Date : - 02.06.2010
Equipment Used : - Digital Earth Resistance Tester, KYORITSU- Model 4105A
Principle of : - This instrument makes earth resistance measurement with fall-of-potential
Measurement method, which is a method to obtain earth resistance value Rx by applying AC
constant current I between the measurement object E (earth electrode) and C
(current electrode), and finding out the potential difference V between E and P
(potential electrode). Rx = V / I
Rx = V / I
E (Earth)
Procedure : - The auxiliary earth spikes P and C were sticked into the ground deeply. They
have been aligned at an interval of 5-10 m from the Inspection point tested. The
green wire was connected to the inspection point, the yellow wire to the
auxiliary spike P and the red wire to the auxiliary earth spike C from terminals
E, P and C of the instrument in order.
01, Measure the earth resistance of the electrical earth electrode at the
Entrance Building 7.8 ohms
02, Measure the earth resistance of the electrical earth electrode at the
02 Shop 19.6 ohms
03, Measure the earth resistance of the electrical earth electrode at the
03 Shop 6.78 ohms
Please purchase PDFcamp Printer on http://www.verypdf.com/ to remove this watermark.
04, Measure the earth resistance of the electrical earth electrode at the
Entrance Toilet Block 7.64 ohms
05, Measure the earth resistance of the electrical earth electrode at the
02 Shop 6.45 ohms
06, Measure the earth resistance of the electrical earth electrode at the
Swing around 122.7 ohms
07, Measure the earth resistance of the electrical earth electrode at the
Kiddies pool area 57.1 ohms
08, Measure the earth resistance of the electrical earth electrode at the
Kiddies pool area 73.9 ohms
09, Measure the earth resistance of the electrical earth electrode at the
slide area 12.64 ohms
10, Measure the earth resistance of the electrical earth electrode at the
Toilet block 5.45 ohms
11, Measure the earth resistance of the electrical earth electrode at the
Toilet block 22.2 ohms
12, Measure the earth resistance of the electrical earth electrode at the
Pump Room 01 11.26 ohms
13, Measure the earth resistance of the electrical earth electrode at the
Pump Room 02 10.40 ohms
14, Measure the earth resistance of the electrical earth electrode at the
Changing room 8.96 ohms
15, Measure the earth resistance of the electrical earth electrode at the
Changing Room 6.2 ohms
16, Measure the earth resistance of the electrical earth electrode at the
Filter/machine room at wave pool 2.8 ohms
17, Measure the earth resistance of the electrical earth electrode at the
Wave pool 178 ohms
18, Measure the earth resistance of the electrical earth electrode at the
Crescent awing 157 ohms
19, Measure the earth resistance of the electrical earth electrode at the
Creasing swing 11.17 (CSU) ohms
20, Measure the earth resistance of the electrical earth electrode at the
UFO Machine 95.2 ohms
21, Measure the earth resistance of the electrical earth electrode at the
Log flume filter room 45.00 ohms
22, Measure the earth resistance of the electrical earth electrode at the
Flume control room 1.2 ohms
Please purchase PDFcamp Printer on http://www.verypdf.com/ to remove this watermark.
23, Measure the earth resistance of the electrical earth electrode at the
Flume pool area 42.00 ohms
24, Measure the earth resistance of the electrical earth electrode at the
Open theatre 144 ohms
25, Measure the earth resistance of the electrical earth electrode at the
Open theatre 11.19 ohms
26, Measure the earth resistance of the electrical earth electrode at the
Admin building 7.17 ohms
27, Measure the earth resistance of the electrical earth electrode at the
Admin building 38.9 ohms
28, Measure the earth resistance of the electrical earth electrode at the
PH 4.58 ohms
29, Measure the earth resistance of the electrical earth electrode at the
01 Shop 19.6 ohms
30, Measure the earth resistanc of the electrical earth electrode at the
Entrance building 8.18 ohms
We certify that above earth resistance test values are true and correct.