7TH FLOOR C1 (G.L. D&E/3,5,7&9) 8pcs. 7TH FLOOR C1A (G.L. K&L/3,5,7&9) 4pcs.

COLUMN C1A SECTION - A

COLUMN C1 REINFORCEMENT COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT

COLUMN C1A REINFORCEMENT COLUMN C1A SECTION - B COLUMN C1A 3D VIEW REINFORCEMENT

BAR SCHEDULE

Elements Number Hooks


Total
Bar Symbol E/R H1 H2 Total mass
Diameter Length (mm) length A (mm) B (mm) C (mm) D (mm) Mass (kg)
BAR SCHEDULE Mark per (mm) (mm) (mm) (mm) (kg)
Name Number total (mm) L R
element
Elements Number Hooks
Total A
Bar Length E/R H1 H2 Total 1 25 4850 4 16 77600 4850 0 0 298.76
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R A
element 2 25 3740 16 64 239360 3570 240 1 0 921.54

h2
A A
1 25 4850 20 240 1164000 4850 0 0 4481.40 3 25 2750 12 48 132000 2750 0 0 508.20
h
C1A 4 h
2293.22
A

A
2 10 3460 17 204 705840 940 740 80 80 2 2 435.50 4 10 3460 17 68 235280 940 740 80 80 2 2 145.17 BAR LOCATION
B B
C1 12 h
6175.58 h
BAR MARK
SPACING
A

A
3 10 2380 34 408 971040 400 740 80 80 2 2 599.13 5 10 2620 34 136 356320 940 320 80 80 2 2 219.85
B B BAR DIAMETER
B h NO OF BARS

A
4 10 2620 34 408 1068960 940 320 80 80 -2 -2 659.55 6 10 2380 34 136 323680 400 740 80 80 2 2 199.71
A

h B BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

COLUMN REINF.DETAIL-1
7TH FLOOR (C1,C1A)
7TH FLOOR LEVEL

SD-4366 0
8TH FLOOR C1 (G.L. D,E,K/G.L. 3,5,7,9) 12pcs. 8TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

COLUMN C1 REINFORCEMENT COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT COLUMN C5 SECTION - A COLUMN C5 3D VIEW REINFORCEMENT

COLUMN C5 REINFORCEMENT
BAR SCHEDULE BAR SCHEDULE
Elements Number Hooks Elements Number Hooks
Total Total
Bar Length E/R H1 H2 Total Bar Length E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) Mark (mm) per (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R Name Number total (mm) L R
element element
A
1 25 4850 20 240 1164000 4850 0 0 4481.40 1 25 4850 16 64 310400
A
4850 0 0 1195.04
h
h
A

2 10 3460 17 204 705840 940 740 80 80 2 2 435.50

A
B
2 10 2460 17 68 167280 740 440 80 80 2 2 103.21
B
C1 12 h
6180.62 C5 4 1495.44
h
A

3 10 2390 34 408 975120 410 740 80 80 2 2 601.65

A
B
3 10 1960 17 68 133280 740 190 80 80 2 2 82.23
B
B
B
4 10 2630 34 408 1073040 940 330 80 80 -2 -2 662.07
A

4 10 1370 34 136 186320 200 440 80 80 -2 -2 114.96

A
h
h

BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

COLUMN REINF.DETAIL-1
8TH FLOOR(C1,C5)
8TH FLOOR LEVEL

SD-4406 0
9TH FLOOR C1 (G.L. D,E,K/G.L. 3,5,7,9) 12pcs. 9TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

COLUMN C1 REINFORCEMENT COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT COLUMN C5 REINFORCEMENT COLUMN C5 SECTION - A COLUMN C5 3D VIEW REINFORCEMENT

BAR SCHEDULE BAR SCHEDULE

Elements Number Hooks Elements Number Hooks


Total Total
Bar Length E/R H1 H2 Total Bar Length E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) Mark (mm) per (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R Name Number total (mm) L R
element element

A A
1 25 4850 20 240 1164000 4850 0 0 4481.40 1 25 4850 16 64 310400 4850 0 0 1195.04
h h

A
2 10 2460 17 68 167280 740 440 80 80 2 2 103.21
A

2 10 3460 17 204 705840 940 740 80 80 2 2 435.50 B


B
C1 12 h
6180.62 C5 4 h
1495.44

A
3 10 1960 17 68 133280 740 190 80 80 2 2 82.23
A

3 10 2390 34 408 975120 410 740 80 80 2 2 601.65 B


B
B B

4 10 2630 34 408 1073040 940 330 80 80 -2 -2 662.07 4 10 1370 34 136 186320 200 440 80 80 -2 -2 114.96

A
A

h h

BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

COLUMN REINF.DETAIL-1
9TH FLOOR(C1,C5)
9TH FLOOR LEVEL

SD-4446 0
10TH FLOOR C1 (G.L. D,E,K/G.L. 3,5,7,9) 12pcs. 10TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

COLUMN C1 REINFORCEMENT COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT COLUMN C5 REINFORCEMENT COLUMN C5 SECTION - A COLUMN C5 3D VIEW REINFORCEMENT

BAR SCHEDULE BAR SCHEDULE


Elements Number Hooks Elements Number Hooks
Total Total
Bar Length E/R H1 H2 Total Bar Length E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) Mark (mm) per (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R Name Number total (mm) L R
element element
A
1 25 4850 20 240 1164000 4850 0 0 4481.40 1 25 4850 16 64 310400
A
4850 0 0 1195.04
h h
10 3460 204 705840 940 740 80 80 435.50
A

2 17 2 2

A
B
2 10 2460 17 68 167280 740 440 80 80 2 2 103.21
B
C1 12 h
6180.62 C5 4 1495.44
h
3 10 2390 34 408 975120 410 740 80 80 601.65
A

2 2

A
B
3 10 1960 17 68 133280 740 190 80 80 2 2 82.23
B
B B
4 10 2630 34 408 1073040 940 330 80 80 -2 -2 662.07 4 10 1370 34 136 186320 200 440 80 80 -2 -2 114.96
A

A
h h

BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

COLUMN REINF.DETAIL-1
10TH FLOOR(C1,C5)
10TH FLOOR LEVEL

SD-4486 0
11TH FLOOR C1 (G.L. D,E,K/G.L. 3,5,7,9) 12pcs. 11TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

COLUMN C1 3D VIEW REINFORCEMENT COLUMN C5 REINFORCEMENT COLUMN C5 SECTION - A COLUMN C5 3D VIEW REINFORCEMENT
COLUMN C1 REINFORCEMENT COLUMN C1 SECTION - A

BAR SCHEDULE BAR SCHEDULE


Elements Number Hooks Elements Number Hooks
Total Total
Bar Length E/R H1 H2 Total Bar Length E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) Mark (mm) per (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R Name Number total (mm) L R
element element
A A
1 25 4850 20 240 1164000 4850 0 0 4481.40 1 25 4850 16 64 310400 4850 0 0 1195.04
h h
A

2 10 3460 17 204 705840 940 740 80 80 2 2 435.50

A
B
2 10 2460 17 68 167280 740 440 80 80 2 2 103.21
B
C1 12 h
6180.62 C5 4 h
1495.44
A

3 10 2390 34 408 975120 410 740 80 80 2 2 601.65

A
B
3 10 1960 17 68 133280 740 190 80 80 2 2 82.23
B
B B
4 10 2630 34 408 1073040 940 330 80 80 -2 -2 662.07 4 10 1370 34 136 186320 200 440 80 80 -2 -2 114.96
A

A
h h

BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

COLUMN REINF.DETAIL-1
11TH FLOOR(C1,C5)
11TH FLOOR LEVEL

SD-4526 0
12TH FLOOR C1 (G.L. D,E,K/G.L. 3,5,7,9) 12pcs. 12TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

COLUMN C1 REINFORCEMENT COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT COLUMN C5 REINFORCEMENT COLUMN C5 SECTION - A COLUMN C5 3D VIEW REINFORCEMENT

BAR SCHEDULE BAR SCHEDULE

Elements Number Hooks Elements Number Hooks


Total Total
Bar Length E/R H1 H2 Total Bar Length Symbol E/R
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Diameter length A (mm) B (mm) C (mm) D (mm) H1 (mm)H2 (mm) Mass (kg) Total mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) Mark (mm) per (mm) (mm)
Name Number total (mm) L R Name Number total (mm) L R
element element

A A
1 25 4850 20 240 1164000 4850 0 0 4481.40 1 25 4850 16 64 310400 3550 700 1300 0 0 1195.04

B
C

h h
A

A
2 10 3460 17 204 705840 940 740 80 80 2 2 435.50 2 10 2460 17 68 167280 740 440 80 80 2 2 103.21
B B
C1 12 h
6180.62 C5 4 h
1492.93
A

A
3 10 2390 34 408 975120 410 740 80 80 2 2 601.65 3 10 1940 17 68 131920 740 180 80 80 2 2 81.39
B B
B B
4 10 2630 34 408 1073040 940 330 80 80 -2 -2 662.07 4 10 1350 34 136 183600 190 440 80 80 -2 -2 113.28
A

A
h h

BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

COLUMN REINF.DETAIL-1
12TH FLOOR(C1,C5)
12TH FLOOR LEVEL

SD-4566 0
13TH FLOOR C1 (G.L. D,E/G.L. 3,5,7,9) 8pcs. 13TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

BEAM B1"

BEAM B1"

BEAM B1"

COLUMN C1 REINFORCEMENT COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT

BAR SCHEDULE BAR SCHEDULE


Elements Number Hooks Elements Number Hooks
Total
Bar Length E/R H1 H2 Total Bar Length Total length Symbol E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Diameter A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) Mark (mm) per (mm) (mm) (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R Name Number total L R
element element
A
1 25 4850 20 160 776000 4850 0 0 2987.60 1 25 4920 16 64 314880
A
4920 0 0 1212.29
h h
A

2 10 3460 17 136 470560 940 740 80 80 2 2 290.34

A
B
2 10 2460 15 60 147600 740 440 80 80 2 2 91.07
B
C1 8 h
4120.41 C5 4 1477.35
h
A

3 10 2390 34 272 650080 410 740 80 80 2 2 401.10

A
B
3 10 1960 15 60 117600 740 190 80 80 2 2 72.56
B
B B
4 10 2630 34 272 715360 940 330 80 80 -2 -2 441.38
A

4 10 1370 30 120 164400 200 440 80 80 -2 -2 101.43

A
h
h

13TH FLOOR C1 (G.L. K/G.L. 3,5,7,9) 4pcs.


BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

BEAM B1"

BEAM B1"

COLUMN C1A REINFORCEMENT COLUMN C1A SECTION - A COLUMN C1A 3D VIEW REINFORCEMENT

BAR SCHEDULE
Elements Number Hooks COLUMN REINF.DETAIL-1
Total
Bar Length E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) 13TH FLOOR(C1,C5)
Mark (mm) per (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R
element 13TH FLOOR LEVEL
A
1 25 4850 20 80 388000 4850 0 0 1493.80
h
2 10 3460 15 60 207600 940 740 80 80 2 2 128.09
A

B
C1A 4 1993.57
3 10 2390 30 120 286800
h
410 740 80 80 2 2 176.96 SD-4606 0
A

B
B
4 10 2630 30 120 315600 940 330 80 80 -2 -2 194.73
A

h
14TH FLOOR C1 (G.L. D,E,K/G.L. 3,5,7,9) 12pcs. 14TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT


COLUMN C1 REINFORCEMENT

BAR SCHEDULE BAR SCHEDULE


Elements Number Hooks Elements Number Hooks
Total
Bar Length E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Bar Length Total length Symbol E/R H1 H2 Total
Mark (mm) per (mm) (mm) (mm) mass (kg) Diameter A (mm) B (mm) C (mm) D (mm) Mass (kg)
Name Number total (mm) L R Mark (mm) per (mm) (mm) (mm) (mm) (mm) mass (kg)
element Name Number total L R
element
A
1 25 4850 20 240 1164000 4850 0 0 4481.40 1 25 4920 16 64 314880
A
4920 0 0 1212.29
h
A

2 10 3460 17 204 705840 940 740 80 80 2 2 435.50 10 2460 68 167280


h
740 440 80 80 103.21

A
B 2 17 2 2
C1 12 6180.62 B
h C5 4 1512.69
A

3 10 2390 34 408 975120 410 740 80 80 2 2 601.65 h

A
B 3 10 1960 17 68 133280 740 190 80 80 2 2 82.23
B
B
B
4 10 2630 34 408 1073040 940 330 80 80 -2 -2 662.07
A

4 10 1370 34 136 186320 200 440 80 80 -2 -2 114.96

A
h
h

BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

COLUMN REINF.DETAIL-1
14TH FLOOR(C1,C5)
14TH FLOOR LEVEL

SD-4646 0
15TH FLOOR C1 (G.L. D,E,K/G.L. 3,5,7,9) 12pcs. 15TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT


COLUMN C1 REINFORCEMENT

BAR SCHEDULE BAR SCHEDULE

Elements Number Hooks Elements Number Hooks


Total
Bar Length E/R H1 H2 Total Bar Length Total length Symbol E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Diameter A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) Mark (mm) per (mm) (mm) (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R Name Number total L R
element element

A A
1 25 4850 20 240 1164000 4850 0 0 4481.40 1 25 4920 16 64 314880 4920 0 0 1212.29
h h

A
2 10 2460 17 68 167280 740 440 80 80 2 2 103.21
A

2 10 3460 17 204 705840 940 740 80 80 2 2 435.50 B


B
C1 12 h
6180.62 C5 4 h
1512.69

A
3 10 1960 17 68 133280 740 190 80 80 2 2 82.23
A

3 10 2390 34 408 975120 410 740 80 80 2 2 601.65 B


B
B B

4 10 2630 34 408 1073040 940 330 80 80 -2 -2 662.07 4 10 1370 34 136 186320 200 440 80 80 -2 -2 114.96

A
A

h h

BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

COLUMN REINF.DETAIL-1
15TH FLOOR(C1,C5)
15TH FLOOR LEVEL

SD-4686 0
16TH FLOOR C1 (G.L. D,E,K/G.L. 3,5,7,9) 12pcs. 16TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT


COLUMN C1 REINFORCEMENT

BAR SCHEDULE BAR SCHEDULE

Elements Number Hooks Elements Number Hooks


Total
Bar Length E/R H1 H2 Total Bar Length Total length Symbol E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Diameter A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) Mark (mm) per (mm) (mm) (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R Name Number total L R
element element

A A
1 25 4850 20 240 1164000 4850 0 0 4481.40 1 25 4920 16 64 314880 4920 0 0 1212.29
h h

A
2 10 2460 17 68 167280 740 440 80 80 2 2 103.21
A

2 10 3460 17 204 705840 940 740 80 80 2 2 435.50 B


B
C1 12 h
6180.62 C5 4 h
1512.69

A
3 10 1960 17 68 133280 740 190 80 80 2 2 82.23
A

3 10 2390 34 408 975120 410 740 80 80 2 2 601.65 B


B
B B

4 10 2630 34 408 1073040 940 330 80 80 -2 -2 662.07 4 10 1370 34 136 186320 200 440 80 80 -2 -2 114.96

A
A

h h

BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

COLUMN REINF.DETAIL-1
16TH FLOOR(C1,C5)
16TH FLOOR LEVEL

SD-4726 0
17TH FLOOR C1 (G.L. D,E/G.L. 3,5,7,9) 8pcs. 17TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

BEAM B1"

BEAM B1"

COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT


COLUMN C1 REINFORCEMENT

BAR SCHEDULE BAR SCHEDULE

Elements Number Hooks Elements Number Hooks


Total
Bar Length E/R H1 H2 Total Bar Length Total length Symbol E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Diameter A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) Mark (mm) per (mm) (mm) (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R Name Number total L R
element element

A A
1 25 4850 20 160 776000 4850 0 0 2987.60 1 25 4920 16 64 314880 4920 0 0 1212.29
h h

A
2 10 2460 17 68 167280 740 440 80 80 2 2 103.21
A

2 10 3460 17 136 470560 940 740 80 80 2 2 290.34 B


B
C1 8 h
4120.41 C5 4 h
1512.69

A
3 10 1960 17 68 133280 740 190 80 80 2 2 82.23
A

3 10 2390 34 272 650080 410 740 80 80 2 2 401.10 B


B
B B

4 10 2630 34 272 715360 940 330 80 80 -2 -2 441.38 4 10 1370 34 136 186320 200 440 80 80 -2 -2 114.96

A
A

h h

17TH FLOOR C1 (G.L. K/G.L. 3,5,7,9) 4pcs.


BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

BEAM B1"

BEAM B1"

COLUMN C1A REINFORCEMENT COLUMN C1A SECTION - A


COLUMN C1A 3D VIEW REINFORCEMENT

BAR SCHEDULE

Elements Number Hooks


Total COLUMN REINF.DETAIL-1
Bar Length E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) 17TH FLOOR(C1,C5)
Name Number total (mm) L R
element
17TH FLOOR LEVEL
A
1 25 4850 20 80 388000 4850 0 0 1493.80
h
A

2 10 3460 15 60 207600 940 740 80 80 2 2 128.09


B
C1A 4 h
1993.57
SD-4766
A

3 10 2390 30 120 286800 410 740 80 80 2 2 176.96


B
B 0
4 10 2630 30 120 315600 940 330 80 80 -2 -2 194.73
A

h
18TH FLOOR C1 (G.L. D,E/G.L. 3,5,7,9) 12pcs. 18TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

BEAM B1"

BEAM B1"

COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT


COLUMN C1 REINFORCEMENT

BAR SCHEDULE BAR SCHEDULE

Elements Number Hooks Elements Number Hooks


Total
Bar Length E/R H1 H2 Total Bar Length Total length Symbol E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Diameter A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) Mark (mm) per (mm) (mm) (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R Name Number total L R
element element

A A
1 25 4850 20 160 776000 4850 0 0 2987.60 1 25 4920 16 64 314880 4920 0 0 1212.29
h h

A
2 10 2460 17 68 167280 740 440 80 80 2 2 103.21
A

2 10 3460 17 136 470560 940 740 80 80 2 2 290.34 B


B
C1 8 h
4120.41 C5 4 h
1512.69

A
3 10 1960 17 68 133280 740 190 80 80 2 2 82.23
A

3 10 2390 34 272 650080 410 740 80 80 2 2 401.10 B


B
B B

4 10 2630 34 272 715360 940 330 80 80 -2 -2 441.38 4 10 1370 34 136 186320 200 440 80 80 -2 -2 114.96

A
A

h h

18TH FLOOR C1 (G.L. K/G.L. 3,5,7,9) 4pcs.


BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

BEAM B1"

BEAM B1"

COLUMN C1A REINFORCEMENT COLUMN C1A SECTION - A COLUMN C1A 3D VIEW REINFORCEMENT

BAR SCHEDULE
Elements Number Hooks
Length
Total
E/R H1 H2 Total
COLUMN REINF.DETAIL-1
Bar
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) 18TH FLOOR(C1,C5)
Mark (mm) per (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R
element 18TH FLOOR LEVEL
A
1 25 4850 20 80 388000 4850 0 0 1493.80
h
A

2 10 3460 15 60 207600 940 740 80 80 2 2 128.09


B
C1A 4 h
1993.57
SD-4806 0
A

3 10 2390 30 120 286800 410 740 80 80 2 2 176.96


B
B
4 10 2630 30 120 315600 940 330 80 80 -2 -2 194.73
A

h
19TH FLOOR C1 (G.L. D,E,K/G.L. 3,5,7,9) 12pcs. 19TH FLOOR C5 (G.L. L/G.L. 3,5,7,9) 4pcs.

COLUMN C1 REINFORCEMENT COLUMN C1 SECTION - A COLUMN C1 3D VIEW REINFORCEMENT COLUMN C5 REINFORCEMENT COLUMN C5 SECTION - A COLUMN C5 3D VIEW REINFORCEMENT

BAR SCHEDULE BAR SCHEDULE

Elements Number Hooks Elements Number Hooks


Total
Bar Length E/R H1 H2 Total Bar Length Total length Symbol E/R H1 H2 Total
Diameter length Symbol (mm) A (mm) B (mm) C (mm) D (mm) Mass (kg) Diameter A (mm) B (mm) C (mm) D (mm) Mass (kg)
Mark (mm) per (mm) (mm) (mm) mass (kg) Mark (mm) per (mm) (mm) (mm) (mm) (mm) mass (kg)
Name Number total (mm) L R Name Number total L R
element element
A
1 25 3800 20 240 912000 3570 300 1 0 3511.20 1 25 3820 10 40 152800 3570 300 0 0 588.28
h2

B
A

h A
A

2 10 3460 17 204 705840 940 740 80 80 2 2 435.50 2 25 3840 6 24 92160 3590 3530 300 0 0 354.82

B
B C
C1 12 h
5210.42 h
A

A
3 10 2390 34 408 975120 410 740 80 80 2 2 601.65 C5 4 3 10 2460 17 68 167280 740 440 80 80 2 2 103.21 1243.50
B B
B h

A
4 10 2630 34 408 1073040 940 330 80 80 -2 -2 662.07 4 10 1370 34 136 186320 200 440 80 80 2 2 114.96
A

h B

A
5 10 1960 17 68 133280 740 190 80 80 2 2 82.23
B

BAR LOCATION
BAR MARK
SPACING
BAR DIAMETER
NO OF BARS
BAR ID

Registration
Number 15

P. O. Box: 3082
AL-SRAIYA Engineering Consultants DOHA QATAR.
Tel. - 4411800
GRADE "A" Fax. - 4425909
CONS. ENG. ( 776 ) E-Mail:
( Executive General Manager )

COLUMN REINF.DETAIL-1
19TH FLOOR(C1,C5)
19TH FLOOR LEVEL

SD-4846 0