Sei sulla pagina 1di 7

A Dynamic Voltage Restorer (DVR) based Interface

Scheme for Microgrids


Imran Syed and Vinod Khadkikar, Member, IEEE

Electrical Engineering and Computer Science Department,


Masdar Institute of Science and Technology,
Abudhabi, UAE

Abstract—This paper deals with the issues related to the make it essential to have an interconnection with the main grid
interconnection between the microgrid and main network. The at times of low generation. One of the research challenges in
Dynamic Voltage Restorer (DVR) is proposed as an interface recent times has been to determine the type of interconnection
between the main network and microgrid in order to improve that should be used between the main grid and the microgrid. A
reliability and limit fault currents. The performance of DVR is
key objective of such an interface is to maintain a connection
demonstrated during fault conditions in two different locations,
firstly in the main grid and then within the microgrid. The DVR is between the systems at times of temporary faults. However
used to inject a voltage during a fault in the main grid isolating the maintaining such a connection during faults leads to further
microgrid from the fault and ensuring normal operation. challenges. This work addresses two specific challenges.
Secondly, a novel technique is proposed employing the The first problem that is solved is the increase in short circuit
magnetizing inductance of the DVR series transformer in order to currents in the grid on adding more generation units. The short
minimize the contribution of the grid currents during a fault circuit current levels in the main grid are increased
within the microgrid. The proposed technique is evaluated using considerably. One small generation unit may not impact much
MATLAB/SIMULINK and shown to possess additional but when multiple generation units are connected, the impact
advantages when compared to traditional fault current limiters.
maybe high.
Keywords—fault current limiters; DVR; mocrogrid; The power grid protection system is designed at its inception
synchronous d-q theory for a particular short circuit current level. Introducing further
sources of generation into the grid via connecting large
I. INTRODUCTION microgrids will lead to an increase in these short circuit current
Recent advances in electric power generation from levels. In [4], a detailed study on the increase in short circuit
renewable sources, such as, photovoltaic power plants and wind levels of such a system has been conducted.
parks, has led to a shift in the way the power grid has been The second challenge is the short circuit current level at times
imagined traditionally. Instead of viewing the power grid as a of a fault within the microgrid. In [5], it is clearly shown that
unidirectional system consisting of large power generation at the contribution of the main grid in this case will lead to higher
one end and loads at the other, researchers have started looking fault currents within the microgrid. Reducing this current level
into distributed generation units supplying power at various will help in reducing the short circuit current rating of
points in the grid. In a quest to make the power grid more equipment in the microgrid hence reducing costs.
reliable, the concept of microgrids operating within a larger A number of papers have been published proposing different
system has drawn a lot of attention in the recently [1][2][3]. kinds of bi directional fault current limiters (FCL) which will
Microgrids generally consist of a mix of renewable sources bring down the short circuit current level in the microgrid as
of power like PV, wind and traditional sources like diesel well as in the main grid during faults in either location [6][7].
generators. These systems are designed with the capability to Use of superconducting materials that have current dependent
operate independently from the main grid if required. This characteristics as fault current limiters is a growing research
increases the reliability of the power system in general by area. Others have proposed hybrid solutions employing solid
making sure that power is available to consumers at times of a state devices and semiconductor switches to achieve the same.
failure of the main grid. Such a system is also highly beneficial One of the disadvantages of such solutions is that the amount of
in remote regions that are difficult to connect to the main grid. control over the system is limited. Any expansion of the
However, in spite of the microgrid being designed to meet all microgrid system itself leads to changes in fault current
the demand that arises locally, the variable nature of some of characteristics based on which the fault current limiter is
the sources that maybe used within the system like PV and wind designed. Solutions different from bidirectional fault current

k,((( 
limiters have been proposed in [8] where a unidirectional FCL
is used to prevent the increased short circuit levels when a fault 1 2 F1 3 4
occurs in the main grid whereas the microgrid is left connected
to the main grid in order to use it for voltage support ignoring
Z12 Z2 3 Z34
the current contributions at the time of a fault in the microgrid.
33KV
In [9], a back to back converter is proposed as an Substation
interconnection between the microgrid and the main grid which L1 L2
ZMG L3 L4
provides frequency isolation between the grids and a control of Main grid
DVR Dynamic Voltage
the amount of reactive and active power flow in either direction. Vgr id 5
Restorer
The use of FACTS devices such as STATCOMs, SVCs and L1-L7:Non-rotating

DVR
loads Microgrid
TCR have revolutionized the power industry. The use of the
Dynamic Voltage restorer (DVR) has been studied extensively VMG 6
in mitigating disturbances in voltages on the power system such
ZD 7
as voltage sags, swells, unbalance and harmonics in the supply G F2
voltage [10][11][12]. Its use has also been investigated in the

0.69/33KV

0.4/33KV
fault ride through of specific sources of power like wind TR1 TR2
turbines that are required by grid codes to remain connected to
the system on the occurrence of a fault in the grid [13][14].
L5 L6
Fault current limiting function of the DVR has also been D
investigated in [15][16]. In [17], a series compensator is shown G
that is connected to each source within a microgrid separately
in order to provide control over power and fault protection.
This paper proposes the use of DVR as the interface between Fig1. System under study
the microgrid and the main grid. The DVR is shown to
successfully address all the challenges listed above while TABLE I
NETWORK DATA
providing more control over the system when compared to
traditional FCL. A novel technique using the magnetizing
Network DATA
impedance of the series transformer in a DVR to limit fault components
currents has also been proposed. The DVR also provides the Feeder 33KV voltage source
added advantage of maintaining microgrid voltage levels in the Z12 0.002+j0.6283 ohms
absence of DG and a voltage sag on the main grid due to faults, Z23 and Z34 2+j4.14 ohms
ZMG 0.5+j0.3142 ohms
hence improving the reliability of the microgrid. This paper is ZDG 0.5+j0.0565 ohms
organized as follows. Section II provides a description of the L1 to L4 6MVA non rotating load
system used for the study and its parameters. Section III L5 8 MVA non rotating load
provides the control strategy of the DVR under different cases L6 2 MVA non rotating load
showcasing also the flexibility of choosing the rating of the
DVR with respect to the amount of control that is needed. taken into consideration. The scenarios are explained here while
Section IV provides the simulation results using the control of the DVR is explained in section III. The first
MATLAB/SIMULINK for different cases and proves the scenario is a fault occurring at BUS 2 (F1) reducing the grid
effectiveness of the system. voltage at the point of microgrid connection to zero. The fault
location is shown in Fig.1 as F1. In this scenario the microgrid
has to be isolated from the fault and continue operating without
II. SYSTEM STRUCTURE any disturbance. The second scenario is a fault in the microgrid
A system with a microgrid containing a DG source connected at bus 7 denoted by F2 in Fig.1.Here the fault currents within
to a main grid is shown in Fig.1. The main grid consists of a the microgrid must be limited by minimizing the contribution
power source connected to four different buses each consisting of the main grid to the fault. Thirdly, the fault at bus 2 is applied
of 5 MVA loads. At bus 2, a connection is made to a microgrid again in the absence of DG. Here, the DVR must compensate
containing a single DG and two separate loads at lower voltage for the voltage sag at bus 2, thus maintaining the microgrid
levels. The main grid is considered here to be at 33kV whereas voltage levels Vmg to pre fault levels, hence maintaining normal
the loads at the microgrid level are stepped down to 0.4 and 0.69 operation of microgrid in the absence of DG and presence of a
kV. The line impedance parameters and load details are given fault in the main grid. This increases the reliability of the
in Table I. The microgrid shown in the system is connected to microgrid. The voltage injection of the DVR is always in phase
the main grid through a DVR. The voltages at bus 5 and bus 6 with the grid voltage since energy conservation is not an issue.
are referred to as Vgrid and Vmg respectively throughout this The control of DVR and its rating is explained in detail in
paper. There are three different scenarios of operation that are section III.


S1
S1
Rf Cf Rf Cf

Vgrid VMG Vgr id VMG


Igrid Igrid

R1

X1
RC
Lf
ENERGY
STORAGE
Xm
Zm
VSC

Fig. 2. Single line diagram of proposed DVR structure Fig. 3. Equivalent circuit of transformer with secondary winding open

ªV º
2 ª cosθ cos (θ − 2π 3) cos (θ + 2π 3) º « a »
I. CONTROL STRATEGY FOR DVR Vdq = « » «Vb » (1)
3 ¬ − sin θ − sin (θ − 2π 3) − sin (θ + 2π 3) ¼
This section details the control strategy of the DVR for the «¬Vc »¼
different scenarios mentioned above. The control is classified
into two modes of operation based on the location of fault. The Since the voltage is injected in phase, the q-axis values are
not controlled. It is also assumed that the grid and microgrid
voltage at bus 6, VMG is used to distinguish between the faults
voltages are harmonics free and balanced. In case of any
locations. Mode 1 comes into play when fault occurs in the unbalance the positive sequence source voltage can be utilized
main grid covering scenarios 1 and 3 mentioned in section II for obtaining the angle from the PLL. The difference between
whereas mode 2 is chosen for a fault within the microgrid i.e. Vgd and Vmgd provides the d-axis values of the DVR voltage
scenario 2. The DVR structure is shown in Fig. 2. The denoted by Vdvrd. The DVR has to inject a voltage equivalent to
parameters of the DVR are listed in Table II. The control the sag at Vgrid in order isolate the microgrid from the fault. The
schematic for the two modes is shown in Fig. 4. reference V*dvrd for the DVR is generated by the difference
between the pre sag grid voltage and the current grid voltage.
TABLE II
DVR PARAMETERS
The error between Vdvrd and V*dvrd is passed through a PI
controller and converted back to three phase in order to obtain
DVR DATA
the reference voltage signals for the DVR. Under Mode 1, these
components signals are sent to a gate signal generator using PWM technique
DC Link 70kV in order to control the VSC and inject the required voltage. This
Lf 300mH control is valid whether the DG is connected or disconnected
Cf 5uF from the microgrid.
Rf 2 ohms
Transformer 20MVA 1:1 turns ratio B. Fault in the microgrid (Mode 2)
During a fault within the microgrid, the objective of the DVR
A. Fault in the main grid (Mode 1) control is to limit the fault current levels by minimizing the fault
current contribution from the main grid. Achieving this saves
When a fault occurs at BUS 2 in the main grid the voltage at
costs by reducing the short circuit current ratings of all
BUS 5, Vgrid reduces to zero. In order to maintain the functioning
protection devices as well as transformers within the microgrid.
of the microgrid, the DVR is controlled to inject a voltage in
phase with the pre sag grid voltage and equivalent to the voltage Previously, the DVR was used to inject a voltage isolating the
sag. Injecting this voltage essentially isolates the microgrid from main grid from the microgrid. In this section another attribute
the main grid fault, as the DVR now injects power equivalent to of the DVR is used to limit the fault current levels. The DVR is
the power previously drawn from the main grid. This ensures connected to the line making use of a series transformer in order
regular operation of microgrid and prevents any current to reduce the voltage level of the DC link and to provide
contribution to the fault from the microgrid. The control isolation. The technique proposed here makes use of the
structure is shown in Fig.4. The voltages Vgrid and VMG are magnetizing inductance of this transformer in order to reduce
converted into their synchronous dq frame values denoted by Vgd the fault currents flowing into the microgrid. The equivalent
and Vmgd as shown in (1). The angle theta is obtained from a circuit of the transformer is shown in Fig.3 as connected to the
phase locked loop applied to the grid voltage.


Vmga Vmgd Vdvra
Vmgb abc Vdvrd Vdvrd
d-q
+- -
+ PI d-q Vdvrb
Vmgc Vdvrq =0 Switch To
abc Vdvrc
ș between Gate Signal IGBTs
Vgrida 3-phase Open all two Generator
Vgridb
PLL
Vgridc switches modes
V*mgd
ș
Vgrida Vmgd
Vgridb abc Vgd V*dvrd Compare and
-+
Vgridc d-q Vmgdlimit decide mode

Fig. 4. Control structure for DVR

system under study with Vgrid on one side and VMG on the other.
R1 and X1 represent the primary winding impedance of the the first mode of operation since no power is injected during the
transformer. The control of the DVR during a fault in the second mode. For full benefit of DVR, the power rating has to
microgrid is shown as a part of the control structure in Fig.2. be equal to the load capacity of the microgrid since the DVR
When a fault occurs within the microgrid at bus 7 as denoted by has to inject power equivalent to its requirement in the absence
F2 in Fig.1, VMG drops to zero. The d-axis value of VMG denoted of DG and presence of a fault in the main grid. This is ideal in
by Vmgd is made use of in order to sense the fault in the cases where the DG is a renewable source and may not be
microgrid. Vmgd is compared with a reference value Vmgdlimit. available at all times. However, the DVR rating can be reduced
The idea is to make sure that the magnetizing inductance of the if the availability of DG is permanent. The rating is based on
transformer comes between the microgrid and the main grid in two factors. Firstly, the current flowing from the main grid to
order to reduce the fault current levels. Fig. 3 shows the the microgrid which is denoted by Igrid. Secondly, the voltage
equivalent circuit of the transformer when connected between injected by the DVR Vdvr.
Vgrid and VMG.On opening the secondary terminal of the series
transformer, the entire grid current Igrid is forced to flow through Pdvr=Igrid*Vdvr (3)
the magnetizing impedance Zm which consists of the
magnetizing inductance Xm and negligible copper loss The DVR rating can be designed based on the level of
component RC. The DVR circuit consists of filter resistance Rf compensation required. For example, it can be decided that the
and capacitance Cf. In order to avoid the currents flowing DVR will only compensate for 0.5 p.u voltage sag at bus 2,
through them during a fault, a semiconductor switch S1 is used which may occur during a less severe fault. Similarly, the DVR
which is controlled by the same signal that opens the inverter can be rated for a maximum of a particular value of Igrid which
switches. The currents flowing through the magnetizing is based on the contribution of the main grid to the load
impedance is governed by the equation requirement in the microgrid. The option of operating the DVR
in mode 2 allows for the flexibility of rating. The rating can be
Vgrid − VMG decided for a particular level of voltage sag. Any fault that is
I grid = (2) more severe than the designed rating can trigger Mode 2 of
ZM
operation wherein no voltage is injected but the magnetizing
inductance of the transformer is used to minimize fault currents.
Hence the amount of fault current can be limited based on the This scheme provides flexibility and cost effectiveness in DVR
magnetizing inductance of the transformer which is generally design since the rating maybe varied based on the reliability of
very high. In this study, the magnetizing impedance has been microgrid sources and the severity of fault that is common to a
rated as 0.2 percent of the active and reactive core losses based particular system.
on transformer rated power and voltage. Using the magnetizing
inductance of the transformer alone is seen as a cost effective
way to minimize the fault currents at times of severe faults. II. SIMULATION RESULTS

The performance of the DVR for various scenarios


C. DVR Rating mentioned earlier is evaluated by simulation study using
The DVR rating has to be decided based on a number of MATLAB/SIMULINK. The study was conducted for severe
factors and operating conditions. The rating is based solely on fault at two different locations shown in Fig.1. and the control
strategy explained earlier is employed.


A. Fault in the main grid 1.5

A severe three phase fault is applied at bus 2 for a duration 1

of 200ms hence creating a voltage sag of 1 p.u. at bus 2(Vgrid). 0.5

The DVR responds by injecting 1 p.u. voltage and protecting 0

-0.5
the microgrid from the fault. The voltage at the microgrid bus
-1
VMG, the DG voltage and the currents drawn by the loads within
-1.5
the microgrid during fault are recorded in order to show the 0.35 0.4 0.45 0.5 (b)0.55 0.6 0.65 0.7

disturbance free operation. The performance of microgrid in the Fig 6. Load 5 current profile (a) without DVR (b) with DVR
absence of DVR is also shown in order to make a comparison.
0.4
Fig 5 shows the grid voltage, the DVR injected voltage and the
microgrid voltage. As can be seen, the DVR injects a voltage 0.2

equal to 1 p.u. for the duration of the fault which is 200ms.


0
Figure 6, 7 and 8 show the currents drawn by the loads L5, L6
and the DG voltage with and without DVR installed. It is clear -0.2

that there is no disturbance in the operation of microgrid during


-0.4
a fault in main grid with DVR installed. 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7
(a)
0.4
1.5

1 0.2

0.5
0
0

-0.5 -0.2

-1
-0.4
0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7
-1.5 (b)
0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7
(a)
1.5 Fig 7.Load 6 current profile (a)without DVR(b)with DVR
1
1.5
0.5
1
0
0.5
-0.5
0
-1
-0.5
-1.5
0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 -1
(b)
1.5 -1.5
0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7
1

0.5 1.5
(a)
0 1

-0.5 0.5

0
-1
-0.5
-1.5
0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7
(c) -1

-1.5
0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7

Fig 5. (a) Voltage sag at the grid (Vgrid) (b) DVR injected voltage (Vdvr) (b)
(c)Microgrid voltage(VMG) Fig 8. DG voltage profile (a)without DVR(b)with DVR

1.5

1 B. Fault in the microgrid


0.5 200

0
100
-0.5

-1 0

-1.5
0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7
-100

(a) -200
0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7
(a)


employedeffectively to minimize fault currents, thus lowering
150
the short circuit rating of breakers and other equipment within
100

50
the microgrid. Flexibility in rating the DVR based on the system
0
requirements has been shown. The proposed control has been
-50
evaluated using MATLAB/SIMULINK and shown to be
-100 effective.
-150

0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 IV. REFERENCES
(b) [1] Lasseter, R.H., "MicroGrids," Power Engineering Society Winter
Fig 9.Fault currents (if) (a)without DVR (b) with DVR Meeting, 2002. IEEE , vol.1, no., pp.305,308 vol.1, 2002
[2] Hatziargyriou, N.; Asano, H.; Iravani, R.; Marnay, C.,
For demonstrating the control of DVR wherein the transformer "Microgrids," Power and Energy Magazine, IEEE , vol.5, no.4, pp.78,94,
July-Aug. 2007
impedance is made use of for limiting fault currents within the
[3] Peas Lopes, J.A.; Moreira, C.L.; Madureira, A.G., "Defining control
microgrid, a severe three phase fault is applied at bus 7 within strategies for MicroGrids islanded operation," Power Systems, IEEE
the microgrid for a duration of 200ms. Fig 9 shows the fault Transactions on , vol.21, no.2, pp.916,924, May 2006
currents at the fault location with and without the DVR. It can [4] Gopalan, S. A.; Sreeram, V.; Iu, H. H C; Xu, Z.; Dong, Z. Y.; Wong, K.
be clearly seen that the currents are close to 150 A (p.u) without P., "Fault analysis of an islanded Multi-microgrid," Power and Energy
Society General Meeting, 2012 IEEE , vol., no., pp.1,6, 22-26 July 2012
any DVR while the transformer impedance of the DVR brings
[5] Sortomme, E.; Mapes, G. J.; Foster, B. A.; Venkata, S.S., "Fault analysis
it down to 70 A (p.u). and protection of a microgrid," Power Symposium, 2008. NAPS '08. 40th
Fig. 10 shows the contribution of the main grid to fault current North American , vol., no., pp.1,6, 28-30 Sept. 2008
Igrid within the microgrid. It is seen to be minimal when the [6] Ustun, T.S.; Ozansoy, C.; Zayegh, A., "A central microgrid protection
transformer impedance comes into play. This clearly system for networks with fault current limiters," Environment and
demonstrates the effectiveness of using the transformer Electrical Engineering (EEEIC), 2011 10th International Conference on ,
vol., no., pp.1,4, 8-11 May 2011
impedance to limit fault currents.
[7] Ghanbari, T.; Farjah, E., "Development of an Efficient Solid-State Fault
100 Current Limiter for Microgrid," Power Delivery, IEEE Transactions on ,
vol.27, no.4, pp.1829,1834, Oct. 2012
50
[8] Ghanbari, T.; Farjah, E., "Unidirectional Fault Current Limiter: An
0 Efficient Interface Between the Microgrid and Main Network," Power
Systems, IEEE Transactions on , vol.28, no.2, pp.1591,1598, May 2013
-50
[9] Majumder, R.; Ghosh, A.; Ledwich, G.; Zare, F., "Power Management
-100 and Power Flow Control With Back-to-Back Converters in a Utility
0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 Connected Microgrid," Power Systems, IEEE Transactions on , vol.25,
no.2, pp.821,834, May 2010
(a)
2
[10] Kanjiya, P.; Singh, B.; Chandra, A.; Al-Haddad, K., "“SRF Theory
1.5
Revisited” to Control Self-Supported Dynamic Voltage Restorer (DVR)
1
for Unbalanced and Nonlinear Loads," Industry Applications, IEEE
0.5
Transactions on , vol.49, no.5, pp.2330,2340, Sept.-Oct. 2013
0 [11] Sadigh, A.K.; Smedley, K.M., "Review of voltage compensation methods
-0.5 in dynamic voltage restorer (DVR)," Power and Energy Society General
-1 Meeting, 2012 IEEE , vol., no., pp.1,8, 22-26 July 2012
-1.5 doi: 10.1109/PESGM.2012.6345153
-2
0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 [12] Nielsen, J.G.; Newman, M.; Nielsen, H.; Blaabjerg, F., "Control and
(b) testing of a dynamic voltage restorer (DVR) at medium voltage
Fig 10.Fault current contribution from main grid (a) without DVR (b)with level," Power Electronics, IEEE Transactions on , vol.19, no.3,
DVR pp.806,813, May 2004
[13] Kyung-Min Jin; Quach Ngoc Thinh; Eel-Hwan Kim, "DVR control of
DFIG for compensating fault ride-through based on stationary and
III. CONCLUSION synchronous reference frame," Power Electronics and Motion Control
Conference (IPEMC), 2012 7th International , vol.2, no., pp.3004,3009,
2-5 June 2012
The Dynamic Voltage Restorer (DVR) has been proposed as an [14] Alaraifi, S.; Moawwad, A.; El Moursi, M.S.; Khadkikar, V., "Voltage
interface between a microgrid and the main grid. Two different Booster Schemes for Fault Ride-Through Enhancement of Variable Speed
fault scenarios were considered in order to show the Wind Turbines," Sustainable Energy, IEEE Transactions on , vol.4, no.4,
pp.1071,1081, Oct. 2013
effectiveness of DVR. Firstly, the DVR has been used to
[15] Choi, S.S.; Wang, T. X.; Vilathgamuwa, D.M., "A series compensator
improve reliability of the microgrid by employing it to protect with fault current limiting function," Power Delivery, IEEE Transactions
the microgrid at times of fault in the main grid by injecting a on , vol.20, no.3, pp.2248,2256, July 2005
series voltage to compensate for the sag in grid voltage. This [16] Badrkhani Ajaei, F.; Farhangi, S.; Iravani, R., "Fault Current Interruption
has been shown to be effective to maintain microgrid operation by the Dynamic Voltage Restorer," Power Delivery, IEEE Transactions
on , vol.28, no.2, pp.903,910, April 2013
even in the absence of DG. Secondly, a novel technique of fault
[17] Vilathgamuwa, D.M.; Poh Chiang Loh; Yunwei Li, "Protection of
current limiting has been proposed at times of faults within the Microgrids During Utility Voltage Sags," Industrial Electronics, IEEE
microgrid to reduce short circuit currents. The magnetizing Transactions on , vol.53, no.5, pp.1427,1436, Oct. 2006
impedance of the series transformer has been




Potrebbero piacerti anche