2. Temperature Control
2.1 Hot Oil Supply Header (250℃) Temperature Control
Each individual consumer heat exchanger has demand control based on a measured process
parameter, temperature. The exchanger outlet process fluid temperature controller controls the
heat input by modulating on temperature control valve at the hot oil outlet. In the event of sudden
drop in flow or trip of the specific heat exchanger the supply header pressure tends to increase
and the corrective action as described under pressure control takes place.
5.2 Hot Oil Pumps Minimum Flow & Discharge Pressure Control
The Hot Oil Main Circulating Pumps are provided with common minimum flow control FIC-2703-
01, which is cascaded with PIC-2703-03 to control PV-2703-03. This valve ensures that the pump
stable minimum flow is maintained during reduced or blocked Discharge condition.