Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
P
art 1 (1) of this three-part series reviewed such basics in the piping system, or increase the efficiency by operating
as derivation of the system curve from plant data, the closer to the pump’s best efficiency point (BEP). The two
construction of composite performance curves for most common methods of flowrate control are throttling
pump networks, and how to operate and control pumps in (Figure 1) and recirculation (Figure 2). This control comes at
parallel to avoid surging and cavitation. This second article a cost, however. With throttling, the cost is a higher pressure
discusses how to use variable-frequency drives (VFDs), a drop, while for recirculation, it is a higher flowrate; both of
subset of variable-speed drives (VSDs), and other energy- these require extra power, which ends up heating the fluid.
efficiency measures such as load management (2) to reduce
pump operating costs. It also presents a new way to account Improving energy efficiency
for variation in pump efficiency with changing speed when On average, approximately 40% of the energy supplied
the static head is significant, and uses a natural gas liquid to centrifugal pumps in the CPI is wasted as unrecoverable
(NGL) pipeline example to explain how the concept works. low-grade heat (Table 2). It is significant that only 6% of
Energy requirements (usually electric power) account for energy losses are caused by operational issues, while 34%
nearly 90% of the cost of operating pumps in the chemical are built in at the design stage — that is, they are attribut-
process industries (CPI). Assuming 8,400 hr/yr of continu- able to decisions made during design and the increasingly
ous operation and 72% pump efficiency, the 15-yr cost of common practice of fast-tracking this critical step. When
operating a typical CPI pump would be as shown in Table 1. inadequate time is budgeted for proper engineering analysis,
Increasing energy efficiency clearly offers the greatest design engineers are forced to compensate by oversizing
potential to significantly reduce overall operating costs and pumps, which ensures inefficient operation and can be very
improve profits. Brake horsepower (BHP), the actual horse- costly to undo after production begins.
power delivered to the pump shaft, is: Fortunately, roughly half of the design-related losses
32 www.aiche.org/cep February 2018 CEP Copyright © 2018 American Institute of Chemical Engineers (AIChE)
Net Flow
to Process Table 2. These five causes
Minimum Flow Bypass Line account for 40% of wasted energy in pumping.
1. Low efficiency due to wrong pump choice 4%
Heat
Exchange 2. Poor installation or maintenance 3%
Storage
FC FC FT 3. Low pump efficiency due to wear 3%
Tank
4. Poor system design (piping, valves, etc.) 10%
FT 5. Poor system control strategy 20%
2,000 40%
Pump Curve
1,600 System w/o CV Table 3. Pumps can be powered by various types of drivers.
Operating Point Driver Type Energy Source
1,200
Head, ft liquid
Copyright © 2018 American Institute of Chemical Engineers (AIChE) CEP February 2018 www.aiche.org/cep 33
Fluids and Solids Handling
FC t Figure 3. Until recently, VFDs were quite expensive, but over the
Variable-frequency
drives (VFDs) must
past 10–15 years, advances in solid-state electronics have
be maintained care- enabled sharp price reductions, especially in the smaller
fully to protect their sizes. The combination of pump and VFD may cost more
sensitive electronic initially than the pump-plus-CV option, but it has lower
components. Outdoor
Rectifier
DC Link
Inverter
34 www.aiche.org/cep February 2018 CEP Copyright © 2018 American Institute of Chemical Engineers (AIChE)
1,800
Table 6. Use the affinity laws to estimate
pump curves for different impeller diameters. 1,600 12-in. dia.
1,400 11-in. dia.
D = 12 in. D = 11 in. D = 10.5 in. 10.5-in. dia.
Head, ft liquid
1,200
Flow, Head, Flow, Head, Flow, Head, 1,000
gpm ft gpm ft gpm ft 800
0 1,500 0 1,260 0 965 600
200 1,496 183 1,257 160 963 400
200
500 1,491 458 1,253 401 959
0
1,000 1,470 917 1,235 802 946 0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000
Flow, gpm
1,500 1,380 1,375 1,160 1,203 888
p Figure 4. The affinity laws allow engineers to quantify possible energy
2,000 1,240 1,833 1,042 1,604 798
efficiency improvements that would be achieved by trimming impellers.
2,500 1,050 2,292 882 2,005 676
3,000 810 2,750 681 2,406 521 2,000 100
1,800 ηB ηA 90
3,500 520 3,208 437 2,807 335
1,600 80
4,000 180 3,667 151 3,208 116 1,400 C 70
Efficiency, %
Head, ft liquid A
1,200 60
especially if the manufacturer has changed the model design 1,000 50
or your original contact at the vendor has left the company. 800 40
B
The use of VFDs enables process engineers to improve 600 30
pump energy efficiency and to achieve a control response 400 20
superior to that provided by other means of flow control. 200 10
that they are only approximations based on the assumption Flow, gpm
of constant pump hydraulic efficiency as speed is reduced,
Pump Curve, 3,600 rpm Pump Curve w/ VFD
which is true only if the static head of the system is negli- System w/o CV Full-Speed Efficiency
gible compared to dynamic head. That is often not the case. Iso-Efficiency Line
When the static head is significant, say >10% of the total,
an efficiency correction must be applied. Over some ranges p Figure 5. The optimum efficiency at reduced speed can be determined
graphically. The first step is determining where the full-speed pump
of flow, the reduced-speed efficiency, η2, will be higher than characteristic curve and the system curve intersect (Point A).
the full-speed efficiency, η1, while over other ranges it may be
lower, depending on whether the full-speed efficiency at the pump curve would intersect Point B at a speed of 2,785 rpm
design condition is to the left or the right of the pump’s BEP. (which is most easily determined graphically, by visual
Moreover, when speed is reduced below 50% of the inspection, using trial-and-error iteration). The challenge
full motor speed, the efficiency at the lower speed must be now is to find the pump efficiency at Point B.
further reduced: According to the affinity laws, the iso-efficiency line
passes through the origin and is a parabola with an exponent
of 2. Draw this line passing through Point B and find its
intersection with the full-speed pump characteristic curve,
where the subscript 1 denotes design (full-speed) conditions. Point C. If the pump curve can be adequately modeled as
The correct method for estimating pump efficiency at a quadratic equation (using parameters a, b, and c in Eq. 3
reduced speed is as follows. Consider the performance and obtained from the vendor’s test data by regression analysis),
system curves shown in Figure 5. Point A is the intersection Point C can be derived algebraically by simultaneously
of the full-speed (3,600 rpm) pump characteristic curve and solving Eq. 3 for the full-speed pump curve and Eq. 4 for the
the system curve when the CV is in the fully open position, iso-efficiency line:
flow is 1,400 gpm, head is 1,383 ft, and efficiency is 82.6%.
Now, let’s assume the actual desired flow is 980 gpm
(Point B), and the required system head is only 870 ft. The
head delivered by a fixed-speed pump would be 1,590 ft
and the CV loss would be 1,590 – 870 = 720 ft. If the pump
were equipped with a VFD, however, the reduced-speed Subtract one from the other to eliminate the system head,
Copyright © 2018 American Institute of Chemical Engineers (AIChE) CEP February 2018 www.aiche.org/cep 35
Fluids and Solids Handling
H, and obtain a quadratic equation in Q that can be solved using the method described here. Table 7 summarizes the
algebraically for the flow QC at Point C, from which the effi- calculation results for this example.
ciency ηC at Point C (which is the same as ηB) can be readily Note that the coordinates of Point B are (980, 870) on
calculated. the system curve and (975, 875) on the reduced-speed pump
For the data depicted in Figure 5, QC = 1,269 gpm, curve. Although these are not exact matches, they are close
HC = 1,458 ft, and ηC = 82.3% enough (<1% error) for engineering and decision-making
In this example, the pump hydraulic efficiency at purposes — and far more accurate than the raw unrecon-
reduced speed, ηB, is only slightly lower than the full-speed ciled plant data that most companies use to monitor pump
efficiency, ηA, but is significantly higher than the full-speed performance.
efficiency of 76.3% at 980 gpm. This may not always be the Also, keep in mind that the VFD itself incurs some
case, however, and will depend on the location of Point A efficiency losses (Figure 6), which must be taken into
relative to the BEP. account when evaluating energy savings relative to fixed-
Most properly selected pumps will have normal oper- speed operation.
ating conditions close to the BEP. Thus, the efficiency
correction at Point B vs. Point A tends to be small and can Estimating VFD energy savings for single pumps
be safely ignored in the first approximation (e.g., for initial For individual pumps, electronic spreadsheets offer
screening purposes). However, it should definitely be taken an easy way to estimate the energy savings that can be
into account when making the final investment decision, obtained with VFDs. Some manufacturers and engineering,
procurement, and construction (EPC) consulting firms may
100
provide such spreadsheet templates for preliminary estimat-
90
80 ing (e.g., Figure 7), but they should be used with caution
Load, % Efficiency, % Load, % Efficiency, %
70 because for simplicity they tend to use embedded generic
Efficiency, %
36 www.aiche.org/cep February 2018 CEP Copyright © 2018 American Institute of Chemical Engineers (AIChE)
Table 8. Pump and system data for
natural gas liquids (NGL) pipeline booster station.
Hmax (ft) 2,300 Pump maximum head
(at zero flow)
Hn (ft) 1,840 Head (pipe and valve friction
+ static) at intersection of
pump and system curves
Hs (ft) 100 Static head of the system
Hv (ft) 2 Valve friction head at
full-open position (~0)
P (hp) 10,000 Pump power consumption
Qn (gpm) 17,500 Pump flow at full-speed
intersection point
ρ (lb/ft 3 ) 44.8 Liquid density
(ρwater = 62.2 @ 80ºF)
ηm (%) 96 Nominal efficiency of motor
ηp (%) 75.0 Pump efficiency at full-speed
intersection point
ηVSD (%) 98 Nominal efficiency of
variable-speed drive
Time (hr) 8,400 Total operating time per year
Cost (US$) 80.0 Cost of electrical energy
(per MWh)
p Figure 7. Commercial software tools use generic pump curves and a generic c –2.0 E–06 –4.57 E–07
efficiency curve. Although they are extremely useful for making initial estimates, they
should never be used as a basis for making investment decisions.
but only one operates at any given time; the other is a spare,
intended for use only in emergencies. Table 8 lists the design where Hs is the static head, ρ is the specific gravity or den-
flowrate and other data. sity in consistent units, and the subscript d refers to an actual
The full-speed head-flow curve and the efficiency-flow operating data point at the desired normal condition (or
Copyright © 2018 American Institute of Chemical Engineers (AIChE) CEP February 2018 www.aiche.org/cep 37
Fluids and Solids Handling
Table 10. Estimation of power savings at selected flowrates over the entire operating range.
Pump Curve Full-Speed Required Power Consumption,
System Efficiency, Speed (N), Flow at N, Efficiency
Flow, gpm Head, ft Head, ft % rpm gpm at N, % Throttling VFD Savings
1 2,300 100 0.0 839 4,080 42.5 0 0 0
1,750 2,295 130 20.1 955 4,643 47.2 3,785 93 3,692
3,500 2,282 198 37.4 1,181 5,739 55.5 4,044 241 3,803
5,250 2,259 301 51.9 1,456 7,078 64.1 4,327 476 3,851
7,000 2,226 436 63.6 1,752 8,519 71.5 4,641 825 3,816
8,750 2,185 601 72.5 2,058 10,002 77.2 4,994 1,317 3,678
10,500 2,134 795 78.6 2,366 11,503 80.9 5,400 1,994 3,406
12,250 2,075 1,017 81.9 2,676 13,008 82.5 5,877 2,916 2,961
14,000 2,006 1,265 82.4 2,985 14,511 82.1 6,454 4,169 2,285
15,750 1,927 1,540 80.1 3,293 16,009 79.6 7,178 5,886 1,292
17,500 1,840 1,840 75.0 3,600 17,500 75.1 8,131 8,284 0
19,250 1,743 2,165 67.1 3,905 18,984 68.6
Table 11. Sample of historical NGL flow data needed for each pump.
Flow, gpm % of Design One Step 3b. Alternatively, if the pump
Pump curve cannot be accurately modeled as a
Date 26FI472A 26FI472B Pump A Pump B Pumps
Only
A+B quadratic equation, approximate the cor-
1-Jan-03 0 7,084 0% 40% 20% 40% rected efficiency η2 (3):
2-Jan-03 0 0 0% 0% 0% 0%
3-Jan-03 0 6,815 0% 39% 19% 39%
4-Jan-03 0 0 0% 0% 0% 0% Step 4. For every intermediate value
5-Jan-03 0 0 0% 0% 0% 0% of flow, calculate power consumption; use
6-Jan-03 0 6,670 0% 38% 19% 38% pump head for throttling control (with a
7-Jan-03 0 6,582 0% 38% 19% 38% CV) and system head for the VFD case.
Step 5. Summarize the results, as in
4-Sep-03 5,663 5,667 32% 32% 32% 65%
Table 10.
5-Sep-03 5,744 5,746 33% 33% 33% 65% Step 6. Determine the fluid flow
6-Sep-03 5,437 5,442 31% 31% 31% 62% profile, preferably using actual historical
7-Sep-03 5,952 5,952 34% 34% 34% 68% data over a 1-yr period in increments of
8-Sep-03 5,765 5,768 33% 33% 33% 66% one day (Table 11 and Figure 9), or for bet-
ter accuracy, increments of one shift.
9-Sep-03 5,477 5,479 31% 31% 31% 63%
When approximation is acceptable,
Average 6,589 7,239 37.7% 41.4% 39.5% 79.0%
the amount of effort can be reduced
38 www.aiche.org/cep February 2018 CEP Copyright © 2018 American Institute of Chemical Engineers (AIChE)
120% 40
35
100%
30
Flow, % of Design
Frequency, %
80%
25
60% 20
15
40%
10
20% 5
0% 0
0 10 20 30 40 50 60 70 80 90 100 110 120
ec an ar y n ug Oc
t
-D -J -M 9-Ma -Ju -A 6- % of Design Flowrate for a Single Pump
10 29 20 28 17
p Figure 9. Use historical data from plant records to calculate the flow p Figure 10. A histogram of the flow profile can be useful for calculating
profile. For a new process or facility, use your best estimates. energy savings on a per-day or per-shift basis.
by creating a histogram of the flow profile for 10 repre- Efficiency and Renewable Energy website (4). In addition,
sentative increments (Figure 10). Although Microsoft’s the calculation of power savings must account for the VFD
Excel now features a built-in histogram-calculation tool, power consumption as an efficiency factor (Figure 6). The
it may be quicker to construct a histogram using the final design employed the cold-switching control scheme
CONDITIONAL COUNT functions (Table 12). shown in Figure 11 (next page).
If the required historical data are not available in the The analysis for a backpressure steam turbine (BPST)
company logs, e.g., for a planned new design, then develop as the VSD (instead of an electric motor with a VFD)
your best estimate of the flow profile. A word of warning, would be similar, except that steam turbine efficiency and
though: Actual plant data never follow the symmetrical net steam costs would be used instead of motor/VFD effi-
normal (Gaussian) distribution that is often seen in some ciency and purchased power cost.
academic simulations, which apply only to random natural Note the deliberate and specific reference to a back
occurrences; real distributions are always
Table 12. CONDITIONAL COUNT functions can be used
asymmetrical because they are not random.
to construct a histrogram of the flow profile.
Step 7. From the frequency data, esti-
Excel Histogram Function Alternative Development of the Histogram
mate the number of hours per year for each
flow increment and calculate the actual Frequency,
power consumption and cost savings for the Cum Bin Frequency Values Range One Pump
year (Table 13, next page). 0 0 0 Low High Number % Cum
The estimated savings calculated by 8 0.1 8 0 0 10 8 3.2 3.2
this method are $1,058,000 per year. The 8 0.2 0 0.1 10 20 0 0.0 3.2
screening software tool calculated savings
8 0.3 0 0.2 20 30 0 0.0 3.2
of $1,283,539 based on the same data set
26 0.4 18 0.3 30 40 18 7.1 10.3
(Figure 7). That is a 20% difference, which
could be enough to sway the investment 32 0.5 6 0.4 40 50 6 2.4 12.7
decision. 32 0.6 0 0.5 50 60 0 0.0 12.7
This example illustrates the importance 44 0.7 12 0.6 60 70 12 4.8 17.5
of not making investment decisions based 90 0.8 46 0.7 70 80 46 18.3 35.7
on simplistic calculations that are crude
154 0.9 64 0.8 80 90 64 25.4 61.1
approximations at best (e.g., generic pump
and efficiency curves). Often, simplicity 244 1 90 0.9 90 100 90 35.7 96.8
and ease of use are purchased at the cost of 252 1.1 8 1 100 110 8 3.2 100.0
lower accuracy and reliability. 252 1.2 0 1.1 110 120 0 3.2 100.0
Part-load motor efficiencies can be 252 1.3 0 1.2 120 130 0 0.0 100.0
estimated using MotorMaster 4.1, a free
More 0 1.3 130 140 0 0.0 100.0
software tool that can be downloaded from
the U.S. Dept. of Energy’s Office of Energy 252 100
Copyright © 2018 American Institute of Chemical Engineers (AIChE) CEP February 2018 www.aiche.org/cep 39
Fluids and Solids Handling
Table 13. Final estimation of cost savings based on flow profile. boilers, furnaces, dryers, etc.
Pump Curve Power Consumption Running Time BPST drives are often a more eco-
nomical option for motors of 5 MW or
Flow, Savings,
gpm Head, ft Throttling VFD Savings % hr/yr MWh larger, as long as the plant can make effec-
tive use of the exhaust steam from process
1 2,300 0 0 0 3.2 267 0
heating, and the load is variable. If the
1,750 2,295 3,785 93 3,692 0.0 0 0 motor load is relatively steady and larger
3,500 2,282 4,044 241 3,803 0.0 0 0 than 10 MW, then a gas turbine may be a
5,250 2,259 4,327 476 3,851 7.1 600 1724 more viable option, but only if the exhaust
7,000 2,226 4,641 825 3,816 2.4 200 569 gas from the gas turbine either is used to
generate useful steam in an HRSG or is
8,750 2,185 4,994 1,317 3,678 0.0 0 0
close-coupled to a furnace or boiler.
10,500 2,134 5,400 1,994 3,406 4.8 400 1,016 If the local electric utility offers
12,250 2,075 5,877 2,916 2,961 18.3 1,533 3,387 time-of-use rate schedules, using dual
14,000 2,006 6,454 4,169 2,285 25.4 2,133 3,637 drives on large pumps and compressors
15,750 1,927 7,178 5,886 1,292 35.7 3,000 2,891 (>10 MW) might minimize purchased
energy costs by switching between
17,500 1,840 8,131 8,284 0 3.2 267 0
electrical and thermal energy. Strictly
19,250 1,743 100.0 8,400 13,224
speaking, this is not necessarily an energy
$/MWh 80 efficiency measure, but rather a cost
$/yr 1,058,000 optimization measure similar to arbitrage.
pressure steam turbine. For reasons that are beyond the Estimating energy savings potential
scope of this article, condensing turbines should never be of VFDs for multiple-pump networks
used in any process plant, except in a few rare situations: A network of pumps in series/parallel configuration has
where steam is generated using excess high-temperature an additional degree of freedom for optimizing the load allo-
exothermic heat of reaction from the process or by burning cation among individual pumps. Energy savings are often
a fuel with significant negative cost; in critical duties such comparable to those that can be obtained using VFDs but at
as an emergency boiler feedwater pump; or when the grid substantially lower capital cost.
power supply is unreliable. Several references on pinch This method is known as load management (2), a
analysis (5–7) explain the thermodynamics involved. powerful technique that is woefully underutilized in the
industry. Often, the energy savings obtained through load
Other drive systems management alone are so significant that the incremental
Steam and gas turbines are alternatives to large motors as energy savings obtained by adding VFDs to the network
pump drivers. However, their economics are favorable only cannot justify their incremental capital cost. The applica-
if they can be integrated with the process in cogeneration tion of load management to complex pump networks, both
mode, with the exhaust heat being effectively used in the with and without VFDs, will be covered in Part 3 of this
process to minimize overall fuel consumption in utility-fired article series.
Public drinking-water distribution systems are an excel-
Proposed Controls Revamp (with VFD) lent example of complex pump networks with multiple
sources, multiple delivery points, and intermediate booster
stations (8).
FT
PC A very important point to note is that in a bank of
Switch VFD
parallel pumps (whether identical or not) with the fluid in a
common header going to a single destination, it is not neces-
sary to have a VFD for each pump. A single VFD, after it
M
has been disconnected from the motor that it was controlling
previously, can be switched to any one of the other motors,
M while the rest of the pumps run at fixed speed. This is
known as cold switching, and the lower capital cost greatly
p Figure 11. This cold-switching configuration can be used to reduce improves the return on investment.
the capital costs of the NGL pipeline booster station in the example. However, if the common discharge header branches out,
40 www.aiche.org/cep February 2018 CEP Copyright © 2018 American Institute of Chemical Engineers (AIChE)
with each branch going to a different location with differ-
ent discharge head requirements, control valves would be Nomenclature
required in each branch line, and the economic benefits a, b, c = coefficients for quadratic equations
would be reduced accordingly. BHP = pump power consumption or brake horsepower
D = impeller diameter
Closing thoughts g = gravitational constant
Variable-frequency drives can be retrofit to fixed-speed H = head of liquid, system head
Hf = dynamic head due to friction
motors (the default case) to provide variable-speed capabil-
H n = head (friction + static) at intersection of pump
ity. They offer a degree of freedom in operation that can be and system curves
exploited to improve overall pumping system efficiency and Hs = static head
reduce energy costs. With the recent advent of powerful and Hv = valve friction head of fully open control valve
cheap solid-state technology and advanced control strategies, N = impeller speed
capital costs for VFDs have dropped substantially, making P = hydraulic power consumption of pump (before
them more economically attractive and increasingly popular motor or VSD efficiency adjustments)
Q = flowrate
with technically progressive companies worldwide. CEP Qiso = hypothetical pump flow at intersection of
full-speed pump curve and reduced-speed
Literature Cited iso-efficiency affinity curve at zero static head
(Point C in Figure 5)
1. Kumana, J., and Suarez, M., “Analyzing the Performance of V = velocity
Pump Networks, Part 1: Basic Theory,” Chemical Engineering Greek Letters
Progress, 114 (1), pp. 34–42 (2018)
ΔP = pressure drop
2. Kumana, J., and A. Aseeri, “Electrical Power Savings in Pump ρ = specific gravity or density (in consistent units)
and Compressor Networks via Load Management,” Proceedings η = efficiency
of 27th Industrial Energy Technology Conference, New Orleans,
ηm = nominal efficiency of motor (typically 93–98%)
LA (May 2005); edited version republished in Saudi Aramco
ηp = pump hydraulic efficiency at full-speed intersec-
Journal of Technology, pp 39–43 (Fall 2005).
tion point (control valve fully open)
3. Coelho, B., and A. Andrade-Campos, “A New Approach for the
ηVSD = nominal efficiency of variable-speed drive (from
Prediction of Speed-Adjusted Pump Efficiency Curves,” Journal
Figure 6)
of Hydraulic Research, 54 (5), pp. 586–593 (2016).
μ = viscosity
4. U.S. Dept. of Energy, “MotorMaster 4.1,” DOE Office of
Subscripts
Energy Efficiency and Renewable Energy, www.energy.gov/eere/
A, B, C = at Point A, B, or C on the head-flow curves
amo/downloads/motormaster-tool.
(Figure 5)
5. Linnhoff, B., et al., “Process Integration for the Efficient Use
d = actual operating data point at the desired normal
of Energy,” Chapter 2, Institution of Chemical Engineers,
(or design) condition
Rugby, U.K. (1994).
max = maximum
6. Kumana, J., and A. Al-Qahtani, “Optimization of Process
n = normal
Topology using Pinch Analysis,” Saudi Aramco Journal of Tech-
o = base case, whether design or normal
nology, pp. 13–23 (Winter 2004).
1 = condition 1 (either full-speed, design, or inlet,
7. Smith, R., “Chemical Process Design and Integration,” John
depending on context)
Wiley & Sons, Ltd., Chichester, U.K., (2005).
2 = condition 2 (reduced-speed, actual, or outlet,
8. Sarbu, I., “A Study of Energy Optimization of Urban Water
depending on context)
Distribution Systems using Potential Elements,” Water, (8) 12,
pp. 593–ff, doi:10.3390/w8120593 (Dec 2016).
JIMMY D. KUMANA (Houston, TX; Email: jkumana@aol.com) has more than MANUEL R. SUAREZ (Email: manuel.r.suarez@gmail.com) has more than 30
35 years of experience working for both manufacturing and engineer- years of experience in process engineering, process documentation,
ing-construction companies. He is the founder of Kumana & Associates, process control and automation, plant operations, logistics of oil stor-
a consulting firm specializing in process integration (pinch analysis) age and transportation, project management, and technical training.
techniques for energy/water optimization, as well as general process His wide experience covers polymers, oil and gas, petrochemicals,
performance troubleshooting/improvement in the full range of chemi- food and beverage, and process equipment fabrication for companies
cal industries. He and his company have been consultants to major in Europe, the Americas, and the Middle East. He has authored or
corporations worldwide, as well as to the U.S. Dept. of Energy, Natural co-authored numerous papers, articles, presentations, and training
Resources Canada, the World Bank, and the United Nations. He has courses on variable-frequency drives as final elements for process con-
authored or co-authored over 70 technical papers and book chapters, trol and variable-speed pumping applications, especially for artificial
and regularly teaches courses on pinch analysis, energy efficiency in lift of oil, and on technical skills training of engineering, operations, and
the process industries, and related subjects. He holds an MS in chemi- maintenance personnel. He earned his BS in chemical engineering from
cal engineering from the Univ. of Cincinnati. the Univ. of Texas at Austin.
Copyright © 2018 American Institute of Chemical Engineers (AIChE) CEP February 2018 www.aiche.org/cep 41