Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
The basic liquid sizing equation tells us that the liquid flow rate through a control
valve is proportional to the square root of pressure drop. This simple relationship
is shown graphically by the green portion of the graph in Figure 1. (Note that the
scale of the horizontal axis is the square root of pressure drop.)
This linear relationship does not always hold true. As the pressure drop is
increased, the flow reaches a point where it no longer increases. Once this
happens, additional increases in pressure drop across the valve do not result in
additional flow, and flow is said to be choked. Here we will call this limiting or
choking pressure drop ΔPchoked, so as to be in agreement the latest versions of
the IEC and ISA control valve sizing equation standards. Prior to the issuance of
the 2011 edition of the IEC valve sizing equation standard and the 2012 version
of the ISA valve sizing equation standard there was no official name given to the
dividing line between non-choked flow and choked flow, so valve manufacturers
made up their own names. Some of the most common ones are listed in Figure
1.
Let’s take a look at what is happening inside the valve to cause this choking of
the flow. When the flow stream passes through the vena contracta (the point at
which the cross sectional area of the stream is at a minimum), the flow velocity
reaches a maximum. Conservation of energy dictates that since kinetic energy at
the vena contracta has increased to a maximum, potential energy, in the form of
static pressure, must decrease to a minimum. (See Figure2.) Note that in the
figure, ΔP is less than ΔPchoked and flow is not choked.
Figure 2. Pressure and velocity profile in a Control Valve
As the pressure drop across the valve increases, the flow also increases,
increasing the velocity at the vena contracta and decreasing the pressure at the
vena contracta. If the vena contracta pressure drops to the vapor pressure of the
liquid, vapor bubbles form at the vena contracta. Any additional decrease in the
downstream pressure causes more bubbles to form, but the pressure at the vena
contracta does not decrease below the vapor pressure. At this point it is worth
noting that the flow through a control valve depends on the pressure difference
between P1 and Pvc (the pressure at the vena contracta), and since the vena
contracta pressure does not decrease below the vapor pressure, the flow does
not increase, resulting in choked flow.
Something that is beyond the scope of this classical discussion of liquid flow in
control valves is that experimentation has shown that the pressure at the vena
contracta must actually drop slightly below the vapor pressure of the liquid before
vaporization and choked flow begin. The amount below the vapor pressure that
the vena contracta pressure must drop to for flow to choke is approximated in the
IEC and ISA Standards by the Liquid critical pressure ratio factor, FF. When the
vapor pressure is very low compared to the liquid’s thermodynamic critical
pressure, the vena contract pressure where choked flow will begin is only about 4
percent lower than the actual liquid’s vapor pressure. This effect is taken into
account in all of the modern control valve sizing softwares. You can read more
about this in Valin Corporation’s book, Control Valve Application Technology.
Cavitation
Figure 3 illustrates the choking process along with the cavitation discussed in the
next paragraph. Note that in the figure, ΔP is greater than ΔPchoked and flow is
choked.
Figure 3. Velocity and pressure profile in a control valve with choked flow
and cavitation.
As the bubbles move down stream, the cross sectional flow area opens up, the
velocity goes down and the pressure goes up. Now we have bubbles with an
internal pressure equal to the vapor pressure surrounded by a higher pressure.
The bubbles collapse in on themselves. This combination of bubble formation
and the resulting choked flow, along with the collapse of the bubbles downstream
is called CAVITATION. When the bubbles collapse they make a popping sound.
The result is a noise like gravel going through the valve. This noise can be loud
enough to be very annoying and even loud enough to damage the hearing of a
person who is exposed to it for long periods. Also, when the bubbles collapse,
they create shock waves that can cause severe damage to the valve. The
appearance of cavitation damage is a rough, cinder like, look. (See the picture of
a globe valve plug in the upper right side of Figure 3.) This damage can happen
very quickly, sometimes in as little as a few weeks or months. Because cavitation
damage happens so quickly, we try to avoid cavitation at all costs. Very hard
materials give some improvement, but usually the improved performance is not
enough to justify the cost.
Flashing
Now, instead of collapsing, the bubbles become larger and very soon transition
from liquid with bubbles in it to vapor with small drops of liquid in it. This is called
FLASHING. The appearance of flashing damage is quite different from cavitation
damage, and appears as smooth, shiny rivers and valleys. (See the picture of a
globe valve plug in the upper right side of Figure 4.) The damage mechanism is
a sand blasting effect. Downstream of the vena contracta the flow consists of a
large volume of vapor with many tiny drops of liquid. Because the volume
increases greatly when liquid vaporizes, the downstream velocity can be several
hundred feet per second, and the high velocity liquid droplets can erode away a
valve part. The damage caused by flashing does not usually happen as quickly
as that caused by cavitation. The use of hard or erosion resistant materials can
usually bring the damage to within tolerable limits. Trim parts made of the hard
stainless steels, such as 17-4 ph, hold up quite well, and 316ss or chrome moly
bodies do much better than carbon steel. The existence of flashing conditions is
dictated by the system (P2 is less than Pv) and the valve selection neither causes
or prevents flashing. The noise caused by flashing is usually below 85 dBA and
to the author’s knowledge there is no method for calculating flashing noise.
Figure 1 and the associated discussion of liquid choked flow is the classical
discussion, and implies that there is a sudden transition from non-choked flow to
fully choked flow. In reality, at pressure drops approaching, but below the
calculated value of ΔPchoked, there is usually some formation of vapor bubbles
and some degree of cavitation. Figure 5 shows what really happens as flow
transitions from non-choked to fully choked flow.
It is interesting to note that current control valve sizing methods do not include a
method of calculating where the transition from non-choked to fully choked flow
begins and ends. The current ISA and IEC control valve sizing standards only
give formulas for calculating the red and green lines in Figures 1 and 5.
The value of ΔPchoked is a function of both the process conditions (P1, the
pressure upstream of the valve and Pv, the vapor pressure of the liquid) and the
valve’s internal geometry represented by the experimentally determined Liquid
Pressure Recovery Factor, FL. Typical values of FL are shown in Figure 6. Note
that FL is a function of both valve style and the percentage of valve opening.
Higher values of FL are associated with valves that have a lower potential for
cavitation, and smaller values of FL are associated with valves that have a
greater potential for cavitation.
There are several methods of increasing the value of ΔPchoked and thus reducing
the potential for cavitation and the associated noise and damage: (1) The value
of P1 can be increased while keeping ΔP the same by moving the control valve to
a location further upstream, or to a location at a lower elevation. (2) The vapor
pressure can be decreased by installing the valve where the liquid temperature is
lower, such as the cool side of a heat exchanger. (3) A valve style with a higher
value of FL can be selected. It is interesting to note that in general, as the
FL increases, so does the price of the valve. There are special cavitation resistant
adaptations of many of the valve styles that have larger values of FL than those
shown in Figure 6, yet which retain the other desirable features of that style.
Because noise and damage often begin before ΔP reaches ΔP choked, there can
be considerable risk in simply applying the old rule of not allowing ΔP to exceed
ΔPchoked. A more reliable method of preventing cavitation damage in control
valves, according to one major control valve manufacturer, is to avoid valve
applications where the calculated noise exceeds limits based on a broad range of
application experience. This method works because both the noise and the
damage are caused by the same thing, the collapse of vapor bubbles. This
manufacturer’s experience has shown that for valves 3 inches and smaller in
nominal size, cavitation damage will be kept to a minimum if the calculated
Sound Pressure Level, SPL, based on un-insulated schedule 40 pipe, does not
exceed 80 dBA. For 4 inch and 6 inch valves this limit can be increased to 85
dBA, and for valves 8 inches and larger the limit is 90 dBA.
Before actually purchasing a control valve, it is always a good idea to ask for the
manufacturer’s or the manufacturer’s representative’s comments regarding your
selection.
The content of these white papers are just a small portion of what you will learn in
Dr. Monsen's book: Control Valve Application Technology
Would you rather learn from Dr. Monsen directly and have the ability to ask him
questions? Take one or more of his webinars: