ALPHA- P
MODBUS-RTU PROTOCOL COMPATIBLE
INSTRUCTIONS MANUAL
DIGITAL PANEL INSTRUMENT FOR PROCESS CONTROL
EDITI ON: 05-09-2006
CODE: 30727008
ALPHA- P
MODBUS-RTU PROTOCOL COMPATIBLE
INTRODUCTION TO THE KOSMOS SERIES
Custom CONFIGURATION for specific applications can be
This manual does not constitute a formal agreement. made quickly and easily through five front panel keys,
All information given in this manual is subject to following structured choice menus aided by display prompts
change without notice. at each programming step.
The instruments CALIBRATION is made at the factory Splash-proof IP65 front cover (Indoor Use).
eliminating the need for adjustment potentiometers.
Any circuit or option liable to be adjusted incorporates a
memory where calibration parameters are stored, making it To guarantee the meter's technical specifications, it is
possible the optional cards be totally interchangeable without recommended to recalibrate the meter at periodical intervals
need of any subsequent adjust. according to the ISO9001 standards for the particular
application operating criteria. Calibration should be performed
at the factory or in a qualified laboratory.
Valid for instruments from s/n 205158
The instruments CALIBRATION is made at the factory Splash-proof IP65 front cover (Indoor Use).
eliminating the need for adjustment potentiometers.
Any circuit or option liable to be adjusted incorporates a
memory where calibration parameters are stored, making it To guarantee the meter's technical specifications, it is
possible the optional cards be totally interchangeable without recommended to recalibrate the meter at periodical intervals
need of any subsequent adjust. according to the ISO9001 standards for the particular
application operating criteria. Calibration should be performed
at the factory or in a qualified laboratory.
Valid for instruments from s/n 205158
2
DIGITAL PANEL INSTRUMENT KOSMOS SERIES
MODEL ALPHA-P
INDEX
1 . MODEL ALPHA-P OVERVIEW ........................................................................................................................................ 4-5
1.1. - KEYBOARD AND DISPLAY DESCRIPTION................................................................................................... 6-7
2 . GETTING STARTED......................................................................................................................................................... 8
2.1 - POWER AND CONNECTORS.......................................................................................................................... 9
2.2 - PROGRAMMING INSTRUCTIONS................................................................................................................. 11
2.3 - INPUT CONFIGURATION ............................................................................................................................ 13
2.4 - DISPLAY CONFIGURATION......................................................................................................................... 17
3 . KEYBOARD AND REMOTE CONTROLS
3.1 - KEYBOARD FUNCTIONS ............................................................................................................................. 30
3.2 - REMOTE FUNCTIONS ................................................................................................................................. 32
3.3 - TABLE OF PROGRAMMABLE FUNCTIONS..................................................................................................... 33
3.4 - REMOTE FUNCTIONS PROGRAMMING ....................................................................................................... 36
3.5 - LOCK OUT PROGRAMMING. ACCESS LEVELS ............................................................................................... 38
4 . OUTPUT OPTIONS ........................................................................................................................................................ 39
4.1 - ADDED FUNCTIONS ................................................................................................................................... 41
5 . TECHNICAL SPECIFICATIONS........................................................................................................................................ 43
5.1 - DIMENSIONS AND MOUNTING ................................................................................................................... 44
6 . WARRANTY .................................................................................................................................................................. 45
7 . DECLARATION OF CONFORMITY ................................................................................................................................... 46
MODEL ALPHA-P
INDEX
1 . MODEL ALPHA-P OVERVIEW ........................................................................................................................................ 4-5
1.1. - KEYBOARD AND DISPLAY DESCRIPTION .................................................................................................. 6-7
2 . GETTING STARTED ........................................................................................................................................................ 8
2.1 - POWER AND CONNECTORS ......................................................................................................................... 9
2.2 - PROGRAMMING INSTRUCTIONS .................................................................................................................11
2.3 - INPUT CONFIGURATION.............................................................................................................................13
2.4 - DISPLAY CONFIGURATION .........................................................................................................................17
3 . KEYBOARD AND REMOTE CONTROLS
3.1 - KEYBOARD FUNCTIONS ..............................................................................................................................30
3.2 - REMOTE FUNCTIONS..................................................................................................................................32
3.3 - TABLE OF PROGRAMMABLE FUNCTIONS .....................................................................................................33
3.4 - REMOTE FUNCTIONS PROGRAMMING ........................................................................................................ 36
3.5 - LOCK OUT PROGRAMMING. ACCESS LEVELS................................................................................................38
4 . OUTPUT OPTIONS.........................................................................................................................................................39
4.1 - ADDED FUNCTIONS....................................................................................................................................41
5 . TECHNICAL SPECIFICATIONS ........................................................................................................................................43
5.1 - DIMENSIONS AND MOUNTING ....................................................................................................................44
6 . WARRANTY...................................................................................................................................................................45
7 . DECLARATION OF CONFORMITY....................................................................................................................................46
3
BCD OUTPUT
BOARD
RS232C or RS485
OUTPUT BOARD
ANALOG OUTPUT
BOARD
SETPOINTS
OUTPUT BOARD
INPUT
BOARD
A/D CONVERTER
CIRCUIT
CASE WITH
POWER FIXING CLIPS
FILTER CIRCUIT
FRONT-PANEL
COVER
DISPLAY MAIN BOARD
BCD OUTPUT
BOARD
RS232C or RS485
OUTPUT BOARD
ANALOG OUTPUT
BOARD
SETPOINTS
OUTPUT BOARD
INPUT
BOARD
A/D CONVERTER
CIRCUIT
CASE WITH
POWER FIXING CLIPS
FILTER CIRCUIT
FRONT-PANEL
COVER
DISPLAY MAIN BOARD
4
1. MODEL ALPHA-P OVERVIEW
The ALPHA-P model incorporates new technical and Standard features of the basic instrument include the reading
functional characteristics including ± 32000 count of the input variable, max and min readings detection, remote
display, signal linearization of up to 30 points and user hold operation, tare function and reset and a full complement
programmable remote logic functions that provides an of programmable logic functions.
extraordinary flexibility to adapt to a w ide range of
indication and control needs. In addition, a variety of plug-in output cards can be installed at
any time to meet further system requirements:
The model ALPHA-P is a digital indicator for measurement and
control of process variables with direct indication in COMMUNICATION
engineering units. RS2 Serial RS232C
The programming software allows selection of the transducer RS4 Serial RS485
type (V, mA, potentiometer), two input levels for voltage BCD BCD 24V/TTL
inputs (1V or 10V), two input levels for current inputs (1mA or
20mA) and two excitation voltages (24V or 10/5V). CONTROL
ANA Analogue 4-20mA, 0-10V
The meter provides two scaling methods (by keyboard or by 2RE 2 SPDT relays 8A
input levels) that make easier the programming task, software 4RE 4 SPST relays 5A*
selectable filtering levels and last digit resolution to help 4OP 4 NPN outputs
stabilizing the display according to the process type. 4OPP 4 PNP outputs
The basic instrument is a soldered assembly composed of the All the outputs are isolated with respect to the input signal and
MAIN BOARD, the DISPLAY and the power FILTERING circuit, to the power supply.
plus the A/ D converter card and the INPUT card which are
installed in their corresponding plug-in connectors (see figure *From nº O5397
in page 4).
The ALPHA-P model incorporates new technical and Standard features of the basic instrument include the reading
functional characteristics including ± 32000 count of the input variable, max and min readings detection, remote
display, signal linearization of up to 30 points and user hold operation, tare function and reset and a full complement
programmable remote logic functions that provides an of programmable logic functions.
extraordinary flexibility to adapt to a w ide range of
indication and control needs. In addition, a variety of plug-in output cards can be installed at
any time to meet further system requirements:
The model ALPHA-P is a digital indicator for measurement and
control of process variables with direct indication in COMMUNICATION
engineering units. RS2 Serial RS232C
The programming software allows selection of the transducer RS4 Serial RS485
type (V, mA, potentiometer), two input levels for voltage BCD BCD 24V/TTL
inputs (1V or 10V), two input levels for current inputs (1mA or
20mA) and two excitation voltages (24V or 10/5V). CONTROL
ANA Analogue 4-20mA, 0-10V
The meter provides two scaling methods (by keyboard or by 2RE 2 SPDT relays 8A
input levels) that make easier the programming task, software 4RE 4 SPST relays 5A*
selectable filtering levels and last digit resolution to help 4OP 4 NPN outputs
stabilizing the display according to the process type. 4OPP 4 PNP outputs
The basic instrument is a soldered assembly composed of the All the outputs are isolated with respect to the input signal and
MAIN BOARD, the DISPLAY and the power FILTERING circuit, to the power supply.
plus the A/ D converter card and the INPUT card which are
installed in their corresponding plug-in connectors (see figure *From nº O5397
in page 4).
5
FRONT-PANEL FUNCTIONS IN RUN MODE
MAIN DISPLAY
Reads the input variable
AUXILIARY DISPLAY
Positive " " or
negative "-" signal
LED 1
PROG Indicates activation/display setpoint 1
A 1
RUN LED
RUN mode indication B 2
LABEL
HOLD LED TEACH ESC ENTER
Engineering unit
Indicates lock read in display
RESET KEY
DATA KEY
Resets Peak/Valley and Displays data.
Tare memories Provides access to PROG mode
LIMIT LED
MAX/MIN KEY
Indicates that Setpoint
Recalls Peak/Valley values
values is being displayed
LABEL
HOLD LED TEACH ESC ENTER
Engineering unit
Indicates lock read in display
RESET KEY
DATA KEY
Resets Peak/Valley and Displays data.
Tare memories Provides access to PROG mode
LIMIT LED
MAX/MIN KEY
Indicates that Setpoint
Recalls Peak/Valley values
values is being displayed
69
FRONT-PANEL FUNCTIONS IN PROG MODE
MAIN DISPLAY
AUXILIARY DISPLAY Reads programming parameters
Indicates program module.
FLT LED
PROG Indicates input filter programming.
A and B LED's A 1
Indicates program module letter.
B 2
STORE LED
Indicates exit from de program
RUN TARE HOLD LIMIT MAX MIN DATA 3 mode with data memory storage.
PROG LED
Indicates programming mode. PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
LABEL
INP1 LED Engineering unit.
TARE RESET LIMIT MAX/MIN DATA
Indicates Input1 programming.
KEYBOARD IN PROG MODE
TEACH ESC ENTER
DSP1 LED
Indicates Display1 programming.
ENTER KEY
TEACH KEY Accepts data.
Reads the INP1, INP2, INP# value. Advances program steps
ESC KEY
Returns to run mode at any program step. KEY
Moves de flashing digit to the right.
INP2 LED
Indicates Input2 programming.
Indicates Input# programming. DSP2 LED
Indicates Display2 programming.
Indicates Display# programming.
KEY
Increments the flashing digit value.
FLT LED
PROG Indicates input filter programming.
A and B LED's A 1
Indicates program module letter.
B 2
STORE LED
Indicates exit from de program
RUN TARE HOLD LIMIT MAX MIN DATA 3 mode with data memory storage.
PROG LED
Indicates programming mode. PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
LABEL
INP1 LED Engineering unit.
TARE RESET LIMIT MAX/MIN DATA
Indicates Input1 programming.
KEYBOARD IN PROG MODE
TEACH ESC ENTER
DSP1 LED
Indicates Display1 programming.
ENTER KEY
TEACH KEY Accepts data.
Reads the INP1, INP2, INP# value. Advances program steps
ESC KEY
Returns to run mode at any program step. KEY
Moves de flashing digit to the right.
INP2 LED
Indicates Input2 programming.
Indicates Input# programming. DSP2 LED
Indicates Display2 programming.
Indicates Display# programming.
KEY
Increments the flashing digit value.
7
2. GETTING STARTED
PACKAGE CONTENTS Programming instructions (page 11 and 12)
Instructions manual in English including Declaration of The software is divided into several independently
Conformity. accessible modules for configuration of the input, the
D.P.M. model Alpha-P. display, the setpoints, the analog output, the
Accessories for panel mounting (sealing gasket and communication output and the logic inputs.
fastening clips).
Accessories for wiring connections (removable plug-in Read carefully this section.
connectors and fingertip).
Wiring label stuck to the Alpha-P case. Input type (pages 13 to 16)
Four sets of engineering units labels.
The instrument provides three excitation voltages to
Check the package contents. supply the transducer; 5V or 10V and 24V, are set up at
fabrication for 10V.
CONFIGURATION
Check the transducer sensitivity, for more detailed
Power supply (page 9 and 10) information, please consult the transducer
specifications.
Instruments supplied for 115/ 230V AC power are factory
set for 230V AC. (USA market 115V AC). Programming Lock-out (page 38)
Instruments supplied for 24/48V AC power are factory set
for 24V AC. The instrument is set at the factory with the switches on
Instruments supplied for 10-30V DC can be powered from the OFF position (program routines are totally accessible).
any voltage between 10 and 30V DC without need of
making changes. Warning! Keep your unlock code in a secure place. If
you lost it, it is possible to reset it (page 41).
Check the wiring label before power connection.
2. GETTING STARTED
PACKAGE CONTENTS Programming instructions (page 11 and 12)
Instructions manual in English including Declaration of The software is divided into several independently
Conformity. accessible modules for configuration of the input, the
D.P.M. model Alpha-P. display, the setpoints, the analog output, the
Accessories for panel mounting (sealing gasket and communication output and the logic inputs.
fastening clips).
Accessories for wiring connections (removable plug-in Read carefully this section.
connectors and fingertip).
Wiring label stuck to the Alpha-P case. Input type (pages 13 to 16)
Four sets of engineering units labels.
The instrument provides three excitation voltages to
Check the package contents. supply the transducer; 5V or 10V and 24V, are set up at
fabrication for 10V.
CONFIGURATION
Check the transducer sensitivity, for more detailed
Power supply (page 9 and 10) information, please consult the transducer
specifications.
Instruments supplied for 115/ 230V AC power are factory
set for 230V AC. (USA market 115V AC). Programming Lock-out (page 38)
Instruments supplied for 24/48V AC power are factory set
for 24V AC. The instrument is set at the factory with the switches on
Instruments supplied for 10-30V DC can be powered from the OFF position (program routines are totally accessible).
any voltage between 10 and 30V DC without need of
making changes. Warning! Keep your unlock code in a secure place. If
you lost it, it is possible to reset it (page 41).
Check the wiring label before power connection.
8
2.1 - Power supply
24/ 48 V AC: The instruments with 24/ 48 V AC power supply, Table 1. Jumper settings
are shipped from the factory for 24 V AC, see figure 9.3 To Pin 1 2 3 4 5
change supply voltage to 48 V AC, set jumpers as indicated in 230V AC -
figure 9.2 (see table 1). The wiring label should be modified to 115V AC -
match new setups. 48V AC -
24V AC -
10-30V DC: The instruments for 10-30V DC power supply are
prepared to withstand any voltage between 10 and 30V without
need of wiring changes.
Fig. 9.2. Supply voltage 230 V or 48 V AC Fig. 9.3. Supply voltage 115 V or 24 V AC
9
24/ 48 V AC: The instruments with 24/ 48 V AC power supply, Table 1. Jumper settings
are shipped from the factory for 24 V AC, see figure 9.3 To Pin 1 2 3 4 5
change supply voltage to 48 V AC, set jumpers as indicated in 230V AC -
figure 9.2 (see table 1). The wiring label should be modified to 115V AC -
match new setups. 48V AC -
24V AC -
10-30V DC: The instruments for 10-30V DC power supply are
prepared to withstand any voltage between 10 and 30V without
need of wiring changes.
Fig. 9.2. Supply voltage 230 V or 48 V AC Fig. 9.3. Supply voltage 115 V or 24 V AC
9
POWER CONNECTION INSTALLATION
To meet the requirements of the directive EN61010-1, where the unit
is permanently connected to the mains supply it is obligatory to install
a circuit breaking device easy reachable to the operator and clearly
marked as the disconnect device.
WARNING
In order to guarantee electromagnetic compatibility, the following
guidelines for cable wiring must be followed:
- Power supply wires must be routed separated from signal wires.
Never run power and signal wires in the same conduit.
- Use shielded cable for signal wiring and connect the shield to
ground of the indicator (pin2 CN1).
- The cable section must be 0.25 mm².
CONNECTORS
To perform wiring connections, remove
AC VERSIONS the terminal block from the meter's connector,
PIN 1 - AC HI strip the wire leaving from 7 to 10mm exposed
PIN 2 - GND (GROUND) and insert it into the proper terminal while pushing
PIN 3 - AC LO (NEUTRAL) the fingertip down to open the clip inside the
connector as indicated in the figure.
DC VERSIONS Proceed in the same manner with all pins and plug the terminal block
PIN 1 - DC POSITIVE into the corresponding meter's connector.
PIN 2 - N/C (not connected) Each terminal can admit cables of section comprised between 0.08mm²
PIN 3 - DC NEGATIVE and 2.5mm² (AWG 26 ÷ 14).
The blocks provide removable adaptors into each terminal to allow
proper fastening for cable sections of <0.5 mm².
10
CONNECTORS
To perform wiring connections, remove
AC VERSIONS the terminal block from the meter's connector,
PIN 1 - AC HI strip the wire leaving from 7 to 10mm exposed
PIN 2 - GND (GROUND) and insert it into the proper terminal while pushing
PIN 3 - AC LO (NEUTRAL) the fingertip down to open the clip inside the
connector as indicated in the figure.
DC VERSIONS Proceed in the same manner with all pins and plug the terminal block
PIN 1 - DC POSITIVE into the corresponding meter's connector.
PIN 2 - N/C (not connected) Each terminal can admit cables of section comprised between 0.08mm²
PIN 3 - DC NEGATIVE and 2.5mm² (AWG 26 ÷ 14).
The blocks provide removable adaptors into each terminal to allow
proper fastening for cable sections of <0.5 mm².
10
2.2 Programming instructions
When power is applied to the instrument, the display briefly The modules 3, 4 and 5 will only be displayed if the option is
illuminates all segments and LED's then shows the software installed. Read the manuals related to these options to
version and finally enters in the normal reading mode. configure them.
Press ENTER to enter in the programming mode. The display The figure below shows the programming diagram. You can
shows the indication "-Pro-". The programming software is accede to each module by pressing ENTER when its name
divided into 6 modules. From the -Pro- stage, press appears in the display.
repeatedly to cycle around the existing modules
In the diagram, the key will allow you to cycle through
ENTER
1. CnInP = Input configuration the modules and the key will be used to input data
2. CndSP = Display configuration and go to the next step.
3. SetP = Setpoints
4. Anout = Analogical output From any step of the program routines, a push on ESC
5. rSout = RS output returns the meter to the run mode without saving.
6. LoGIn = Remote inputs
11
Press ENTER to enter in the programming mode. The display The figure below shows the programming diagram. You can
shows the indication "-Pro-". The programming software is accede to each module by pressing ENTER when its name
divided into 6 modules. From the -Pro- stage, press appears in the display.
repeatedly to cycle around the existing modules
In the diagram, the key will allow you to cycle through
1. CnInP = Input configuration the modules and the key ENTER
will be used to input data
2. CndSP = Display configuration and go to the next step.
3. SetP = Setpoints
4. Anout = Analogical output From any step of the program routines, a push on ESC
5. rSout = RS output returns the meter to the run mode without saving.
6. LoGIn = Remote inputs
11
The programming instructions are composed by a general description and a series of step-by-step instructions to be followed
sequentially. Each menu step is represented by an illustration of the display and keyboard module with indicators (display and
LED's), reference [page number. figure number] and a text describing the action of each key at that step.
In the step-by-step instructions, you are given the action of the three buttons mainly
[page nº/figure nº] Mnemo used to program data. The normal procedure at each step is to push on a
number of times to make changes and push on ENTER to validate changes and
PROG advance to the next programming step. At the end of a complete menu sequence the
A 1
B 2
meter returns to the run mode saving changes in memory.
In general the following actions can be made during the program mode.
RUN TARE HOLD LIMIT MAX MIN DATA 3
ENTER
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 validate changes and advance to next step
ESC
TARE RESET LIMIT MAX/MIN ENTER discard changes and go to the run mode
TEACH ESC DATA select among a list of available options / shift to next digit to the right
increment digit value
With respect to the figures in the step-by-step instructions, the display indications may have the
Program following meanings:
module and
menu step 1./ The display shows one of the available options with filled-out segments. That means
indicators that the display shows the choice made previously. The use of allows to select from
available options.
2./ A series of black "8" also represents the display indication of a previous choice, with
the difference that it cannot be changed in the current step. If it is already the desired
parameter, you may exit from the menu by a push of ESC without making changes or,
if wanted to modify it, a push of ENTER advances the meter to the next step where
changes are allowed.
3./ A series of white "8" represents any numerical value that is programmed by using keys
(Increments digit value) and (advances to the next digit).
12
The programming instructions are composed by a general description and a series of step-by-step instructions to be followed
sequentially. Each menu step is represented by an illustration of the display and keyboard module with indicators (display and
LED's), reference [page number. figure number] and a text describing the action of each key at that step.
In the step-by-step instructions, you are given the action of the three buttons mainly
[page nº/figure nº] Mnemo used to program data. The normal procedure at each step is to push on a
number of times to make changes and push on ENTER to validate changes and
PROG advance to the next programming step. At the end of a complete menu sequence the
A 1
B 2
meter returns to the run mode saving changes in memory.
In general the following actions can be made during the program mode.
RUN TARE HOLD LIMIT MAX MIN DATA 3
ENTER
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 validate changes and advance to next step
ESC
TARE RESET LIMIT MAX/MIN ENTER discard changes and go to the run mode
TEACH ESC DATA select among a list of available options / shift to next digit to the right
increment digit value
With respect to the figures in the step-by-step instructions, the display indications may have the
Program following meanings:
module and
menu step 1./ The display shows one of the available options with filled-out segments. That means
indicators that the display shows the choice made previously. The use of allows to select from
available options.
2./ A series of black "8" also represents the display indication of a previous choice, with
the difference that it cannot be changed in the current step. If it is already the desired
parameter, you may exit from the menu by a push of ESC without making changes or,
if wanted to modify it, a push of ENTER advances the meter to the next step where
changes are allowed.
3./ A series of white "8" represents any numerical value that is programmed by using keys
(Increments digit value) and (advances to the next digit).
12
2.3 - Input configuration
The Alpha-P provides a choice of three input types: volts (VoLt), milliamp (AMP) and potentiometer (Pot).
Programming menu of "VoLt" and "AMP" inputs (process indicator) include selection of input range and transducer excitation.
Programming menu of "Pot" input (displacement indicator) requires no further configuration. When entering this option the meter
automatically sets the excitation to 10V. This voltage is used to feed the potentiometer so the input signal may take values
between 0 and 10V.
After deciding the input range, we are ready to enter in the input configuration module (1 CnInP) to program this parameter.
Connect the instrument to the mains. The self-test routine starts: for a few seconds, the display illuminates all segments, decimal
points and LED's, then shows the software version.
A 1 indication given on figure 13.1 that corresponds to the entry stage of the input
B 2 programming module.
RUN TARE HOLD LIMIT MAX MIN DATA 3
A 1 AMP= process input in mA, or Pot= potentiometer input] . If POT input is selected,
B 2 the instrument goes to the run mode without passing through the following sequence.
RUN TARE HOLD LIMIT MAX MIN DATA 3
ENTER
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
To access the input range selection.
ESC
TARE RESET LIMIT MAX/MIN ENTER
To exit from the programming mode without saving changes.
TEACH ESC DATA
13
The Alpha-P provides a choice of three input types: volts (VoLt), milliamp (AMP) and potentiometer (Pot).
Programming menu of "VoLt" and "AMP" inputs (process indicator) include selection of input range and transducer excitation.
Programming menu of "Pot" input (displacement indicator) requires no further configuration. When entering this option the meter
automatically sets the excitation to 10V. This voltage is used to feed the potentiometer so the input signal may take values
between 0 and 10V.
After deciding the input range, we are ready to enter in the input configuration module (1 CnInP) to program this parameter.
Connect the instrument to the mains. The self-test routine starts: for a few seconds, the display illuminates all segments, decimal
points and LED's, then shows the software version.
A 1 indication given on figure 13.1 that corresponds to the entry stage of the input
B 2 programming module.
RUN TARE HOLD LIMIT MAX MIN DATA 3
A 1 AMP= process input in mA, or Pot= potentiometer input] . If POT input is selected,
B 2 the instrument goes to the run mode without passing through the following sequence.
RUN TARE HOLD LIMIT MAX MIN DATA 3
ENTER
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
To access the input range selection.
ESC
TARE RESET LIMIT MAX/MIN ENTER
To exit from the programming mode without saving changes.
TEACH ESC DATA
13
[14.1] Input range
Depending on the previous step selection, the meter presents a choice of two voltage
levels [1- V or 10- V] or two current levels [1- mA or 20-mA]. Press the key to
PROG
A 1
B 2 ENTER
To save the entry into the memory and return to the run mode.
ESC
RUN TARE HOLD LIMIT MAX MIN DATA 3 To exit from the programming mode without saving changes.
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
Jumper ON = EXC. 5V
Jumper OFF = EXC.
10V
14
A 1
B 2 ENTER
To save the entry into the memory and return to the run mode.
ESC
RUN TARE HOLD LIMIT MAX MIN DATA 3 To exit from the programming mode without saving changes.
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
Jumper ON = EXC. 5V
Jumper OFF = EXC.
10V
14
Input signal wiring schematics
DISPLACEMENT INDICATORS
15
DISPLACEMENT INDICATORS
15
Process indicators with current input
16
16
2.4 - Display configuration
After selection of the input range, it may be necessary to Fig. 17.1: Linearizing (inp7, dsp7)
scale the instrument for the particular application. For many function with 6 (inp6, dsp6)
common applications, single slope scaling (2 points) should segments (7 points). (inp5, dsp5)
be sufficient to have good readings over the entire process Up to 29 segments are (inp3, dsp3)
(inp4, dsp4)
range. Other applications, in which non-linear devices are available. (inp2, dsp2)
(inp1, dsp1)
used may require linearizing the signal. This is accomplished
by scaling the meter with more than two points (see fig. 2./ Action modes
17.1) The figure below represents two modes of operation
obtained by programming increasing or decreasing display
Type of function Nº of scaling points values for increasing input values.
Linear function 2 points
Non-linear function Max 30 points
DISPLAY 2 DISPLAY 1
17
After selection of the input range, it may be necessary to Fig. 17.1: Linearizing (inp7, dsp7)
scale the instrument for the particular application. For many function with 6 (inp6, dsp6)
common applications, single slope scaling (2 points) should segments (7 points). (inp5, dsp5)
be sufficient to have good readings over the entire process Up to 29 segments are (inp3, dsp3)
(inp4, dsp4)
range. Other applications, in which non-linear devices are available. (inp2, dsp2)
(inp1, dsp1)
used may require linearizing the signal. This is accomplished
by scaling the meter with more than two points (see fig. 2./ Action modes
17.1) The figure below represents two modes of operation
obtained by programming increasing or decreasing display
Type of function Nº of scaling points values for increasing input values.
Linear function 2 points
Non-linear function Max 30 points
DISPLAY 2 DISPLAY 1
17
3./ Scaling the indicator.
After deciding the values for INPUT and DISPLAY and the decimal point position, we are ready to enter in the display configuration
module (2 CndSP) to effectively scale the meter. The scaling procedure is completed with digital filters and display rounding.
From the run mode, press ENTER to get access to the programming mode (the display
[18.1] Display configuration shows -Pro-). Press two times the key to go to the entry stage of the display
configuration module, represented in fig. 18.1. This module provides five menus: scaling,
PROG balanced filter, damping filter, round and tare (lockout). Press ENTER to accede to the first
1
A
menu (SCAL) and press repeatedly the key if you want to shift around the different
B 2
menus (See next pages for instructions on each menu).
RUN TARE HOLD LIMIT MAX MIN DATA 3
4 ENTER
PRG INP1 DSP1 INP2 DSP2 FLT STORE
To get access to the menu select.
ESC
TARE RESET LIMIT MAX/MIN ENTER
To exit from the programming routines and brings the instrument to the run mode.
TEACH ESC DATA
ENTER
A 1 A 1 A 1 A 1 A 1 A 1
B 2 B 2 B 2 B 2 B 2 B 2
RUN TARE HOLD LIMIT MAX MIN DATA 3 RU HOLD LIMI MAX MIN DATA 3 RU HOLD LIMI MAX MIN DATA 3 RU HOLD LIMI MAX MIN DATA 3 RUN TARE HOLD LIMIT MAX MIN DATA 3 RU HOLD LIMI MAX MIN DATA 3
TARE TARE TARE TARE
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 PR DSP1 INP DSP2 STOR 4 PR DSP1 INP DSP2 STOR 4 PR DSP1 INP DSP2 STOR 4 PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 PR DSP1 INP DSP2 STOR 4
INP1 2 FL E INP1 2 FL E INP1 2 FL E INP1 2 FL E
TARE RESET LIMIT MAX/MIN ENTER RESE LIMI MAX/MI ENTE RESE LIMI MAX/MI ENTE RESE LIMI MAX/MI ENTE TARE RESET LIMIT MAX/MIN ENTER RESE LIMI MAX/MI ENTE
TARE T T N R TARE T T N R TARE T T N R TARE T T N R
TEACH ESC DATA TEAC ESC DATA TEAC ESC DATA TEAC ESC DATA TEACH ESC DATA TEAC ESC DATA
H H H H
18
From the run mode, press ENTER to get access to the programming mode (the display
[ 18.1] Display configuration shows -Pro-). Press two times the key to go to the entry stage of the display
configuration module, represented in fig. 18.1. This module provides five menus: scaling,
PROG balanced filter, damping filter, round and tare (lockout). Press ENTER to accede to the first
1
A
menu (SCAL) and press repeatedly the key if you want to shift around the different
B 2
menus (See next pages for instructions on each menu).
RUN TARE HOLD LIMIT MAX MIN DATA 3
4 ENTER
PRG INP1 DSP1 INP2 DSP2 FLT STORE
To get access to the menu select.
ESC
TARE RESET LIMIT MAX/MIN ENTER
To exit from the programming routines and brings the instrument to the run mode.
TEACH ESC DATA
ENTER
A 1 A 1 A 1 A 1 A 1 A 1
B 2 B 2 B 2 B 2 B 2 B 2
RUN TARE HOLD LIMIT MAX MIN DATA 3 RU HOLD LIMI MAX MIN DATA 3 RU HOLD LIMI MAX MIN DATA 3 RU HOLD LIMI MAX MIN DATA 3 RUN TARE HOLD LIMIT MAX MIN DATA 3 RU HOLD LIMI MAX MIN DATA 3
TARE TARE TARE TARE
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 PR DSP1 INP DSP2 STOR 4 PR DSP1 INP DSP2 STOR 4 PR DSP1 INP DSP2 STOR 4 PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 PR DSP1 INP DSP2 STOR 4
INP1 2 FL E INP1 2 FL E INP1 2 FL E INP1 2 FL E
TARE RESET LIMIT MAX/MIN ENTER RESE LIMI MAX/MI ENTE RESE LIMI MAX/MI ENTE RESE LIMI MAX/MI ENTE TARE RESET LIMIT MAX/MIN ENTER RESE LIMI MAX/MI ENTE
TARE T T N R TARE T T N R TARE T T N R TARE T T N R
TEACH ESC DATA TEAC ESC DATA TEAC ESC DATA TEAC ESC DATA TEACH ESC DATA TEAC ESC DATA
H H H H
18
MENU 2A - SCALING
This menu allows programming the necessary parameters to determine the display range (INP1 - DSP1 - Decimal Point - INP2 -
DSP2 - INP3 - DSP3 - ). As a default, these values are expected to be introduced by keyboard. To use the actual signal input
values as INP# parameters, it is sufficient to push on the TEACH key while in the INPUT programming phases.
VERY IMPORTANT: Scaling the meter with a tare value different from zero may cause false readings when exiting
to the run mode. Before trying to program the scale, check the TARE LED and, if activated proceed to clear the tare
memory (Fig. 30.2)
[19.1] Scaling configuration The figure 19.1 shows the indication (SCAL) corresponding to entry stage into the
scaling menu. Press ENTER to accede this menu.
PROG
A 1 ENTER
B 2
To accede the scaling configuration.
RUN TARE HOLD LIMIT MAX MIN DATA 3
To skip over this stage and go to the next programming menu.
ESC
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 To exit from the programming mode without saving changes.
TARE RESET LIMIT MAX/MIN ENTER
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 Teach method: Apply signal to the meter input. Press TEACH to view the actual
TARE RESET LIMIT MAX/MIN ENTER
signal value present at the input connector (LED INP1 flashes). Press ENTER to accept
TEACH ESC DATA this value as INP1 and go next step.
ESC
To exit from the programming mode without saving changes.
[19.3] Display 1 value
The previously programmed DSP1 value appears on the display, LED DSP1 activated,
PROG with the auxiliary digit (sign) in flash. By means of the and procedure,
A 1
B 2
program desired DSP1 value and press ENTER . The limits of the span are -32000 and
RUN TARE HOLD LIMIT MAX MIN DATA 3
32000 points. I f the programmed value exceeds from these limits, the meter indicates
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 Error, then displays 32000 to allow reprogramming the DSP1 value within limits.
TARE RESET LIMIT MAX/MIN ENTER
ENTER
To save the entry into the memory and go to the next programming menu.
ESC
TEACH ESC DATA To exit from the programming mode without saving changes.
19
MENU 2A - SCALING
This menu allows programming the necessary parameters to determine the display range (INP1 - DSP1 - Decimal Point - INP2 -
DSP2 - INP3 - DSP3 - ). As a default, these values are expected to be introduced by keyboard. To use the actual signal input
values as INP# parameters, it is sufficient to push on the TEACH key while in the INPUT programming phases.
VERY IMPORTANT: Scaling the meter with a tare value different from zero may cause false readings when exiting
to the run mode. Before trying to program the scale, check the TARE LED and, if activated proceed to clear the tare
memory (Fig. 30.2)
[19.1] Scaling configuration The figure 19.1 shows the indication (SCAL) corresponding to entry stage into the
scaling menu. Press ENTER to accede this menu.
PROG
A 1 ENTER
B 2
To accede the scaling configuration.
RUN TARE HOLD LIMIT MAX MIN DATA 3
To skip over this stage and go to the next programming menu.
ESC
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 To exit from the programming mode without saving changes.
TARE RESET LIMIT MAX/MIN ENTER
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 Teach method: Apply signal to the meter input. Press TEACH to view the actual
TARE RESET LIMIT MAX/MIN ENTER
signal value present at the input connector (LED INP1 flashes). Press ENTER to accept
TEACH ESC DATA this value as INP1 and go next step.
ESC
To exit from the programming mode without saving changes.
[19.3] Display 1 value
The previously programmed DSP1 value appears on the display, LED DSP1 activated,
PROG with the auxiliary digit (sign) in flash. By means of the and procedure,
A 1
B 2
program desired DSP1 value and press ENTER . The limits of the span are -32000 and
RUN TARE HOLD LIMIT MAX MIN DATA 3
32000 points. I f the programmed value exceeds from these limits, the meter indicates
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 Error, then displays 32000 to allow reprogramming the DSP1 value within limits.
TARE RESET LIMIT MAX/MIN ENTER
ENTER
To save the entry into the memory and go to the next programming menu.
ESC
TEACH ESC DATA To exit from the programming mode without saving changes.
19
[20.1] Decimal point
The decimal point goes in flash. Press repeatedly the key to move it to the
PROG right until desired position. If no decimal point is required, it must be placed to the
A 1
right side of the display. The decimal point remains in the selected position in all
B 2
programming phases and the run mode.
RUN TARE HOLD LIMIT MAX MIN DATA 3
4
ENTER
To save the entry into the memory and go to the next programming menu
PRG INP1 DSP1 INP2 DSP2 FLT STORE
ESC
TARE RESET LIMIT MAX/MIN ENTER
To exit from the programming mode without saving changes.
TEACH ESC DATA
[20.2] Input 2 value The previously programmed INP2 value appears on the display, LED INP2 activated,
with the auxiliary digit (sign) in flash. There are two methods:
PROG
Key- in method: Use to switch between "0" (positive) and "-" (negative).
A 1 Press to advance to the next digit to the right which goes in flash. Press
B 2
repeatedly to increment the active digit until it takes desired value. Proceed in
RUN TARE HOLD LIMIT MAX MIN DATA 3
the same manner with all the digits until desired value is completed on the display
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
with sign. Press ENTER to accept this value as INP2 and go next step.
TARE RESET LIMIT MAX/MIN ENTER
PROG
A 1
B 2 The previously programmed DSP2 value appears on the display, LED DSP2 activated,
RUN TARE HOLD LIMIT MAX MIN DATA 3
with the auxiliary digit (sign) in flash. By means of the and procedure,
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 program desired DSP2 value and press ENTER . The limits of the span are -32000 and
TARE RESET LIMIT MAX/MIN ENTER 32000 points. I f the programmed value exceeds from these limits, the meter indicates
TEACH ESC DATA Error, then displays 32000 to allow reprogramming the DSP2 value within limits.
c) To validate data and access to multi-slope scaling, press ENTER for 3 seconds; or
VERY IMPORTANT: Scaling the meter with d) To save the entry into the memory and return to run mode, press ENTER
a tare value different from zero may cause ESC
To exit from the programming mode without saving changes.
false readings when exiting to the run
mode. Before trying to program the scale,
check the TARE LED and, if activated
proceed to clear the tare memory (Fig.
30.2) 20
[20.2] Input 2 value The previously programmed INP2 value appears on the display, LED INP2 activated,
with the auxiliary digit (sign) in flash. There are two methods:
PROG
Key- in method: Use to switch between "0" (positive) and "-" (negative).
A 1 Press to advance to the next digit to the right which goes in flash. Press
B 2
repeatedly to increment the active digit until it takes desired value. Proceed in
RUN TARE HOLD LIMIT MAX MIN DATA 3
the same manner with all the digits until desired value is completed on the display
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
with sign. Press ENTER to accept this value as INP2 and go next step.
TARE RESET LIMIT MAX/MIN ENTER
PROG
A 1
B 2 The previously programmed DSP2 value appears on the display, LED DSP2 activated,
RUN TARE HOLD LIMIT MAX MIN DATA 3
with the auxiliary digit (sign) in flash. By means of the and procedure,
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 program desired DSP2 value and press ENTER . The limits of the span are -32000 and
TARE RESET LIMIT MAX/MIN ENTER 32000 points. I f the programmed value exceeds from these limits, the meter indicates
TEACH ESC DATA Error, then displays 32000 to allow reprogramming the DSP2 value within limits.
a) To validate data and access to multi-slope scaling, press ENTER for 3 seconds; or
VERY IMPORTANT: Scaling the meter with b) To save the entry into the memory and return to run mode, press ENTER
a tare value different from zero may cause ESC
To exit from the programming mode without saving changes.
false readings when exiting to the run
mode. Before trying to program the scale,
check the TARE LED and, if activated
proceed to clear the tare memory (Fig.
30.2)
20
[21.1] Point 3
1 second flag indication for scaling point 3.
PROG
A 1 Key- in method: Use Displ to switch between "0" (positive) and "-" (negative).
B 2 Press to advance to the next digit to the right. Press repeatedly to
RUN TARE HOLD LIMIT MAX MIN DATA 3 increment the active digit until it takes desired value. Proceed in the same manner
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 with all the digits until desired value is completed on the display with sign. Press
TARE RESET LIMIT MAX/MIN ENTER ENTER
to accept this value as INP3 and go next step.
TEACH ESC DATA
Teach method: Apply signal to the meter input. Press TEACH to view the actual
signal value present at the input connector, LED INP2 flashes. Press ENTER to accept
this value as INP3 and go next step.
A 1 program desired DSP3 value and press ENTER . The limits of the span are -32000 and
B 2 32000 points. I f the programmed value exceeds from these limits, the meter indicates
RUN TARE HOLD LIMIT MAX MIN DATA 3 Error, then displays 32000 to allow reprogramming the DSP3 value within limits.
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 c) To validate data and advance to the next point, press ENTER ; or
TARE RESET LIMIT MAX/MIN ENTER
d) To save the programmed data in the memory and return to the run mode, the
TEACH ESC DATA
meter is scaled with two segments, press and hold down ENTER for 3 seconds.
ESC
To exit from the programming mode without saving changes.
21
[21.1] Point 3
1 second flag indication for scaling point 3.
PROG
A 1 Key- in method: Use Displ to switch between "0" (positive) and "-" (negative).
B 2 Press to advance to the next digit to the right. Press repeatedly to
RUN TARE HOLD LIMIT MAX MIN DATA 3 increment the active digit until it takes desired value. Proceed in the same manner
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 with all the digits until desired value is completed on the display with sign. Press
TARE RESET LIMIT MAX/MIN ENTER ENTER
to accept this value as INP3 and go next step.
TEACH ESC DATA
Teach method: Apply signal to the meter input. Press TEACH to view the actual
signal value present at the input connector, LED INP2 flashes. Press ENTER to accept
this value as INP3 and go next step.
A 1 program desired DSP3 value and press ENTER . The limits of the span are -32000 and
B 2 32000 points. I f the programmed value exceeds from these limits, the meter indicates
RUN TARE HOLD LIMIT MAX MIN DATA 3 Error, then displays 32000 to allow reprogramming the DSP3 value within limits.
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 a) To validate data and advance to the next point, press ENTER ; or
TARE RESET LIMIT MAX/MIN ENTER
b) To save the programmed data in the memory and return to the run mode, the
TEACH ESC DATA
meter is scaled with two segments, press and hold down ENTER for 3 seconds.
ESC
To exit from the programming mode without saving changes.
21
[22.1] Point 30
1 second flag indication for scaling point 30.
PROG
A 1
B 2
PROG
The previously programmed DSP30 value appears on the display, LED DSP2 activated,
A 1 with the auxiliary digit (sign) in flash. By means of the and procedure,
B 2
program desired DSP30 value and press ENTER . The limits of the span are -32000 and
RUN TARE HOLD LIMIT MAX MIN DATA 3 32000 points. I f the programmed value exceeds from these limits, the meter indicates
INP1 DSP1 INP2 DSP2 FLT STORE 4
PRG
Error, then displays 32000 to allow reprogramming the DSP30 value within limits.
TARE RESET LIMIT MAX/MIN ENTER
ENTER
To save the entry into the memory, the meter is scaled with eleven segments,
TEACH ESC DATA
and return to run mode.
ESC
Return to previous point.
22
[22.1] Point 30
1 second flag indication for scaling point 30.
PROG
A 1
B 2
PROG
The previously programmed DSP30 value appears on the display, LED DSP2 activated,
A 1 with the auxiliary digit (sign) in flash. By means of the and procedure,
B 2
program desired DSP30 value and press ENTER . The limits of the span are -32000 and
RUN TARE HOLD LIMIT MAX MIN DATA 3 32000 points. I f the programmed value exceeds from these limits, the meter indicates
INP1 DSP1 INP2 DSP2 FLT STORE 4
PRG
Error, then displays 32000 to allow reprogramming the DSP30 value within limits.
TARE RESET LIMIT MAX/MIN ENTER
ENTER
To save the entry into the memory, the meter is scaled with eleven segments,
TEACH ESC DATA
and return to run mode.
ESC
Return to previous point.
22
MENU 2B - INTEGRATOR
The instruments has a counter of 8 digits (or 7 with a negative sign) that can be use whether to count quantities with a totalizer +
batch counter mode or to integrate through time.
The integration mode is activated in the Display menu (page 18). When activated it deactivates the totalizer + batch counter
mode.
PROG
A 1
B 2
RU
TARE
HOLD LIMI MAX MIN DATA 3 Fig. 23.1: Diagram of the The figure 23.1 represents the diagram of the integrator
integrator, menu 2B
4
no yES
S M H d
00.000
Point.Dec. There are 5 steps to configure the integrator:
6. Deactivation (no) or Activation (yES).
00001
Factor 7. Time unit used to integrate: seconds, minutes, hours or days (S, M, H, D).
8. Position of the decimal point of the display.
00001. 9. Factor of multiplication (between 0.0001 and 9999) and its decimal point.
Fact.Dec 10. Low- cut Level from which the integrator starts to integrate. If the dynamic measure is
below this level, the function will not integrate.
- 32.000
Low- Cut At each step, press the following keys to configure the integrator:
Modify a value.
ENTER
Go to next step (at the last step, save the new configuration and go back to run mode)
ESC
Cancel the configuration and return to the run mode without saving.
23
MENU 2B - INTEGRATOR
The instruments has a counter of 8 digits (or 7 with a negative sign) that can be use whether to count quantities with a totalizer +
batch counter mode or to integrate through time.
The integration mode is activated in the Display menu (page 18). When activated it deactivates the totalizer + batch counter
mode.
PROG
A 1
B 2
RU
TARE
HOLD LIMI MAX MIN DATA 3 Fig. 23.1: Diagram of the The figure 23.1 represents the diagram of the integrator
integrator, menu 2B
4
no yES
S M H d
00.000
Point.Dec. There are 5 steps to configure the integrator:
1. Deactivation (no) or Activation (yES).
00001
Factor 2. Time unit used to integrate: seconds, minutes, hours or days (S, M, H, D).
3. Position of the decimal point of the display.
00001. 4. Factor of multiplication (between 0.0001 and 9999) and its decimal point.
Fact.Dec 5. Low- cut Level from which the integrator starts to integrate. If the dynamic measure is
below this level, the function will not integrate.
- 32.000
Low- Cut At each step, press the following keys to configure the integrator:
Modify a value.
ENTER
Go to next step (at the last step, save the new configuration and go back to run mode)
ESC
Cancel the configuration and return to the run mode without saving.
23
MENU 2B - BALANCED FILTER
The balanced filter acts as a delay on the display response to signal variations produced at the input. The effect of incrementing
this filter level results in a softer response of the display to the input variations.
The filtering level is programmable from 0 to 9. Level 0 disables the filter.
A 1
ENTER
B 2 To get access to program filter level.
RUN TARE HOLD LIMIT MAX MIN DATA 3 To skip over this menu and go to next one.
4 ESC
PRG INP1 DSP1 INP2 DSP2 FLT STORE
To exit from the programming mode without saving changes.
TARE RESET LIMIT MAX/MIN ENTER
A 1 Press repeatedly the key to change the digit until desired value appears on the
B 2 display.
RUN TARE HOLD LIMIT MAX MIN DATA 3
24
A 1
ENTER
B 2
To get access to program filter level.
RUN TARE HOLD LIMIT MAX MIN DATA 3 To skip over this menu and go to next one.
4 ESC
PRG INP1 DSP1 INP2 DSP2 FLT STORE
To exit from the programming mode without saving changes.
TARE RESET LIMIT MAX/MIN ENTER
A 1 Press repeatedly the key to change the digit until desired value appears on the
B 2 display.
RUN TARE HOLD LIMIT MAX MIN DATA 3
24
MENU 2B - DAMPING FILTER
The damping filter cuts off input values exceeding from the limits of a moving band. This band becomes more selective as the
filter level is increased.
The filtering level is programmable from 0 to 9. Level 0 disables the filter.
A 1
ENTER
B 2 To get access to program the filter level.
RUN TARE HOLD LIMIT MAX MIN DATA 3 To skip over this menu and go to next one.
4 ESC
PRG INP1 DSP1 INP2 DSP2 FLT STORE
To exit from the programming mode without saving changes.
TARE RESET LIMIT MAX/MIN ENTER
A 1 Press repeatedly the key to change the digit until desired value appears on the
B 2 display.
RUN TARE HOLD LIMIT MAX MIN DATA 3
25
A 1
ENTER
B 2
To get access to program the filter level.
RUN TARE HOLD LIMIT MAX MIN DATA 3 To skip over this menu and go to next one.
4 ESC
PRG INP1 DSP1 INP2 DSP2 FLT STORE
To exit from the programming mode without saving changes.
TARE RESET LIMIT MAX/MIN ENTER
A 1 Press repeatedly the key to change the digit until desired value appears on the
B 2 display.
RUN TARE HOLD LIMIT MAX MIN DATA 3
25
MENU 2AB - ROUND FILTER
This menu allows selection among 4 levels of display rounding. When resolution is not critical, a rounding increment higher than 1,
may help to stabilize the display.
A 1
ENTER
B 2 To get access to the round level selection.
RUN TARE HOLD LIMIT MAX MIN DATA 3 To Skip over this menu and pass to the next one.
4 ESC
PRG INP1 DSP1 INP2 DSP2 FLT STORE
To exit from the programming mode without saving changes.
TARE RESET LIMIT MAX/MIN ENTER
26
A 1
ENTER
B 2 To get access to the round level selection.
RUN TARE HOLD LIMIT MAX MIN DATA 3 To Skip over this menu and pass to the next one.
4 ESC
PRG INP1 DSP1 INP2 DSP2 FLT STORE
To exit from the programming mode without saving changes.
TARE RESET LIMIT MAX/MIN ENTER
26
MENU 2 CALCULATE A VOLUME
PRESENTATION
There a several ways to calculate a volume of a liquid within a container. By using a pressure-sensor fixed at the bottom of the
container, it is possible to know the height of the liquid by adopting the adequate scale (page 19).
3. Fill the container with pre-defined quantities and look at the value of the output signal. Introduce these values in the scaling
menu (page 17). The more points are introduced the more precise will be the indicator.
4. If the shape of the container is regular (vertical roll, cube) then the volume will be proportional to the height and thus to the
pressure. By introducing a multiplicative factor in the scaling (page 17), it is possible to have the volume directly.
AUTOMATIC CALCULATION
The Alpha-P1.00 offers the possibility of calculating directly volumes for container having the shape of a sphere, a cylinder or a
combination of both, as well as SILO containers (figures 27). All the user has to do is to introduce the dimensions following the
corresponding menu.
To use this function fix a pressure-sensor at the bottom of the container and scale the instrument so that the output signal
indicates the height of the volume in meters. The height is proportional to the pressure, it is thus sufficient to introduce only two
points into the scaling menu (page 19 to 22): for each signal introduce the corresponding height in meters.
Example: Silo with total high of 10 meters, Pressure sensor with 4- 20 mA output signal corresponding to 0-1 bar. On SCAL menu
will be programmed INP1 = 4.000 mA, DSP1 = 0.00 m; INP2 = 20.000 mA, DSP2 = 10.00 m.
After in menu PROGRAMMING AUTOMATIC CALCULATION page 29 put the information asked for this menu according to the shape
chosen.
27
PRESENTATION
There a several ways to calculate a volume of a liquid within a container. By using a pressure-sensor fixed at the bottom of the
container, it is possible to know the height of the liquid by adopting the adequate scale (page 19).
1. Fill the container with pre-defined quantities and look at the value of the output signal. Introduce these values in the scaling
menu (page 17). The more points are introduced the more precise will be the indicator.
2. If the shape of the container is regular (vertical roll, cube) then the volume will be proportional to the height and thus to the
pressure. By introducing a multiplicative factor in the scaling (page 17), it is possible to have the volume directly.
AUTOMATIC CALCULATION
The Alpha-P1.00 offers the possibility of calculating directly volumes for container having the shape of a sphere, a cylinder or a
combination of both, as well as SILO containers (figures 27). All the user has to do is to introduce the dimensions following the
corresponding menu.
To use this function fix a pressure-sensor at the bottom of the container and scale the instrument so that the output signal
indicates the height of the volume in meters. The height is proportional to the pressure, it is thus sufficient to introduce only two
points into the scaling menu (page 19 to 22): for each signal introduce the corresponding height in meters.
Example: Silo with total high of 10 meters, Pressure sensor with 4- 20 mA output signal corresponding to 0-1 bar. On SCAL menu
will be programmed INP1 = 4.000 mA, DSP1 = 0.00 m; INP2 = 20.000 mA, DSP2 = 10.00 m.
After in menu PROGRAMMING AUTOMATIC CALCULATION page 29 put the information asked for this menu according to the shape
chosen.
27
Fig. 28.1: Sphere Typ 1 Fig. 28.2: Cylinder Typ 2 Fig. 28.3: Sphere + Cylinder Typ 3
D D D
h h h
L L
D3
D3
L3
L3
D2 L2 L2
L1 L1 L1
D1 D1 D1
D2 D2 D2
Fig. 28.4: Silo 1 Typ 4 Fig. 28.5: Silo 2 Typ4 Fig. 28.6: Silo 3 Typ 4
28
Fig. 28.1: Sphere Typ 1 Fig. 28.2: Cylinder Typ 2 Fig. 28.3: Sphere + Cylinder Typ 3
D D D
h h h
L L
D3
D3
L3
L3
D2 L2 L2
L1 L1 L1
D1 D1 D1
D2 D2 D2
Fig. 28.4: Silo 1 Typ 4 Fig. 28.5: Silo 2 Typ4 Fig. 28.6: Silo 3 Typ 4
28
MENU 2 CALCULATE A VOLUME
MENU AUTOMATIC
ENTER
The figure 29.1 represents the diagram of the calculator (VoL). Press to enter the configuration menu.
A
B
1
2
steps:
RU HOLD LIMI MAX MIN DATA 3
Fig. 29.1: Diagram of the
PR
TARE
INP1
DSP1 INP
2
DSP2
FL
STOR
E
4
calculator, menu 2 i) Deactivation (no) or Activation by choosing the shape of
RESE LIMI MAX/MI ENTE
TARE
TEAC
H
T
ESC
T N R
DATA the container (see page 28):
tyP 1 = sphere
no Typ 1 Typ 2 Typ 3 Typ 4 tyP 2 = cylinder
tyP 3 = sphere + cylinder
tyP 4 = silo,
00.000 00.000 00.000 00.100
Diameter Diameter Diameter Diam. 1 j) Diameter (in meters) or Diameter1 for the SILO.
k) Length only for tyP 2 and (in meters) or Lenght1 for
00.000 00.000 03.000 the tyP 4.
Length Length Length. 1
l) Diameter2 only for the tyP 4.
00000. 00000. 00000. 02.000 m) Length2 only for the tyP 4.
Dec. Pt Dec. Pt Dec. Pt Diam. 2
n) Diameter3 only for the tyP 4.
06.000 o) Length3 only for the tyP 4.
Long. 2
At each step, press the following keys to con- p) Position of the decimal point of the display (in meters).
figure the integrator: 01.000
Modify a value. Diam. 3 The display will indicate the volume in liter.
ENTER
Go to next step (at the last step, save
the new configuration and go back to run 01.000 For the tyP 4, if some parameters are equal to zero than it
mode) Long. 3 will change its shape. Example: if D3 and L3 are equal to
ESC
Cancel the configuration and return to 00000. zero, than we will have the silo of the figure 28.5
the run mode without saving. Dec. Pt
29
MENU AUTOMATIC
ENTER
The figure 29.1 represents the diagram of the calculator (VoL). Press to enter the configuration menu.
A
B
1
2
steps:
RU HOLD LIMI MAX MIN DATA 3
Fig. 29.1: Diagram of the
PR
TARE
INP1
DSP1 INP
2
DSP2
FL
STOR
E
4
calculator, menu 2 a) Deactivation (no) or Activation by choosing the shape of
RESE LIMI MAX/MI ENTE
TARE
TEAC
H
T
ESC
T N R
DATA the container (see page 28):
tyP 1 = sphere
no Typ 1 Typ 2 Typ 3 Typ 4 tyP 2 = cylinder
tyP 3 = sphere + cylinder
tyP 4 = silo,
00.000 00.000 00.000 00.100
Diameter Diameter Diameter Diam. 1 b) Diameter (in meters) or Diameter1 for the SILO.
c) Length only for tyP 2 and (in meters) or Lenght1 for
00.000 00.000 03.000 the tyP 4.
Length Length Length. 1
d) Diameter2 only for the tyP 4.
00000. 00000. 00000. 02.000 e) Length2 only for the tyP 4.
Dec. Pt Dec. Pt Dec. Pt Diam. 2
f) Diameter3 only for the tyP 4.
06.000 g) Length3 only for the tyP 4.
Long. 2
At each step, press the following keys to con- h) Position of the decimal point of the display (in meters).
figure the integrator: 01.000
Modify a value. Diam. 3 The display will indicate the volume in liter.
ENTER
Go to next step (at the last step, save
the new configuration and go back to run 01.000 For the tyP 4, if some parameters are equal to zero than it
mode) Long. 3 will change its shape. Example: if D3 and L3 are equal to
ESC
Cancel the configuration and return to 00000. zero, than we will have the silo of the figure 28.5
the run mode without saving. Dec. Pt
29
3. KEYBOARD AND REMOTE CONTROLS
TARE. Pressing this key adds the current display value to the LIMIT. During the RUN mode, this key is only operative in
tare memory and brings the display to zero. The "TARE" LED case that the instrument incorporates one of the following
indicates that a tare value different from zero is contained in output options: 2 relays (ref. 2RE), 4 relays (ref. 4RE), 4
the tare memory. NPN transistors (ref. 4OP) or 4 PNP transistors (ref.4OPP).
At one push of "LIMIT" key the display illuminates the "limit"
PROG LED and reads the first programmed setpoint value with the
A 1
B 2
LED 1 activated. New strokes on the LIMIT key recall
successively the rest of the setpoints with the corresponding
RUN TARE HOLD LIMIT MAX MIN DATA 3
1
15 seconds after the last key operation or by a push of
A
B 2 "LIMIT" from the visualisation of the last setpoint, the
RUN TARE HOLD LIMIT MAX MIN DATA 3
auxiliary display blanks and the meter returns to the normal
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 reading.
TARE RESET LIMIT MAX/MIN ENTER
TARE. Pressing this key adds the current display value to the LIMIT. During the RUN mode, this key is only operative in
tare memory and brings the display to zero. The "TARE" LED case that the instrument incorporates one of the following
indicates that a tare value different from zero is contained in output options: 2 relays (ref. 2RE), 4 relays (ref. 4RE), 4
the tare memory. NPN transistors (ref. 4OP) or 4 PNP transistors (ref.4OPP).
At one push of "LIMIT" key the display illuminates the "limit"
PROG LED and reads the first programmed setpoint value with the
A 1
B 2
LED 1 activated. New strokes on the LIMIT key recall
successively the rest of the setpoints with the corresponding
RUN TARE HOLD LIMIT MAX MIN DATA 3
1
15 seconds after the last key operation or by a push of
A
B 2 "LIMIT" from the visualisation of the last setpoint, the
RUN TARE HOLD LIMIT MAX MIN DATA 3
auxiliary display blanks and the meter returns to the normal
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 reading.
TARE RESET LIMIT MAX/MIN ENTER
A 1
B 2
PROG
RUN TARE HOLD LIMIT MAX MIN DATA 3
A 1
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
B 2
TARE RESET LIMIT MAX/MIN ENTER
RUN TARE HOLD LIMIT MAX MIN DATA 3
TEACH ESC DATA
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
MAX/MIN. This key calls up the peak and valley values contained in To erase the peak and/ or valley memories, press "MAX/ MIN"
memory. The first push recalls the maximum value reached for the one or two times to display the value to be reset. Press and
variable since the last reset operation (peak) and activates the "MAX" hold down the "RESET" key and simultaneously press
LED.
"MAX/MIN". Release "MAX/MIN" then "RESET".
PROG
A 1
B 2
PROG
RUN TARE HOLD LIMIT MAX MIN DATA 3
A 1
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
B 2
TARE RESET LIMIT MAX/MIN ENTER
RUN TARE HOLD LIMIT MAX MIN DATA 3
TEACH ESC DATA
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
31
3.2 - Remote functions
The rear connector CN2 provides 4 user programmable opto-coupled inputs that can be operated from external contacts or
logic levels supplied by an electronic system. Four different functions may be then added to the functions available from the
front-panel keys. Each function is associated to one of the CN2 connector pins (PIN 1, PIN 2, PIN 4 and PIN 5) and is
activated by applying a falling edge or a low level pulse to the corresponding pin with respect to common (PIN 3).
Each pin can be assigned one of the 28 functions listed on the following pages.
Default configuration
As shipped from the factory, the CN2 connector allows the
TARE, MAX/ MIN and RESET operations be made in the same
way as from the front-panel keyboard and incorporates one
more function: the display HOLD.
The HOLD state, which is acknowledged by the LED "HOLD",
freezes the display, the BCD and the analog outputs but does
not halt the meter's internal operation nor the alarm outputs.
The HOLD state is maintained as long as pin2 is kept to a low
level with respect to pin 3. Fig. 32.1
32
The rear connector CN2 provides 4 user programmable opto-coupled inputs that can be operated from external contacts or
logic levels supplied by an electronic system. Four different functions may be then added to the functions available from the
front-panel keys. Each function is associated to one of the CN2 connector pins (PIN 1, PIN 2, PIN 4 and PIN 5) and is
activated by applying a falling edge or a low level pulse to the corresponding pin with respect to common (PIN 3).
Each pin can be assigned one of the 28 functions listed on the following pages.
Default configuration
As shipped from the factory, the CN2 connector allows the
TARE, MAX/ MIN and RESET operations be made in the same
way as from the front-panel keyboard and incorporates one
more function: the display HOLD.
The HOLD state, which is acknowledged by the LED "HOLD",
freezes the display, the BCD and the analog outputs but does
not halt the meter's internal operation nor the alarm outputs.
The HOLD state is maintained as long as pin2 is kept to a low
level with respect to pin 3. Fig. 32.1
32
3.3 - Table of programmable functions
Nº : Function number.
Function: Function name.
Description: Description and characteristics of the function.
Activation :
Falling edge: The operation is performed on a falling edge applied to the pin with respect to COMMON.
Low level: The function remains activated while the corresponding pin is held at a low level with respect to COMMON.
(*) Default factory configuration. It can be restored by programming all pins to '0'.
33
(*) Default factory configuration. It can be restored by programming all pins to '0'.
33
13 to 16: FUNCTIONS ASSOCIATED WITH THE ANALOG OUTPUT
Nº Function Description Activation
13 ANA GROSS Makes the analog output follow the gross value (measured value + tare) Low level
14 ZERO ANA Puts the analog output to the zero state (0V for 0-10V, 4mA for 4-20mA) Low level
15 ANA PEAK Makes the analog output follow the peak value Low level
16 ANA VALLEY Makes the analog output follow the valley value Low level
34
34
29 to 36: NEW FUNCTIONS
35
35
3.4 Remote functions programming
After deciding the functions for each connector pin, we are ready to enter in the logic inputs configuration module (6 LoGIn) to
effectively program the logic inputs.
A 1 inputs configuration module, represented in fig. 36.1. This module provides four
B 2 menus for programming the input pins. Press ENTER to accede to the first menu
RUN TARE HOLD LIMIT MAX MIN DATA 3 (InP1) and press repeatedly the key if you want to select to different pins.
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
A 1 A 1 A 1 A 1
B 2 B 2 B 2 B 2
RUN TARE HOLD LIMIT MAX MIN DATA 3 RUN TARE HOLD LIMIT MAX MIN DATA 3 RUN TARE HOLD LIMIT MAX MIN DATA 3 RUN TARE HOLD LIMIT MAX MIN DATA 3
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
TARE RESET LIMIT MAX/MIN ENTER TARE RESET LIMIT MAX/MIN ENTER TARE RESET LIMIT MAX/MIN ENTER TARE RESET LIMIT MAX/MIN ENTER
TEACH ESC DATA TEACH ESC DATA TEACH ESC DATA TEACH ESC DATA
36
After deciding the functions for each connector pin, we are ready to enter in the logic inputs configuration module (6 LoGIn) to
effectively program the logic inputs.
A 1 inputs configuration module, represented in fig. 36.1. This module provides four
B 2 menus for programming the input pins. Press ENTER to accede to the first menu
RUN TARE HOLD LIMIT MAX MIN DATA 3 (InP1) and press repeatedly the key if you want to select to different pins.
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
A 1 A 1 A 1 A 1
B 2 B 2 B 2 B 2
RUN TARE HOLD LIMIT MAX MIN DATA 3 RUN TARE HOLD LIMIT MAX MIN DATA 3 RUN TARE HOLD LIMIT MAX MIN DATA 3 RUN TARE HOLD LIMIT MAX MIN DATA 3
PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 PRG INP1 DSP1 INP2 DSP2 FLT STORE 4 PRG INP1 DSP1 INP2 DSP2 FLT STORE 4
TARE RESET LIMIT MAX/MIN ENTER TARE RESET LIMIT MAX/MIN ENTER TARE RESET LIMIT MAX/MIN ENTER TARE RESET LIMIT MAX/MIN ENTER
TEACH ESC DATA TEACH ESC DATA TEACH ESC DATA TEACH ESC DATA
36
MENU 6A - PIN 1 programming
This menu allows selecting the logic function for PIN 1. Available functions are represented by a number from 0 to 36. Consult
tables pages 33 to 35 to find the number corresponding to the desired function. The instructions given below apply to pin function
1. Follow the same procedure to configure the rest of the pins.
A 1
ENTER
B 2
To accede to the programming of the PIN 1 function.
RUN TARE HOLD LIMIT MAX MIN DATA 3 To skip over this menu and go to PIN 2.
INP1 4 ESC
PRG DSP1 INP2 DSP2 FLT STORE
To exit from the programming mode without saving changes.
TARE RESET LIMIT MAX/MIN ENTER
37
This menu allows selecting the logic function for PIN 1. Available functions are represented by a number from 0 to 36. Consult
tables pages 33 to 35 to find the number corresponding to the desired function. The instructions given below apply to pin function
1. Follow the same procedure to configure the rest of the pins.
A 1
ENTER
B 2
To accede to the programming of the PIN 1 function.
RUN TARE HOLD LIMIT MAX MIN DATA 3 To skip over this menu and go to PIN 2.
INP1 DSP1 4 ESC
PRG INP2 DSP2 FLT STORE
To exit from the programming mode without saving changes.
TARE RESET LIMIT MAX/MIN ENTER
37
3.5 - Programming lock out / access levels
In the RUN mode pulse the ENTER key during 3 second to access to
the lock menu (diagram). The instrument has an original lock code
which is "0000". By using the and keys, it is possible to A
B
PROG
1
2
A
B
PROG
1
2
enter a new lock CodE. If the introduced code is false, the instrument RU
PR
TARE
INP1
HOLD
DSP1
RESE
LIMI
INP
2
LIMI
MAX
DSP2
MAX/MI
MIN
FL
DATA
STOR
E
ENTE
3
4
RU
PR
TARE
INP1
HOLD
DSP1
RESE
LIMI
INP
2
LIMI
MAX
DSP2
MAX/MI
MIN
FL
DATA
STOR
E
ENTE
3
4
TARE T T N R
goes back in RUN mode. When the display shows LiSt push
TARE T T N R
TEAC ESC DATA TEAC ESC DATA
H H
to change the code. Keep your new code in a secure place! PROG PROG
RU HOLD LIMI MAX MIN DATA 3 RU HOLD LIMI MAX MIN DATA 3
TARE
means lock whereas 0 means unlock. After pressing the last ENTER ,
TARE
PR DSP1 INP DSP2 STOR 4 4
PR DSP1 INP DSP2 STOR
INP1 2 FL E INP1 2 FL E
RESE LIMI MAX/MI ENTE RESE LIMI MAX/MI ENTE
TARE T T N R TARE T T N R
TEAC ESC DATA TEAC ESC DATA
A 1
B 2
3
TARE
TARE
DSP1
RESE
T
INP
2
LIMI
T
DSP2
MAX/MI
N
FL
ENTE
R
STOR
E
4
3
B
RU
TARE
HOLD LIMI MAX MIN DATA
2
3
RU
PR
TARE
INP1
HOLD
DSP1
LIMI
INP
2
MAX
DSP2
MIN
FL
DATA
STOR
E
3
4
PROG
A 1
B 2
PROG
PROG
A 1
B 2
INP1
DSP1 INP
2
DSP2
FL
STOR
E
4
=1
38
enter a new lock CodE. If the introduced code is false, the instrument RU
PR
TARE
INP1
HOLD
DSP1
RESE
LIMI
INP
2
LIMI
MAX
DSP2
FL
MAX/MI
MIN
STOR
E
ENTE
DATA 3
4
RU
PR
TARE
INP1
HOLD
DSP1
RESE
LIMI
INP
2
LIMI
MAX
DSP2
MAX/MI
MIN
FL
DATA
STOR
E
ENTE
3
4
TARE T T N R
goes back in RUN mode. When the display shows LiSt push
TARE T T N R
TEAC ESC DATA TEAC ESC DATA
H H
to change the code. Keep your new code in a secure place! PROG PROG
RU HOLD LIMI MAX MIN DATA 3 RU HOLD LIMI MAX MIN DATA 3
TARE
means lock whereas 0 means unlock. After pressing the last ENTER ,
TARE
PR DSP1 INP DSP2 STOR 4 4
PR DSP1 INP DSP2 STOR
INP1 2 FL E INP1 2 FL E
RESE LIMI MAX/MI ENTE RESE LIMI MAX/MI ENTE
TARE T T N R TARE T T N R
TEAC ESC DATA TEAC ESC DATA
A 1
B 2
3
TARE
TARE
DSP1
RESE
T
INP
2
LIMI
T
DSP2
MAX/MI
N
FL
ENTE
R
STOR
E
4
3
B
RU
TARE
HOLD LIMI MAX MIN DATA
2
3 PR
RU
TARE
INP1
HOLD
DSP1
LIMI
INP
2
MAX
DSP2
MIN
FL
DATA
STOR
E
3
4
PROG
A 1
B 2
PROG
PROG
A 1
B 2
=0 PR
TARE
INP1
DSP1 INP
2
DSP2
FL
STOR
E
4
=1 38
4. OUTPUT OPTIONS
Optionally, the model ALPHA-P can incorporate one or several The options are supplied with a specific instructions manual
output options for communications (this output should never describing characteristics, installation, connections and
be connected to the telephone lines) or control including: programming. The output cards are easily installed on the
meter's main board by means of plug-in connectors and each
COMMUNICATION one activates its own programming module that provides
RS2 Serial RS232C complete software configuration.
RS4 Serial RS485 Additional capabilities of the unit with output options:
BCD BCD 24V/TTL
Control and processing of limit values via ON/ OFF logic
CONTROL outputs (2 relays, 4 relays, 4 NPN outputs or 4 PNP
ANA Analogue 4-20mA, 0-10V outputs) or proportional output (4-20mA or 0-10V).
2RE 2 SPDT relays 8A Communication, data transmission and remote
4RE 4 SPST relays 5A* programming via serial interface.
4OP 4 open-collector NPN outputs
4OP 4 open-collector PNP outputs For more detailed information on characteristics, applications,
mounting and programming, please refer to the specific
All options are isolated with respect to the input signal and the manual supplied with each option.
power supply.
* from nº O5397
39
4. OUTPUT OPTIONS
Optionally, the model ALPHA-P can incorporate one or several The options are supplied with a specific instructions manual
output options for communications (this output should never describing characteristics, installation, connections and
be connected to the telephone lines) or control including: programming. The output cards are easily installed on the
meter's main board by means of plug-in connectors and each
COMMUNICATION one activates its own programming module that provides
RS2 Serial RS232C complete software configuration.
RS4 Serial RS485 Additional capabilities of the unit with output options:
BCD BCD 24V/TTL
Control and processing of limit values via ON/ OFF logic
CONTROL outputs (2 relays, 4 relays, 4 NPN outputs or 4 PNP
ANA Analogue 4-20mA, 0-10V outputs) or proportional output (4-20mA or 0-10V).
2RE 2 SPDT relays 8A Communication, data transmission and remote
4RE 4 SPST relays 5A* programming via serial interface.
4OP 4 open-collector NPN outputs
4OP 4 open-collector PNP outputs For more detailed information on characteristics, applications,
mounting and programming, please refer to the specific
All options are isolated with respect to the input signal and the manual supplied with each option.
power supply.
* from nº O5397
39
The figure page shows the different locations of the
plug-in output cards. Each location corresponds to a
specific function: setpoints, analogue and serial
outputs.
40
40
4.1 NEW FUNCTIONS 5. Activate or deactivate relay / opto (+ LED) via an order
The new ALPHA-P provides improved functionality and from rs232C or rs485.
incorporates new functions from which the following refer to
This function is available by introducing 3 in the first digit of
the output options:
the parameter mode setpoints (3B ModE).
FACTORY CONFIGURATION
3 0 0 0 0
To restore the original configuration, press RESET and then
ENTER
during 3 seconds. The lock CodE will also be put to In this configuration the rest of the options (HI-LO, RET-
zero. HYS ) are deactivated except the blink option (last digit of
the parameter).
SETPOINTS Once activated, these options does not deactivate by
overflow or by programming, it only wait an order via RS2 or
4. Each setpoint can be programmed for auto reset or RS4.
latched operation. Latched setpoints require a manual
reset to deactivate (see logic function 25, page 29). This 6. Use setpoint2 to detect a peak.
may be useful in installations where permanent visual This function is activated by introducing 6 or 7 in the
control is not made. fourth digit of the parameter mode setpoints (3B ModE).
5. Each setpoint can be programmed to activate on eithe
the measured net value, gross value, the peak the valley 1 0 0 6 0
or. if activated the totalizer or integrator, with the
TOTAL.
6 is for the detection of a peak without a filter, and 7 is
This function is activated by introducing 8 in the for the detection of a peak filtered. In this configuration all
fourth digit of the parameter mode setpoints (3B ModE). the other options are activated (Latch, HI-LO, RET-HYS,
Blink).
1 0 0 8 0 The value parameter of the setpoint (3A SEtP) will be the
6. Each setpoint may be programmed to blink the display value from which the peak starts to be evaluated.
when alarm is active. The LED indicator still lights in
either case.
41
4.1 NEW FUNCTIONS 4. Activate or deactivate relay / opto (+ LED) via an order
The new ALPHA-P provides improved functionality and from rs232C or rs485.
incorporates new functions from which the following refer to
This function is available by introducing 3 in the first digit of
the output options:
the parameter mode setpoints (3B ModE).
FACTORY CONFIGURATION
3 0 0 0 0
To restore the original configuration, press RESET and then
ENTER
during 3 seconds. The lock CodE will also be put to In this configuration the rest of the options (HI-LO, RET-
zero. HYS ) are deactivated except the blink option (last digit of
the parameter).
SETPOINTS Once activated, these options does not deactivate by
overflow or by programming, it only wait an order via RS2 or
1. Each setpoint can be programmed for auto reset or RS4.
latched operation. Latched setpoints require a manual
reset to deactivate (see logic function 25, page 29). This 5. Use setpoint2 to detect a peak.
may be useful in installations where permanent visual This function is activated by introducing 6 or 7 in the
control is not made. fourth digit of the parameter mode setpoints (3B ModE).
2. Each setpoint can be programmed to activate on eithe
the measured net value, gross value, the peak the valley 1 0 0 6 0
or. if activated the totalizer or integrator, with the
TOTAL.
6 is for the detection of a peak without a filter, and 7 is
This function is activated by introducing 8 in the for the detection of a peak filtered. In this configuration all
fourth digit of the parameter mode setpoints (3B ModE). the other options are activated (Latch, HI-LO, RET-HYS,
Blink).
1 0 0 8 0 The value parameter of the setpoint (3A SEtP) will be the
3. Each setpoint may be programmed to blink the display value from which the peak starts to be evaluated.
when alarm is active. The LED indicator still lights in
either case.
41
The value parameter of the delay / hysteresis parameter New functions:
(3AB ModE) indicates how long will the relay / opt be
activated when the peak is reached. (Except in latch mode) Command Function
The relay / opto output will be activated when the display Data Request
stops increasing (once reached the value of setpoint2) during Z Totalizer value
a number of evaluations programmable by the user and B Batch Counter value
between 0 and 99.
The selection of the number of evaluations appears at the Orders
continuation of the configuration of setpoint2 after z Reset Totalizer
introducing 6 or 7 in the fourth digit. x Reset Batch Counter
a# Activate setpoint nº#
RS232 d# Deactivate setpoint nº#
Compatible with ModBus-RTU protocol (see ModBus manual).
Parameter Modification
RS485 S# Change the value of setpoint
nº# without saving it
This output can be used to print several data on the panel
printer DITEL Print K180 (see logic functions page 33).
ANALOGICAL
Once chosen the print function, the next step presents
on / off to activate the function TIME which prints the time See remote inputs, page 34.
and date.
BCD
Compatible with ModBus-RTU protocol (see ModBus manual).
See remote inputs, page 33 and 34.
OUTPUT SERIE
The function 10 (write) is now available in the ModBus
protocol, whereas the 01 and 0F are no longer available.
42
The relay / opto output will be activated when the display Data Request
stops increasing (once reached the value of setpoint2) during Z Totalizer value
a number of evaluations programmable by the user and B Batch Counter value
between 0 and 99.
The selection of the number of evaluations appears at the Orders
continuation of the configuration of setpoint2 after z Reset Totalizer
introducing 6 or 7 in the fourth digit. x Reset Batch Counter
a# Activate setpoint nº#
RS232 d# Deactivate setpoint nº#
Compatible with ModBus-RTU protocol (see ModBus manual).
Parameter Modification
RS485 S# Change the value of setpoint
nº# without saving it
This output can be used to print several data on the panel
printer DITEL Print K180 (see logic functions page 33).
ANALOGICAL
Once chosen the print function, the next step presents
on / off to activate the function TIME which prints the time See remote inputs, page 34.
and date.
BCD
Compatible with ModBus-RTU protocol (see ModBus manual).
See remote inputs, page 33 and 34.
OUTPUT SERIE
The function 10 (write) is now available in the ModBus
protocol, whereas the 01 and 0F are no longer available.
42
5. TECHNICAL SPECIFICATIONS
INPUT SIGNAL A/D CONVERSION
Configuration.......................... differential asymmetrical Technique ................................................... dual slope
INPUT PROCESS VOLTAGE CURRENT Resolution .....................................................(±16 bit)
Input ..................................±10V DC ........... 20mA DC Read rate .............................................................16/s
Resolution ...............................0.1mV .................0.1µA DISPLAY
Input impedance........................ 1M ................... 15 Main......................... -32000/32000, 5 digits 14mm red
Excitation ..................... 24V @ 30mA, 10/ 5V @ 120mA Auxiliary ..................................... 1 digit 7.62mm green
INPUT POTENTIOMETER Decimal point.........................................programmable
Applicable voltage............................................ 10V DC LED's............................. 14 (programming and control)
Input impedance.................................................. 1M Display update time ............................................ 62ms
Excitation .............................................. 10V @ 120mA Positive over range...........................................+oVFLo
Negative over range..........................................-oVFLo
ACCURACY
POWER SUPPLY
Max. error ................ ± (0.1% of the reading +2 digits)
AC voltages .. 115V/230V, 24V/48V (±10%) 50/60Hz AC
Temperature coefficient ............................ 100ppm/ ºC
DC voltages ................................................ 10-30V DC
Warm-up.................................................... 10 minutes
Consumption ........... 5W (without options), 10W (max.)
FUSES (DIN 41661) - (recommended) ENVIRONMENTAL
Alpha-P (230/115V AC) ........................... F 0.2A/ 250 V Splash-proof ...............................................Indoor Use
Alpha-P1 (10-30V DC) ................................F 2A/ 250 V Operating temp. ....................................... -10 ºC to 60 ºC
Alpha-P2 (24/48V) .................................. F 0.5A/ 250 V Storage temperature ............................-25ºC to +85ºC
Relative humidity .................................. <95% at 40ºC
FILTERS Max. altitude.................................................... 2000 m
Filter P MECHANICAL
Cut -off frequency (-3 dB) ...............from 4Hz to 0.05Hz Dimensions........................................... 96x48x120mm
Slope ........................................... from 14 to 37 dB/10 Panel cut out ............................................... 92x45mm
Filter E Weight ................................................................600g
Programmable ............................................... 10 levels Case material................. UL 94 V-0 rated polycarbonate
Front Sealed ........................................................ IP65
43
5. TECHNICAL SPECIFICATIONS
INPUT SIGNAL A/D CONVERSION
Configuration ..........................differential asymmetrical Technique....................................................dual slope
INPUT PROCESS VOLTAGE CURRENT Resolution..................................................... (±16 bit)
Input.................................. ±10V DC ........... 20mA DC Read rate............................................................. 16/s
Resolution .............................. 0.1mV ................ 0.1µA DISPLAY
Input impedance ........................1M ...................15 Main ......................... -32000/32000, 5 digits 14mm red
Excitation......................24V @ 30mA, 10/ 5V @ 120mA Auxiliary...................................... 1 digit 7.62mm green
INPUT POTENTIOMETER Decimal point ........................................ programmable
Applicable voltage ............................................ 10V DC LED's ............................. 14 (programming and control)
Input impedance .................................................. 1M Display update time.............................................62ms
Excitation............................................... 10V @ 120mA Positive over range .......................................... +oVFLo
Negative over range ......................................... -oVFLo
ACCURACY
POWER SUPPLY
Max. error................. ± (0.1% of the reading +2 digits)
AC voltages...115V/230V, 24V/48V (±10%) 50/60Hz AC
Temperature coefficient............................. 100ppm/ ºC
DC voltages ................................................ 10-30V DC
Warm-up ....................................................10 minutes
Consumption............ 5W (without options), 10W (max.)
FUSES (DIN 41661) - (recommended) ENVIRONMENTAL
Alpha-P (230/115V AC)............................F 0.2A/ 250 V Splash-proof .............................................. Indoor Use
Alpha-P1 (10-30V DC) ............................... F 2A/ 250 V Operating temp. ....................................... -10 ºC to 60 ºC
Alpha-P2 (24/48V)...................................F 0.5A/ 250 V Storage temperature ........................... -25ºC to +85ºC
Relative humidity................................... <95% at 40ºC
FILTERS Max. altitude ....................................................2000 m
Filter P MECHANICAL
Cut -off frequency (-3 dB)............... from 4Hz to 0.05Hz Dimensions ........................................... 96x48x120mm
Slope............................................ from 14 to 37 dB/10 Panel cut out................................................ 92x45mm
Filter E Weight................................................................ 600g
Programmable ............................................... 10 levels Case material .................UL 94 V-0 rated polycarbonate
Front Sealed ........................................................ IP65
43
5.1 - Dimensions and mounting
44
If a product appears to have a defect or fails during the normal use within the warranty
period, please contact the distributor from which you purchased the product.
This warranty does not apply to defects resulting from action of the buyer such as
mishandling or improper interfacing.
The liability under this warranty shall extend only to the repair of the instrument. No
responsibility is assumed by the manufacturer for any damage which may result from its
use.
All the DITEL products benefit from an unlimited and unconditional warranty of THREE (3)
years from the date of their purchase. Now you can extend this period of warranty up to
FIVE (5) years from the product commissioning, only by fulfilling a form.
45
The instruments are warranted against defective materials and workmanship for a period of
three years from date of delivery.
If a product appears to have a defect or fails during the normal use within the warranty
period, please contact the distributor from which you purchased the product.
This warranty does not apply to defects resulting from action of the buyer such as
mishandling or improper interfacing.
The liability under this warranty shall extend only to the repair of the instrument. No
responsibility is assumed by the manufacturer for any damage which may result from its
use.
All the DITEL products benefit from an unlimited and unconditional warranty of THREE (3)
years from the date of their purchase. Now you can extend this period of warranty up to
FIVE (5) years from the product commissioning, only by fulfilling a form.
45
7. DECLARATION OF CONFORMITY
Manufacture : DITEL - Diseños y Tecnología S.A. Applicable Standards: EN50081- 1 Generic emission
EN55022/CISPR22 Class B
Address: Travessera de les Corts, 180 Applicable Standards: EN50082- 1 Generic immunity
08028 Barcelona IEC1000-4-2 Level 3 Criteria B
ESPAÑA Air Discharge 8kV
Contact Discharge 6kV
46
7. DECLARATION OF CONFORMITY
Manufacture : DITEL - Diseños y Tecnología S.A. Applicable Standards: EN50081- 1 Generic emission
EN55022/CISPR22 Class B
Address: Travessera de les Corts, 180 Applicable Standards: EN50082- 1 Generic immunity
08028 Barcelona IEC1000-4-2 Level 3 Criteria B
ESPAÑA Air Discharge 8kV
Contact Discharge 6kV
46
INSTRUCTIONS FOR THE RECYCLING
This electronic instrument is covered by the 2002/96/CE European Directive so, it is properly marked with
the crossed-out wheeled bin symbol that makes reference to the selective collection for electrical and
electronic equipment which indicates that at the end of its lifetime, the final user cannot dispose of it as
unsorted municipal waste.
In order to protect the environment and in agreement with the European legislation regarding waste of
electrical and electronic equipments from products put on the market after 13 August 2005, the user can
give it back, without any cost, to the place where it was acquired to proceed to its controlled treatment and
recycling.
This electronic instrument is covered by the 2002/96/CE European Directive so, it is properly marked with
the crossed-out wheeled bin symbol that makes reference to the selective collection for electrical and
electronic equipment which indicates that at the end of its lifetime, the final user cannot dispose of it as
unsorted municipal waste.
In order to protect the environment and in agreement with the European legislation regarding waste of
electrical and electronic equipments from products put on the market after 13 August 2005, the user can
give it back, without any cost, to the place where it was acquired to proceed to its controlled treatment and
recycling.