCP/IP • Surge Monitoring
• Component Traceability • 46 x CT rating • IEC60870-5-103 & 104 • Vibration Monitoring
• ALT & HALT Testing • 1024 lines of Flexlogic • 2 – Independent IP Addresses Asset Diagnostics
• Automated Final Testing • 1024 SOE / T.S. 1ms • 2 - Fiber Ethernet ports • Broken Rotor Bar
• 100% Complete Burn-in • 32 Digital Inputs • 1 - Copper Ethernet port • Stator Turn Fault
• 16 Digital Inputs • 1 – 485 port • Break wear & Travel Time
• USB Front Port • Hot Spot Detection
• Optional Wi-Fi for configuration • Loss of Life Detection
• IEEE1588/ IRIG-B / SNTP
845 Product Overview
845 Introduction

Protection Relay Asset Mgmt. System

Reliability… Designed for Extended Life


Protection ….High Speed differential protection based on proven algorithms
Enhanced Situational Awareness….Integrated DGA & Transformer analytics
Advanced Security & Communications…Enabling NERC/CIP compliance
Ease-of-use & Retrofit ability….Intuitive set-up & ease of retrofits
845 Introduction

Protection Relay Asset Mgmt. System

Reliability… Designed for Extended Life


Protection ….High Speed differential protection based on proven algorithms
Enhanced Situational Awareness….Integrated DGA & Transformer analytics
Advanced Security & Communications…Enabling NERC/CIP compliance
Ease-of-use & Retrofit ability….Intuitive set-up & ease of retrofits
Reliability – Product Architecture
No Electrolytic Caps Self-diagnostics Conformal Coating

CPU 0 1 0 0 1 1 0 1 0 IO

Extrusion Environmental Monitor IPC Class III

Design, Validation and Process Control for Improved Reliability


Page 7
GE Digital Energy
Rugged Mechanical Design

Ease of insertion, Thermal management & grounding requirements


Page 8
GE Digital Energy
www.GEDigitalEnergy.com
845 Introduction

Protection Relay Asset Mgmt. System

Reliability… Designed for Extended Life


Protection ….High Speed differential protection based on proven algorithms
Enhanced Situational Awareness….Integrated DGA & Transformer analytics
Advanced Security & Communications…Enabling NERC/CIP compliance
Ease-of-use & Retrofit ability….Intuitive set-up & ease of retrofits
Typical Transformer Configurations
Configuration 1 Configuration 2 Configuration 3 Configuration 4
2 Winding no Voltage 2 winding with 3 Winding with > 3 Terminals
8 CT, 5 DO+7 DI Voltage Voltage >12 CT + 4 VT, 5 DO+7 DI
Transformer Differential, 8 CT + 4 VT, 5 DO+7 DI 12 CT + 4 VT, 5 DO+7 DI Transformer Differential,
no Voltage protection Transformer Differential, Transformer Differential, Voltage protection
Voltage protection Voltage protection
90% Applications 10% Applications

845ENNM5G5HNNANNGSNBBSENNBN 845EP5H5G5HNNANNGSSBBSENNBN 845EP5R5G5HNNANNGSSBBSENNBN


345-E-P5-G5-H-E-E-N-N-1E-D-H 745-W2-P5-G5-HI-R-T-H 745-W3-P5-G5-HI-R-T-H

Page 10
GE Digital Energy
GE Private & Confidential
845 Transformer Protection Elements

Functions ANSI
Transformer Differential 87T
Restricted Ground Fault 87G
Over-excitation (V/Hz 24
IOC/TOC 50/51 G/N/P
Negative Sequence 46
Undervoltage 27P
Overvoltage 59N/P/X/2
Directional 67 N/P
Thermal Overload 49
Directional Power 32
Breaker Failure 51BF
VT Fuse Failure VTFF
Under/Overfrequency 81U/O
Synchrocheck 25
FlexElementsTM
Arc Flash Protection AFD*

Enhanced Protection Functions in 845 Page 11


GE Digital Energy
GE Private & Confidential
Proven High Speed Differential Algorithm
• Dual slope differential  Proven spline characteristics
• First in the Industry
o Excellent CT Saturation + Directional Supervision for heavy through fault security
• 2nd harmonic inhibit include Per Phase, Average, 2-out-of-3, 1-out-of-3 allowing best selection for
specific application
• 5th harmonic inhibit for over fluxing conditions
• Per phase restraint, differential and harmonic information available for post fault analysis
• Proven for decades in UR T60/T35, B30/B90, 345

Differential Operating Time (msec)


GE 845 Relay 1 Relay 2 Relay 3
Min 25.8 43.6 NA NA
Max 31.3 47.7 NA NA
Typical 28.5 45.3 33 35

87 T Operating Time Faster by 16 msec Page 12


GE Digital Energy
GE Private & Confidential
Restricted Ground/Earth Fault Protection

• Per winding (RGF/REF) element (max 3)


• Low impedance biased differential with restraints and ground supervision
• RGF/REF Protection Operating time of ~25msec

REF Operating Time Faster by 50 msec Page 13


GE Digital Energy
GE Private & Confidential
Control Features

• SLDs for various configurations


• 3 breaker control & monitoring
• 3 breaker failure elements
• Tap position detection
• BCD
• Potentiometer
• dcmA
• 61850 logical nodes
• 1024 lines of FlexLogicTM
• Synchrocheck

Ease of Use & Configuration Flexibility Page 14


GE Digital Energy
GE Private & Confidential
845 Introduction

Protection Relay Asset Mgmt. System

Reliability… Designed for Extended Life


Protection ….High Speed differential protection based on proven algorithms
Enhanced Situational Awareness….Integrated DGA & Transformer analytics
Advanced Security & Communications…Enabling NERC/CIP compliance
Ease-of-use & Retrofit ability….Intuitive set-up & ease of retrofits
845 Transformer Monitoring & Diagnostics
Basic Monitoring
Dry type Distribution Transformer (<2 MVA)
• Breaker Monitoring
• Harmonics & THD
• RTD
Standard Monitoring
Low End Oil Filled Transformer (<10MVA)
• Basic Monitoring +
• Hottest spot
• Aging factor
• Loss of life
Advanced Monitoring
Mid Range & High End Power Transformers (>10 MVA)
• Standard Monitoring +
• Learned Data, Historic max data
• Energization Record
• Transformer Health Report
• Transformer Models
• Patented* DGA Analysis (Requires Kelman DGA device)
Page 16
GE Digital Energy
GE Private & Confidential
845 Advanced Transformer
Monitoring & Diagnostics
Transformer M&D Today…

Transformer Electrical Characteristics

• Continuous monitoring of electrical parameters


• Internal or external fault detection and electrical data collection
• Enervista for pre and post fault analysis of electrical data - transient
record and fault report

Transformer Dissolved gas characteristics

• Continuous monitoring of single or multiple gas parameters


• Transformer incipient fault detection using DGA data and models
• Perception – Transformer condition based monitoring and fleet
management

No Convergence of Physics & Chemistry


Page 18
GE Digital Energy
GE Private & Confidential
Simple Analogy

Stressed Blood ECG 2D-Echo TMT -


Heart Test Record Model Stress Report

Single Health Checkup Report

Page 19
GE Digital Energy
GE Private & Confidential
Innovative integrated solution…

Stressed Heart Blood Test ECG Record 2D-Echo Model TMT - Stress Report

Asset DGA V&I DGA Models Reports

Page 20
GE Digital Energy
GE Private & Confidential
Innovative integrated solution…

Electrical Models DGA Models Energization Record Health Report

Page 21
GE Digital Energy
GE Private & Confidential
Electrical Models

What is it ? Customer value


• 40+ Critical electrical parameters • Simplified data analytics from
computation/monitoring ready to read monitoring data
• 1 year daily max operational data log • Powerful data correlation e.g.
& trending load vs. temperature
Page 22
GE Digital Energy
GE Private & Confidential
DGA Models

Duval triangle Gas ratios Key gas

What is it ? Customer value


• Supported DGA devices: Hydran / • Evolving incipient fault conditions
Transfix / DGA 500 / Minitrans detection & monitoring
• Last 100 DGA history values in 845 • Eliminates offline DGA assessment
• DGA models as per IEC and IEEE and need for DGA analysis consulting
standards • Simple and direct analytics

Page 23
GE Digital Energy
GE Private & Confidential
Data Correlation Models

What is it ? Customer value


• Customized correlation between • Built-in correlation model to monitor
Electrical and DGA data – overload, electrical and DGA data together e.g.
over heat, corona, PD etc. load vs. H2, WHST/Aging vs. CO/CO2
• 1 year daily max operational data • Take preventive actions upon detection
available for correlation of incipient fault conditions
• Correlating electrical and DGA historical
data during Xfmr fault analysis Page 24
GE Digital Energy
GE Private & Confidential
Transformer Energization Record

What is it ? Customer value


• 6 last xmfr energization • Accurate capture of energization
characteristics captured event
• Current and voltage samples for 10 • Baseline energization behavior in a
initial cycles at 64 s/c transformer and compare through
• Computed inrush parameters: peak the operational life of transformer
inrush current, max voltage dip, • Profile stress induced in transformer
Volts/Hertz, 2nd and 5th harmonics during energization
• Operational data post energization • Simplified commissioning tool
Page 25
Measured & Computed parameters GE Digital Energy
GE Private & Confidential
Integrated Transformer Fault Report

What is it ?
Pre-fault • 845 detects internal or external fault
Principal gas:
CO
• 845 triggers post fault DGA measurement
Over heated • 845 combines pre/post fault electrical and
paper DGA data for fault analysis
• Comtrade, fault report and DGA models
Customer value
• Comprehensive view of transformer condition
post external / internal fault
Post-fault
Principal gas: • Avoid expensive offline DGA or DGA analysis
C2H2 consulting after fault
Arcing fault
• Detect incipient fault evolution post external
faults and take preventive action Page 26
GE Digital Energy
GE Private & Confidential
Transformer Health Report

What is it ?
• Compilation of transformer operational and
fault data in one place
• Name plate data, trend in energization
behaviors, 1 year learned data, historic
maximums, DGA models, alarm/trip history
Customer value
• Eliminate multi layered monitoring and
recording devices
• One stop operational, monitoring and fault
analytics Page 27
• Simple and intuitive analytics GE Digital Energy
GE Private & Confidential
What Sets the 845 Apart?

Protection Relay Asset Mgmt. System

Reliability… Designed for Extended Life


Protection ….High Speed differential protection based on proven algorithms
Enhanced Situational Awareness….Integrated DGA & Transformer analytics
Advanced Security & Communications…Enabling NERC/CIP compliance
Ease-of-use & Retrofit ability….Intuitive set-up & ease of retrofits
Advanced Cyber Security

Ready for Achilles level 1 certification*

NERC/CIP Compliance Enabler


Page 29
GE Digital Energy
GE Private & Confidential
COMMs – Flexible & Interoperable Solution

• Redundant networks…PRP IEC62439


• Time Sync…IRIGB, SNTP, 1588
• 61850 Ed2
• Wifi with iPad App
• Multi Protocols support

Industry first XML Based Config File Enabling


Centralized Config Management
Page 30
GE Digital Energy
845 Introduction

Protection Relay Asset Mgmt. System

Reliability… Designed for Extended Life


Protection ….Differential protection based on proven algorithms
Enhanced Situational Awareness….integrated DGA & transformer analytics
Advanced Security & Communications…Enabling NERC/CIP compliance
Ease-of-use & Retrofit ability….Intuitive set-up & ease of retrofits

Page 31
GE Digital Energy
GE Private & Confidential
Trip Matrix for 3 winding applications

Page 32
GE Digital Energy
GE Private & Confidential
Custom logic application

Drag & Drop Logic Designer Online testing tool Logic Monitor

Simplified Engineering & Commissioning


Page 33
GE Digital Energy
GE Private & Confidential
SR to 8 Series upgrade kit

• Two options with the same kit


o Remove SR terminal block with wires and snap on using retrofit 8 Series chassis
o Unscrew wires of SR and terminate back on retrofit 8 series chassis

• Target date: Sep 2015


Migrate SR to 8 Series more Easily Page 34
GE Digital Energy