Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
COLLEGE OF ENGINEERING
GROUP 2
Submitted to:
Engr. Sinforoso D. Cimatu Jr.
Submitted by:
Kimberly S. Pambid
Trial 6
Trial 4 Trial 5
P.F.= cosθT
P.F.= cosθT P.F.= cosθT
P.F.= cos-54˚
P.F.= cos-3.60˚ P.F.= cos-36˚
P.F.= 0.59
P.F.= 0.99 P.F.= 0.81
PLoad = VLITcosθT
PLoad = VLITcosθT PLoad = VLITcosθT
PLoad = (5.4V)(20.50mA) cos-54˚
PLoad = (5.6V)(11.90mA) cos-3.60˚ PLoad = (5.6V)(14.90mA) cos-3.60˚
PLoad = 87.96mW
PLoad = 86.70mW PLoad = 88mW
2. Plot the graph of the Power Factor (P.F.) against the following quantities:
a. Capacitance CT using the axes suggested in Figure 8.5;
b. Total current IT using the suggested in Figure 8.6;
c. Load voltage VL using the suggested in Figure 8.7;
d. Line losses PLoss using the suggested in Figure 8.8.
1. What generalization can be drawn regarding the plot of Power Factor (P.F.)
against:
a. Capacitance in Figure 8.5?
Regarding the plot of Power Factor against Capacitance in Figure 8.5
there’s a part of the graph where it reaches its peak and it happened when
the power factor is leading and higher among others.
Load 1 Load 2
Q = (70.71kVA)sin45° = 50kVars
PT = 12kW+50kW = 62kW
QT = 16kVars+50kVars = 66kVars
C = 53.41kVars/2π(60)(460)2
C = 669.54uF
The table below contains the results of the experiment and the computed values of
With the data we have gathered the measured values of VS are constant
throughout all the trials while measured values of VL are unstable similar to the total
current. The phase angle from Trial 1 to Trial 6 decreases. PLoad increases when the power
factor changed from lagging to leading and PLoss starts to decrease when the power factor
is lagging away from zero and starts to increase when the power factor is leading
approaching zero. The power factor is said to be lagging when the phase angle is positive
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf