Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Condition Monitoring?
Meg-ohm test: will show if the motor
has a dead short to earth, is wet or
contaminated, and can perform a
Polarisation test (PI test). A meg-ohm test
cannot show if a motor is in good condition,
Michael Herring, EU Product Manager, Baker Instruments
as it does not test the entire insulation
system.
PI Test: is a 10 minute test, which
It is argued that condition monitoring of electric motors should incorporates the 1 minute meg-ohm
Abstract
life of the motor and reduce the overall operating cost of the facility. DC Step Voltage Test: is typically
performed at twice line voltage plus 1000
volts. The voltage is increased in a series
of steps, ideally five steps or more, and the
F
or many engineers, condition Static or insulation testing: is performed leakage current is plotted. Good insulation
monitoring of electric motors is with the motor disconnected from the to earth will show a linear plot (see Figure
seen as the use of vibration analysis, power supply. It is typically performed from 1), whereas a non-linear plot (see Figure 2)
thermography, laser alignment and oil the motor control cabinet, and should be would suggest an insulation weakness (or
analysis. All too often, electrical testing as carried out in a specific test sequence: contamination) at that voltage where the
part of a condition monitoring regime is leakage current suddenly increased. The
Winding resistance test: will highlight step voltage test provides a great deal more
deemed as unnecessary. However, studies
dead shorts, loose connections and open information than the basic DC hipot test.
show that, after bearing failure, electrical
circuits. Such tests must be performed
faults are the most common mode of motor The DC Hipot test: simply applies a
with accurate equipment, which is
failure, so in addition, a structured electrical voltage, measures leakage current and
capable of measuring down to 0.001
testing regime is vital for ensuring plant calculates meg-ohms. If the meg-ohms
ohm. It is extremely important to correct
reliability. The meg-ohm test has long been are higher than the accepted minimum
the resistance values to a constant
the tool of choice for most engineers, and value, the motor passes. Even if there is an
temperature, typically 20 degrees Celsius.
this simple test is often the only electrical area of damaged insulation which causes
The motor temperature must be measured
test performed on a motor. However, while a lower reading of meg-ohms, as long
as accurately as possible, and where
the meg-ohm test has a valid role to play, as that value is higher than the minimum
possible, the copper temperature should
it is simply not capable of detecting all the accepted value, it will still pass.
be used. A motor that has been recently
likely faults within a motor’s winding.
operating is very unlikely to be at ambient
Modern test equipment utilises PC control temperature, so
to provide automatic testing and fault the use of ambient
diagnosis, thus removing the onus on temperatures
the operator to interpret the results. The should be avoided.
equipment has the ability to detect micro Upon completion
arcs, and to stop the test automatically. of the test, the
Database software allows assets to be percentage
saved with all test results, so that a trend unbalance between
can be built up over time, ideally from when the phase-to-
the motor is new. phase readings
is calculated
Automated testing also helps remove
[Unbalance =
operator error, inconsistency created
(maximum –
by different operators applying different
minimum)/average,
parameters and the possibility of the
and expressed as
operator applying over-voltage to the
a percentage]. An
motor. The latest testers combine all
unbalance of less
static electrical tests within one portable
than 1% is typical
device, which also have the ability to create
for a good winding,
professional test reports. Figure 1 Linear leakage current plot
although trending of this gives the best
Fig. 1 – Linear leakage current plot
The author
Michael Herring (michael.herring@skf.
com) is EU product manager for the Baker
Instruments Company, an SKF Group
Company. He works closely with Whitelegg
Machines, the UK and Ireland sales and
Figure 6 Torque ripple graph service engineers for Baker Testers.