Sei sulla pagina 1di 2

SYSTEM EXTERNAL STATIC CALCULATION FOR

FCU

SUPPLY AIR QUANTITY = 235 L / Sec.


Project: MPH Lusail Sports Club - Package 2 Minimum: 100 Pa
Basement 2 - Area 1 Actual : 36.98 Pa
Equipment ref : PK2-FCU-B2-14

Sl. DUCT TYPE QNTY. DUCT SIZE AREA AIR QNTY. LENGTH VELOCITY FRIC. LOSS / VP1 VP2 VALUE TOTAL ST. PR.
No. SECN. NOS. ( IN MM ) ( IN INCHES ) Sq. Ft. L/Sec. CFM IN M. IN Ft. FPM 100Ft IN.-WG IN-WG IN-WG N LOSS IN -WG

2 A RETURN AIR
DUCT 250 250 10 10 0.7 205 434 1.43 4.69 626 0.058 0.00272
VCD 1 250 250 10 10 0.7 205 434 - 0.01200
PLENUM BOX 850 300 34 12 2.8 205 434 0.30 0.98 0.00100

2 B SUPPLY AIR
FLEX. CONEC. 800 250 32 10 2.2 235 498 0.03 0.09 224 0.00100
REDUCER 800 x 250 300 x 250 10 x 10 12 x 10 2.2 / 0.8 - - - - 224 / 598 0.003 0.022 1.02 0.01938
DUCT 300 250 12 10 0.8 235 498 0.10 0.31 598 0.047 0.00015
REDUCER 300 x 250 250 x 200 12 x 10 10 x 8 0.8 / 0.6 - - - - 598 / 515 0.022 0.017 1.02 0.00510
DUCT 250 200 10 8 0.6 135 286 3.80 12.46 515 0.046 0.00573
REDUCER 250 x 200 200 x 200 10 x 8 8x8 0.6 / 0.4 - - - - 515 / 429 0.017 0.011 1.02 0.00612
DUCT 200 200 8 8 0.4 90 191 5.30 17.38 429 0.037 0.00643
REDUCER 200 x 200 200 x 150 8x8 8x6 0.4 / 0.3 - - - - 429 / 286 0.011 0.005 1.02 0.00612
DUCT 200 150 8 6 0.3 45 95 4.37 14.33 286 0.02 0.00287
VCD 1 200 150 8 6 0.3 45 95 - - - 0.01200
DIFFUSER 0.04800

NOTE :- Total Ext. Press. Loss 0.13


1 S.P. LOSS DETAIL FROM " CARRIER MANUAL DESIGN " Safety Factor 15% 0.15
2 ST. DUCT = LENGTH OF DUCT X FRICTION LOSS /100 Ft. Pressure Dropped in Pa. 36.98
3 ELBOWS = EQUIV. LENGTH X FRICTION LOSS / 100 Ft.
4 REDUCERS = N ( VP2 - VP 1 )
5 EXPANSION = N ( VP1 - VP2 )
6 ALL PRESSURE DROP DETAILS FOR GRILLES/ DIFF./DAMPERS/MOT./F.-DAMPERS/F. SMOKE DAMPERS TAKEN FROM RUSKIN /TITUS PRODUCT CATALOGUE
SYSTEM EXTERNAL STATIC CALCULATION FOR
FCU

SUPPLY AIR QUANTITY = 105 L / Sec.


Project: MPH Lusail Sports Club - Package 2 Minimum: 100 Pa
Basement 2 - Area 1 Actual : 22.08 Pa
Equipment ref : PK2-FCU-B2-20

Sl. DUCT TYPE QNTY. DUCT SIZE AREA AIR QNTY. LENGTH VELOCITY FRIC. LOSS / VP1 VP2 VALUE TOTAL ST. PR.
No. SECN. NOS. ( IN MM ) ( IN INCHES ) Sq. Ft. L/Sec. CFM IN M. IN Ft. FPM 100Ft IN.-WG IN-WG IN-WG N LOSS IN -WG

2 B SUPPLY AIR
FLEX. CONEC. 500 200 20 8 1.1 105 223 0.03 0.09 200 0.00100
REDUCER 500 x 200 200 x 200 x 8x8 1.1 / 0.4 - - - - 200 / 358 0.003 0.008 1.02 0.00510
DUCT 200 200 8 8 0.4 75 159 1.61 5.28 358 0.026 0.00137
ELBOW-90 DEG. 200 200 8 8 0.4 75 159 - 4.00 358 0.026 0.00104
DUCT 200 200 8 8 0.4 75 159 0.82 2.69 358 0.026 0.00070
REDUCER 200 x 200 200 x 150 20 x 8 8x6 0.4 / 0.3 - - - - 358 / 223 0.008 0.003 1.02 0.00510
DUCT 200 150 8 6 0.3 35 74 1.80 5.90 223 0.012 0.00071
ELBOW-90 DEG. 200 150 8 6 0.3 35 74 - 3.00 223 0.012 0.00036
DUCT 200 150 8 6 0.3 35 74 3.57 11.71 223 0.012 0.00141
VCD 1 200 150 8 6 0.3 35 74 - 0.01200
DIFFUSER 0.04800

NOTE :-
1 S.P. LOSS DETAIL FROM " CARRIER MANUAL DESIGN "
2 ST. DUCT = LENGTH OF DUCT X FRICTION LOSS /100 Ft. Total Ext. Press. Loss 0.08
3 ELBOWS = EQUIV. LENGTH X FRICTION LOSS / 100 Ft. Safety Factor 15% 0.09
4 REDUCERS = N ( VP2 - VP 1 ) Pressure Dropped in Pa. 22.08
5 EXPANSION = N ( VP1 - VP2 )
6 ALL PRESSURE DROP DETAILS FOR GRILLES/ DIFF./DAMPERS/MOT./F.-DAMPERS/F. SMOKE DAMPERS TAKEN FROM RUSKIN /TITUS PRODUCT CATALOGUE