Abstract
Maintaining optimal energy efficiency in air conditioning systems is a constant challenge
– one that all heating, ventilation and air conditioning (HVAC) engineers work tirelessly to
overcome. However, for many years, the air conditioning industry has struggled to identify
and resolve common problems that affect chiller operations and lead to poor performance,
high energy consumption and greater operating cost. This paper explores the most common
operational challenges in chillers identified by Infosys upon analyzing historical data from
chiller plants on its own campuses. It also explains the solutions Infosys used to address these
issues in a systematic manner.
1.0 Introduction the temperature of chilled water entering range
and leaving the chiller system, is not
Infosys has made significant investments
achieved. Here, even though the building
• Improper selection of coils and control
in green initiatives across its campuses valves
has a maximum heat load, the chiller
in India. For instance, all the campus
operates at sub-par capacity in a partial • Choked cooling coils
buildings and chiller plants have been
outfitted with the latest Internet-of-Things
load condition. Low ΔT syndrome arises
• Improper water balancing
due to the following reasons:
(IoT) technology. These sensors capture Thus, to meet the maximum building load,
real-time operational data that can be • Air handling units (AHUs) temperature the control valve responds by opening
monitored through a centralized command set-points are below the designed value the valve to 100%, thereby allowing more
centre. Infosys also uses advanced
• The variable frequency drives (VFDs) of chilled water to circulate. This reduces
technologies such as the Industrial IoT AHUs operate in a fixed mode the chilled water flow rate in secondary
to continuously improve efficiency and water pumps. Further, it causes a ‘negative’
manage energy, water, waste, security, • Peripheral system components not
flow of return chilled water though the
designed for the same temperature
and transportation within its campuses. de-coupler line in order to meet the flow
As a direct result of these initiatives, we requirement, as shown in Figure 1.
have reduced nearly 50% of our per capita Primary chiller water pump
energy consumption over a period of 9 540F
years [1].
540F
Air conditioning systems, particularly 1440 GPM
chillers, consume a large share of the
total energy used in buildings. Over Building load
De-coupler line
the past several years, Infosys has been at 600 TR
Chiller # 2
Chiller # 1
De-coupler line
Number of chillers 4 4 - at 600 TR
Chiller # 2
Chiller # 1
Number of pumps 14 8 43%
350 TR of
OFF
Number of valves 74 25 600 TR66%
Negative flow
Load of chilled water pumps 223 kW 44 kW 80% 960 GPM
@ 540F
Load of condenser water pumps 75 kW 44 kW 41%
440F
480F
Chiller plant space 3,200 sq.ft. 2,450 sq.ft. 23%
Annual energy consumption 2.13 million kWh 1.49 million kWh 30% Secondary chiller water pump
Table 1: Effect of variable primary chiller water flow system
2.2 Higher small temperature refrigerant pressure and leaving chilled approach is due to fouling of condenser
water temperature for regular monitoring. tubes as these are open loops and they
difference of chiller heat
Usually, the main reason for a high depend on the quality of the condenser
exchangers water.
The performance of chiller heat exchangers
(including evaporators and condensers) Saturation condenser temperature (Ts) = 97oF @ 187 psig for R-22
depends on the small temperature Condenser
difference, also known as the ‘approach’ [3]. Approach
The value of the approach is determined Heat of condensation
T2 ‐ 950F
by the difference between the refrigerant
saturation temperature and leaving water
temperature, as illustrated in Figure 2.
Typically, chiller heat exchangers are
designed for an approach of 2.2°C. A higher
approach value increases the load of the T1 - 850F
chiller and is caused by the following
problems: T1 - 540F
Table 2: Performance of chiller heat exchangers (evaporator and condenser)
To minimize the high approach of condenser tubes, Infosys installed an automatic tube cleaning system for all the chillers. This system
Pump Curve
helped us get close to the desired chiller operating efficiency (ikW/TR). We also tested next-generation water treatment systems such as non-
chemical, ozone and magnetic water treatment systems.
2.3 High temperature of • Improper sizing of cooling towers condenser water and ambient wet bulb.
condenser water entering Best Efficiency Point After identifying the importance of entry
Total Head (ft)
0.8 Legend:
Chiller Efficiency (ikW/TR)
ECWT (oF)
86 F
0.6 82 F
78 F
74 F
0.4
70 F
66 F
0.2
0
100% 90% 80% 70% 60% 50% 40% 30% 23%
% of Load (TR)
Pump Curve
Best Efficiency Point
Total Head (ft)
System Curve
2.5 Low quality of condenser heat exchangers, thereby reducing the results in microbiologically-induced
performance of the cooling system corrosion, which can affect human health.
water 1
• Metal corrosion – Corroding metal Infosys monitors and controls water quality
While condenser water is not typically reduces the integrity, strength and using various control parameters such as
considered a parameter for operational thickness of the metal structure by creating conductivity, oxygen reduction potential,
0.8
efficiency, low-quality condenser water can
Chiller Efficiency (ikW/TR)
4.0 Acknowledgements
I would like to acknowledge the technical
support provided by the Green Initiatives
team and Advanced Engineering Group.
Special thanks to subject matter experts
Dr. Ravi Kumar G.V.V., Dr. Ravi Prakash and
Guruprakash Sastry for their useful inputs
and valuable time spent in reviewing this
paper.
5.0 References
1. Sustainability Report 2016-17,
Infosys Limited https://www.infosys.
com/sustainability/Documents/infosys-
sustainability-report-2016-17.pdf
© 2017 Infosys Limited, Bengaluru, India. All Rights Reserved. Infosys believes the information in this document is accurate as of its publication date; such information is subject to change without notice. Infosys