EARTH RESISTANCE TEST CERTIFICATE

Client : - Leisure World Water Park -

Site Address : - Kaluaggala

Date : - 02.06.2010
Equipment Used : - Digital Earth Resistance Tester, KYORITSU- Model 4105A
Principle of : - This instrument makes earth resistance measurement with fall-of-potential
Measurement method, which is a method to obtain earth resistance value Rx by applying AC
constant current I between the measurement object E (earth electrode) and C
(current electrode), and finding out the potential difference V between E and P
(potential electrode). Rx = V / I

Constant Current Generator


~
Voltmeter
V
V=Rx x 1 P (Potential) C (Current)

Rx = V / I
E (Earth)

Procedure : - The auxiliary earth spikes P and C were sticked into the ground deeply. They
have been aligned at an interval of 5-10 m from the Inspection point tested. The
green wire was connected to the inspection point, the yellow wire to the
auxiliary spike P and the red wire to the auxiliary earth spike C from terminals
E, P and C of the instrument in order.

Earth Resistance Value:-

01, Measure the earth resistance of the electrical earth electrode at the
Entrance Building 7.8 ohms

02, Measure the earth resistance of the electrical earth electrode at the
02 Shop 19.6 ohms

03, Measure the earth resistance of the electrical earth electrode at the
03 Shop 6.78 ohms
Please purchase PDFcamp Printer on http://www.verypdf.com/ to remove this watermark.
04, Measure the earth resistance of the electrical earth electrode at the
Entrance Toilet Block 7.64 ohms

05, Measure the earth resistance of the electrical earth electrode at the
02 Shop 6.45 ohms

06, Measure the earth resistance of the electrical earth electrode at the
Swing around 122.7 ohms

07, Measure the earth resistance of the electrical earth electrode at the
Kiddies pool area 57.1 ohms

08, Measure the earth resistance of the electrical earth electrode at the
Kiddies pool area 73.9 ohms

09, Measure the earth resistance of the electrical earth electrode at the
slide area 12.64 ohms

10, Measure the earth resistance of the electrical earth electrode at the
Toilet block 5.45 ohms

11, Measure the earth resistance of the electrical earth electrode at the
Toilet block 22.2 ohms

12, Measure the earth resistance of the electrical earth electrode at the
Pump Room 01 11.26 ohms

13, Measure the earth resistance of the electrical earth electrode at the
Pump Room 02 10.40 ohms

14, Measure the earth resistance of the electrical earth electrode at the
Changing room 8.96 ohms

15, Measure the earth resistance of the electrical earth electrode at the
Changing Room 6.2 ohms

16, Measure the earth resistance of the electrical earth electrode at the
Filter/machine room at wave pool 2.8 ohms

17, Measure the earth resistance of the electrical earth electrode at the
Wave pool 178 ohms

18, Measure the earth resistance of the electrical earth electrode at the
Crescent awing 157 ohms

19, Measure the earth resistance of the electrical earth electrode at the
Creasing swing 11.17 (CSU) ohms

20, Measure the earth resistance of the electrical earth electrode at the
UFO Machine 95.2 ohms

21, Measure the earth resistance of the electrical earth electrode at the
Log flume filter room 45.00 ohms

22, Measure the earth resistance of the electrical earth electrode at the
Flume control room 1.2 ohms
Please purchase PDFcamp Printer on http://www.verypdf.com/ to remove this watermark.

23, Measure the earth resistance of the electrical earth electrode at the
Flume pool area 42.00 ohms

24, Measure the earth resistance of the electrical earth electrode at the
Open theatre 144 ohms

25, Measure the earth resistance of the electrical earth electrode at the
Open theatre 11.19 ohms

26, Measure the earth resistance of the electrical earth electrode at the
Admin building 7.17 ohms

27, Measure the earth resistance of the electrical earth electrode at the
Admin building 38.9 ohms

28, Measure the earth resistance of the electrical earth electrode at the
PH 4.58 ohms

29, Measure the earth resistance of the electrical earth electrode at the
01 Shop 19.6 ohms

30, Measure the earth resistanc of the electrical earth electrode at the
Entrance building 8.18 ohms

We certify that above earth resistance test values are true and correct.

Athula Jayarathne Nalin d Fernando


Managing Director Asst Project Manager