Sei sulla pagina 1di 12

20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.

com/overcurrent-protection-knowledge

20 Simple Questions to Check Your


Overcurrent Protection Knowledge

Overcurrent protective devices


As you already know, reliable overcurrent protective devices, such as
fuses and circuit breakers, prevent or minimize costly damage to
transformers, conductors, motors, equipment, and the other many
components and loads that make up a complete electrical system.

As an electrician, you should understand all facts and NEC codes related
to overcurrent protection.

1 of 12 8/26/17, 10:18 PM
20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.com/overcurrent-protection-knowledge

Answers and following NEC explanations are listed at the bottom. Don’t
peak :)

Question #1

When a circuit breaker trips, its operating handle will be in which of


the following positions?

A. Closed (energized) position


B. Open position
C. Half-way between the ON and OFF positions
D. No change

Question #2

Which of the following conductors need overcurrent protection on a


residential electric service?

A. Grounded conductor
B. Bonding conductor
C. Ungrounded conductors
D. Equipment grounding conductor

Question #3

A circuit feeding three single-phase motors with full-load current ratings of


40, 20 and 20 amperes, respectively, requires the following dual-element
time-delay fuse size:

A. 110 amperes
B. 150 amperes
C. 200 amperes
D. 250 amperes

Question #4

2 of 12 8/26/17, 10:18 PM
20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.com/overcurrent-protection-knowledge

motor drawing a full-load current of 40 amperes, and two other motors


drawing a full-load current of 15 amperes each.

What fuse size should be used?

A. 100 amperes
B. 150 amperes
C. 175 amperes
D. 250 amperes

Question #5

Conductors may be tapped, without overcurrent protection at the tap, to a


feeder or transformer secondary if certain conditions are met. If the
ampacity of the tap conductor is not less than the combined computed
loads on the circuits supplied by the tap conductor, the length of the tap
conductor cannot exceed:

A. 5 feet
B. 10 feet
C. 15 feet
D. 25 feet

Question #6

Where must an overcurrent device be located in a circuit?

A. At the point where the conductor receives its supply


B. At the last outlet on the circuit
C. On the line side of the electric meter
D. At the first fitting or connector in the circuit

Question #7

If a multiwire branch circuit supplies line-to-line loads, the branch-circuit


protective device must open each:

3 of 12 8/26/17, 10:18 PM
20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.com/overcurrent-protection-knowledge

Grounded conductor
C. Ungrounded conductor individually
D. Bonding conductor

Question #8

To meet NEC regulations, fuses or circuit breakers connected in


parallel must be:

A. Assembled by the electrician or technician on the job


B. Encased in a PVC housing
C. Factory assembled in parallel
D. Rated over 200 amperes

Question #9

When a fuse or circuit breaker is used for circuit protection, the fuse or
overcurrent trip unit shall be connected:

A. In series
B. In series and parallel
C. In parallel
D. In tandem

Question #10

At what point must a branch-circuit overcurrent protection device be placed


in an electrical system?

A. At the equipment ground location


B. Where the conductor being protected receives its supply
C. At a tap on the conductor being protected
D. At the outlet where power is consumed

Question #11

4 of 12 8/26/17, 10:18 PM
20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.com/overcurrent-protection-knowledge

at the tap if the ampacity of the tap conductor is at least:

A. 50% of the feeder conductor


B. 40% of the feeder conductor
C. 33 1/3% of the feeder conductor
D. 20% of the feeder conductor

Question #12

When designing or installing circuits for diagnostic equipment in health


care facilities, what is the minimum percentage allowed for the
momentary ampacity of the equipment when sizing branch-circuit
conductors and the overcurrent protection?

A. 25%
B. 50%
C. 75%
D. 100%

Question #13

If an autotransformer has a full-load input current of 40 amperes, what is


the maximum overcurrent protection device rating allowed?

A. 45 amperes
B. 50 amperes
C. 60 amperes
D. 70 amperes

Question #14

In an autotransformer, overcurrent devices shall not be installed:

A. In parallel with the output conductors


B. In parallel with the shunt winding
C. In series with the output conductors
D. In series with the shunt winding

5 of 12 8/26/17, 10:18 PM
20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.com/overcurrent-protection-knowledge

Question #15

A grounding autotransformer is used to create a three-phase, 4-wire


distribution system from a three-phase, 3-wire ungrounded system.

At what percent must the overcurrent device be set to trip in case of


an overload?

A. 100% of the transformer’s continuous current per phase or neutral


rating
B. 110% of the transformer’s continuous current per phase or neutral
rating
C. 125% of the transformer’s continuous current per phase or neutral
rating
D. 150% of the transformer’s continuous current per phase or neutral
rating

Question #16

What must the continuous neutral current rating be for an


autotransformer used to create a three-phase, 4-wire distribution system
from a three-phase, 3-wire ungrounded system?

A. It must be sufficient to handle the minimum neutral unbalanced load


B. It must be sufficient to handle the maximum possible neutral
unbalanced load
C. It must be sufficient to handle 75% of the neutral unbalanced load
D. It must be sufficient to handle 50% of the unbalanced load

Question #17

What is the minimum branch circuit and maximum overcurrent protection


rating for a circuit supplying a household electric range rated at 8 ¾
kW or more?

A. 20 amperes
B. 30 amperes
C. 40 amperes

6 of 12 8/26/17, 10:18 PM
20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.com/overcurrent-protection-knowledge

Question #18

If the allowable current rating of a busway is 46 amperes, what is the


maximum allowable rating of the overcurrent device?

A. 40 amperes
B. 50 amperes
C. 60 amperes
D. 70 amperes

Question #19

A circuit breaker with a slash rating of 120/240 volts is rated for what
voltage to ground?

A. 120 volts to ground


B. 240 volts to ground
C. Any voltage up to 240
D. None of these

Question #20

What overcurrent requirements are specified for grounded conductors?

A. An overcurrent device must be provided in parallel for every conductor


that is intentionally grounded
B. An overcurrent device must be provided in series for every conductor
that is intentionally grounded
C. No overcurrent device is permitted in series with any conductor that is
intentionally grounded
D. An overcurrent device must be provided both in series and in parallel
for every conductor that is intentionally grounded

7 of 12 8/26/17, 10:18 PM
20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.com/overcurrent-protection-knowledge

Answers //
To check your overcurrent protection knowledge , results should
be the same as provided answers. NEC articles mentioned in answers
you can observe in a free draft version of NEC 2014 //

NEC 2014 FREE DRAFT

1. C – The conventional circuit-breaker handle has four possible


positions: on, off, trip, and reset. When tripped, the handle jumps
to the middle position.
2. C A fuse or an overcurrent trip unit of a circuit breaker shall be
connected in series with each ungrounded conductor. NEC
Section 240.15.
3. A – Size the fuse at 175% of the full-load current of the largest
motor plus the full-load current of all other motors. NEC Table
430.52.
4. B – Size the fuse at 300% of the full-load current of the largest
motor plus the full-load current of all other motors. NEC Table
430.52.
5. B – The length of the tap conductor must not exceed 10 feet.
NEC Section 240.21(B)(1).

8 of 12 8/26/17, 10:18 PM
20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.com/overcurrent-protection-knowledge

6. A – An overcurrent device shall be connected at the point where


the conductor to be protected receives its supply. NEC Section
240.21.
7. A – For example, if a 3-wire circuit is connected to a 3-pole circuit
breaker, and one of the three wires should develop a fault, the
circuit breaker must open all three wires simultaneously and not
just the one that developed the fault. NEC Section 240.15(B).
8. C – Fuses, circuit breakers, or combinations thereof shall not be
connected in parallel unless they are factory-assembled and listed
as a unit. NEC Section 240.8.
9. A – Fuses or overcurrent trip units (circuit breakers) must be
connected in series with each ungrounded conductor so they will
open or trip when an overload or ground fault occurs. NEC

9 of 12 8/26/17, 10:18 PM
20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.com/overcurrent-protection-knowledge

B – For example, branch circuits must be protected at the


panelboard where they receive their supply. NEC Section 240.21.
11. C – NEC Section 240.21(B)(2) requires that feeder tap
conductors must not be over 25 feet in length and the ampacity
of the tap conductor must be not less than one-third that of the
feeder conductor. Therefore, answer C (331/3%) is the correct
answer. See Figure 1.

12. B – NEC Section 517.73(A)(1) requires that the ampacity of


supply branch-circuit conductors and the current rating of
overcurrent protective devices must not be less than 50 percent

10 of 12 8/26/17, 10:18 PM
20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.com/overcurrent-protection-knowledge

whichever is greater.
13. B – 40 amperes × 1.25 = 50 amperes. NEC Section 450.4(A).
14. D – NEC Section 450.4(A) requires an overcurrent device to be
installed in series with each ungrounded input conductor.
However, an overcurrent device shall not be installed in series
with the shunt winding.
15. C – NEC Section 450.5(A)(2) requires the overcurrent device to
open or trip if the load on the autotransformer reaches or exceeds
125% of its continuous current per phase or neutral rating.

Delayed tripping for temporary


overcurrents sensed at the
autotransformer overcurrent device is
permitted for the purpose of allowing
proper operation of branch or feeder
protective devices on a 4-wire system.

16. B – NEC Section 450.5(A)(4) requires the autotransformer to


have a continuous neutral current rating sufficient to handle the
maximum possible neutral unbalanced load current of the 4-wire
system.
17. C – NEC Section 210.19(A)(3) states that the minimum branch-
circuit rating for this load should be 40 amperes. A 40-ampere
circuit breaker or cartridge fuse is the maximum allowable rating
for a 40-ampere circuit.
18. B – A rating of 46 amperes is not a standard overcurrent device
rating. However, 50 amperes is a standard rating and may be
used in accordance with NEC Section 240.4(B).
19. A – NEC Section 240.85 requires the voltage to ground to be the
lower of the 2 values on a slash rated circuit breaker.
20. C – NEC Section 240.22 requires that no overcurrent device be
connected in series with any conductor that is intentionally
grounded, unless one of two conditions listed is met.

11 of 12 8/26/17, 10:18 PM
20 Simple Questions to Check Your Overcurrent Protection Knowledge http://electrical-engineering-portal.com/overcurrent-protection-knowledge

About Author //

Edvard Csanyi

Edvard - Electrical engineer, programmer and founder of EEP. Highly


specialized for design of LV/MV switchgears and LV high power busbar
trunking (<6300A) in power substations, commercial buildings and industry
fascilities. Professional in AutoCAD programming. Present on Google+

12 of 12 8/26/17, 10:18 PM

Potrebbero piacerti anche