Air-Cooled
PRODUCT SYSTEM
Application
Air Cooled Mini
Chiller
Solution
Fan Coil Unit
R22 020/025/030/040/050/060/080/100/120/150
UAE 020/025/030/040/050/060/080/100/120/150
Application
025/030/040/050/060/080/100/120/150
01 R407C
UAP 060/080/100/120/150
020/025/030/040/050/055
04
FWE-E
Solution
FWC-C
13
19 20 21 22 24
Wall Mounted Ceiling Cassette Ceiling Cassette Ceiling Cassette Ceiling Convertible
Compact Type (600 x 600) Type (900 x 900) Type (900 x 900) Type
With Brushless DC Motor
25 27
Ceiling Concealed Type Ducted Blower Type
Remark: All unit photos in this catalog are solely for illustration purpose, actual outlook may differ slightly.
All specifications are subjected to change by the manufacturer without prior notice.
Application
Availablility of
cooling only
& heatpump
models
Hotels Office Rooms @ Coffee Houses
Restaurant
Long Piping
Application
Chilled Water
System Solution
Advantages
1 2
Air Cooled
QUIET OPERATION VERSATILITY IN SYSTEM COUPLING
Quiet operation due to fan coil units Chilled water system is designed with versatility in system
and chiller can be placed far away coupling where there is no limitation in the number of
Mini Chiller
from room fan coil unit coupling with mini chiller as long as they meet
the designed capacity requirament & water flow rate.
System coupling of one to one and one to many
configurations
The Daikin mini chiller is fully assembled, complete FACTORY PRECHARGED REFRIGERANT
with all necessary components in one unit like water
Each heat exchanger in the chiller is brazed
pump, internal wiring, fully charged with refrigerant SERVICEABILITY & ERROR CODE FOR EASE OF
and undergo strict testing and quality check before and tested against leakages through dried air
TROUBLESHOOTING
delivery. Only connection to water piping and power at 30 bars. After that, another process of
supply is required at site. system vacuuming is done before it is By opening the front panel, one can access and service all the
components in the chiller. The chiller is equipped with self
accurately charged with refrigerant to ensure
diagnosis function which allow the chiller panel to display total of
optimum performance. Thus, it saves the 19 type of faulty occurred in the system by showing different
hustles of field charging by installers. error code on the LCD screen of the panel.
Refrigarent
3 4
PARALLEL INSTALLATION MICROPROCESSOR CONTROL SAFETY PROTECTION
Daikin Mini Chiller provides flexibility in adding Daikin chillers are equipped with microprocessor The safety protections provided for the Daikin chiller
capacity for building extension. This can be done controller that will control and regulate the operation are:
by installing the mini chiller in parallel of the unit. • High & Low Pressure Switches
connection. • Anti-Freeze Protection Sensor
Besides that, the controller that contains the well • Discharge Temperature Sensor
A network of up to 50 chillers is possible to be
developed algorithm will provide protection to the • Over Pressure Relief Valve
connected in a system. For ease of controlling
chiller by accurately sensing the key temperatures in • Water Pressure Differential Switch
and setting, Daikin Mini Chiller panel implement both the water and refrigerant circuit. Should there be • Anti-Freeze Heater on BPHE
Master and Slave function. This function allows any abnormal reading received by controller, an alarm • Compressor Water Pump & Fan Motor Overload
user to monitor all the settings on the slave units signal will be sent to chiller panel, followed by Protector
at the master unit. protection action plans such as to stop the operation
of compressor, condenser fan motor or circulating
water pump.
Supported Up To 50 Units Of Chiller
Chiller 0 Chiller 1 Chiller 2
BRAZED PLATE HEAT EXCHANGER (BPHE)
The heat exchanger is
made of AISI 316
stainless steel plates
closely arranged and
brazed together to
5 way wire (CM8)
Chiller
maximize possible
Chiller Panel 0 Chiller Panel 1 Communication Bus heat exchange
(Master) (Slave) efficiency.
AISI 316 stainless steel BPHE
SUPERIOR RELIABILITY :
EFFICIENCY AND PERFORMANCE :
State-Of-The-Art Components
CHILLER CONTROL PANEL • The display is shown in an 8-lines graphical LCD
SCROLL COMPRESSOR ANTI-FREEZE PROTECTION display. There are 8 dedicated keys available in the
The chiller panel controller is designed to control the
panel.
Scroll Compressors are used for the units to offer a The chiller unit has several anti-freeze protection chiller operation. This device allows the user to have
• Menu selection.
quieter and more reliable performance over a wide features: customized control for each connected unit.
• Navigation on the screen.
operating temperature range. (Except UAE020C/CR
1. Built-in heater in BPHE • Modification of the selected value.
which uses rotary compressor). Each chiller will have a chiller control panel that
The BPHE has a strip heater around it to prevent water
comes as a standard accessory. At the same time, the
freezing inside.
For UA(E/P) 030, 040, 050, 060, 080, 100, 120, 150 chiller control panel is able to be installed remotely
CR, phase protector is provided to prevent the 2. Anti-Freeze sensor through the cable up to a distance of 100 meters.
compressor from rotating in the wrong directions. BPHE can avoid the frosting as the anti-freeze sensor Example, the chiller panel can be installed in a
will send the signal to cut out the compressor if the centralized plant control room for the building.
water temperature becomes too cold.
Copeland 3. Water pressure differential switch The chiller control panel has been designed taking into
Compliant ®
This protection feature will ensure there is water flow consideration of the user friendly and yet versatile
Scrolls
in pipings when the chiller is in operation. Otherwise, control features.
High Efficiency
the compressor will cut out immediately.
Motor
Features:
• Whole system configuration.
Quiet Shutdown • Unique parameter settings.
Device
• Operation status display.
• Tracing fault record (offer quick troubleshooting
solutions).
5 6
LOAD BALANCING CONTROL ANTI CORROSION GOLD ALUMINUM FIN
FLEXIBILITY :
For UA(E/P)080 ~ 150 C/CR both compressors will Gold Aluminum fin is offered as the standard material
cut in and cut out depending on their of the condenser heat exchanger of this series of
TRUE DUAL CIRCUITS BPHE
accumulative operating time. This sequencing chiller. Apply sophisticated technology of true dual circuit
control feature will ensure no single compressor is BPHE.
overload in operation as well as to ensure longer
reliability of compressors. The true dual BPHE puts the secondary circuit
(water) in contact with 2 primary circuits
CAPACITY STEP CONTROL (refrigerant). So even if one primary circuit is shut
UA(E/P)080 ~ 150 C/CR has been designed with two off, each secondary channel is still in contact with a
separate refrigerant circuits, i.e. it has two primary channel. These advantages have made the
compressors. By doing so, the unit has part loading product the natural choice for flexible chillers,
capabilities, i.e. 0-50-100% of rated capacity. This will climate control applications and high-precision
improve the reliability and energy efficiency of the systems food cooling cabinets in supermarkets.
unit, especially during low loading operations.
Ref.1 Ref.2 Ref.1 Ref.2 Ref.1
BETTER PERFORMANCE
PARALLEL INSTALLATION
• Usage of higher efficient R-410A rotary compressors
Air-Cooled Mini Chiller in tandem configuration A network up to 50 chillers in a system is possible.
• Tight tolerances between moving parts resulting in Control on the operation of the chillers will be done
Model: UAQ 030/040/050/055 CR high compressor volumetric efficiency through the microprocessor controller. The external
• Minimize mechanical losses water piping connection can be made either from
This innovative air cooled chiller by Daikin the left or right side of the unit.
• Minimize gas flow losses and turbulence
was designed with one purpose in mind,
• Optimize compressor oil return
which is to offer cost and energy saving for
users.
CAPACITY STEP CONTROL
3 steps compressor loading (0%-40%-60%-100%) for
UAQ 040 CR & UAQ 050 CR
7 8
R22 AIR COOLED MINI CHILLER SPECIFICATION
R22 COOLING MODEL R22 HEATPUMP MODEL
MODEL UAE020C UAE025C UAE030C UAE040C UAE050C UAE060C MODEL UAE020CR UAE025CR UAE030CR UAE040CR UAE050CR UAE060CR
Btu/h 20,000 24,200 30,000 39,500 48,500 54,000 Btu/h 19,000 23,000 27,500 38,000 44,000 50,000
NOMINAL COOLING CAPACITY NOMINAL COOLING CAPACITY W 5,570 6,740 8,060 11,140 12,900 14,650
W 5,860 7,090 8,790 11,580 14,210 15,830
NORMAL TOTAL INPUT POWER (COOLING) W 2,650 2,680 3,580 4,490 5,080 5,770 Btu/h 22,000 27,000 35,000 43,000 50,000 55,000
NOMINAL HEATPUMP CAPACITY
NORMAL RUNNING CURRENT (COOLING) A 12.25 12.17 16.41 9.67 9.75 12.01 W 6,450 7,910 10,260 12,600 14,650 16,120
EER W/W 2.21 2.65 2.48 2.58 2.80 2.74 COOLING W 2,530 2,670 3,440 4,230 5,190 5,580
NORMAL TOTAL INPUT POWER
HEATPUMP W 2,600 2,790 3,440 4,390 5,100 5,320
REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE
REFRIGERANT CHARGE kg 1.25 1.80 1.88 2.80 3.15 3.30 COOLING A 11.78 12.17 17.27 9.05 9.77 12.60
NORMAL RUNNING CURRENT
POWER SOURCE (OUTDOOR) V/Ph/Hz 220-240/1/50 380-415/3/50 HEATPUMP A 11.62 12.70 17.25 9.14 9.72 11.50
REFRIGERANT TYPE R22 EER W/W 2.20 2.52 3.44 2.63 2.48 2.63
SOUND PRESSURE LEVEL dBA 57 57 58 59 59 59 COP W/W 2.48 2.84 3.43 2.87 2.87 3.03
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 790 x 1,160 x 460 1,140 x 1,160 x 460 REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE
PACKING HEIGHT X WIDTH X DEPTH mm 920 x 1,270 x 570 1,551 x 1,270 x 570 REFRIGERANT CHARGE kg 1.43 1.75 1.83 3.50 4.10 4.00
UNIT WEIGHT kg 116 123 126 182 189 196 POWER SOURCE (OUTDOOR) V/Ph/Hz 220-240/1/50 380-415/3/50
NOMINAL WATER FLOW RATE COOLING I/s/m3/hr 0.29 / 1.03 0.33 / 1.20 0.42 / 1.51 0.53 / 1.90 0.67 / 2.40 0.76 / 2.73 REFRIGERANT TYPE R22
INDOOR UNIT
INDOOR UNIT
NOMINAL WATER FLOW RATE
CAPACITY / VOLUME L 22 40 HEATPUMP I/s/m3/hr 0.31 / 1.12 0.38 / 1.38 0.49 / 1.75 0.56 / 2.00 0.62 / 2.20 0.76 / 0.72
TANK
MATERIAL MILD STEEL WITH ZINC TYPE ROTARY SCROLL
COMPRESSOR
STAGE OF CAPACITY CONTROL 0 - 100% 0 - 100% 0 - 100% 0 - 100% 0 - 100% 0 - 100%
TYPE THREAED
MODEL UAE080C UAE100C UAE120C UAE150C
CONNECTION mm 25.4
Btu/h 65,000 95,000 116,000 138,000 PIPING 110
NOMINAL COOLING CAPACITY COOLING kPa 79 94 92 118 104
W 24,910 27,840 34,000 40,450 HEAD
HEATPUMP kPa 79 86 73 103 85 87
NORMAL TOTAL INPUT POWER (COOLING) W 8,870 10,590 11,370 14,220 CAPACITY / VOLUME L 22 40
NORMAL RUNNING CURRENT (COOLING) A 17.00 18.50 25.83 31.80 TANK
MATERIAL MILD STEEL WITH ZINC
EER W/W 8.87 2.63 2.99 2.84
REFRIGERANT CONTROL (EXPENSION DEVICE) TXV
REFRIGERANT CHARGE kg 3.90 x 2 4.60 x 2 6.00 x 2 7.10 x 2
POWER SOURCE (OUTDOOR) V/Ph/Hz 380-415/3/50 380-415/3/50 MODEL UAE080CR UAE100CR UAE120CR UAE150CR
REFRIGERANT TYPE R22 Btu/h 80,000 95,000 113,000 138,000
SOUND PRESSURE LEVEL dBA 63 63 67 67 NOMINAL COOLING CAPACITY W 23,450 27,840 33,120 40,450
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 1,245 x 1,500 x 900 1,245 x 1,800 x 1,150 Btu/h 95,000 105,000 120,000 132,000
NOMINAL HEATPUMP CAPACITY
PACKING HEIGHT X WIDTH X DEPTH mm 1,452 x 1,732 x 1,032 1,452 x 2,032 x 1,282 W 27,840 30,770 35,170 38,690
INDOOR UNIT
UNIT WEIGHT kg 328 340 480 560 COOLING W 8,490 11,100 12,070 14,320
NORMAL TOTAL INPUT POWER
NOMINAL WATER FLOW RATE COOLING I/s/m3/hr 0.29 / 1.03 0.33 / 1.20 0.42 / 1.51 0.53 / 1.90 HEATPUMP W 8,750 10,310 12,370 15,020
TYPE SCROLL COOLING A 18.40 18.90 26.60 31.40
COMPRESSOR NORMAL RUNNING CURRENT
STAGE OF CAPACITY CONTROL 0 - 100% 0 - 100% 0 - 100% 0 - 100% HEATPUMP A 18.90 17.10 26.80 32.20
TYPE THREAED EER W/W 2.76 2.51 2.74 2.82
PIPING CONNECTION mm 31.75 COP W/W 3.18 2.98 2.86 2.58
HEAD COOLING kPa 229 229 188 157 REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE
REFRIGERANT CHARGE kg 5.00 x 2 5.40 + 5.30 7.60 x 2 6.50 x 2
ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE POWER SOURCE (OUTDOOR) V/Ph/Hz 380-415/3/50
ALL UNIT ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT) REFRIGERANT TYPE R22
SOUND PRESSURE LEVEL dBA 63 63 67 67
TEMPERATURE COOLING HEATING UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 1,245 x 1,500 x 900 1,245 x 1,800 x 1,150
ENTERING 12°C 40°C PACKING HEIGHT X WIDTH X DEPTH mm 1,452 x 1,732 x 1,032 1,452 x 2,032 x 1,282
EVAPORATOR UNIT WEIGHT kg 328 340 480 560
LEAVING 7°C 45°C
INDOOR UNIT
COOLING I/s/m3/hr 1.13 / 4.05 1.33 / 4.80 1.67 / 6.00 2.00 / 7.20
NOMINAL WATER FLOW RATE
CONDENSOR AMBIENT 35°C 7°C / 6°C HEATPUMP I/s/m3/hr 1.13 / 4.05 1.33 / 4.80 1.67 / 6.00 2.00 / 7.20
SCROLL
COMPRESSOR
STAGE OF CAPACITY CONTROL 0 - 100% 0 - 100% 0 - 100% 0 - 100%
TYPE THREAED
CONNECTION mm 31.75
PIPING COOLING kPa 254 173 188 157
HEAD
HEATPUMP kPa 229 144 188 157
ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
ALL UNIT ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT)
9 10
R407C AIR COOLED MINI CHILLER SPECIFICATION R407C HEATPUMP MODEL
R407C COOLING MODEL MODEL UAP060CR UAP080CR UAP100CR UAP120CR UAP150CR
Btu/h 50,000 74,000 87,500 110,000 130,000
MODEL UAP025C UAP030C UAP040C UAP050C UAP060C NOMINAL COOLING CAPACITY W 14,650 21,690 25,640 32,240 38,100
Btu/h 23,000 26,900 38,500 47,000 50,000 Btu/h 55,000 90,000 96,000 118,000 144,000
NOMINAL COOLING CAPACITY NOMINAL HEATPUMP CAPACITY
W 6,740 7,880 11,280 13,920 14,650 W 16,120 26,380 28,140 34,500 42,200
NORMAL TOTAL INPUT POWER (COOLING) W 2,950 3,770 4,680 5,430 6,040 (COOLING) W 6,280 8,990 11,100 12,630 15,900
NORMAL TOTAL INPUT POWER
NORMAL RUNNING CURRENT (COOLING) A 13.30 17.41 9.62 10.20 11.28 (HEATPUMP) W 5,570 9,350 11,110 12,750 16,100
EER W/W 2.29 2.09 2.41 2.56 2.43 (COOLING) A 11.60 18.90 19.00 27.10 34.40
NORMAL RUNNING CURRENT
(HEATPUMP) A 11.50 19.00 19.10 26.10 34.80
REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE 2.55
EER W/W 2.33 2.41 2.31 2.40
REFRIGERANT CHARGE kg 1.72 1.63 3.00 3.30 3.20 COP W/W 2.83
2.89 2.53 2.71 2.62
POWER SOURCE (OUTDOOR) V/Ph/Hz 220-240/1/50 380-415/3/50 REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE
REFRIGERANT TYPE R407C REFRIGERANT CHARGE kg 4.00 3.70 X 2 4.80 + 4.70 5.80 x 2 6.40 x 2
SOUND PRESSURE LEVEL dBA 57 58 59 59 60 POWER SOURCE (OUTDOOR) V/Ph/Hz 380-415/3/50 380-415/3/50
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 790 x 1,160 x 460 1,140 x 1,160 x 460 REFRIGERANT TYPE R407C
mm 920 x 1,270 x 570 1,551 x 1,270 x 570 SOUND PRESSURE LEVEL dBA 60 63 63 67 67
PACKING HEIGHT X WIDTH X DEPTH
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 1,140 x 1,160 x 460 1,245 x 1,500 x 900 1,245 x 1,800 x 1,150
UNIT WEIGHT kg 123 126 188 189 196 PACKING HEIGHT X WIDTH X DEPTH mm 1,551 x 1,270 x 570 1,452 x 1,732 x 1,032 1,452 x 2,032 x 1,282
INDOOR UNIT
NOMINAL WATER FLOW RATE COOLING I/s/m3/hr 0.31 / 1.11 0.38 / 1.36 0.53 / 1.90 0.64 / 2.30 0.69 / 2.50 UNIT WEIGHT kg 203 340 340 480 560
COOLING I/s/m3/hr 0.64 / 2.30 1.03 / 3.70 1.25 / 4.50 1.67 / 6.00 1.89 / 6.80
INDOOR UNIT
TYPE SCROLL NOMINAL WATER FLOW RATE
COMPRESSOR HEATPUMP I/s/m3/hr 0.78 / 2.80 1.03 / 3.70 1.25 / 4.50 1.67 / 6.00 1.89 / 6.80
STAGE OF CAPACITY CONTROL 0 - 100% 0 - 100% 0 - 100% 0 - 100% 0 - 100%
TYPE THREAED COMPRESSOR TYPE SCROLL
STAGE OF CAPACITY CONTROL 0 - 100% 0 - 50 -100% 0 - 50 -100% 0 - 50 -100% 0 - 50 -100%
PIPING CONNECTION mm 25.4
TYPE THREAED
HEAD COOLING kPa 94 93 117 93 110 CONNECTION mm 25.4 31.75
CAPACITY / VOLUME L 22 40 PIPING
COOLING kPa 110 263 193 188 172
TANK HEAD HEATPUMP 170 170 172
MATERIAL MULTISTAGE END SUCTION kPa 87 188
ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
MODEL UAP080C UAP100C UAP120C UAP150C ALL UNIT ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT)
Btu/h 80,000 90,000 115,000 137,000
NOMINAL COOLING CAPACITY TEMPERATURE COOLING HEATING
W 23,450 26,380 33,730 40,150
NORMAL TOTAL INPUT POWER (COOLING) W 9,430 11,210 12,170 14,970 ENTERING 12°C 40°C
NORMAL RUNNING CURRENT (COOLING) A 18.00 19.22 26.50 33.00 EVAPORATOR
EER W/W 2.49 2.35 2.77 2.68 LEAVING 7°C 45°C
CONDENSOR AMBIENT 35°C 7°C / 6°C
REFRIGERANT CONTROL (EXPENSION DEVICE) TXV
REFRIGERANT CHARGE kg 3.90 x 2 3.80 x 2 5.60 x 2 6.00 x 2
POWER SOURCE (OUTDOOR)
REFRIGERANT TYPE
V/Ph/Hz 380-415/3/50
R407C
R410A AIR COOLED MINI CHILLER SPECIFICATION
SOUND PRESSURE LEVEL dBA 63 63 67 67
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 1,245 x 1,500 x 900 1,245 x 1,800 x 1,150 R410A HEATPUMP MODEL
PACKING HEIGHT X WIDTH X DEPTH mm 1,452 x 1,732 x 1,032 1,452 x 2,032 x 1,282
UNIT WEIGHT kg 340 340 480 560 MODEL UAQ020CR UAQ025CR UAQ030CR UAQ040CR UAQ050CR UAQ055CR
INDOOR UNIT
NOMINAL WATER FLOW RATE COOLING I/s/m3/hr 1.14 / 4.10 1.25 / 4.50 1.67 / 6.00 2.00 / 7.20 Btu/h 15,700 21,000 24,800 34,000 41,600 45,000
NOMINAL COOLING CAPACITY
TYPE SCROLL W 4,600 6,150 7,270 10,000 12,200 13,200
COMPRESSOR Btu/h 21,500 25,000 32,500 43,000 48,000 55,000
STAGE OF CAPACITY CONTROL 0 - 50 - 100% 0 - 50 - 100% 0 - 50 - 100% 0 - 50 - 100% NOMINAL HEATPUMP CAPACITY
TYPE THREAED W 6,300 7,330 9,530 12,600 14,070 16,120
(COOLING) W 2,620 2,760 3,830 5,000 5,310 5,490
PIPING CONNECTION mm 31.75 NORMAL TOTAL INPUT POWER
(HEATPUMP) W 2,590 2,790 3,630 4,650 5,150 5,440
HEAD COOLING kPa 229 229 188 157 (COOLING) A 11.76 12.70 16.88 7.44 7.90 8.18
NORMAL RUNNING CURRENT
(HEATPUMP) A 11.93 12.90 16.32 7.20 7.83 8.38
ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE EER W/W 1.76 2.23 1.90 2.00 2.30 2.40
ALL UNIT ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT) COP W/W 2.43 2.63 2.62 2.71 2.73 2.96
REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE
TEMPERATURE COOLING HEATING REFRIGERANT CHARGE kg 1.20 1.725 2.20 4.30 4.20 4.30
POWER SOURCE (OUTDOOR) V/Ph/Hz 220-240/1/50 380-415/3/50
ENTERING 12°C 40°C REFRIGERANT TYPE R410A
EVAPORATOR
LEAVING 7°C 45°C SOUND PRESSURE LEVEL dBA 58 59 57 59 59 61
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 790 x 1,160 x 460 1,140 x 1,160 x 460
CONDENSOR AMBIENT 35°C 7°C / 6°C PACKING HEIGHT X WIDTH X DEPTH mm 920 x 1,270 x 570 1,551 x 1,270 x 570
UNIT WEIGHT kg 128 128 128 195 195 195
INDOOR UNIT
NOMINAL WATER FLOW RATE COOLING I/s/m3/hr 0.24 / 0.86 0.28 / 1.00 0.42 / 1.50 0.50 / 1.80 0.60 / 2.15 0.75 / 2.70
HEATPUMP I/s/m3/hr 0.32 / 1.16 0.35 / 1.25 0.42 / 1.50 0.50 / 1.80 0.60 / 2.15 0.75 / 2.70
TYPE ROTARY TANDEM ROTARY
COMPRESSOR STAGE OF CAPACITY CONTROL 0-100% 0-100% 0-50-100% 0-40-60-100% 0-40-60-100% 0-50-100%
TYPE THREADED
CONNECTION mm 25.4
PIPING
COOLING kPa 90 98 93 90 74 70
HEAD
HEATPUMP kPa 73 90 80 71 64 53
CAPACITY / VOLUME L 22 40
TANK
MATERIAL MILD STEEL WITH ZINC
ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
ALL UNIT ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT)
11 12
DISPLAY UP TO 46 TYPES OF CHILLER FAULT /
SMART MANAGER CONTROLLER ALARM AND 6 TYPES OF FCU FAULT / ALARM
By adopting the Daikin chilled water system, the comfort in residential and light commercial Whenever a fault occurred in either the chiller or fan coil unit,
buildings such as offices, hospital, restaurant, hotel and shopping complex can be controlled and a signal will be sent to Smart Manager and an alarm message will (Ch 0)
appear on the LCD, showing type of alarm, alarm occured time,
managed from just one point, that is through the Smart Manager. Alarm 1
date and unit.
The Smart Manager is acting as a central command to manage the operation of both the chilled Comp 1 overload
This will greatly ease the troubleshooting process and thus
water fan coil units and the chillers. reduce the valuable time of service technicians.
01/01/00 12.00am
Besides allowing the user to have customized control for each connected unit, the Smart As soon as the fault is solved, the alarm will automatically
Manager is also able to manage the overall system operating mode of all units based on the air dissolve from the LCD.
conditioning system load demand of the building.
Fan Coil Network BUS Chiller Network BUS ENERGY SAVING PROGRAMMABLE TIMER
The operation of the chiller and each fan
coil unit can be preset to operate and to
stop at different time schedule and at FWC
Unit
FWE 2
Time
Through the versatile Smart Manager controller, the operation of each equipments in the Daikin chilled
water system connected through the chiller Bus and Daikin own proprietary NIM BUS can be managed At the same time, Smart Manager allows
and controlled. setting of up to five sets of 7 days programmable operation schedules (2 On/Off timer per day) for each
fan coil unit
Up to
A
B 50 units
Smart Manager Controller CHILLER BUS
of Chiller
NIM BUS Up to
A
B 120 units
of FCUs
NIM NIM NIM
13 14
THRESHOLD VALUE SETTING
If the priority setting is being preset to fan coil unit, the
FWC
operating mode of the complete Daikin chilled water
system can be synchronized to operate under one same
mode. This is achievable through the unique feature called
“Threshold Value Setting”
FWE 1
FWW
Example,
In a network of 10 fan coil units that is currently operating
in COOL mode and a threshold of 60% was set for COOL
mode and threshold of 50% was set for HEAT mode. Should
6 of the fan coil units are requesting for HEAT mode then
the threshold for HEAT is crossed. Signal will be sent by
Smart Manager to chiller BUS to switch the operating
mode of all chillers to HEAT mode. Requirement of users
will be met.
• Heat Treshold •
Chiller to operate at
PASSWORD PROTECTION FOR ADVANCED HOLIDAY SETTING
Heat Mode
PARAMETER SETTINGS (CHILLER) While designing the Smart Manager, the practical aspects of
A Daikin chilled water product system with key equipment application were always the key points to be
0 1 2 3 4 5 6 7 8 9 10 parameters that were set by personnel to optimize considered. Thus resulting in the creation of “Holiday
Chiller to operate at operating conditions will need to be protected against Setting” feature.
Cool Mode any unauthorized disturbance or changes. The built in
“Password Settings” feature will prevent the losing of In this feature, users are allowed to set up to 10 holiday
key parameter settings in the Smart Manager timers with each timer can last for duration of 99 days.
• Cool Treshold • controller as well as the chiller panel
During the duration of Holiday Timer set earlier, all fan coil
units and chiller will automatically be turned Off.
15 16
LOW POWER MODE (CHILLER + FCU)
Smart Manager controller will turn into low power mode during electricity power breakdown. It will
operate based on the built in backup battery and only one timer and interrupt is active. CPU operation
is Off and no display on LCD as well for energy saving purpose.
To complement the new innovative Smart Manager range of air cooled chillers,
Daikin is offering an extensive range of chilled water fan coil units that will meet
ACCUMULATIVE COMPRESSOR RUN TIME most of indoor application requirements covering residential, light commercial and
User can also check the compressor run time of chiller in Smart Manager Controller. It will provide a commercial.
guideline as well as posting a reminder for requirement of routine system service.
The aesthetically attractive decorative fan coil units such as Wall Mounted models,
Ceiling Cassette and Ceiling Convertible are compact and ergonomic, the ranges
can blend in easily to any interior designs whether it is residential houses, office,
restaurant or shops.
In addition, the Daikin chilled water fan coil units are designed with easy
installation and easy servicing in mind. The fan coil units also include the
microprocessor controller that has built in algorithm to control the operation of the
fan coil unit as well as to provide protection to the unit.
17 18
Wall Mounted Type Ceiling Cassette Compact Type (600x600)
*
AL AL
MODEL FWW02L FWW03L FWW04L FWW05L FWW06L Specification for Ceiling Cassette Compact Type
Btu/h 8300 9200 11300 15500 18000
NOMINAL COOLING CAPACITY MODEL FWF02C FWF04C FWF05C
W 2430 2700 3310 4540 5280
Btu/h 8500 14000 15500
Btu/h 6300 6900 9000 11700 14000 NOMINAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY W 2490 4100 4540
W 1850 2020 2640 3430 4100
Btu/h 6500 10000 11500
NOMINAL HEATING CAPACITY Btu/h 11000 12000 15000 20500 25000 NOMINAL SENSIBLE COOLING CAPACITY
W 1910 2930 3370
(ENTERING WATER TEMP. = 50°C) W 3220 3520 4400 6010 7330
NOMINAL HEATING CAPACITY Btu/h 12000 16000 18000
NOMINAL TOTAL INPUT POWER W 31 32 42 57 72
(ENTERING WATER TEMP. = 50°C) W 3520 4690 5280
NOMINAL RUNNING CURRENT A 0.20 0.20 0.21 0.30 0.34
NOMINAL TOTAL INPUT POWER W 63 64 79
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
NOMINAL RUNNING CURRENT A 0.28 0.28 0.35
REFRIGERANT TYPE N/A
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
AIR DISCHARGE AUTOMATIC LOUVER (UP & DOWN)
CONTROL REFRIGERANT TYPE N/A
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
HIGH CFM 260 280 370 510 620 CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
MEDIUM CFM 230 250 320 450 520
AIR FLOW HIGH CFM 380 400 440
LOW CFM 200 220 260 390 460
AIR FLOW MEDIUM CFM 290 310 330
QUIET CFM 180 190 240 360 440
LOW CFM 230 220 280
USGPM 1.85 2.03 2.51 3.43 4.01
NOMINAL WATER FLOW RATE USGPM 2.03 3.43 3.57
litres/min 7.00 7.68 9.50 13.00 15.18 NOMINAL WATER FLOW RATE
INDOOR UNIT
INDOOR UNIT
HEAD LOSS (HEATING) : 50°C kPa 16.8 23.9 26.5
MAX. WORKING PRESSURE kPa 1608
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 0.68 0.74 0.97 0.83 1.01
SOUND PRESSURE LEVEL (H/M/L/Q) dBA 34 / 29 / 25 / 24 35 / 30 / 25 / 24 42 / 39 / 32 / 29 42 / 38 / 34 / 32 46 / 42 / 39 / 37 SURFACE AIR VELOCITY m/s 0.75 0.76 0.83
UNIT DIMENSION HXWXD mm 288 X 800 X 206 310 X 1065 X 224 SOUND PRESSURE LEVEL (H/M/L) dBA 42 / 35 / 29 45 / 38 / 30 48 / 40 / 36
PACKING DIMENSION HXWXD mm 344 x 874 x 274 386 X 1136 X 314 UNIT DIMENSION - ( ) WITH PANEL HXWXD mm 250 X 570 X 570 (295 X 640 X 640)
UNIT WEIGHT kg 9 14 PACKING DIMENSION - ( ) PANEL HXWXD mm 316 X 630 X 630 (126 X 700 X 726)
19 20
Ceiling Cassette Type (900x900) Ceiling Cassette Type (900x900) With Brushless DC Motor
* *
AL AL
NOMINAL HEATING CAPACITY Btu/h 28000 33600 38300 45500 52000 FWKE05E FWKE08E FWKE11E
(ENTERING WATER TEMP. = 50°C) W 8210 9850 11230 13340 15240 MODEL
QUIET LOW MEDIUM HIGH QUIET LOW MEDIUM HIGH QUIET LOW MEDIUM HIGH
NOMINAL TOTAL INPUT POWER W 95 126 167 186 227 Btu/h 8200 11900 15900 20100 15200 19800 24700 30000 21000 26800 33100 40100
NOMINAL RUNNING CURRENT A 0.44 0.55 0.74 0.85 1.03 NOMINAL COOLING CAPACITY
W 2400 3500 4650 5900 4550 5800 7250 8800 6150 7850 9700 11750
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
Btu/h 5800 8700 11700 15400 11000 14500 18500 21900 14600 18900 23800 28600
REFRIGERANT TYPE N/A NOMINAL SENSIBLE COOLING CAPACITY
W 1710 2540 3440 4510 3220 4260 5410 6430 4270 5540 6970 8370
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
CONTROL NOMINAL HEATING CAPACITY Btu/h 11300 15200 19800 24200 18400 23900 30400 38200 24100 31600 39100 46700
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL (ENTERING WATER TEMP. = 50˚C) W 3300 4450 5800 7100 5400 7000 8900 11200 7050 9250 11450 13700
HIGH CFM 750 860 890 1000 1140
FAN INPUT POWER W 7 12 19 37 17 26 50 90 23 39 83 120
MEDIUM CFM 620 700 720 840 1000
AIR FLOW NOMINAL RUNNING CURRENT A 0.11 0.13 0.19 0.26 0.19 0.28 0.43 0.74 0.21 0.35 0.55 0.95
LOW CFM 480 540 570 680 840
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
QUIET CFM 320 380 420 540 700
REFRIGERANT TYPE N/A
USGPM 4.71 5.59 6.69 8.45 9.60
NOMINAL WATER FLOW RATE
litres/min 17.83 21.17 25.29 31.94 36.29 AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
CONTROL
HEAD LOSS (COOLING) kPa 20 37 22 44 53 OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
INDOOR UNIT
HEAD LOSS (HEATING) : 50°C kPa 19 33 19 38 47 AIR FLOW CFM 220 350 470 620 420 560 720 890 510 680 870 1060
MAX. WORKING PRESSURE kPa 1600 EXTERNAL STATIC PRESSURE (H/M/L) Pa N/A
SURFACE AIR VELOCITY m/s 0.91 1.04 1.14 1.03 1.17 USGPM 1.84 2.68 3.56 4.52 3.41 4.44 5.55 6.74 4.71 6.01 7.43 9.00
NOMINAL WATER FLOW RATE
SOUND PRESSURE LEVEL (H/M/L/Q) dBA 42/38/32/23 46/42/35/27 48/43/38/30 50/47/43/33 52/49/45/39 Litres/min 6.96 10.15 13.48 17.10 12.90 16.81 21.02 25.51 17.83 22.76 28.12 34.06
UNIT DIMENSION - ( ) WITH PANEL HXWXD mm 265 X 820 X 820 (340 X 990 X 990) 300 X 820 X 820 (375 X 990 X 990)
HEAD LOSS (COOLING) kPa 5 10 15 24 7 9 14 20 15 22 30 41
PACKING DIMENSION - ( ) PANEL HXWXD mm 341 X 916 X 916 (125 X 1020 X 1020) 376 X 916 X 916 (125 X 1020 X 1020)
INDOOR UNIT
21 22
TEMPRATURE 60°c (4 PIPES SYSTEM)
Ceiling Convertible Type
*
AL
Litres/min 5.44 9.20 9.20 11.09 9.28 13.91 13.91 16.23 13.55 16.60 19.64 22.68
HEAD LOSS (COOLING) kPa 5 9 13 18 6 10 15 19 12 19 24 32 MODEL FWE05E FWE06E FWE07E FWE08E FWE10E FWE12E
HEAD LOSS (HEATING) : 70˚C kPa 7 10 17 22 13 18 25 32 21 30 39 52 Btu/h 15500 20300 21000 24800 33700 40000
NOMINAL COOLING CAPACITY
W 4540 5950 6150 7270 9880 11720
MAX. WORKING PRESSURE kPa 1608
Btu/h 12700 15400 16150
SURFACE AIR VELOCITY m/s 0.27 0.42 0.60 0.64 0.43 0.55 0.68 0.81 0.45 0.57 0.71 0.83 NOMINAL SENSIBLE COOLING CAPACITY COMING SOON
W 3720 4510 4730
SOUND PRESSURE LEVEL dBA 16 23 31 37 31 37 42 47 34 41 46 51
NOMINAL HEATING CAPACITY Btu/h 19500 25000 28000 34500 46300 51600
UNIT DIMENSION - ( ) WITH PANEL HXWXD mm 265 X 820 X 820 (340 X 990 X 990) 300 X 820 X 820 (375 X 990 X 990)
(ENTERING WATER TEMP. = 50 ⁰C) W 5720 7330 8210 10110 13570 15120
PACKING DIMENSION - ( ) PANEL HXWXD mm 341 X 916 X 916 (125 X 1020 X 1020) 376 X 916 X 916 (125 X 1020 X 1020)
NOMINAL TOTAL INPUT POWER W 86 135 160
UNIT WEIGHT kg 26 + 4 28 + 4 32 + 4
NOMINAL RUNNING CURRENT A 0.38 0.67 0.79
CONDENSATE DRAIN SIZE mm 19.05
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
PIPE CONNECTION mm 19.05 REFRIGERANT TYPE N/A
NOTE :
AIR DISCHARGE AUTOMATIC LOUVER (UP & DOWN)
CONTROL
A) BASED ON EUROVENT CONDITIONS LCD WIRELESS MICRO-COMPUTER
B) ADDITIONAL 10W IS REQUIRED FOR CONDENSATE DRAIN PUMP OPERATION
REMOTE CONTROL
C) SOUND PRESSURE LEVEL IS TESTED AS PER JIS STANDARD AS BELOW :
ON
FWKE05EH MODEL - 1.4M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT HIGH CFM 520 580 640
FWKE08/11EH MODEH - 1.5M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT AIR FLOW MEDIUM CFM 460 530 560
SO
MODE COOLING HEATING
LOW CFM 406 490 460
ENTERING AIR TEMPRATURE 27°c DB / 19°c WB 20°c DB
G
USGPM 3.43 4.49 4.67
50°c (2 PIPES SYSTEM) NOMINAL WATER FLOW RATE
IN
ENTERING WATER
7°c Litres/min 13 17 17.68
TEMPRATURE 70°c (4 PIPES SYSTEM)
M
INDOOR UNIT
LEAVING WATER HEAD LOSS (COOLING) kPa 27 48 57
CO
12°c
TEMPRATURE 60°c (4 PIPES SYSTEM) HEAD LOSS (HEATING) : 50⁰C kPa 24 42 50
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 0.87 1.01 1.08
SOUND PRESSURE LEVEL (H/M/L) dBA 45 / 38 / 36 46 / 43 / 39 49 / 46 / 41
UNIT DIMENSION HXWXD mm 212 X 1090 X 630
PACKING DIMENSION HXWXD mm 297 X 1197 X 740
UNIT WEIGHT kg 27
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 12.7
23 24
Ceiling Concealed Type
*
AL
Specification for Ceiling Concealed Type
MODEL FWC09C FWC11C FWC12C FWC14C FWC16C
Btu/h 24800 38000 37000 44700 51800
NOMINAL COOLING CAPACITY
W 7270 11140 10840 13100 15180
Btu/h 19700 29800 29300 35100 40900
NOMINAL SENSIBLE COOLING CAPACITY
W 5770 8730 8590 10290 11990
INDOOR UNIT
› Valve Or Valveless Control Option
› Left/Right Piping Option › 4 Speed Fan Motor For Application Flexibility HEAD LOSS (COOLING) kPa 14.0 39.0 23.0 38.0 51.0
› Wide Capacity Range HEAD LOSS (HEATING) : 50°C kPa 11.0 37.0 19.0 33.0 48.0
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.40 1.74 1.83 1.54 1.52
Specification for Ceiling Concealed Type
SOUND PRESSURE LEVEL (H/M/L) dBA 46 / 42 / 38 51 / 48 / 45 49 / 45 / 41 52 / 50 / 47 53 / 50 / 47
UNIT DIMENSION HXWXD mm 384 x 917 x 462 316 x 1225 x 559 384 x 1003 x 462 384 x 1287 x 462 384 x 1487 x 462
MODEL FWC03C FWC04C FWC06C FWC07C
PACKING DIMENSION HXWXD mm 415 x 1126 x 631 355 x 1461 x 727 415 x 1245 x 631 415 x 1497 x 631 415 x 1701 x 631
Btu/h 9900 11600 18000 22500
NOMINAL COOLING CAPACITY UNIT WEIGHT kg 42 47 44 50 56
W 2900 3400 5280 6590
CONDENSATE DRAIN SIZE mm 19.05
Btu/h 7000 8120 12600 15750
NOMINAL SENSIBLE COOLING CAPACITY PIPE CONNECTION mm 19.05
W 2050 2380 3690 4620
NOMINAL HEATING CAPACITY Btu/h 11500 15000 23000 29000 MODE COOLING HEATING
(ENTERING WATER TEMP. = 50°C) W 3370 4400 6740 8500 ENTERING AIR TEMPRATURE 27°c DB / 19°c WB 20°c DB
50°c (2 PIPES SYSTEM)
NOMINAL TOTAL INPUT POWER W 89 140 168 182 ENTERING WATER
7°c
TEMPRATURE 70°c (4 PIPES SYSTEM)
NOMINAL RUNNING CURRENT A 0.40 0.65 0.77 0.86
LEAVING WATER
220-240 / 1 / 50 12°c
POWER SOURCE V/Ph/Hz TEMPRATURE 60°c (4 PIPES SYSTEM)
REFRIGERANT TYPE N/A ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED MICRO-COMPUTER REMOTE CONTROL
HIGH CFM 300 510 700 730
AIR FLOW MEDIUM CFM 285 490 675 660
LOW CFM 260 400 640 580
EXTERNAL STATIC PRESSURE Pa 49 / 44 / 36 49 / 42 / 28 49 / 45 / 41 49 / 43 / 30
USGPM 2.20 2.60 4.05 5.06
NOMINAL WATER FLOW RATE
litres/min 8.33 9.84 15.33 19.15
INDOOR UNIT
25 26
Ducted Blower Type
* *
AL
FUD20/25B FUD40/50B
27
Controller
BRC52A
BRC52A61 – Heatpump with auto mode
BRC52A62 – Cooling only
BRC52A63 - Heatpump
7 1. Vertical Automatic Air Swing
2. Selectable Mode:
Auto Mode, Cooling , Heating, Dry, Fan
3. Turbo Function
4. Quiet Function
8
5. ON Timer Setting
1 9
2 6. Real Time Clock
3 7. Transmission Source
10
4 8. “Glow in the dark” ON/OFF Button
11
9. Fan Speed Selection: Low, Med, High, Auto
5 12
10. Temperature Setting: Up & Down
6 11. Sleep Mode Function
12. OFF Timer Setting
BRC51A
BRC51A61 – Heatpump with auto mode
BRC51A62 – Cooling only
Features:
• Cool/Heat/Fan/Dry/Auto mode
• Auto/High/Med/Low fan speed
• Temperature operate in ºC and ºF
• Turbo and Quiet Function
• Sleep function
• Swing function
• Real time clock and day display
• 7-days programmable timer
• Error indicator
• Key lock and fan lock features
• Batteries backup and retain setting during power failure
• Last state memory (Memory backup setting from main board)
• Delay Timer (1 or 2 hours)
• Interaction with Wireless Handset (BRC52A61/BRC52A62)
28
Standard Features
COMFORT FIN TYPE
Turbo Mode - Rapid cooling/heating with
highest fan speed for immediate comfort AL Bare Aluminium Fin
Sleep Mode
Ionizer
29
Intelligent Control Series
Supported Configuration
Master Slave
BRC51A
BRC52A
Network Interface Module (NIM) is a networking system which enables communication among Daikin air conditioners.
With the Network Interface Module (NIM), all your air conditioning systems can be controlled with just a single controller giving
you benefits: Communication Bus Connection Recommended Maximum Cable Length (m)
Network Control NIM A 2-way twisted pair cable is used as the First NIM to the furthest
1000
communication bus. Recommended cable for connected NIM
communication bus is a pair of screened &
Benefits shielded, twisted single core wire with core
NIM to Main Board 10
• More convenience. No more individually controlling air conditioning units NIM to Wired Controller
• Quicker and easier zone control from the master control unit
diameter of 0.5mm to 1.0mm. 10
• Better control of air conditioning systems operating conditions
Connection
NIM utilizes master-slave type system whereby the master node will issue commands
to each of the slave nodes.
The communication bus must be connected serially to the adjacent NIM. (Daisy chain connection). The same
polarity has to be connected between the NIMs (A to A, B to B).
Every master unit will have a group address so that every slave can only response to
their respective master. Each slave unit must have a unique address so that it can be
addressed independently of other nodes.
G-Way
The master unit will be operating in conjunction with a control panel. Any settings
done via the control panel connected to the master will overwrite the settings of its
slave units. Function
Slave unit can be operated with or without control panel. If a slave unit is operating • Gateway between DX fan coil unit and basic Building
with a control panel, its settings can be changed without following its master. NIM Management System (BMS).
S-NIM
Features
• Auto restart feature with last state settings.
• 2 air conditioning units in a master & slave system, operating at alternate sequence of preset time (3/4/5/7/9/11/12 hours).
• System controlled by a single BRC51A controller.
• When the operating unit is at fault, the standby unit automatically takes over.
• Error indication via error code displayed on LCD panel. (only is using Netware 3 control panel)
• During system OFF mode, running timer will stop. It resumes when changing to ON mode.
• Preset operation hours can be set via DIP Switch.
* The air conditioning unit connected to the wired controller is always the master unit.
Communication Bus
A 2-way twisted pair cable is used as the communication bus.
Recommended cable for communication bus is a pair of screened & shielded, twisted single core wire with core diameter
of 0.5mm to 1.0mm.
S-NIM S-NIM
Slave Unit
Control Panel
Master Unit
Typical connection structure for S-NIM
32