I. WALL TYPE Curtain Wall • Fully Unitized System with Thermal Break • Laterally supported by Steel Framing at every 4500mm (Steel Framing-By Others) II. STRUCTURAL DESIGN PARAMETERS Glass Design • As per ASTM E-1300-03 Aluminum Design • As per Aluminum Design Manual 2005 Wind Velocity • As per NSCP 2015 - 250 kph Exposure Category • As per NSCP 2015 - Exposure B Design Wind Load As per NSCP 2015 : • At Building Apex (Elev. 301m) = +6.93 kPa / -11.23 kPa • At Observatory Level (Elev. 189m) = +6.06 kPa / -9.83 kPa Building Movement Vertical (Up/Down) • 16mm (subject to verification of Project Structural Engineer) Lateral (In/Out) • 10mm (subject to verification of Project Structural Engineer) Horizontal (Left/Right) • 10mm (subject to verification of Project Structural Engineer) Mullion Deflection Limitation For mullion unsupported height (L) of 4100mm and up : • (L/240) + 6.35 mm Transom Deflection Limitation Due to Wind Load • 10mm Due to Dead Load • 3mm Center of Glass Deflection Limitation At Full Wind Load • 35mm At Half Wind Load • b/60 or 20mm (b being the shorter dimension in a glass panel) III. MATERIAL SPECIFICATIONS Glass Thickness and Type • 43.04mm thk Laminated-IGU: 6mm Grey Heat Strengthened+1.52mm Clear PVB+8mm Clear Clear Greyish Low-E #4 Heat Strengthened + 12mm Air Space + 6mm Clear Heat Strengthened +1.52mm Clear PVB + 8mm Clear Heat Strengthened U-Value • 1.55 W/m2.k Shading Coefficient • 0.26 Aluminum Frame Alloy and Temper • 6063-T5/T6 for Main Frame; 6061-T6 for Brackets Finish • Super Durable Powder Coated exposed to Indoor View PVDF - exposed to Outdoor View Aluminum Fin Alloy and Temper • 6063-T5/T6 Finish • PVDF Aluminum Cladding Thickness and Type • 3mm thk Solid Aluminum Sheet Alloy and Temper • 3003-H14 Finish • PVDF Backpan • Powder Coated 2mm thk Aluminum Sheet Insulation • Thermal Insulation - 50mm thk , 100kg/m3 • Firesafing Insulation - 100mm thk, 60 kg/m3 Screws • S/S 304 and S/S 316 Anchor Bolt • Zinc-plated galvanized Steel IV. TESTING Performance Mock-Up Test • Included. At Local Testing Facility • Mock-Up Panel: 3 bays and 2 floors ASTM E-1105, Field Water Leak Test • Included. 3 Specimens only Visual Mock-Up • Included. Submitted by: