OPERATION MANUAL
OF DIESEL GENERATING SETS
Dear Aksa Generating Set Operator
First of all, we would like to thank you for your choice of Aksa Power
Generator.
1. INTRODUCTION......................................................................................... 1
2. SAFETY ....................................................................................................... 2
2.1 General ........................................................................................... 2
2.2 Installation, Handling and Towing ......................................................... 2
2.3 Fire and Explosion .................................................................................. 2
2.4 Mechanical .......................................................................................... 3
2.5 Chemical ................................................................................................ 3
2.6 Noise ..................................................................................................... 3
2.7 Electrical ................................................................................................ 3
2.8 First aid For Electric Shock ................................................................................... 4
3. GENERAL DESCRIPTION..................................................................................... 6
3.1 Generating Set Description and Identification...................................... 6
3.2 Diesel Engine ......................................................................................... 6
3.3 Engine Electrical System ....................................................................... 6
3.4 Cooling System ...................................................................................... 6
3.5 Alternator .......................................................................................... 6
3.6 Fuel Tank and Baseframe ...................................................................... 6
3.7 Vibration Isolation ................................................................................. 6
3.8 Silencer and Exhaust System ........................................................... 6
3.9 Control System .................................................................................. 6
4. INSTALLATION, HANDLING AND STORAGE........................................... 8
4.1 General ................................................................................................. 8
4.2 Canopies ...................................................................................... 8
4.3 Location ................................................................................................ 8
4.4 Moving the Generating Set ................................................................ 8
4.5 Foundations Vibration Isolation ................................................... 9
4.6 Combustion Air Inlet ........................................................................... 9
4.7 Cooling and Ventilation ...................................................................... 9
4.8 Exhaust .................................................................................................. 10
4.9 Fuel System .......................................................................................... 16
4.9.1 Day Tank .................................................................................... 16
4.9.2 Bulk Storage Tank ....................................................................... 16
4.9.3 Fuel Lines .......................................................................................... 16
4.10 Lubrication Oil ................................................................................... 23
4.10.1 Oil Performance Properties ....................................................... 23
4.10.2 Lubrication Recommendations for Cummins Engines............. 23
4.10.3 Recommended Oil Properties for Perkins Diesel Engines........ 23
4.10.4 Lubrication Oil Recommendations by Lister Petter 23
4.10.5 Lubrication Oil Recommendations by Deutz ........................................... 23
4.10.6 Lubrication Oil Recommendations by Volvo Penta ......................... 23
4.10.7 Lubrication Oil Recommendations by MTU .................................. 23
4.11 Batteries .............................................................................................................. 24
4.11.1 Maintenance Batteries .......................................................................... 24
4.11.1.1 First Filling of Acid Water to The Battery .................................... 24
4.11.1.2 Battery Maintenance ..................................................................... 24
4.11.1.3 Testing the Battery............................................................................................. 24
4.11.1.4 Hydrometer Test ........................................................................................ 24
4.11.2 Maintenance Free Batteries.......................................................................... 24
4.12 Electrical Connection ....................................................................................... 24
4.12.1 Cabling ................................................................................................... 25
4.12.2 Protection ...................................................................................................... 25
4.12.3 Loading ................................................................................................................ 25
4.12.4 Power Factor ....................................................................................................... 25
4.12.5 Grounding / Earthing Requirements ............................................ 30
4.12.6 Alternator Reconnection ...... ............................................................. 30
4.12.7 Parallel Running ..................................................................................... 30
4.12.8 Insulation Test ........................................................................................ 30
4.13 Acoustic Silencing................................................................................ 30
4.13.1 Exhausts Silencers ..................................................................... 30
4.13.2 Canopies .......................................................................................................... 30
4.13.3 Other Sound Attenuation................................................................... 30
4.14 Engine Jacket Water Heater......................................................... 30
I
4.15 Towing (Mobile Generating Sets).......................................... 30
4.15.1 Preparing to Low ........................................................................ 30
4.15.2 Towing .................................................................................... 30
4.15.3 Parking ..................................................................................... 30
4.16 Storage..................................................................................... 30
4.16.1 Engine Storage ......................................................................... 31
4.16.2 Alternator Storage ................................................................... 31
4.16.3 Battery Storage ................................................................... 31
5. GENERATING SET MAINTENANCE ............................................................... 31
6. GENERAL PRECATIONS AND CONTROLS WHICH MUST BE DONE 31
BEFORE STARTING UP THE GENERATING SET ........................................
7. GENERATING SET CONTROL SYSTEMS ............................................................. 32
7.1 Starting with ME 40 Manual Control Panel ................................................................... 32
7.2 Starting with P 500 Automatic Control Panel .......................................................... 32
7.2.1 Manual Operation ....................................................................................................... 32
7.2.2 Automatic Mode of Operation......................................................................... 32
7.3 Starting With P 2010 Autostart Control Panel .................................................... 33
7.3.1 Manual Operation ....................................................................................................... 33
7.3.2 Automatic Mode of Operation ......................................................................... 33
7.4 Starting with P 2020 Automatic Control Panel ..................................................... 34
7.4.1 Manual Operation .......................................................................................... 34
7.4.2 Automatic Mode of Operation ..................................................................... 34
7.4.3 Test Operation ............................................................................................................ 35
8. GENERAL PRECATIONS AND CONTROL WHICH MUST BE DONE
AFTER STARTING UP THE GENSET ........................................................................... 35
9. STOPPING THE GENERATING SETS ....................................................................... 35
9.1 At Manual Models ........................................................................................ 35
9.2 At Automatic Models .................................................................................................. 36
10. GENERATING SET CONTROL SYSTEMS ............................................... 36
10.1 Control Panels .................................................................................................. 36
10.1.1 Manual Control System ME40................................................................ 36
10.1.1.1 DSE 701 Module Features ............................................................... 36
10.1.1.2 DSE 701 Module Emergency Leds ............................................................... 36
10.2.1 Automatic Control System P 500 ................................................................ 36
10.2.1.1 DSE 704 Module Features ................................................................ 37
10.2.1.2 Status and Fault Conditions Displayed by LED illumination 37
10.3.1 Automatic Control System P 2020 Panel Specification ................. 37
10.3.1.1 DSE 5220 Module Features ................................................................ 37
10.4.1 Autostart Control System P 2010 Panel Specification ................. 38
10.4.1.1 DSE 5210 Module Features .............................................................................. 38
10.5. Panel Equipments ..................................................................................... 39
10.5.1 AC Voltmeter ...................................................................................................... 39
10.5.2 Voltmeter Selector Switch ..................................................................................... 39
10.5.3 AC Ampermeter ...................................................................................................... 39
10.5.4 Frequencymeter ...................................................................................................... 39
10.5.5 Hoursrunmeter ...................................................................................................... 39
10.5.6 Water Temperature Gauge .................................................................... 39
10.5.7 Oil Pressure Gauge ................................................................................................. 39
10.5.8 Emergency Stop Pushbutton ............................................................................. 39
10.5.9 Alternator Protection ............................................................................................ 39
11. THE PLACEMENT AND INSTULATION OF TRANSFER SWITCH ..... 41
12. DSE 530 MODEL FULL AUTOMATIC TRANSFER SWITCH CONTROL
SYSTEM .................................................................................................................... 42
12.1 Automatic Mode of Operation .......................................................... 42
12.2 Manual Restore Mode of Operation .......................................................... 42
12.3 Manual Operation................................................................................................... 42
12.4 Indications .................................................................................................................... 42
13. ALTERNATOR TROUBLESHOOTING................................................................ 43
14. ENGINE TROBLESHOOTING........................................................................... 44
II
1. INTRODUCTION
1
2. SAFETY
2.1 GENERAL
The generating set is designed to be safe ! Engine exhaust emissions are hazardous to
when used in the correct manner. However personnel. The engine exhaust for all indoor
responsibility for safety rests with the generating sets must be piped outdoors via
personnel who install, use and maintain the leak-free piping in compliance with relevant
set. If the following safety precautions are Codes, Standards and other requirements.
followed, the possibility of accidents will be Ensure that hot exhaust silencers and piping
minimized. Before performing any procedure are clear of combustible material and are
or operating technique, it is up to the user guarded for personnel protection per safety
to ensure that it is safe. The generating set requirements. Ensure that fumes
should only be operated by personnel who from the exhaust outlet will not
are authorized and trained. be a hazard.
WARNING ! Never lift the generating set by
attaching to the engine or
! Read and understand all safety precautions and
alternator lifting lugs, instead use
warnings before operating or performing
the lifting points on the
maintenance on the generating set.
baseframe or canopy.
! Failure to follow the instructions, procedures,
! Ensure that the lifting rigging and supporting
and safety precautions in this manual may
structure is in good condition and has a
increase the possibity of accidents and injuries.
! capacity suitable for the load.
Do not attempt to operate the generating set ! Keep all personnel away from the generating
with a known unsafe condition.
set when it is suspended.
! If the generating set is unsafe, put danger notices
and disconnect the battery negative (-) lead so 2.3 FIRE AND EXPLOSION
that it cannot be started until the condition is Fuel and fumes associated with generating
corrected. sets can be flammable and potentially
! Disconnect the battery negative (-) lead prior explosive. Proper care in handling these
to attempting any repairs or cleaning inside the materials can dramatically limit the risk of
enclosure. fire or explosion. However, safety dictates
! Install and operate this generating set only in that fully charged BC and ABC fire
full compliance with relevant National, Local, extinguishers are kept on hand. Personnel
or Federal Codes, Standards or other must know how to operate them.
requirements.
WARNING
2.2 INSTALLATION,
! Ensure that the generating set room is
HANDLING AND TOWING
properly ventilated.
Chapter 4 of this manuel covers procedures ! Keep the room, the floor and the
for installation, handling, and towing of generating set clean. When spills of fuel,
generating sets. That chapter should be read oil, battery electrolyte or coolant occur,
before installing, moving and lifting the they should be cleaned up immediately.
generating set or towing a mobile set. The
! Never store flammable liquids near the
following safety precautions should be noted:
engine.
WARNING ! Do not smoke or allow
! Make electrical connections in compliance sparks, flames or other
with relevant Electrical Codes, Standards or sources of ignition around
other requirements. This includes fuel or batteries. Fuel
requirements for grounding and ground/earth
vapours are explosive.
faults.
! For stationary generating sets with remote Hydrogen gas generated by charging
fuel storage systems, make sure such systems batteries is also explosive.
are installed in compliance with relevant
Codes, Standards or other requirements.
2
! Turn off or disconnect the power to the 2.5 CHEMICAL
battery chargen before making or breaking
Fuels, oils, coolants, lubricants and battery
connections with the battery.
electrolyte used in this generating set are
! To avoiding arcing keep grounded conductive
typical of the industry. However, they can
objects (such as tools) away from exposed
be hazardous to personnel if not treated
live electrical parts (such as terminals). Sparks
properly.
and arcing might ignite fuel or vapours.
! Avoid refiling the fuel tank while the engine WARNING
is running. ! Do not swallow or allow skin contact with
! Do not attempt to fuel, oil, coolant, lubricants or battery
operate the generating electrolyte. If swallowed, seek medical
set with any known leaks treatment immediately. Do not induce
in the fuel system. vomiting if fuel is swallowed. For skin contact,
wash with soap and
2.4 MECHANICAL water.
The generating set is designed with guards ! Do not wear clothing
for protection from moving parts. Care must that has been
still be taken to protect personnel and contaminated by fuel or
equipment from other mechanical hazards lube oil.
when working around the generating set. ! Wear an acid resistant
apron and face shield or goggles when
WARNING servicing the battery. If electrolyte is spilled
! Do not attempt to operate the generating on skin or clothing, flush immediately with
set with the safety guards removed. While large quantities of water.
the generating set is running do not attempt
to reach under or around the guards to do 2.6 NOISE
maintenance or for any other reason. Generating sets that are not equipped with
! Keep hands, arms, long hair, loose clothing sound attenuating enclosures can produce
and jewellery away noise levels in excess of 105 dBA. Prolonged
from pulleys, belts exposure to noise levels above 85 dBA is
and other moving hazardous to hearing.
parts.
Attention: Some WARNING
moving parts can not ! Ear protection must be
be seen clearly when the set is running. worn when operating or
! If equipped keep working around an
access doors on operating generating set
enclosures closed 2.6 ELECTRICAL
and locked when not
Safe and efficient operation of electrical
required to be open.
equipment can be achieved only if the
! Avoid contact with
equipment is correctly installed, operated
hot oil, hot coolant, hot exhaust gases, hot
and maintained.
surfaces and sharp edges and corners.
! Wear protective clothing including gloves WARNING
and hat when ! The generating set must be connected to
working around the the load only by trained and qualified
generating set. electricians who are authorized to do so,
! Do not remove the and in compliance with relevant Electrical
radiator filler cap Codes, Standards and other requlations.
until the coolant has ! Ensure that the generating set, including a
cooled. Then loosen the cap slowly to relieve mobile set is effectively grounded/earthed
any excess pressure before removing the in accordance with all relevant regulations
cap completely. priorts operation.
3
! The generating set should be shutdown with OPEN THE AIRWAY
the battery negative (-) terminal disconnected
Tilt the victims head
prior to attempting to connect or disconnect
back and lift the chin
load connections.
upwards.
! Do not attempt to connect or disconnect
Remove objects from
load connections while standing in water or
the mouth or throat
on wet or soggy ground.
(including false teeth,
! Do not touch electrically
tobacco, or chewing
energized parts of the
gum).
generating set and/or
interconnecting cables BREATHING
or conductors with any
Check that the victim is breathing by looking,
part of the body or with
listening and feeling for
any non insulated conductive object.
the breath.
! Replace the generating set terminal box
cover as soon as connection or disconnection CIRCULATION
of the load cables is complete. Do not
Check for pulse in the
operate the generating set without the cover
victims neck.
securely in place.
! Connect the generating set only to loads IF NO BREATHING BUT
and/or electrical systems that are compatible PULSE IS PRESENT
with its electrical characteristics and that
1 Pinch the victims nose
are within its rated capacity.
! firmly.
Keep all electrical equipment clean and dry. 2 Take a deep breath and
Replace any wiring where the insulation is
seal your lips around the
cracked, cut, abraded or otherwise degraded.
victims lips.
Replace terminals that are worn, discolored
3 Blow slowly into the
or corroded. Keep terminals clean and tight.
mouth watching for the
! Insulate all connections and disconnected
chest to rise. Let the chest fall completely.
wires.
Give breaths at a rate of 10 per minute.
! Use only Class BC or Class ABC 4 If the victim must be left to get help, give 10
extinguishers on electrical fires.
breaths first and then return quickly and
2.8 FIRST AID FOR ELECTRIC SHOCK continue.
5 Check for pulse after every 10 breaths.
WARNING 6 When breathing restarts, place the victim
! Do not touch the victims skin with bare into the recovery position described later
hands until the source of electricity has been in this section.
turned off.
! Switch off power if possible other wise pull
the plug or the cable away from the viation.
! If this is not possible, stand on dry insulating
material and pull the victim clear of the
conductor, preferably using insulated material
such as dry wood.
! If victim is breathing, turn thi victim clear of
the conductor, preferably using insulated
material such as dry wood.
! If victim is breathing, turn the victim into
the recovery position described below.
If victim is unconscious, perform resuscitation
as required:
4
IF NO BREATHING AND NO PULSE RECOVERY POSITION
Call or telephone for Turn the victim onto the
medical help. side.
Give two breaths and Keep the head tilted
start chest compresion with the jaw forward to
as follows: maintain the open
Place heel of hand 2 airway.
fingers breadth above ribcage/breastbone Make sure the victim cannot roll forwards
junction. or backwards.
Place other hand on top Check for breathing and pulse regularly. If
and interlock fingers. either stops, proceed as above.
Keeping arms straight,
press down 4-5 cm (1.5- WARNING
2 inch) at a rate of 15 times per minute. ! Do not give liquids until victim is conscious.
Repeat cycle (2 breaths
and 15 compressions)
until medical help takes
over.
If condition improves,
confirm pulse and
continue with breaths. Check for pulse after
every 10 breaths.
When breathing restarts, place the victim
into the recovery position described below.
5
3. GENERAL DESCRIPTION
6
4
7
4. INSTALLATION, HANDLING AND
STORAGE
4.1 GENERAL 4.2 CANOPIES
Once the size of the generating set and any Installation and handling is greatly simplified
associated control systems or switchgear when the generating set has been equipped
have been established, plans for installation with a canopy. The canopy also gives
can be prepared. This section discusses protection from the elements and protection
factors important in the effective and safe from unauthorized access.
installation of the generating set.
8
Clearance around the generating set for cooling 4.7. COOLING AND VENTILATION
and access for service: at least 1 meter (3.3
The engine, alternator, and exhaust piping
feet) around the set and at least 2 meters (6.6
radiate heat which can result in a temperature
feet) headroom above the set.
high enough to adversely affect the performance
Access to move the entire generating set into
of the generating set. It is therefore important
the room. Air inlet and outlet vents can often
that adequate ventilation is provided to keep
be made removeble to provide an access point.
the engine and alternator cool. Proper air flow,
Limited access to unauthorized personnel.
as shown in Figure 4.4, requires that the air
comes in at the alternator end of the set, passes
If it is necessary to locate the generating set
over the engine, through the radiator and out
outside of the building, the generating set should
of the room via a flexible exhaust duct. Without
be enclosed in a canopy. A canopy is also useful
the ducting of the hot air outside the room,
for temporary installations inside or outside
the fan will tend to draw that hot air around
the building.
and back through the radiator, reducing the
4.5. FOUNDATIONS VIBRATION ISOLATION cooling effectiveness.
The generating set is shipped assembled on a
rigid baseframe that precisely aligns the
alternator and engine and needs to be bolted
down only to a suitably prepared surface.
Foundation
A reinforced concrete pad provides a rigid
support to prevent deflection and vibration.
Typically the foundation should be 150 mm to
200 mm (6 to 8 inches) deep and at least as
wide and long as the generating set. The ground
or floor below the foundation should be
properly prepared and should be structurally Figure 4.2 Directing the air thrown from the
suited to carry the weight of the foundation radiator with deviating wings
pad and the generating set. (If the generating
set is to be installed above the ground floor Sharp corners on the radiator, hot air outlet
the building structure must be able to support channel or its chimney must be avoided. Some
the weight of the generating set, fuel storage rearrangements to turn thrown air should be
and accessories). If the floor may be wet from done (Figure 4.2 and 4.3).
time to time such as in a boiler room, the pad
should be raised above the floor. This will
provide a dry footing for the generating set
and for those who connect, service or operate
it. It will also minimize corrosive action on the
baseframe.
4.6. COMBUSTION AIR INLET
Air for engine combustion must be clean and
as cool as possible. Normally this air can be
drawn from the area surrounding the generating
set via the engine mounted air filter. However, Figure 4.3 Weak ventilation installation
in some cases due to dust, dirt, or heat, the
air around the set is unsuitable. In these cases
an inlet duct should be fitted. This duct should
run from the source of clean air (outside the
building, another room, etc.) to the engine
mounted air filter. Do not remove the air filter
and mount it at a remote location as this can
increase the possibility of dirt leaking through
the ductwork and into the engine inlet.
9
The air inlet and outlet openings should be generating set is not operating the louvres
large enough to ensure free flow of air into can be closed. This will allow the room to
and out of the room. As a rough guide the be kept warm which will assist starting and
openings should each be at least 1.5 times load acceptance. For automatic starting
the area of the radiator core. generating sets. If the louvres are movable
Both the inlet and outlet openings should they must be automatic-ally operated. They
have louvres for weather protection. These should be programmed to open immediately
may be fixed but preferably should be upon starting the engine.
movable in cold climates so that while the
4.8 EXHAUST
The purpose of the engine exhaust system Ensure hot exhaust silencers and piping are
is to direct the exhaust outside to a location clear of combustible material and are guarded
and height where the fumes and odors will for personnel protection per safety
not become an annoyance or hazard, and to requirements.
reduce noise. A suitable exhaust silencer Ensure that fumes from the exhaust outlet
must be incorporated into the exhaust piping will not be a hazard.
to reduce the noise level from the engine.
(See Figure 4.4-4.5) In designing an exhaust system, the primary
WARNING: consideration is to not exceed the allowable
back pressure permitted by the engine
Engine exhaust
manufacturer. Excessive back pressure
emmissions are hazardous
seriously affects engine output, durability
to personnel. The engine
and fuel consumption. To limit the back
exhaust for all indoor
pressure the exhaust piping should be as
generating sets must be
short and straight as possible. Any required
piped outdoors via leak-
bends should have a curve radius of at least
free piping in compliance with relevant
1.5 times the inside diameter of the pipe.
Codes, Standards and other requirements.
10
Other exhaust design criteria are as follows: reduce heat radiation and noise levels. Pipes
A flexible connection between the exhaust and the silencer, whether located inside and
manifold and the piping system should be outside the building, should be located well
used to prevent transmission of engine clear of any combustible material.
vibration to the piping and the building and The outer end of the exhaust pipe, if
to allow for thermal expansion and any slight horizontal, should be cut at 60° to the
misalignment of the piping. (See Figure 4.4) horizontal or should be fitted with a rain
The exhaust gas pipes should be supported hood or cap, if vertical, to prevent rain or
by the building in order to prevent the dead snow from entering the exhaust system.
weight carried by the engine manifold The exhaust pipe must not be connected to
and turbocharger. For that, stretching, exhausts from other generating sets.
elements should be used. (See Figure 4.5) Exhaust pipes must be made up of black iron
Exhaust system components located within pipe.
the generator room should be insulated to
11
Radiator Hot Rooms
Generating Sets Room Air Outlet Air Inlet Door
Dimensions
Dimensions Openings Openings Dimensions Exhaust
(m) Louvers
(m) Total Area (m)
Standby (m)
Model (m2)
Power P
Diameter
(kVA) Length With Height Length With Height D E K L M (inch) (m)
ALP 8 8.5 1.37 0.75 0.97 3 3 2.5 0.55 0.4 0.4 0.5 1 2.2 2 1.5
ALP 12 12 1.45 0.8 1.04 3 3 2.5 0.55 0.5 0.4 0.5 1 2.2 2 1.6
ALP 15 15 1.37 0.75 0.97 3 3 2.5 0.55 0.4 0.4 0.5 1 2.2 2 1.5
ALP 18 17.5 1.45 0.8 1.04 3 3 2.5 0.55 0.5 0.4 0.5 1 2.2 2 1.6
ALP 22 22 1.45 0.8 1.04 3 3 2.5 0.55 0.5 0.4 0.5 1 2.2 2 1.6
ALP 30 30 1.45 0.8 1.04 3 3 2.5 0.55 0.5 0.4 0.5 1 2.2 2 1.6
ADZ 110 110 2.15 1 1.53 5 3 3 0.55 0.75 0.56 0.5 1.2 2.2 3.5 2.1
ADZ 175 175 2.46 1.1 1.62 5 3 3 0.75 0.8 0.46 1 1.3 2.2 4 2.2
ADZ 360 360 2.96 1.37 2.1 5 3 4 0.85 1.05 0.45 1.5 1.6 2.5 2x4 2.6
ADZ 400 400 2.96 1.37 2.1 5 3 4 0.85 1.05 0.45 1.5 1.6 2.5 2x4 2.6
ADZ 490 490 3.2 1.43 2.07 6 3 4 1.5 1.6 0.25 2 1.8 2.5 2x4 2.6
ADZ 538 538 3.2 1.43 2.07 6 3 4 1.5 1.6 0.25 2 1.8 2.5 2x4 2.6
ADZ 550 550 3.2 1.43 2.07 6 3 4 1.5 1.6 0.25 2 1.8 2.5 2x4 2.6
AP 500 500 3.6 1.22 2.1 6 3 4 1.3 1.4 0.4 2 1.8 2.5 6 2.7
AP 550 550 3.6 1.22 2.1 6 3 4 1.3 1.4 0.4 2 1.8 2.5 6 2.7
AVP 515 515 3.6 1.3 1.96 6 3 3.5 1.35 1.35 0.4 1.5 1.5 2.5 6 2.5
AVP 550 550 3.6 1.3 1.96 6 3 3.5 1.35 1.35 0.4 2 1.5 2.5 6 2.5
AKMTU 720 720 4 1.58 1.9 6 5 4 1.6 1.3 0.4 2.5 2.2 2.7 2x6 2.7
AKMTU 780 780 4.1 1.58 2 7 5 4 1.6 1.3 0.4 2.5 2.2 2.7 2x6 2.8
AKMTU 925 925 4.38 1.58 2 7 5 4 1.6 1.55 0.3 3 2.2 2.7 2x6 2.8
AKMTU 1030 1030 4.38 1.76 2.2 7 5 4 2.2 2 0.25 4.5 2.4 3 2x6 3
AKMTU 1500 1500 3.85 1.8 2.3 7 5 4 Remote Radiator * 2.4 3 2x12 3.1
AKMTU 1700 1700 3.85 1.8 2.3 7 5 4 Remote Radiator * 2.4 3 2x12 3.1
AKMTU 2050 2050 4.55 1.8 2.33 8 5 4 Remote Radiator * 2.4 3 2x12 3.1
AKMTU 2250 2250 4.55 1.8 2.33 8 5 4 Remote Radiator * 2.4 3 2x12 3.1
Table 4.1.1 Aksa open type diesel (look figure 4.5 genset room) gen-sets dimensions, room dimensions, air inlet
and outlet openings dimensions and exhaust pipe dimensions.
Please contact us for gen-sets which have remote radiator system.
12
Generating Sets Radiator Hot Rooms
Room Air Outlet Air Inlet Door
Dimensions Openings Openings Dimensions Exhaust
Dimensions (m) Louvres
Standby
Total Area (m)
(m) (m)
Model (m2)
Power A B C P
Diameter
(kVA) Length With Hight Length With Height D E K L M (inch) (m)
AC 39 39 1.86 0.9 1.3 3.5 3 2.5 0.7 0.75 0.45 0.8 1.5 2 3 2
AC 55 55 1.86 0.9 1.3 3.5 3 2.5 0.8 0.85 0.4 0.8 1.5 2 3 2
AC 66 66 1.86 0.9 1.3 3.5 3 2.5 0.75 0.8 0.5 0.8 1.5 2 3 2
AC 70 70 1.86 0.9 1.3 3.5 3 2.5 0.75 0.8 0.5 0.8 1.5 2 3 2
AC 90 90 1.86 0.9 1.3 3.5 3 2.5 0.75 0.8 0.5 0.8 1.5 2 3 2
AC 150 150 2.31 1.1 1.6 4 3 2.5 1.1 1 0.55 1.3 1.5 2 4 2
AC 160 160 2.15 1.1 1.67 4 3 2.5 0.8 0.9 0.45 1 1.5 2 3 2
AC 200 200 2.31 1.1 1.6 4 3 2.5 1.1 1 0.55 1.3 1.5 2 4 2
AC 250 250 2.53 1.1 1.6 4 3 2.5 1.1 1 0.55 1.3 1.5 2 4 2
ACL 250 250 2.9 1.15 1.73 5 3.3 3 2.5 1.2 0.45 1.5 1.5 2 6 2.2
AC 275 275 2.9 1.15 1.73 5 3.3 3 2.5 1.2 0.45 1.5 1.5 2 6 2.2
AC 350 350 3.23 1.15 2 5 3.3 3 1.25 1.2 0.7 1.5 1.5 2.5 6 2.5
AC 400 400 3.23 1.15 2 5 3.3 3 1.25 1.2 0.7 1.5 1.5 2.5 6 2.5
AC 500 500 3.4 1.3 2.1 5.5 3.5 3 1.5 1.5 0.52 3 1.7 2.6 6 2.5
ACQ 515 515 3.6 1.3 2 5.5 3.5 3 1.5 1.5 0.4 3 1.7 2.6 6 2.5
AC 550 550 3.43 1.3 2.1 5.5 3.5 3 1.5 1.5 0.5 3 1.7 2.6 6 2.5
ACQ 550 550 3.6 1.3 2 5.5 3.5 3 1.5 1.5 0.4 3 1.7 2.6 6 2.5
AC 650 650 3.6 1.3 2 5.5 3.5 3 1.5 2.5 0.4 2.5 1.7 2.6 6 2.5
AC 703 703 3.9 1.4 2.13 5.5 3.5 3.3 1.6 1.5 0.5 3.6 2 2.6 2x6 2.6
ACQ 720 720 4.2 1.7 2.2 6 3.7 3.5 1.8 1.8 0.3 4 2.5 2.7 8 2.7
AC 825 825 3.9 1.4 2.13 5.5 3.5 3.3 1.6 1.5 0.5 3.6 2 2.6 2x6 2.6
ACQ 830 830 4.2 1.7 2.2 6 3.7 3.5 1.8 1.8 0.3 4 2.5 2.7 8 2.7
ACQ 881 880 4.2 1.7 2.2 6 3.7 3.5 1.8 1.8 0.3 4 2.4 2.7 8 2.7
AC 1030 1030 4.3 1.8 2.4 6.5 4 3.5 2.2 2 0.3 5 2.5 3 2x6 3
ACQ 1030 1030 4.23 1.8 2.35 6.5 4 3.5 2.3 2 0.3 5 2.5 3 2x6 3
AC 1130 1130 4.35 1.8 2.35 6.5 4 3.5 2.2 2 0.3 5 2.5 3 2x6 3
ACQ 1130 1130 4.4 2 2.3 6.5 4 3.5 2.3 2 0.3 5 2.5 3 2x6 3
AC 1435 1435 4.95 2.15 2.3 7 4.5 3.5 2.5 2 0.3 5 2.7 3 2x8 3
AC 1675 1675 5.5 2.15 2.9 7.5 4.5 4 2.5 2 0.3 6 2.7 3.4 2x8 3.5
ACQ 2100 2100 6.05 2.5 3.22 8 5 4.5 3 3 0.3 9 3 3.5 2x12 4
ACQ 2250 2250 6.05 2.5 3.22 8 5 4.5 3 3 0.3 10 3 3.5 2x12 4
Table 4.1.2 Aksa open type 50 Hz diesel gen-sets dimensions, room sizes, air inlet and outlet openings
dimensions (look figure 4.5. genset room) Without acoustic treatment. Single sets.
13
Generating Sets Radiator Hot Rooms
Room Air Outlet Air Inlet Door
Dimensions Openings Openings Dimensions Exhaust
Dimensions (m) Louvers Total Area
Standby (m)
(m) (m)
Model (m2)
Power P
Diameter
(kVA) Length With Height Length With Height D E K L M (inch) (m)
ALP 10-6 10 1.38 0.77 0.98 2.5 3 2.5 0.55 0.4 0.4 0.5 1 2.2 2 1.5
ALP 15-6 15 1.45 0.82 1.04 2.5 3 2.5 0.55 0.5 0.4 0.5 1 2.2 2 1.6
ALP 21-6 21 1.45 0.82 1.04 2.5 3 2.5 0.55 0.5 0.4 0.5 1 2.2 2 1.6
AP 616-6 616 3.6 1.3 2.1 5.5 3.5 3 1.5 1.5 0.4 3 1.8 2.6 6 2.5
AP 693-6 693 3.6 1.3 2.1 5.5 3.5 3 1.5 1.5 0.4 3 1.8 2.6 6 2.5
Table 4.1.3 Aksa 60 Hz, open type diesel gen-set dimensions, air inlet and outlet openings dimensions and exhaust
pipe dimensions. (look figure 4.5. genset room) Without acoustic treatment. Single sets.
14
Generating Sets Radiator Hot Rooms
Room Air Outlet Air Inlet Door
Dimensions Openings Openings Dimensions Exhaust
Dimensions (m) Louvers Total Area
Standby (m)
(m) (m)
Model (m2)
Power A B C P
Diameter
(kVA) Length With Height Length With Height D E K L M (inch) (m)
AC 44-6 44 1.86 0.9 1.3 3.5 3 2.5 0.7 0.75 0.45 0.8 1.5 2.2 3 2
AC 66-6 66 1.86 0.9 1.3 3.5 3 2.5 0.8 0.85 0.4 0.8 1.5 2.2 3 2
AC 77-6 77 1.86 0.9 1.3 3.5 3 2.5 0.75 0.8 0.5 0.8 1.5 2.2 3 2
AC 100-6 100 1.86 0.9 1.3 3.5 3 2.5 0.75 0.8 0.5 0.8 1.5 2.2 3 2
AC 135-6 135 2.15 1 1.67 3.5 3 2.5 0.8 0.9 0.45 1 1.5 2.2 3 2
AC 165-6 165 2.31 1.1 1.6 4 3 2.5 1.1 1 0.55 1.3 1.5 2.2 4 2
AC 225-6 225 2.31 1.1 1.6 4 3 2.5 1.1 1 0.55 1.3 1.5 2.2 4 2
AC 275-6 275 2.9 1.15 1.73 5 3.3 2.5 1.1 1.2 0.45 1.5 1.5 2.2 6 2.1
AC 350-6 350 3.23 1.15 2 5 3.3 3 1.25 1.2 0.7 1.5 1.5 2.5 6 2.5
AC 383-6 383 3.23 1.15 2 5 3.3 3 1.25 1.2 0.7 1.35 1.5 2.5 6 2.5
AC 450-6 450 3.23 1.15 2 5 3.3 3 1.25 1.2 0.7 1.35 1.5 2.5 6 2.5
ACQ 498-6 498 3.6 1.3 2 5.5 3.5 3 1.5 1.5 0.4 3 1.7 2.6 6 2.5
AC 550-6 550 3.43 1.3 2.1 5.5 3.5 3 1.5 1.5 0.5 3 1.7 2.6 6 2.5
AC 616-6 616 3.43 1.3 2.1 5.5 3.5 3 1.5 1.5 0.5 3 1.7 2.6 6 2.5
ACQ 616-6 616 3.6 1.3 2 5.5 3.5 3 1.5 1.5 0.4 3 1.7 2.6 6 2.5
AC 754 6 754 3.9 1.4 2.13 5.5 3.5 3.3 1.6 1.8 0.5 3.6 2 2.6 2 x 6 2.6
ACQ 758-6 758 4.2 1.7 2.2 6 3.7 3.5 1.8 1.8 0.3 4 2.4 2.7 8 2.7
ACQ 935-6 935 4.2 1.7 2.2 6 3.7 3.5 1.8 1.8 0.3 4 2.4 2.7 8 2.7
ACQ 1030-6 1030 4.2 1.7 2.2 6 3.7 3.5 1.8 1.8 0.3 4 2.4 2.7 8 2.7
ACQ 1025-6 1025 4.23 1.8 2.35 6.5 4 3.5 2.3 2 0.3 5 2.5 3 2x6 3
AC 1150-6 1150 4.3 1.8 2.4 6.5 4 3.5 2.2 2 0.3 5 2.5 3 2x6 3
ACQ 1160-6 1160 4.23 1.8 2.35 6.5 4 3.5 2.3 2 0.3 5 2.5 3 2x6 3
ACQ 1232-6 1232 4.4 2 2.35 6.5 4 3.5 2.3 2 0.3 5 2.5 3 2x6 3
AC 1450 6 1450 4.95 2.15 2.3 7 4.5 3.5 2.5 2 0.3 5 2.7 3 2 x8 3
AC 1590-6 1590 4.95 2.15 2.35 7 4.5 3.5 2.5 2 0.3 5 2.7 3 2x8 3
AC 1930-6 1930 5.5 2.15 2.9 7.5 4.5 4 2.5 2 0.3 6 2.7 3.4 2 x 8 3.5
Table 4.1.4 Aksa 60 Hz, open type diesel gen-set dimensions, room sizes. air inlet and outlet openings dimensions
and exhaust pipe dimensions. (look figure 4.5. genset room) Without acoustic treatment. Single sets.
15
4.9 FUEL SYSTEM 4.9.2 Bulk Storage Tanks: For extended
operation. a separate bulk fuel storage tank
The fuel system for the generating set must
is required. The bulk tank should generally
be capable of delivering a clean and
be located outside the building where it will
continuous supply of fuel to the engine. For
be convenient for refilling, cleaning and for
most installations this will include a small
inspection. It should not, however, be
day tank, a bulk storage tank and fuel lines.
exposed to freezing weather because fuel
flow will be restricted as viscosity increases.
WARNING: The tank may be located either above or
For stationary gene- below ground.
rating sets with remote A vent must be installed on the bulk tank to
fuel storage systems, relieve the air pressure created by filling the
make sure such tank or created by evaporation and
systems are installed in expansion. It will also prevent a vacuum as
compliance with the fuel is consumed. The base of the tank
relevant Codes, should have a slope, so the water and the
Standards or other sediment can be collected. A sludge drain
requirements. valve should be installed at the low point to
allow removal of water and sediment on a
Do not smoke or allow sparks, flames or regular basis.
other sources of ignition around fuel. Fuel
vapours and oil vapours are explosive. 4.9.3 Fuel Lines: The fuel lines can be of
any fuel compatible material such as steel
4.9.1 Day tank: Day tanks provide a readily pipe or flexible hoses that will tolerate
available supply of fuel directly to the environmental conditions.
generating set and should therefore be
located within the generator room. The Flexible piping should be used to connect
baseframe is designed to contain a day tank to the engine to avoid damage or leaks
up to 700 kVA. caused by engine vibration.
16
Figure 4.6.1 Typical fuel installation using a base tank fed from a bulk tank
1. Fill cabinet with overfill alarm and gauge 11. Electric fuel shutoff valve
2. Tank fill line 12. Optional band
3. Vent 13. Day tank incorporated in baseframe
4. Contents gauge 14. Float Control switches
5. Bulk storage tank 15. Manual fill and vent
6. Sludge drain 16. Level gauge
7. Bund tank 17. Drain
8. Outlet valve 18. Leakage alarm unit (optional)
9. Supply line to day tank 19. Fuel filter
10. Electric fuel transfer pump 20. Engine fuel pump
17
WARNING
! The fuel must be clean and must not contain
any water or any erasive liquids.
! Fuel pipes must best made of black pipe, not
galvanized pipe.
! When the engine stops, there should not
be any gravitational free flow in the fuel pipes
towards of the engine.
! The fuel temperature is a critical factor for
appropriate working conditions of the engine.
Fuel temperature above 71°C, due to Figure 4.8 Fuel tank which is put 1500 mm
expansion of the fuel, will decrease the engine above the fuel conversion
output power.
! The connection pipe from the bulk storage
tank to the day tank must be equal or greater
than the daily feed pipe.
In fuel system line, using the water filter
seperators will prevent the injectors and
fuel pump, and it will be usefull for healthy
working of the engine.
! In the simplest tank settlement, the fuel level
should not be above the injectors and should
not be lower than the fuel pump for more
than 1.8 m, see Figure 4.7.
CHECK VALVE
18
Fuel Consumption
Oil Specifications
Coolant Capacity
Generating Sets
Oil Capacity
at Full Load
Fuel Tank
Capacity
Not: Lubricating oil viscosity level will
Stand by be chosen from Table 4.3 according
Engines Model Power Engine Model to the ambient temperature
(kVA)
L/h Lt Lt Lt
ADZ 360 360 BF6M 1015 C 67.6 500 57 38 Deutz: Recommends API CF, API
Deutz
AVP 515 515 TAD1630GE 96.1 520 64 64 Volvo: Recommends API CD, API CE,
API CF, API CF4, CCMC D4
AVP 550 550 TAD1631GE 107 520 64 64 CCMC D5 lubricating oils
Table 4.2.1 Coolant and oil capacities and lubricating oil specifications (50 Hz, Gen-sets).
19
Fuel Consumption
Oil Specifications
Coolant Capacity
Generating Sets
Oil Capacity
at Full Load
Fuel Tank
Capacity
Not: Lubricating oil viscosity level will
Stand by Cummins be chosen from Table 4.5 according
Model Power to the ambient temperature
(kVA) Engine Model
L/h Lt Lt Lt
AC 66 66 4BT3.9-G4 14 132 19 11
AC 70 70 4BT3.9-G4 15 132 19 11
AC 90 90 4BTA3.9-G3 18 132 20 11
API CI-4
AC 400 400 NTA855G4 76 420 70 38.6
API CF4
AC 500 500 KTA19-G3 97 550 92 50
Table 4.2.2 Fuel consumption and coolant, fuel and lubricating oil capacities (50 Hz, Gen-sets).
20
Fuel Consumption
Oil Specifications
Coolant Capacity
Generating Sets
Oil Capacity
at Full Load
Fuel Tank
Capacity
Not: Lubricating oil viscosity level will
Stand by be chosen from Table 4.3 according
Engines Model Power Engine Model to the ambient temperature
(kVA)
L/h Lt Lt Lt
ALP 10-6 10 LPW 2 2,3 80 5,5 3,2 Recommends API CC at first use
Heavy load conditions and below
Petter
Lister
Table 4.2.3 Coolant and oil capacities and lubricating oil specifications (60 Hz, Gen-sets).
21
Fuel Consumption
Oil Specifications
Coolant Capacity
Generating Sets
Oil Capacity
at Full Load
Fuel Tank
Capacity
Not: Lubricating oil viscosity level will
Stand by Cummins be chosen from Table 4.5 according
Model Power to the ambient temperature
(kVA) Engine Model
L/h Lt Lt Lt
API CI - 4
AC 616-6 616 KTA 19-G4 122 550 92 50
API CF4
ACQ 616-6 616 QSX 15-G9 117.8 620 90 91
Table 4.2.4 Coolant and oil capacities and lubricating oil specifications (60 Hz, Gen-sets).
22
4.10 LUBRICATION OIL
23
4.11BATTERIES
24
4.12.1 Cabling: Due to movement of gen- 4.12.2 Protection: The cables connecting
erating sets on their vibration mounts, the the generating set with the distribution system
electrical connection to the set should be are protected by means of a circuit breaker
made with flexible cable. to automatically disconnect the set in case of
The cable should be protected by laying it in overload or short circuit. (Manual models
a duct or cable tray. only).
The cable must be suitable for the output 4.12.3 Loading: When planning the electrical
voltage of the generating set and the rated distribution system, it is important to ensure
current of the set. In determining the size, that a balanced load is presented to the
allowances should be made for ambient tem- generating set. If loading on one phase is
perature. method of installation, proximity substantially higher than the other phases it
of other cables. etc. will cause overheating in the alternator wind-
All connections should be carefully checked ings, imbalance in the phase to phase output
for integrity. voltage and possible damage to sensitive 3
Current carrying capacity of power cables phase equipment connected to the system.
that will be used for generator has been given Ensure that no individual phase current ex-
in table 4.4. and the cable cross sections ceeds the current rating of the generating
which must be used according to the gener- set. For connection to an existing distribution
ator powers has been given in table 4.5.1- system, it may be necessary to reorganize
4.5.2 the distribution system to ensure these loading
On the other hand, there is a one more factors are met..
important point while cable cross sections 4.12.4 Power Factor: The power factor
are being selected. If the distance between (cosø) of the connected load should be de-
load and generator is too length, voltage falling termined. Power factors below 0.8 lagging
at the load side can be too much at the (inductive) can overload the generator. The
transient current duration. In this case you set will provide its kilowatt rating and operate
should calculate the cable cross sections with satisfactorily from 0.8 lagging to unity power
electrical formula which has been given below. factor (1.0). Particular attention must be given
e= x L x x (R CosØ + X Sn Ø) to installations with power factor correction
e : Voltage falling (volt) equipment such as capacitors to ensure that
L : Cable length (meter) a leading power factor is never present. This
: Current (Amper) will lead to voltage instability and may result
R : Resistance of cable (ohm/m) in damaging overvoltages. Generally whenever
x : Reactance of cable (ohm/m) the generating set is supplying the load any
power factor correction equipment should
be switched off.
PVC - ISOLATED CABLES YVV (NYY) SUITABLE TO 0.6/1KV VDE NORMS AND TS
0,6/1 KV, YVV type Cable Current Capacity
Wire
Section Soil %25ºC @ Air %40ºC @ Air
(mm2) Multiple Multiple Multiple Single HO7RN-F
Core Core Core Core
2.5 36 25 22 25 21
4 46 34 30 33 28
6 58 44 38 42 36
10 77 60 53 57 50
16 100 80 71 76 67
25 130 105 94 101 8/8
35 155 130 114 123 110
50 185 160 138 155 138
70 230 200 176 191 170
95 275 245 212 228 205
120 315 285 248 267 245
150 355 325 283 305 271
185 400 370 322 347 310
240 465 435 380 - -
Table 4.4: Current carrying capacity of power cables PVC insulated conductors in accordance with VDE 0298
25
GENERATING SETS Full Load Current
Current Capacity of Cable Section
U=400 Vac Cable at Air YVV 25ºC
Stand by (mm)
Model Power Cosj: 0,8 (Ampere)
(kVA)
AC 39 39 57 80 4 x 16
AC 55 55 80 105 3 x 25 / 16
AC 66 66 95 130 3 x 35 / 16
AC 70 70 101 130 3 x 35 / 16
AC 90 90 130 160 3 x 50 / 25
ALP 12 12 17 25 4 x 2.5
Lister Petter
ALP 15 15 21 25 4 x 2.5
ALP 22 22 31 34 4x4
ALP 30 30 43 60 4 x 10
Perkins
27
Current
GENERATING SETS Full Load Capacity of Cable Section
Current Cable at Air (NYY) Single core
Stand by U=400 Vac (40°C ambient for each phase
Model Power Cosj: 0,8 temperature) (mm2)
(kVA) (Ampere)
ALP 21-6 21 30 38 6
28
Current
GENERATING SETS Full Load Capacity of Cable Section
Current Cable at Air (NYY) Single core
Stand by U=400 Vac (40°C ambient for each phase
Model Power Cosj: 0,8 temperature) (mm2)
(kVA) (Ampere)
AC 44-6 44 63,5 76 16
AC 66-6 66 95 123 35
29
4.12.5 Grounding/Earthing Requirements: sound absorbing wall coverings, that can be
The frame of the generating set must be used to reduce the noise levels of generating
connected to an earth ground. Since the set is sets.
mounted on vibration isolators, the ground 4.14 ENGINE JACKET WATER HEATER
connection must be flexible to avoid possible Jacket water heater is used in order to startup
breakage due to vibration. the generating set more easily and to take the
Ground connection cables or straps should have load. In automatic generating sets jacket water
at least full load current carrying capacity and heater is standard. In manual type generating
meet applicable regulations. sets it is an option. Heater warms up the jacket
4.12.6 Alternator Reconnection: Most water of the engine when the generating set is
alternators can be reconnected to suit different not working.
output voltages. Ensure that all other
components such as circuit breakers, current 4.15. TOWING (Mobile Generating Sets)
transformers, cables and ammeters are suitable 4.15.1 Preparing to Tow: Inspect all
before operating at a different voltage. components of the coupling equipment on the
4.12.7 Parallel Running: Extra equipment towing vehicle and the generating set for defects
must be fitted for the standard generating sets such as excessive wear, corrosion, cracks, bent
to be operated in parallel with other generating metal, or loose bolts.
sets or with mains power. Inspect tyres for condition and proper inflation.
4.12.8 Insulation Test: Before starting the Check that all tail lights, if equipped, are operating
generating set after installation, test the insulation properly and that all reflectors are clean and
resistance of the windings. The Automatic functional.
Voltage Regulator (AVR) should be disconnected 4.15.2 Towing: Whenever towing a mobile
and the rotating diodes either shorted out with generating set, remember that manoeuvra-bility
temporary links or disconnected. Any control and stopping distance will be affected by the
wiring must also be disconnected. weight of the trailer.
A 500V Megger or similar instrument should
be used. Disconnect any earthing conductor WARNING
connected between neutral and earth and When towing mobile generating set, observe
megger an output terminal to earth. The all Codes, Standards or other regulations and
insulation resistance should be in excess of 1Mý traffic laws. These include those regulations
to earth. Should the insulation resistance be specifying required equipment and maximum
less than 1Mý the winding must be dried out. and minimum speeds.
4.13 ACOUSTIC SILENCING Do not permit personnel to ride on the mobile
generating set. Do not permit personnel to
Control of generating set noise is becoming stand or ride on the drawbar or to stand or
very important in most installations. There is a walk between the generating set and the towing
range of components available to control the vehicle.
noise level. Avoid gradients and avoid potholes, rocks or
other obstructions and soft or unstable terrain.
WARNING
Ensure the area behind and under the mobile
Ear protection must be worn when operating
set is clear before reversing.
or working around an operating generating set.
4.15.3 Parking: Park the set on a dry level
4.13.1 Exhaust Silencers: As discussed in
area that can support its weight. If it must be
Section 4.8 the exhaust silencer will decrease
located on a slope, park it across the grade so
sound levels from the engine.
that it does not tend to roll downhill. Do not
4.13.2 Canopies: Section 4.2 discusses sound
park the set on grades exceeding 15°.
attenuating canopies that lower the noise level
of the entire generating set. 4.16 STORAGE
4.13.3 Other Sound Attenuation: For
Long term storage can have detrimental effects
installations in buildings there are other types
on both the engine and alternator. These effects
of equipment such as acoustic louvers, splitter
can be minimized by properly preparing and
vents and fan silencers, as well as
storing the generating set.
30
6. GENERAL PRECAUTIONS
AND CONTROLS WHICH
4.16.1 Engine Storage: The engine should MUST BE DONE BEFORE
be put through an engine preservation STARTING UP THE
procedure that includes cleaning the engine
and replacing all the fluids with new or GENERATING SET
preserving fluids. Make a general visual inspection on the engine
and alternator. Check if there is any breakage,
4.16.2 Alternator Storage: When an crack, indentation, leakage or looseness.
alternator is in storage, moisture tends to Never operate the generating set before
condense in the windings. To minimize removing any fault, if any.
condensation, store the generating set in a Take out foreign materials such as keys, tools,
dry storage area. If possible use space heaters cleaning wool, papers etc. on the engine and
to keep the windings dry. the alternator.
After removing the generating set from Check the fuel level in the day tank. Refill
storage, perform an insulation Check as with fuel if it is low.
discussed in 4.12.8. Check the engine oil level on the dip stick.
Refill with an appropriate oil if it is low. Oil
4.16.3 Battery Storage: While the battery level normally must be close to the maximum
is stored, it should receive a refreshing charge level line.
every 8 weeks up to a fully charged condition. Look at the water level by opeing the radiator
tap. If it is inadequate add more water. Water
5. GENERATING SET level must be 30 mm. lover than the water
MAINTENANCE filling neck.
Engine cooling water must include antifreeze
A good maintenance program is the key to according to the coolest weather conditions
long generating set life. The recommended in the area. A mixture of 50% antifreeze and
maintenance program is provided on the 50% water provides a good protection in all
Periodic Maintenance Chart. This chart is area.
given with all generating sets. Inspect the radiator air outlet hood, open if
Maintenance and service should only be clogged and clear away all obstructions in
carried out by qualified technicians. The front of the air outlet.
maintenance and service which are done must Check the air filter gauge. Clean or replace
be recorded to the Maintenance Record the air filter, if necessary.
Form. In General, the generating set should Keep the inlet opening open.
be kept clean. Do not permit liquids such as Make sure that the generating set can easily
fuel or oil film to accumulate on any internal take air from te environment.
or external surfaces. Wipe down surfaces Check the battery connection cables. Take
using an aqueous industrial cleaner. care to tighten the loosened battery terminals
with spanner and, cover with special substance
and keep clean in order to avoid oxidation.
Open the battery caps and check the liquid
level in the cells. Add distilled water, if
necessary, so as to be 1 cm higher than the
separation. Never fill the cells with tap water,
acid water or acid.
Check if the circuit breaker outlet switch is
in OFF position.
Make sure that the emergency stop button
is not pressed.
31
7. GENERATING SET CONTROL SYSTEMS
To control and monitor the generating set, 7.2. STARTING WITH P500 AUTOMATIC
an electronic control system has been used. CONTROL PANEL (with AMF)
Depending on the requirements of the set,
one of several different standard control systems 7.2.1 Manual Operation
may be fitted. These include ME 30, ME 40
model Manual Control Systems, P 500 Check the precautions and controls starting up
Automatic Control Systems (with AMF), P 2010 the generating set.
Auto start Control System and P 2020 To initiate a start sequence in MANUAL, press
Automatic Control System (with AMF). Control the push button and the start sequence is
panel provides a means of starting and stopping initiated.
the generating set, monitoring its operation and After fuel solenoid is energised, then the starter
output and automatically shutting down the set motor is engaged.
in the event of a critical condition arising such Engine cranked for a 10 second period, If the
as low oil pressure or high engine temperature. engine fails to fire during this cranking attempt
then the starter motor is disengaged for a 10
7.1 Starting with ME 30 or ME 40 second period. Should this sequence continue
Manual Control Panel terminated and fail to start fault will be
illuminated.
Check the precautions and controls before When the engine fires, the starter motor is
starting up the generating set disengaged and locked out at 20 Hz measured
To start the generating set, turn the key from the Alternator output.
switch to the hand position, which will After the starter motor has disengaged, the
power up the unit (DSE 701 module) Safety On timer is activated, allowing Oil
Pressing start button (1) will energise the pressure, High Engine Temperature, Under
Fuel solenoid, then the starter motor. The -speed, Charge Fail and any delayed Auxiliary
button should be pressed for the duration of fault inputs to stabilise without triggering the
the crank period. fault. The generator will run off load, unless
When the engine fires, the starter motor is the mains supply fails or Remote start on
disengaged and locked out at 20 Hz measured load signal is applied, at which point the load
from the alternator output. will be transferred to the generator. If Auto
After the starter motor has disengaged, safety mode is selected, and the mains supply is
on timer is activated (which is fixed at 12 healthy with the remote start on load signal
seconds), allowing oil pressure, high engine not active, then the Remote Start Delay Timer
temperature and charge fail to stabilise without begins, after which, the load is disconnected.
triggering the fault. The generator will then run off load allowing
If the generator has not started when the the engine a cooling down period.
start button has been released or generator Selecting STOP de-energises the fuel solenoid,
fails once it is running, the key switch must bringing to stop.
be turned to stop (0) and then back to hand
position before another start cn be invoked. 7.2.2 Automatic Mode Of Operation
Check the alternator output voltage and
frequency and engine oil pressure, engine This mode is activated by pressing the A U T O
temperature. pushbutton. An LED indicator beside the button
The gen set should run 2-3 minute no load confirms this action. Whether the start sequence
When the engine warm after alternator output is initiated by mains (utility) failure or remote
circuit breaker sholud be ON position. input, the following sequence is followed:
After Start Delays the Fuel Solenoid is energised,
then one second later, Starter Motor is engaged.
The engine is cranked for 10 second period. If
the engine fails to fire during this cranking attempt
then the starter motor is disengaged for a 10
second rest period. Should this sequence continue
beyond the 3 starting attempts, the start sequence
will be terminated and Fail to Start fault
Figure 7.2 will be illuminated. When the engine fires, the
Model DSE 704 module starter motor is disengaged and Safety On timer
activated.
Figure 7.1 If the remote start is being used and has been
Model DSE 701 module configured to Remote start is on load or the
mains has failed, the load will be transferred to
the generator.
On the return of mains supply, (or removal of
the Remote Start signal if the set was started by
remote signal), the Stop delay timer is initiated.
Once it has timed out, the load is transferred
back to the mains (utility). The Cooling timer
expires the Fuel Solenoid is de -energised, bringing
the generator to a stop.
32
7.3 Starting with P2010 Autostart This mode is activated by pressing the
Control Panel AUTO push button. An LED indicator beside
7.3.1 Manual Operation the button confirms this action.
When a Remote Start signal is applied to the
Check the precautions and controls starting remote start input, the following sequence is
up the generating set. initiated:
NOTE: If a digital input configured to panel The Remote Start Active indicator illuminates
lock is active, the LCD will display the (if configured)
icon. When in panel lock, changing modules To allow for false signals the Start Delay timer
will not be possible. is initiated.
Viewing the instruments and event logs After this delay the Fuel Solenoid is energized,
is not affected by panel lock. then one second later, the Starter Motor is
To initiate a start sequence in MANUAL press engaged. The engine is cranked for a pre-set
the pushbutton. When the controller is in time period. If the engine fails to fire during
the manual button), pressing the START (1) this cranking attempt then the strter motor
button will initiate the start sequence. is disengaged for the pre-set period. Should
NOTE: There is no Start Delay in this mode this sequence continue beyond the set number
of operation. of attempts, the start sequence will be
The Fuel Solenoid is energized, then the terminated and Fail to Start fault will
Starter Motor is engaged. The engine is be displayed accompanied by a flashing
cranked for a preset time period. If the engine shutdown symbol.
fails to fire during this cranking attempt then When the engine fires, the starter motor
the starter motor is disengaged for the preset disengaged and locked out at a pre-set frequeny
rest period. Should this continue beyond the from the alternator output. Rising oil pressure
set number of attempts, the start sequence can also be used to disconnect the starter
will be terminated and fail to start fault motor, however it cannot be used for under
will be displayed accompanied by a flashing speed or over speed detection.
shutdown indicator. If an auxiliary output has been selected to give
When the engine fires, the starter motor a load transfer signal, this would then active.
disengaged and locked out at a pre-set frequency On removal of the Remote Start signal, the
from the Alternator output. Rising oil pressure stop delay timer is initiated, once it has timed
can also be used to disconnect the starter out, the Load Transfer is de-energise, removing
motor, however it cannot be used for under the load. The cooling timer is then initiated,
speed or over speed detection. allowing the engine a cooling down period off
The generator will run off load, unless a Remote load before shutting down. Once the Cooling
Start signal is applied, and if Load Transfer has timer expires the Fuel Solenoid is de-energised,
been selected as a control source, the bringing the generator to a stop.
appropriate auxiliary output selected will active. Should the Remote Start signal be re-activated
If the Remote Start signal is removed, the during the cooling down period, the set will
generator will continue to run On load until return on load.
Auto mode is selected. The Remote Stop Delay
Timer will time out, the load is then Scroll Config / LCD display User configurable
disconnected. The generator will then run off button log button LCD indicators
with text insert
load allowing the engine a cooling down period.
Selecting STOP (0) de-energises the Fuel Alarm
Solenoid, bringing the generator to a stop. indicators
33
7.4 Starting with P 2020 Automatic
Control Panel (with AMF)
7.4.1 Manual Operation 7.4.2 Automatic Mode of Operation
Check the precautions and controls starting NOTE: If a digital input configured to panel
up the generating set. lock is active, the LCD will display the
NOTE: If a digital input configured to panel icon. When in panel lock, changing modules
lock is active, the LCD will display the will not be possible.
icon. When in panel lock, changing modules Viewing the instrument and event logs
will not be possible. is not affected by panel lock.
Viewing the instruments and event logs This mode is activated by pressing the
is not affected by panel lock. AUTO push button. An LED indicator beside
To initiate a start sequence in MANUAL press the button confirms this action.
the pushbutton. When the controller is in When a Remote Start signal is applied to the
the manual button), pressing the START (1) remote start input, the following sequence is
button will initiate the start sequence. initiated:
NOTE: There is no Start Delay in this mode The Remote Start Active indicator illuminates
of operation. (if configured)
The Fuel Solenoid is energized, then the To allow for false signals the Start Delay timer
Starter Motor is engaged. The engine is is initiated.
cranked for a preset time period. If the engine After this delay the Fuel Solenoid is energized,
fails to fire during this cranking attempt then then one second later, the Starter Motor is
the starter motor is disengaged continue engaged. The engine is cranked for a pre-set
beyond the set number of attempts, the start time period. If the engine fails to fire during
sequence will be terminated and fail to start this cranking attempt then the starter motor
fault will be displayed accompanied by is disengaged for the pre-set period. Should
a flashing shutdown indicator. this sequence continue beyond the set number
When the engine fires, the starter motor of attempts, the start sequence will be
disengaged and locked out at a pre-set terminated and Fail to Start fault will
frequency from the Alternator output. Rising be displayed accompanied by a flashing
oil pressure can also be used to disconnect shutdown symbol.
the starter motor, however it cannot be When the engine fires, the starter motor
used for under speed or over speed detection. disengaged and locked out at a pre-set
The generator will run off load, unless a frequency from the alternator output. Rising
Remote Start signal is applied, and if Load oil pressure can also be used to disconnect
Transfer has been selected as a control source, the starter motor, however it cannot be used
the appropriate auxiliary output selected will for under speed or over speed detection.
active. If an auxiliary output has been selected to
If the Remote Start signal is removed, the give a load transfer signal, this would then
generator will continue to run On load until active.
Auto mode is selected. The Remote Stop On removal of the Remote Start signal, the
Delay Timer will time out, the load is then stop delay timer is initiated, once it has timed
disconnected. The generator will then run out, the Load Transfer is de-energise,
off load allowing the engine a cooling down removing the load. The cooling timer is then
period. initiated, allowing the engine a cooling down
Selecting STOP (0) de-energises the Fuel period off load before shutting down. Once
Solenoid, bringing the generator to a stop. the Cooling timer expires the Fuel Solenoid
is de-energised, bringing the generator to a
stop.
Should the Remote Start signal be re-activated
during the cooling down period, the set will
return on load.
34
8. GENERAL PRECAUTIONS AND
CONTROLS WHICH MUST BE
7.4.3 Test Operation DONE AFTER STARTING UP
NOTE: If a digital input configured to panel THE GENERATING SET
lock is active, the LCD will display the
Check for any abnormal noise or vibration
icon. When in panel lock, changing modules on the generating set.
will not be possible. Check if the exhaust system has any leakage.
Viewing the instruments and event logs Monitor the generating set operation by
is not affected by panel lock. means of the gauges on the control panel.
To initiate a start sequence in TEST, press Check the engine temperature and oil
pressure by means of the gauges on the panel.
the pushbutton. When the controller is
Oil pressure must reach the normal value 10
in the test mode (indicated by an LED indicator seconds after the generating set operation.
beside the button), pressing the START (1) Monitor the generating set outlet voltage and
button will initiate the start sequence. frequency by means of the gauges on the
NOTE: There is no Start Delay in this mode panel. Check on the voltmeter, if the voltage
of operation. between phases is 400 V and between phase
and neutral is 230 V. Check that the frequency
The Fuel Solenoid is energized, then the
at idle is 51-52 Hz (for 50 Hz operation or
Starter Motor is engaged. The engine is 61-62 Hz for 60 Hz operation) on generating
cranked for a preset time period. If the engine sets with mechanical governors and 50 Hz
fails to fire during this cranking attempt then or 60 Hz on generating sets with electronic
the starter motor is disengaged for the pre- governors. Outlet voltage is adjusted ex-
set rest period. Should this sequence continue factory. Adjustments should be done only by
authorized personnel.
beyond the set number of attempts, the start
If an engine block water heater is not available,
sequence will be terminated and Fail to Start put the generating set under load after
fault will be displayed accompanied by warming with a 10 minute idle run (manual
a flashing shutdown indicator. models).
The generator will continue to run on load Putting the generating set under load must
regardless of the state of the mains supply or be done as follows:
Set the alternator outlet switch on the panel
remote start input until the Auto mode is to ON position.
selected. If Auto mode is selected, and the Set the load switches (or fuses) on the
mains supply is healthy with the remote start distribution panel to ON position one by one.
on load signal not active, then the Remote This way, the generating set cannot be
Stop Delay Timer begins, after which, the suddenly put under full load. Otherwise, the
load is disconnected. The generator will then engine stalling or alternator winding insulation
deformation or burning can occur.
run off load allowing the engine a cooling Set the alternator outlet switch on the circuit
down period. to OFF position before you stop the
Selecting STOP (0) removes the Close generating set.
Generator output (if configured) and de- Continue to run the unloaded diesel engine
energises the Fuel Solenoid, bringing the for the purpose of cooling for 5 minutes and
generator to a stop. then stop.
Never operate the generating set before
Scroll Config /
button log button
LCD display User configurable
LCD indicators
removing any fault, if any.
with text insert
9. STOPPING THE GENERATING SET
Alarm 9.1 At Manual Models:
indicators
Before stopping the generator, alternator
Load
indicators Generator output, circuit braker should be OFF position.
indicators
The genset should run 2-3 minute with no
load.
To stop the generator turn the key switch
to the STOP O position, de-energises key
Stop mode Manual mode Config+ Auto mode
(config.)
Start button
(config enter) (when in manual)
switch the fuel solenoid, bringing the generator
to a stop.
Figure 7. 4 Desription of Controls on DSE5220 module
35
9.2 At Automatic Models: 10.1.1.1 DSE 701 MODULE FEATURES
The genset should run 2-3 minute with no Engine supervision and protection
load. Key switch operation on the fron panel
Selecting STOP O position, de-energises
the fuel solenoid, bringing the generator to 10.1.1.2 DSE 701 MODULE EMERGENCY LEDs
a stop. High engine temperature, shutdown
Low oil pressure, shutdown
10. GENERATING SET CONTROL SYSTEMS Over speed, shutdown
To control and monitor the generating set, Charge failure, warning
an electronic control system has been used.
Depending on the requirements of the set,
one of several different standard control
systems may be fitted. These include ME 40
Model Manual Control panel or P 500, P2020
Auto Mains Failure panel and 2010 Autostart
Panel Control panel provides a means of
starting and stopping the generating set,
monitoring its operation and output, and
automatically shutting down the set in the
event of a critical condition arising such as
low oil pressure or high engine temperature.
OP
36
10.2.1.1 DSE 704 MODULE FEATURES 10.3.1 AUTOMATIC CONTROL SYSTEM
Three phases mains sensing P 2020 PANEL SPECIFICATIONS
Engine protection Control with DSE 5220 Full Automatic Mains
Automatic engine starting and stopping Failure Module
Simple push button controlled operation Static Battery Charger
Stop-Reset/Manual/Auto Emergency stop shutdown push button
Micro processor based design
Configurable via front panel
Configurable timer setting
Adjustable mains fail voltage level
Mains/Generator, change-over contactor
control
External remote start input
N CY
GE
ST
EMER
OP
Figure 10.5 P 2020 Automatic Control Panel
37
Multiple Alarms 10.4.1.1 DSE 5210 MODULE FEATURES
Under/over generator volts; Pre-Alarm and Automatic start and stop the genset
Shutdown Provides signal to Load Transfer
Under/over generator frequency; Pre-Alarm Remote communication via RS 232 port or
and Shutdown RS 485 modbus output.
Under/over mains volts Front panel programming of the module
Under/over mains frequency settings
Over current; Shutdown Scrolling digital LCD display
Low oil pressure; Pre-Alarm and Shutdown Event logging of shutdown alarms
High engine temperature; Pre-Alarm and Easy pushbutton control
Shutdown Stop/Reset, Auto, Manual, Test
Under/over speed; Shutdown
Low coolant level; Shutdown Metering via LCD display with the
Fail to start; Shutdown following instrumentation displays
Fail to stop; Warning Generator volts (F-F / F-N)
Low/High Battery volts; Warning Generator amperes (L1, L2, L3)
Charge fail; Warning Generator frequency (Hz)
Emergency stop; Shutdown Generator kVA
Can Data Fail; Shutdown Generator kW
Can ECU Fail; Pre-Alarm and Shutdown Generator Cosj
Engine oil pressure (PSI & Bar)
The Event Log Engine coolant temperature (ºC&ºF)
5220 control module maintains a log of the Engine speed RPM
last 15 shutdown alarms to enable the Engine hours run
operator or engineer to view the past alarms Plant battery volts
history.
N CY
GE
ST
EMER
OP
38
Multiple Alarms 10.5.4 Frequency Meter
Under/over generator volts; Pre-Alarm and A meter that indicates the output frequency
Shutdown of the generating set. The engine maintain a
Under/over generator frequency; Pre-Alarm relatively constant speed under governor
and Shutdown control so as to provide the proper operating
Over current; Shutdown frequency of 50 Hz or 60 Hz when the
Low oil pressure; Pre-Alarm and Shutdown generating set is operating at full load. In
High engine temperature; Pre-Alarm and practice, if the generating set has a manual
Shutdown governor control system, no load frequencies
Under/over speed; Shutdown of approximately 52 62 Hz for 50 Hz and 60
Low coolant level; Shutdown Hz respectively, are considered. The frequencies
Fail to start; Shutdown will fall, as the set is loaded, to 50 Hz and 60
Fail to stop; Warning Hz at full load.
Low / High Battery volts; Warning
Charge fail; Warning 10.5.5 Hours Run Meter
Emergency stop; Shutdown
A meter that indicates the total number of
The Event Log hours of generating set operation to aid in
maintenance.
5220 control module maintains a log of the
last 15 shutdown alarms to enable the operator 10.5.6 Water Temperature Gauge
or engineer to view the past alarms history.
A temperature gauge connected to a sensor
10.5 Panel Equipments in the engine to monitor engine coolant
temperature. Normal level of the engine coolant
Before starting or running the generating set, temperature is approximately 85ºC (185ºF).
the operator should become fully acquainted
with the instruments and controls. The 10.5.7 Oil Pressure Gauge
instuments should be observed from time to
time while the generating set is running so that A gauge to monitor engine oil pressure from
any abnormal readings can be detected before the moment the engine is cranked. On cold
problems arise. Some of our standard manual engines the oil pressure will be significantly
and automatic control panels are shown in higher until the engine warms up.
figures 10.1, 10.3, 10.5 and 10.7. In addition
optional equipment items can be added to the 10.5.8 Emergency Stop Pushbutton
panel so the panel fitted on the generating set
may be slightly different from the typical ones A red lockdown pushbutton that immediately
shown. shut dow the generating set and will inhibit
start until the pushbutton has been released
10.5.1 Ac Voltmeter by turning it.
A voltmeter that indicates the AC voltage 10.5.9 Alternator Protection
generated at the alternator output terminals.
The reading indicated on the voltmeter will In our standard production, the alternators in
vary depending on the connections made inside automatic operation generating sets are
the alternator terminal box, the setting of the protected with a thermic protector against
voltage regulator and the position of the overload (with P 500 control panel).
voltmeter selector switch. In our standard production of manual operated
generating sets, the alternators are protected
10.5.2 Voltmeter Selector Switch against overload and short circuit by a thermic
magnetic switch and then the generating set is
A selector switch allowing the operator to given load.
select voltage reading between phases.
10.5.3 AC Ammeter
An ammeter that indicates the AC electrical
current being delivered which is dependend
on the connected load. There are three
ammeters.
39
10.9 ICONS AND LCD IDENTIFICATION ON
DSE 5210 and DSE 5220 MODULE
v
Under Voltage
(DC) Under-speed Hz Under Frequency
40
11. THE PLACEMENT AND INSTALLATION
OF TRANSFER SWITCH
The placement of the transfer switch and its Current from one phase should not exceed
mountings: the nominal current. Two different power
Position the transfer switch near the emergency cables, which will be used between the
power panel. generating set and the transfer switch is on
Locate the transfer switch in a place where it the generating set. (Main supply cable and
is clean, not over-heated, and having a good power cable for emergency power panel)
ventilation. If the environment temperature is If the transfer switch panel is apart from the
above 40 °C, fuses and breakers will open generating set, transfer switch must be placed
more easily. There must be enough working as close as possible to the distributor panel.
place around the transfer switch. In this case power cables are drawn from
Having a fuse or breaker between the generating generating set, mains panel and emergency
set and the transfer switch is optional. power panel. Furthermore 8 x 2.5 mm control
(Connection cables used in transfer switch). cable must be drawn from the generating set
Currents from the generating set must be control panel.
distributed equally to the three phase if possible.
Current from one phase should not exceed
the nominal current.
MAINS
GENERATING SET
MAINS
BREAKER
EMERGENCY
TRANSFER
OVER CURRENT SWITCH
PROTECTION
OTHER
41
12. DSE 530 MODEL FULL AUTOMATIC
TRANSFER SWITCH CONTROL SYSTEM
Control of the DSE 530 module is by a four position 12.2 Manual Restore Mode Of Operation
rotary key-switch, mounted on the front of the If the module is placed in
module with Auto, Auto with Manual Restore and AUTO
Manual Restore mode, it will mon-
Manual Run On Load and Off-Load position. itor the incoming mains supply. Should the incoming
mains supply fail (or fall outside of pre-set limits),
the following sequence will occur like automatic
mode until the generator close signal will be supplied
and run on load.
On return of the mains supply to within limits, the
mains return delay timer is initiated, once the timer
expires the 530 module will wait for a manual
restore to mains. This is achieved by placing the
keyswitch control into the auto position, the se-
quence will then continue as described in auto
mode of operation.
Figure: 7.10 DSE 530 Automatic Transfer 12.3 Manual Operation
Switch Control Module To initiate a start sequence
12.1 Automatic Mode Of Operation in manual, turn the selector switch to
Start and Run Generator Off Load. The start and
AUTO If the module is placed in run generator output relay is de-energised and the
AUTO mode, it will monitor the in- relay contacts close, givin a Remote Start signal to
coming mains supply. Should the incoming mains the engine starting controller.
supply fail, the following sequence will occur. The engine stating controller should now start the
The module will start its Start Delay timer, this generator, the 530 module will monitor the gener-
is used to ensure that the start event is really ator voltage and frequency and on the monitored
required and the failure is notjust a momentary dip values are above a pre-set Loading level the
in the supply. Once this timer has expired the generator will become available.
module will continue with its normal sequence.
If the mains supply returns to within limits during To transfer the load from the
the start delay timer the unit will retun to a stand- mains supply to the generator, turn
by state. the selector switch to Start and Run generator
The start and run generator output relay is de- On Load.
energised and the relay contacts close, giving a To stop the generator return the selector switch
Remote Start signal to the engine starting con- to the Auto position. The sequence will then continue
troller. as described in auto mode of operation.
The engine starting controller (DSE 560, etc.) will
now start the generator, the 530 module monitor 12.4 INDICATIONS
the generator voltage and frequency (and an optional The module status is indicated by front panel LEDs.
generator ready input) and once the monitored Mains Available LED: Indicates that the incoming
values are above a pre-set Loading level the AC mains supply is within limits and available o
generator will become available. This is indicated supply the load.
by the illumination of the appropriate LED on the Generator Available LED: Indicates that the
mimic diagram. generator output voltage and frequency are within
As soon as the generator is available the transfer acceptable limits and available to supply the load.
timer is initiated (3 second). Once the transfer Generator On Load LED: Indicates that the
timer has expired, the generator close signal will generator close signal has been supplied.
be supplied and run on load. Alternatively it can be configured to give true
On return of the mains supply to within limits, the indication of load switching device status
mains return delay timer is initiated, once the timer Mains On Load LED: As above but with respect
expires the generator close signal is removed, to the mains.
removing the load. The cooling timer is then initiated, Auxiliary LEDs: Use PC808 software to configure
allowing the engine a cooling down period off load function.
before shutting down. Start Delay Active LED: Indicates that the 530
Should the mains fall out of limits during the cooling internal start delay timer is running. Once expired
down period, the set will return on load after the the start signal will be given to the generator
start delay timer has expired. controller.
Mains Return Timer Active LED: Indicates
that the 530s internal mains return timer is running.
Once expired the load will be transferred back to
the mains supply.
42
13. ALTERNATOR TROUBLESHOOTING
Higher than rated voltage Voltage potentiometer out of setting Reset voltage potentiometer
at load Failed regulator Substitude regulator
Unstable voltage Speed variation in engine Check regularity of rotation
Regulator out of setting Regulate stability of regulator by
acting on stability potentiometer
43
14. ENGINE TROUBLESHOOTING
The starter motor turns the engine too slowly: Restriction in fuel tank vent
Battery capacity to low Wrong type or grade of fuel used
Bad electrical connection Restriction in exhaust pipe
Fault in starter motor
Wrong grade of lubrication Not enough power:
Restriction in a fuel pipe
The engine does not start or difficult to start: Fault in fuel lift pump
Starter motor turns engine too showly Dirty fuel filter element
Fuel tank empty Air in fuel system
Fault in fuel control solenoid Restriction air filter/cleaner or induction system
Restriction in a fuel pipe Fault in atomisers or atomisers of an incorrect type
Fault in fuel lift pump Restriction in exhaust pipe
Dirty fuel filter element Restriction in fuel tank vent
Air in fuel system Wrong type or grade of fuel used
Fault in atomsers Restricted movement of engine speed control
Cold start systems used incorrectly Engine temperature is too high or low
Fault in cold start system
44
GENERAL PRECAUTIONS ABOUT WARRANTY
PLEASE TAKE CARE TO THE FOLLOWING IN ORDER TO PREVENT THE GENERATING SET WARRANTY
TO BECOME INVALID BEFORE THE TERMINATION OF THE WARRANTY PERIOD AND TO ENSURE
TROUBLE-FREE OPERATION OF THE GENERATING SET WITH A LONG LIFE!...
MAINTENANCE AND REPAIR WORKS WILL NOT BE COVERED BY THE WARRANTY UNLESS THE
WARRANTY CERTIFICATE, INVOICE OR DELIVERY CERTIFICATE OF THE GENERATING SET IS SUBMITTED.
THE WARRANTY OF THE GENERATING SET WILL BECOME INVALID IN CASE OF ANY INTERVENTION
OF ANY PERSON OTHER THAN AUTHORIZED AKSA SERVICES OR BY PRIOR WRITTEN APPROVAL FROM
AKSA POWER GENERATION ON THE GENERATING SET FOR ANY REASON.
CONTROL AND MAINTENANCE WORKS INDICATED IN THE PERIODICAL MAINTENANCE SCHEDULE AND
THE OPERATING MANUAL MUST BE CARRIED OUT COMPLETELY AND TIMELY. THE FAILURES DUE TO
INCOMPLETE OR UNTIMELY MAINTENANCE ARE NOT COVERED BY THE WARRANTY.
CUSTOMER IS RESPONSIBLE FOR THE FAILURES WHICH ARE LIKELY TO OCCUR IN CASE THAT THE
DIESEL OIL USED CONTAINS DIRT OR WATER.
THE OIL TYPE INDICATED IN THE OPERATING MANUAL SHOULD BE USED IN THE ENGINE. OTHERWISE,
THE FAILURES WHICH ARE LIKELY TO OCCUR WILL NOT BE COVERED BY THE WARRANTY.
BATTERIES WILL NOT BE COVERED BY THE WARRANTY IF THEY ARE SUBJECTED TO BREAKAGE,
EXCESSIVE ACID FILL OR HARDENING BY LEAVING UNCHARGED.
ON MODEL KSD 501 MANUAL GENERATING SETS WITH START PANEL, THE IGNITION KEY SHOULD
BE RELEASED IMMEDIATELY AFTER THE ENGINE IS STARTED-UP. IN CASE THAT THE ENGINE DOES
NOT START UP, THE STARTING SEQUENCE SHOULD NOT BE APPLIED MORE THAN 3 TIMES EACH
WITH 10 SECOND INTERVALS. OTHERWISE, STARTING GEAR CAN BE BROKEN OR STARTER MOTOR
CAN BURN. THESE CONDITIONS ARE NOT COVERED BY THE WARRANTY.
ON MANUAL GENERATING SETS, NEVER START OR STOP THE DIESEL ENGINE WHEN THE GENERATING
SET IS UNDER LOAD. ENGINE SHOULD BE STARTED AND STOPPED AFTER LOAD IS DISCONNECTED
AND THE GENERATING SET IS AT IDLE CONDITION. OTHERWISE, THE VALVES CAN BE SEIZED, THE
VOTAGE REGULATOR, TRANSFORMER AND DIODES CAN BE BROKEN DOWN. THESE CONDITIONS ARE
NOT COVERED BY THE WARRANTY.
OUR COMPANY DOES NOT TAKE THE RESPONSIBILITY OF THE DAMAGES ON THE MAINS SUPPLY
CONTACTOR OF THE AUTOMATIC GENERATING SETS DUE TO OVERCURRENT, LOW OR HIGH
VOLTAGE.
NEVER REMOVE THE BATTERY TERMINALS WHILE THE GENERATING SET IS IN USE. EVEN A MOMENT
OF DISCONNECTION CAN CAUSE A DAMAGE ON THE ELECTRONIC CLOSING RELAY OF THE CHARGE
ALTERNATOR AND ON THE ELECTRONIC ENGINE SPEED CONTROL CIRCUIT. THESE CONDITIONS
ARE NOT COVERED BY THE WARRANTY.
FAILURES DUE TO OVERLOAD AND UNBALANCED LOAD IN EXCESS OF THE GENERATING SET POWER
(SUCH AS ALTERNATOR AND CONTACTOR FAILURES) ARE NOT COVERED BY THE WARRANTY.
FAILURES DUE TO OVERLOAD AND UNBALANCED LOAD IN EXCESS OF THE GENERATING SET POWER
(SUCH AS ALTERNATOR AND CONTACTOR FAILURES) ARE NOT COVERED BY THE WARRANTY.
WHEN THE MANUAL GENERATING SET IS STARTED UP, IT SHOULD BE WARMED BY OPERATING AT IDLE
FOR 5 MINUTES. WHEN STOPPING THE DIESEL ENGINE, IT SHOULD BE UNLOADED AND THEN
CONTINUED TO BE OPERATED FOR COOLING FOR 10 MINUTES BEFORE STOPPING. OTHERWISE,
PROBLEMS WHICH ARE LIKELY TO OCCUR WILL NOT BE COVERED BY THE WARRANTY.
45
HEAD OFFICE
Aksa Jeneratör Sanayi A.Þ.
Gülbahar Caddesi 1. Sokak 34212
Güneþli, stanbul - Turkey
Tel: +90 212 478 66 66
Fax: +90 212 657 55 16
E-mail: export@aksa.com.tr
FACTORIES
TURKEY
Gülbahar Caddesi 1. Sokak 34212
Güneþli, stanbul - Turkey
Tel: +90 212 478 66 66
Fax: +90 212 657 55 11
www.aksa.com.tr