Sei sulla pagina 1di 5

SETTINGS SHEET Page 1 of

5
FOR THE SEL-501 RELAY Date
RELAY SETTINGS FOR FEEDER-OVERCURRENT PROTECTION APPLICATION: “FDR”
(SERIAL PORT COMMAND SET AND FRONT PANEL)

CHECKMARK TO INDICATE X SIDE RELAY ______ OR Y SIDE RELAY ______

General Data
Relay Identifier (13 characters) ID =                                                                             
Relay Application (OFF, MOT, BFR, FDR, OC1, TMR) APP =        
   FDR             
Current Transformer Ratio (CTR:1); (1–6000) CTR =                         
Demand Ammeter Time Constant (Off, 5–60 minutes) DATC =                      

Phase Definite-Time/Instantaneous Overcurrent Elements


Phase Definite­Time Overcurrent Pickup—step size 0.1 A
(Off, 0.5–80 A sec {5 A Model}, 0.1–16 A sec {1 A Model}) 50PP =                        
Phase Definite­Time Overcurrent Delay
(0–16,000 cycles in 0.25­cycle steps) 50PD =                       
Phase Instantaneous Overcurrent Pickup—step size 0.1 A
(Off, 0.5–80 A sec {5 A Model}, 0.1–16 A sec {1 A Model}) 50H =                          

Negative-Sequence Definite-Time Overcurrent Element


Negative­Sequence Definite­Time Overcurrent Pickup—step size 0.1 A
(Off, 0.5–80 A sec {5 A Model}, 0.1–16 A sec {1 A Model}) 50QP =                       
Negative­Sequence Definite­Time Overcurrent Delay
(1.5–16,000 cycles in 0.25­cycle steps) 50QD =                       

Ground Definite-Time/Instantaneous Overcurrent Elements


Ground Definite­Time Overcurrent Pickup—step size 0.1 A
(Off, 0.5–80 A sec {5 A Model}, 0.1–16 A sec {1 A Model}) 50NP =                       
Ground Definite­Time Overcurrent Delay
(0–16,000 cycles in 0.25­cycle steps) 50ND =                       
Ground Instantaneous Overcurrent Pickup—step size 0.1 A
(Off, 0.5–80 A sec {5 A Model}, 0.1–16 A sec {1 A Model}) 50NH =                       

Phase Time-Overcurrent Element


Phase Time­Overcurrent Pickup—step size 0.1 A
(Off, 0.5–16 A sec {5 A Model}, 0.1–3.2 A sec {1 A Model}) 51PP =                        
Phase Time­Overcurrent Operating Curve
(U1–U4 {US Curves}, C1–C4 {IEC Curves}) 51PC =                        
Phase Time­Overcurrent Time­Dial—step size 0.01
(0.5–15 {US Curves}, 0.05–1.0 {IEC Curves}) 51PTD =                     
Phase Time­Overcurrent EM Reset (Y, N) 51PRS =                     

Date Code 20111101


SETTINGS SHEET Page 2 of
5
FOR THE SEL-501 RELAY Date
RELAY SETTINGS FOR FEEDER-OVERCURRENT PROTECTION APPLICATION: “FDR”
(SERIAL PORT COMMAND SET AND FRONT PANEL)

Negative-Sequence Time-Overcurrent Element


Negative­Sequence Time­Overcurrent Pickup—step size 0.1 A
(Off, 0.5–16 A sec {5 A Model}, 0.1–3.2 A sec {1 A Model}) 51QP =                       
Negative­Sequence Time­Overcurrent Operating Curve
(U1–U4 {US Curves}, C1–C4 {IEC Curves}) 51QC =                       
Negative­Sequence Time­Overcurrent Time­Dial—step size 0.01
(0.50–15 {US Curves}, 0.05–1.0 {IEC Curves}) 51QTD =                    
Negative­Sequence Time­Overcurrent Electromechanical Reset (Y, N) 51QRS =                     

Ground Time-Overcurrent Element


Ground Time­Overcurrent Pickup—step size 0.1 A
(Off, 0.5–16 A sec {5 A Model}, 0.1–3.2 A sec {1 A Model}) 51NP =                       
Ground Time­Overcurrent Operating Curve
(U1–U4 {US Curves}, C1–C4 {IEC Curves}) 51NC =                       
Ground Time­Overcurrent Time­Dial—step size 0.01
(0.50–15 {US Curves}, 0.05–1.0 {IEC Curves}) 51NTD =                    
Ground Time­Overcurrent Electromechanical Reset (Y, N)  51NRS =                     

Date Code 20111101


SETTINGS SHEET Page 3 of
5
FOR THE SEL-501 RELAY Date
RELAY SETTINGS FOR FEEDER-OVERCURRENT PROTECTION APPLICATION: “FDR”
(SERIAL PORT COMMAND SET P AND FRONT PANEL)

Protocol Setting (see below)


Protocol (SEL, LMD, SYMAX, MOD) PROTOCOL =                                      

Protocol Settings.
Set PROTOCOL = SEL for standard SEL ASCII protocol.
Set PROTOCOL = LMD for SEL Distributed Port Switch Protocol (LMD).
Set PROTOCOL = SYMAX for the Square D PowerLogic SY/MAX protocol (SEL­501­1 only). 
Set PROTOCOL = MOD for Modbus® RTU protocol (not available with SEL­501­1). 
Refer to Appendix D:  Distributed Port Switch Protocol for details on the LMD protocol.
Refer to Appendix F:  SY/MAX Protocol for details on the SY/MAX protocol.
Refer to Appendix G:  Modbus RTU Communications Protocol.

Protocol = SEL
If PROTOCOL is set to SEL, the following are the applicable fields that need to be entered by 
the user.

Communications Settings
Baud Rate (300, 1200, 2400, 4800, 9600, 19200, 38400) SPEED =                                              
Data Bits (7, 8) DATA_BITS =                                     
Parity (None [N], Even [E], Odd [O]) PARITY =                                            
Stop Bits (1, 2) STOP =                                                 

Other Port Settings (see below)


Time­Out (0–30 minutes) TIMEOUT =                                         
Automatic Message Output (Y, N) AUTO =                                               
Enable RTS/CTS Hardware Handshaking (Y, N) RTS_CTS =                                          
Fast Operate Enable (Y, N) FAST_OP =                                          

Other Port Settings.  Set TIMEOUT to the number of minutes of serial port inactivity for an 
automatic log out.  Set TIMEOUT = 0 for no port time­out.

Set AUTO = Y to allow automatic messages at the serial port.

Set RTS_CTS = Y to enable hardware handshaking.  With RTS_CTS = Y, the relay will not send 
characters until the CTS input is asserted.  Also, if the relay is unable to receive characters, it 
deasserts the RTS line.  Setting RTS_CTS is not applicable for EIA­485 serial port option or 
when PROTOCOL = LMD.

Date Code 20111101


SETTINGS SHEET Page 4 of
5
FOR THE SEL-501 RELAY Date
RELAY SETTINGS FOR FEEDER-OVERCURRENT PROTECTION APPLICATION: “FDR”
(SERIAL PORT COMMAND SET P AND FRONT PANEL)
Set FAST_OP = Y to enable binary Fast Operate messages at the serial port.  Set FAST_OP = N 
to block binary Fast Operate messages.

Protocol = LMD
If PROTOCOL is set to LMD, the following are the applicable fields that need to be entered by
the user.

Communications Settings
LMD Prefix (@, #, $, %, &) PREFIX =                                             
LMD Address (1–99) ADDRESS =                                        
LMD Settling Time (0–30 seconds) SETTLE_TIME =                                 
Baud Rate (300, 1200, 2400, 4800, 9600, 19200, 38400) SPEED =                                              
Data Bits (7, 8) DATA_BITS =                                     
Parity (None[N], Even [E], Odd [O]) PARITY =                                            
Stop Bits (1, 2) STOP =                                                 

Other Port Settings (see below)


Time­Out (0–30 minutes) TIMEOUT =                                         
Automatic Message Output (Y, N) AUTO =                                               
Fast Operate Enable (Y, N) FAST_OP =                                          

Other Port Settings.  Set TIMEOUT to the number of minutes of serial port inactivity for an 
automatic log out.  Set TIMEOUT = 0 for no port time­out.

Set AUTO = Y to allow automatic messages at the serial port.

Set FAST_OP = Y to enable binary Fast Operate messages at the serial port.  Set FAST_OP = N 
to block binary Fast Operate messages.

Date Code 20111101


SETTINGS SHEET Page 5 of
5
FOR THE SEL-501 RELAY Date
RELAY SETTINGS FOR FEEDER-OVERCURRENT PROTECTION APPLICATION: “FDR”
(SERIAL PORT COMMAND SET P AND FRONT PANEL)

Protocol = SYMAX
If PROTOCOL is set to SYMAX, the following are the applicable fields that need to be 
entered by the user.

Communications Settings
Baud Rate (300, 1200, 2400, 4800, 9600, 19200, 38400) SPEED =                                              
AddressX (1–99) ADDRESSX =                                      
AddressY (1–99) ADDRESSY =                                      
Data Bits (7, 8) DATA_BITS =                                     
Parity (None[N], Even [E], Odd [O]) PARITY =                                            
Stop Bits (1, 2) STOP =                                                 

Protocol = MOD
If PROTOCOL is set to MOD, the following are the applicable fields that need to be entered by
the user.

Communications Settings
Baud Rate (300, 1200, 2400, 4800, 9600, 19200) SPEED =                                              
Parity (None [N], Even [E], Odd [O]) PARITY =                                            
Stop Bits (1, 2) STOP =                                                 
Modbus Slave ID (1–247) SLAVEID =                                          

Date Code 20111101

Potrebbero piacerti anche